SIST EN 16623:2015
(Main)Paints and varnishes - Reactive coatings for fire protection of metallic substrates - Definitions, requirements, characteristics and marking
Paints and varnishes - Reactive coatings for fire protection of metallic substrates - Definitions, requirements, characteristics and marking
This European Standard relates to reactive coating systems intended to provide fire protection to metallic based structural members, including various grades and types of steel and aluminium. Reactive coating systems may comprise the reactive coating component alone and/or that component used in conjunction with associated primers), topcoats and, if applicable, reinforcement. It covers the characterization of such systems in end use conditions.
NOTE Fundamental to proving the suitability of any reactive coating system to provide fire protection to any metallic substrate is its fire resistance performance determined in accordance with CEN fire resistance test methods, which are currently EN 13381-6, EN 13381-8 and prEN 13381-9. Consequently, the scope of application and fire performance of any reactive protection system is limited by the scope of available and applicable published CEN fire test methods.
The European Standard sets out the performance criteria, the verification methods used to examine the various aspects of performance, the assessment criteria used to judge the performance for the intended use and the presumed conditions for the design and execution of the reactive coating system in the works.
It deals with the compatibility of the reactive coating component with various primers and topcoats, and a reactive coating system's durability in a number of different service and end use conditions. Specifically, it provides a process for establishing 'generic' primer compatibility and acceptable topcoats for use with a given reactive component layer without prejudicing the reactive coating systems fire performance.
The European Standard also provides guidelines for the manufacture, storage, application, maintenance and repair of the reactive coating system and the final inspection of its installation in end use.
This European Standard does not specify the required level 1) of a given property to be achieved by a product to demonstrate fitness for purpose in a particular application. This European Standard establishes the route for generic primer approval and the use of specific top-coats with which the reactive coating may carry the CE mark.
This European Standard provides guidelines for the manufacture, storage, application, maintenance and repair of the reactive coating system and final inspection of works.
--------------------------------------------------------------------------------------
1) The levels required for a given application are to be found in regulations.
Beschichtungsstoffe - Reaktive Beschichtungen für den Brandschutz metallischer Substrate - Begriffe, Einteilung, Eigenschaften und Bezeichnung
Diese Europäische Norm bezieht sich auf reaktive Beschichtungen unter den Bedingungen der Endanwendung und behandelt die reaktive Beschichtung allein oder in Verbindung mit Grundierungen und Deckbeschichtungen und, falls zutreffend, Bewehrungssystemen.
Diese Europäische Norm legt die Leistungskriterien sowie die Verifizierungsverfahren zur Untersuchung der verschiedenen Aspekte der Leistungsfähigkeit, die Bewertungskriterien zum Beurteilen der Leistung für den vorgesehenen Verwendungszweck und die vorausgesetzten Bedingungen für die Planung und Ausführung der reaktiven Beschichtung im Werk fest.
Diese Europäische Norm bezieht sich auf reaktive Beschichtungen für den Brandschutz von tragenden I- und H Profil Trägern und -Stützen aus Stahl einschließlich galvanisiertem Stahl, von Hohlprofil-Trägern und Stützen mit kreisförmigem und rechteckigem Querschnitt, von betonverfüllten Hohlprofilen und Trägern mit Stegöffnungen.
Diese Europäische Norm gilt nicht für zugbeanspruchte Bauteile, Bauteile aus nichtrostendem Stahl und Bauteile, die ausschließlich aus Holz oder Beton bestehen. Diese Europäische Norm ist nicht für die Anwendung in Verbindung mit Brandschutzsystemen für Kohlenwasserstoffbrand-Beanspruchungen vorgesehen.
Diese Europäische Norm behandelt die Leistungsfähigkeit der reaktiven Beschichtung im Brandfall und auch ihre Verträglichkeit mit Grundierungen und Deckbeschichtungen sowie ihre Haltbarkeit bei einer Reihe unterschiedlicher Einsatz- und Endanwendungsbedingungen. Insbesondere legt sie Verfahren für die Identifizierung, Charakterisierung, Ersttypprüfung und Konformität des reaktiven Beschichtungssystems fest. Die Norm legt allgemeine Verfahren für die Stichprobenprüfung im Rahmen der kontinuierlichen Produktüberwachung am Einsatzort fest.
Diese Europäische Norm enthält Anforderungen an die Kennzeichnung und Etikettierung.
Diese Europäische Norm legt nicht die erforderliche Stufe ) einer bestimmten Eigenschaft fest, die ein Produkt erreichen muss, um seine Gebrauchstauglichkeit für eine bestimmte Anwendung nachzuweisen. Diese Europäische Norm legt die Strategie für die Anerkennung spezifischer Grundierungen und die Anwendung bestimmter Deckbeschichtungen fest, in Verbindung mit denen die reaktive Beschichtung das CE-Kennzeichen tragen darf.
Diese Europäische Norm liefert Leitlinien für die Herstellung, Lagerung, Anwendung, Instandhaltung und Instandsetzung des reaktiven Beschichtungssystems sowie die Endkontrolle des Werks.
Peintures et vernis - Revêtements réactifs pour la protection contre l'incendie des subjectiles métalliques - Partie 1: Définitions, classification, caractéristiques et marquage
La présente Norme se rapporte aux revêtements réactifs dans les conditions d’utilisation finales et couvre le revêtement réactif seul ou combiné à des primaires et des couches de finition et, le cas échéant, des systèmes de renforcement.
La présente Norme stipule les critères de performance, les méthodes de vérification utilisées pour examiner les divers aspects de performance, les critères d’évaluation utilisés afin de juger la performance pour l’utilisation prévue et les conditions estimées pour la conception et l’exécution du revêtement réactif dans les travaux.
La présente Norme se rapporte aux revêtements réactifs pour la protection contre l’incendie d’acier de construction comprenant l’acier galvanisé, les poutres et poteaux de section en I et H, les poutres et poteaux creux à section rectangulaire et circulaire, les sections creuses remplies de béton et les poutres avec ouvertures dans l’âme.
La présente Norme ne s’applique pas aux éléments précontraints, éléments en acier inoxydable et éléments de construction en bois ou en béton seuls. La présente Norme n’est pas destinée à être utilisée en conjonction avec des systèmes de protection contre l’incendie pour l’exposition à des feux d’hydrocarbures.
La présente Norme traite de la performance du revêtement réactif dans un incendie et également de la compatibilité avec les primaires et les couches de finition, de sa durabilité dans diverses utilisations et conditions d’utilisation finale. En particulier, elle décrit des méthodes pour l’identification, la caractérisation, les essais de type initiaux et la conformité du système de revêtement réactif. La norme définit des procédures communes d’essais d’audit pour la surveillance continue du produit sur le marché.
La présente Norme comprend des exigences de marquage et d’étiquetage.
La présente Norme ne spécifie pas le niveau requis ) d’une propriété donnée qu’un produit doit atteindre pour démontrer son adéquation à une application particulière. La présente Norme établit le cheminement pour l’approbation d’un primaire générique et l’utilisation de couches de finition spécifiques grâce auxquels le revêtement réactif peut porter le marquage CE.
La présente Norme donne des directives pour la fabrication, le stockage, l’application, la maintenance et la réparation du système de revêtement réactif et l’inspection finale des travaux.
Barve in laki - Reaktivni premazi za požarno zaščito kovinskih podlag - Definicije, zahteve, karakteristike in označevanje
Ta evropski standard se uporablja za reaktivne premazne sisteme za požarno zaščito konstrukcijskih elementov s kovinsko podlago, vključno z različnimi razredi in vrstami jekla ter aluminija. Reaktivni premazni sistemi lahko vključujejo eno samo reaktivno premazno komponento in/ali to komponento v povezavi z ustreznimi osnovnimi premazi, vrhnjimi premazi in (če je ustrezno) z armaturo. Zajema karakterizacijo takšnih sistemov v pogojih končne uporabe.
OPOMBA: Podlaga za ugotavljanje primernosti izbranega reaktivnega premaznega sistema za zagotavljanje požarne zaščite katere koli kovinske podlage je njegova požarna odpornost, opredeljena v skladu z metodami preskušanja požarne odpornosti CEN, ki jih trenutno vključujejo standardi EN 13381-6, EN 13381-8 in prEN 13381-9. Posledično so področje uporabe in požarne lastnosti katerega koli reaktivnega zaščitnega sistema omejene s področjem objavljenih razpoložljivih in uporabnih požarnih preskusnih metod CEN. Evropski standard določa merila učinkovitosti, metode za preverjanje različnih vidikov učinkovitosti, merila za presojo učinkovitosti za predvideno uporabo ter predvidene pogoje za zasnovo in izvedbo reaktivnega premaznega sistema pri delu. Obravnava združljivost reaktivne premazne komponente z različnimi osnovnimi in vrhnjimi premazi ter trajnost reaktivnega premaznega sistema v več različnih načinih uporabe in pogojih končne uporabe. Zagotavlja predvsem postopek za ugotavljanje združljivosti »generičnega« osnovnega premaza in sprejemljive vrhnje premaze za uporabo z določenim slojem reaktivne komponente brez vpliva na požarne lastnosti reaktivnih premaznih sistemov.
Evropski standard vključuje tudi smernice za izdelavo, shranjevanje, uporabo, vzdrževanje in popravilo reaktivnega premaznega sistema ter za končni pregled njegove namestitve in končne uporabe.
Ta evropski standard ne določa zahtevane ravni 1) določene lastnosti, ki jo mora izdelek doseči, da se dokaže njegova primernost za predvideni namen pri posameznem načinu uporabe. Ta evropski standard zagotavlja način za odobritev generičnega osnovnega premaza in uporabo posebnih vrhnjih premazov, s katerimi lahko reaktivni premaz pridobi oznako CE.
Ta evropski standard vključuje smernice za izdelavo, shranjevanje, uporabo, vzdrževanje in popravilo reaktivnega premaznega sistema ter za končni pregled del.
General Information
Standards Content (Sample)
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.Beschichtungsstoffe - Reaktive Beschichtungen für den Brandschutz metallischer Substrate - Begriffe, Einteilung, Eigenschaften und BezeichnungPeintures et vernis - Revêtements réactifs pour la protection contre l'incendie des subjectiles métalliques - Partie 1: Définitions, classification, caractéristiques et marquagePaints and varnishes - Reactive coatings for fire protection of metallic substrates - Definitions, requirements, characteristics and marking87.040Barve in lakiPaints and varnishes13.220.50Požarna odpornost gradbenih materialov in elementovFire-resistance of building materials and elementsICS:Ta slovenski standard je istoveten z:EN 16623:2015SIST EN 16623:2015en,fr,de01-maj-2015SIST EN 16623:2015SLOVENSKI
STANDARD
SIST EN 16623:2015
EUROPEAN STANDARD NORME EUROPÉENNE EUROPÄISCHE NORM
EN 16623
February 2015 ICS 13.220.50; 87.040 English Version
Paints and varnishes - Reactive coatings for fire protection of metallic substrates - Definitions, requirements, characteristics and marking
Peintures et vernis - Revêtements réactifs pour la protectioncontre l'incendie des subjectiles métalliques - Définitions, classification, caractéristiques et marquage
Beschichtungsstoffe - Reaktive Beschichtungen für den Brandschutz metallischer Substrate - Begriffe, Einteilung, Eigenschaften und Bezeichnung This European Standard was approved by CEN on 12 December 2014.
CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN-CENELEC Management Centre or to any CEN member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC Management Centre has the same status as the official versions.
CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and United Kingdom.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION EUROPÄISCHES KOMITEE FÜR NORMUNG
CEN-CENELEC Management Centre:
Avenue Marnix 17,
B-1000 Brussels © 2015 CEN All rights of exploitation in any form and by any means reserved worldwide for CEN national Members. Ref. No. EN 16623:2015 ESIST EN 16623:2015
EN 16623:2015 (E) 2 Contents Page Foreword .4 Introduction .5 1 Scope .6 2 Normative references .6 3 Terms and definitions .7 4 Symbols and abbreviations .8 5 Requirements .9 5.1 Reaction to fire .9 5.2 Resistance to fire .9 5.3 Durability .9 5.3.1 General .9 5.3.2 Verification of durability . 10 5.3.3 Use of topcoats . 10 5.4 Primer Compatibility . 11 5.4.1 General . 11 5.4.2 Generic types . 11 5.4.3 Verification of primer compatibility . 12 5.5 Emission of dangerous substances . 12 6 Evaluation of conformity . 13 6.1 General . 13 6.2 Sampling . 13 6.3 Initial type testing . 13 6.4 Characterization of the reactive coating . 13 6.4.1 Analytical characterization . 13 6.4.2 Physical characterization . 13 6.5 Factory production control . 13 7 Sustainability . 14 8 Marking . 14 9 Additional voluntary requirements . 14 Annex A (normative)
Method for determination of reaction to fire . 15 A.1 Guidance for testing in accordance with EN 13823 . 15 A.1.1 Dimensions of the test rig . 15 A.1.2 Test specimens . 15 A.2 Guidance for testing in accordance with EN ISO 11925-2 (small burner test) . 15 A.3 Guidance for testing in accordance with EN ISO 1716 and EN ISO 1182 (if relevant for reactive fire protection systems) . 16 Annex B (normative)
Exposure conditions for determination of durability classification . 17 B.1 General . 17 B.2 Exposure conditions for Type X: Reactive coating system intended for all conditions internal or external. 17 B.3 Exposure conditions for Type Y: Reactive coating system intended for semi external conditions . 18 B.4 Exposure conditions for Type W: Reactive coating system intended for temporary external exposure prior to final exposure conditions . 18 B.5 Exposure conditions for Type Z1: Reactive coating system intended for internal conditions with high humidity . 18 B.6 Exposure conditions for Type Z2: Reactive coating system intended for internal conditions with controlled environment . 18 SIST EN 16623:2015
EN 16623:2015 (E) 3 Annex C (normative)
Insulating Efficiency — Test Procedure . 20 C.1 General . 20 C.2 Test specimens . 20 C.3 Test Procedure . 20 C.4 Test Report . 21 Annex D (normative)
Determination of identification characteristics . 25 D.1 General . 25 D.2 Reporting of Specific Methodology for determination of identification characteristics . 25 Annex E (normative)
Factory production control . 26 E.1 General . 26 E.2 Quality control testing . 26 E.3 Initial factory inspection . 27 Annex F (normative)
Alternative raw materials, formulation and process changes . 28 F.1 General . 28 F.2 Formulation tolerances . 28 F.3 Formulation change . 28 F.4 Raw material approval of an alternative . 28 F.5 Process and equipment change . 31 F.6 Managing multiple production sites . 31 Annex G (normative)
Audit testing . 32 G.1 General . 32 G.2 Selection of product and preparation of test specimens . 32 G.3 Choice of test specimens . 32 G.4 Illustrative testing pattern. 33 G.5 Audit test procedure . 33 G.6 Audit test results . 33 G.7 Non-compliance . 34 Annex H (normative)
Levels of fire testing . 35 H.1 General . 35 H.2 Level 1 fire testing . 35 H.3 Level 2 fire testing . 35 H.4 Level 3 fire testing . 36 H.5 Level 4 independent fire testing . 37 H.6 Level 5 independent fire testing . 37 Annex I (informative)
Guidance for manufacture, storage, application, inspection and repair . 38 I.1 Manufacture . 38 I.1.1 Manufacturing equipment. 38 I.1.2 Temperature during manufacture . 38 I.1.3 Manufacturing blending time . 38 I.1.4 Raw material quality and traceability . 38 I.2 Storage of raw materials . 38 I.3 Storage of finished product. 38 I.4 Application . 39 I.4.1 General . 39 I.4.2 Application schedule . 39 I.4.3 Compatibility . 39 I.4.4 Application requirements and environmental conditions . 39 I.4.5 Application controls . 40 I.5 Inspection . 40 I.5.1 General . 40 I.5.2 Inspection criteria . 40 I.6 Maintenance and repair . 41 Bibliography . 42
SIST EN 16623:2015
EN 16623:2015 (E) 4 Foreword This document (EN 16623:2015) has been prepared by Technical Committee CEN/TC 139 “Paints and vanishes”, the secretariat of which is held by DIN. This European Standard shall be given the status of a national standard, either by publication of an identical text or by endorsement, at the latest by August 2015, and conflicting national standards shall be withdrawn at the latest by August 2015. Attention is drawn to the possibility that some of the elements of this document may be the subject of patent rights. CEN [and/or CENELEC] shall not be held responsible for identifying any or all such patent rights. According to the CEN/CENELEC Internal Regulations, the national standards organizations of the following countries are bound to implement this European Standard: Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and the United Kingdom. SIST EN 16623:2015
EN 16623:2015 (E) 5 Introduction This European Standard applies to reactive coatings intended for the fire protection of steel and other ferrous substrates used as structural elements such as beams and columns, beams supporting composite steel deck floors and concrete filled hollow steel sections. The reactive coating can be applied directly to the substrate or over a priming system. The reactive coating may require a protective top-coat depending on the end service conditions. Throughout this European Standard, steel and other ferrous substrates are referred to as steel. Currently, under the requirements of the Construction Products Regulation 2011 (CPR), which superseded the requirements of the Construction Products Directive (CPD), each reactive coating product used to provide fire protection to structural members is required to be subject to a European Technical Assessment (ETA). These are elaborated and issued by a European Technical Assessment Body (TAB) on the basis of guidance given in a European Assessment Document (EAD) produced by the European Organisation for Technical Approvals (EOTA). Previously, under the requirements of the CPD, the relevant equivalent guidance for the issue of ETAs (then termed European Technical Approvals) for reactive coatings was documented in the EOTA Technical Specification ETAG018-2. At the time of ratification of this standard, ETAG018-2 is being edited into an EAD but all existing ETAs issued against ETAG018-2 remain valid until their expiry date. The ETA forms the basis of the voluntary CE marking of the product by the manufacturer based on a 'certificate of conformity' provided by a 'notified certification body' endorsing ongoing compliance of the product with its ETA. This standard is intended to be supportive to the above mandatory process, reflecting agreed best practice within the industry and for adoption by manufacturers on a voluntary basis. Requirements of this standard do not conflict with requirements of ETAG018-2 or its superseding EAD. They may elaborate on the detail of essential production processes and procedures necessary to provide consistency of reactive products. Approaches are specified to assess the consequences to a products fire protection performance caused by variation or changes in product specification (e.g. changes in raw material) and/or production process (e.g. a process temperature). As such, it provides support to 'notified certification bodies', especially in relation to 'factory production controls' that should be exercised by product manufacturers. This standard also provides a common basis for non-mandatory product characteristics that a manufacturer may wish to claim for a product, that fall beyond the scope of a product's ETA. SIST EN 16623:2015
EN 16623:2015 (E) 6 1 Scope This European Standard relates to reactive coating systems intended to provide fire protection to metallic based structural members, including various grades and types of steel. Reactive coating systems may comprise the reactive coating component alone and/or that component used in conjunction with associated primers, topcoats and, if applicable, reinforcement. It covers the characterization of such systems in end use conditions. NOTE Fundamental to proving the suitability of any reactive coating system to provide fire protection to any metallic substrate is its fire resistance performance determined in accordance with CEN fire resistance test methods, which are currently EN 13381-6, EN 13381-8 and prEN 13381-9. Consequently, the scope of application and fire performance of any reactive protection system is limited by the scope of available and applicable published CEN fire test methods. The European Standard sets out the performance criteria, the verification methods used to examine the various aspects of performance, the assessment criteria used to judge the performance for the intended use and the presumed conditions for the design and execution of the reactive coating system in the works. It deals with the compatibility of the reactive coating component with various primers and topcoats, and a reactive coating system's durability in a number of different service and end use conditions. Specifically, it provides a process for establishing 'generic' primer compatibility and acceptable topcoats for use with a given reactive component layer without prejudicing the reactive coating systems fire performance. The European Standard also provides guidelines for the manufacture, storage, application, maintenance and repair of the reactive coating system and the final inspection of its installation in end use. This European Standard does not specify the required performance level or classification 1) of a given property to be achieved by a product to demonstrate fitness for purpose in a particular application. This European Standard establishes the route for generic primer approval and the use of specific top-coats with which the reactive coating may carry the CE mark. This European Standard provides guidelines for the manufacture, storage, application, maintenance and repair of the reactive coating system and final inspection of works. 2 Normative references The following documents, in whole or in part, are normatively referenced in this document and are indispensable for its application. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. EN 1363-1:2012, Fire resistance tests — Part 1: General Requirements EN 13238, Reaction to fire tests for building products — Conditioning procedures and general rules for selection of substrates EN 13381-6, Test methods for determining the contribution to the fire resistance of structural members — Part 6: Applied protection to concrete filled hollow steel columns EN 13381-8:2013, Test methods for determining the contribution to the fire resistance of structural members — Part 8: Applied reactive protection to steel members prEN 13381-9, Test methods for determining the contribution to the fire resistance of structural members — Part 9: Contribution of fire resistance to steel beams with web opening EN 13501-1, Fire classification of construction products and building elements — Part 1: Classification using data from reaction to fire tests
1) The performance levels or classes required for a given application can be found in regulations. SIST EN 16623:2015
EN 16623:2015 (E) 7 EN 13501-2:2007+A1:2009, Fire classification of construction products and building elements — Part 2: Classification using data from fire resistance tests, excluding ventilation services EN 13823, Reaction to fire tests for building products — Building products excluding floorings exposed to the thermal attack by a single burning item EN ISO 1182, Reaction to fire tests for products — Non-combustibility test (ISO 1182) EN ISO 1716, Reaction to fire tests for products — Determination of the gross heat of combustion (calorific value) (ISO 1716) EN ISO 4618:2014, Paints and varnishes — Terms and definitions (ISO 4618:2014) EN ISO 11664-4, Colorimetry — Part 4: CIE 1976 L*a*b* Colour space (ISO 11664-4) EN ISO 11925-2, Reaction to fire tests - Ignitability of products subjected to direct impingement of flame — Part 2: Single-flame source test (ISO 11925-2) EN ISO 13788, Hygrothermal performance of building components and building elements — Internal surface temperature to avoid critical surface humidity and interstitial condensation — Calculation methods (ISO 13788) EN ISO 16474-3:2013, Paints and varnishes — Methods of exposure to laboratory light sources — Part 3: Fluorescent UV lamps (ISO 16474-3:2013) EN ISO/IEC 17025, General requirements for the competence of testing and calibration laboratories (ISO/IEC 17025) 3 Terms and definitions For the purposes of this document, the terms and definitions given in EN ISO 4618:2014 and the following apply. 3.1 reactive coating reactive materials which are specifically formulated to provide a chemical reaction upon heating such that their physical form changes and in so doing provide fire protection by thermal insulative and cooling effects 3.2 reactive coating system reactive coating layer together with a specified, blast primer, primer, tie-coat and topcoat if applicable Note 1 to entry: The reactive coating system can contain reinforcing mesh. 3.3 test specimen substrate, plus the reactive coating system under test 3.4 reactive coating thickness mean dry film thickness (DFT) of the reactive coating only 3.5 section factor ratio of the fire exposed outer perimeter area of the steel structural member itself, per unit length, to its cross sectional volume per unit length SIST EN 16623:2015
EN 16623:2015 (E) 8 3.6 steel temperature overall mean temperature of the steel 3.7 blast primer layer of corrosion protection applied to grit or shot blasted steel as a temporary protection to prevent corrosion prior to application of the main coat of primer 3.8 primer coating applied directly to a suitably prepared steel surface to provide corrosion protection 3.9 tie-coat coating applied prior to the reactive coating to improve the bonding 3.10 topcoat coating(s) applied over the reactive coating as a protection against environmental degradation and/or for decorative purposes 3.11 reinforcing mesh mesh applied in close proximity or fixed to the substrate 3.12 batch unit or quantity of reactive coating produced in a single, complete production operation 3.13 durability ability of the reactive coating system to maintain an adequate level of fire protection after exposure to environmental conditions 3.14 initial type testing testing carried out in accordance with EN 13381-6 and/or EN 13381-8 to establish fire performance 3.15 controlled stock product in stock that is traceable to a manufacturing record and factory production control test results 3.16 yield strength stress level, for a given temperature, at which the stress-strain relationship of steel is truncated to provide a yield plateau as given in EN 1993-1-2 3.17 approved body body nominated in accordance with Article 18 of the Construction Products Directive by an EU Member State or by an EFTA State (contracting party to the EEA Agreement), to perform specific tasks in the framework of the Attestation of Conformity decision for specific construction products (certification, inspection or testing) Note 1 to entry: All such bodies are members of the Group of Notified Bodies. 4 Symbols and abbreviations For the purposes of this document, the following symbols and abbreviations apply: SIST EN 16623:2015
EN 16623:2015 (E) 9 A/V section factor DFT dry film thickness FPC factory production control QC quality control RH relative humidity SBI single burning item 5 Requirements 5.1 Reaction to fire The reactive coating system shall be tested, using the test method(s) relevant for the corresponding reaction to fire class, in order to be classified according to EN 13501-1. Guidance on mounting and fixing arrangements for tests in accordance with the test methods is given in Annex A. If the reactive coating system is intended to be used wit
...