Standard Specification for Fibrous Glass Duct Lining Insulation (Thermal and Sound Absorbing Material)

ABSTRACT
This specification covers fibrous glass insulation used as a thermal and sound absorbing liner for interior surfaces of ducts, plenums, and other air handling equipment. The insulation shall be of the following types: Type I and Type II. The basic material shall be made from glass processed from the molten state into fibrous form with a binder added to form dimensionally stable insulation. The following test methods shall be performed: corrosiveness; water vapor sorption; fungi resistance; temperature resistance; erosion resistance; odor emission; surface burning characteristics; apparent thermal conductivity; sound absorption coefficients; bacteria resistance; and combustion characteristics.
SCOPE
1.1 This specification covers fibrous glass insulation used as a thermal and sound absorbing liner for interior surfaces of ducts, plenums, and other air handling equipment that handle air up to 250°F (121°C).  
1.2 The values stated in inch-pound units are the standard. The SI values in parentheses are for information only.
1.3 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.

General Information

Status
Historical
Publication Date
31-Mar-2005
Current Stage
Ref Project

Relations

Buy Standard

Technical specification
ASTM C1071-05e1 - Standard Specification for Fibrous Glass Duct Lining Insulation (Thermal and Sound Absorbing Material)
English language
4 pages
sale 15% off
Preview
sale 15% off
Preview
Technical specification
REDLINE ASTM C1071-05e1 - Standard Specification for Fibrous Glass Duct Lining Insulation (Thermal and Sound Absorbing Material)
English language
4 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)

NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
´1
Designation: C1071 – 05
Standard Specification for
Fibrous Glass Duct Lining Insulation (Thermal and Sound
1
Absorbing Material)
This standard is issued under the fixed designation C1071; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
This standard has been approved for use by agencies of the Department of Defense.
1
´ NOTE—Sections 2.2 and 12.9 were editorially updated in June 2008.
1. Scope sulation for Light Frame Construction and Manufactured
Housing
1.1 This specification covers fibrous glass insulation used as
C1104/C1104M Test Method for Determining the Water
a thermal and sound absorbing liner for interior surfaces of
Vapor Sorption of Unfaced Mineral Fiber Insulation
ducts, plenums, and other air handling equipment that handle
C1114 Test Method for Steady-State Thermal Transmission
air up to 250°F (121°C).
Properties by Means of the Thin-Heater Apparatus
1.2 The values stated in inch-pound units are the standard.
C1304 Test Method for Assessing the Odor Emission of
The SI values in parentheses are for information only.
Thermal Insulation Materials
1.3 This standard does not purport to address all of the
C1338 Test Method for Determining Fungi Resistance of
safety concerns, if any, associated with its use. It is the
Insulation Materials and Facings
responsibility of the user of this standard to establish appro-
E84 Test Method for Surface Burning Characteristics of
priate safety and health practices and determine the applica-
Building Materials
bility of regulatory limitations prior to use.
E795 Practices for MountingTest Specimens During Sound
2. Referenced Documents Absorption Tests
2
E2231 Practice for Specimen Preparation and Mounting of
2.1 ASTM Standards:
Pipe and Duct Insulation Materials to Assess Surface
C167 TestMethodsforThicknessandDensityofBlanketor
Burning Characteristics
Batt Thermal Insulations
G21 Practice for Determining Resistance of Synthetic Poly-
C168 Terminology Relating to Thermal Insulation
meric Materials to Fungi
C177 Test Method for Steady-State Heat Flux Measure-
G22 Practice for Determining Resistance of Plastics to
ments and Thermal Transmission Properties by Means of
3
Bacteria
the Guarded-Hot-Plate Apparatus
2.2 Other Standards:
C390 Practice for Sampling and Acceptance of Thermal
4
NAIMA Fibrous Glass Duct Liner Standard
Insulation Lots
5
SMACNA HVAC Duct Construction Standards
C411 Test Method for Hot-Surface Performance of High-
UL723 Test for Surface Burning Characteristics of Building
Temperature Thermal Insulation
6
Materials
C423 Test Method for Sound Absorption and Sound Ab-
NFPA 255 Method of Test of Surface Burning Characteris-
sorption Coefficients by the Reverberation Room Method
7
tics of Building Materials
C518 Test Method for Steady-State Thermal Transmission
NFPA 259 Test Method for Potential Heat of Building
Properties by Means of the Heat Flow Meter Apparatus
7
Materials
C665 Specification for Mineral-Fiber Blanket Thermal In-
1 3
This specification is under the jurisdiction of ASTM Committee C16 on Withdrawn. The last approved version of this historical standard is referenced
Thermal Insulation and is the direct responsibility of Subcommittee C16.23 on on www.astm.org.
4
Blanket and Loose Fill Insulation. Available from North American Insulation Manufacturers Association, 44
Current edition approved April 1, 2005. Published April 2005. Originally Canal Center Plaza, Suite 310, Alexandria, VA 22314.
5
approved in 1986. Last previous edition approved in 2000 as C1071 – 00. DOI: Available from Sheet Metal and Air Conditioning Contractors National
10.1520/C1071-05E01. Association, Inc., 4201 Lafayette Center Drive, Chantilly, VA 22021-1209.
2 6
For referenced ASTM standards, visit the ASTM website, www.astm.org, or Available from Underwriters Laboratories Inc., 333 Pfingsten Road, North-
contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM brook, Illinois 60062–2096.
7
Standards volume information, refer to the standard’s Document Summary page on Available from National Fire ProtectionAssociation, 1 Batterymarch Park, PO
the ASTM website. Box 9101, Quincy, MA 02269–9101.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.
1

---------------------- Page: 1 ----------------------
´1
C1071 – 05
CAN/ULC-S102 Method of Test for Surface Burning Char- 7.5 Erosion Resistance—When tested in accordance with
8
acteristics of Building Materials and Assemblies 12.7, the insulation shall not break away, crack, peel, flake off,
or show evidence of delamination or continued
...

This document is not an ASTM standard and is intended only to provide the user of an ASTM standard an indication of what changes have been made to the previous version. Because
it may not be technically possible to adequately depict all changes accurately, ASTM recommends that users consult prior editions as appropriate. In all cases only the current version
of the standard as published by ASTM is to be considered the official document.
e1
Designation:C1071–00 Designation: C 1071 – 05
Standard Specification for
Fibrous Glass Duct Lining Insulation (Thermal and Sound
1
Absorbing Material)
This standard is issued under the fixed designation C 1071; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
This standard has been approved for use by agencies of the Department of Defense.
1
e NOTE—Sections 2.2 and 12.9 were editorially updated in June 2008.
1. Scope
1.1 This specification covers fibrous glass insulation used as a thermal and sound absorbing liner for interior surfaces of ducts,
plenums, and other air handling equipment that handle air up to 250°F (121°C).
1.2 The values stated in inch-pound units are the standard. The SI values in parentheses are for information only.
1.3 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility
of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory
limitations prior to use.
2. Referenced Documents
2
2.1 ASTM Standards:
C 167 Test Methods for Thickness and Density of Blanket or Batt Thermal Insulations
2
C 168Terminology Relating to Thermal Insulating Materials Terminology Relating to Thermal Insulation
C 177 Test Method for Steady-State Heat Flux Measurements and Thermal Transmission Properties by Means of the
Guarded-Hot-Plate Apparatus
C 390Criteria Practice for Sampling and Acceptance of Preformed Thermal Insulation Lots
C 411 Test Method for Hot-Surface Performance of High-Temperature Thermal Insulation
C 423 Test Method for Sound Absorption and Sound Absorption Coefficients by the Reverberation Room Method
C 518 Test Method for Steady-State Heat Flux Measurements andThermalTransmission Properties by Means of the Heat Flow
Meter Apparatus
C 665 Specification for Mineral-Fiber Blanket Thermal Insulation for Light Frame Construction and Manufactured Housing
C 1104/C 1104M Test Method for Determining the Water Vapor Sorption of Unfaced Mineral Fiber Insulation
C 1114 Test Method for Steady-State Thermal Transmission Properties by Means of the Thin-Heater Apparatus
C 1304 Test Method for Assessing the Odor Emission of Thermal Insulation Materials
C 1338 Test Method for Determining Fungi Resistance of Insulation Materials and Facings
E 84 Test Method for Surface Burning Characteristics of Building Materials
2
E 795Practices for Mounting Test Specimens During SoundAbsorption Tests Practices for Mounting Test Specimens During
Sound Absorption Tests
E 2231 Practice for Specimen Preparation and Mounting of Pipe and Duct Insulation Materials to Assess Surface Burning
Characteristics
G 21 Practice for Determining Resistance of Synthetic Polymeric Materials to Fungi
G 22 Practice for Determining Resistance of Plastics to Bacteria
2.2 Other Standards:
3
NAIMA Fibrous Glass Duct Liner Standard
1
ThisspecificationisunderthejurisdictionofASTMCommitteeC16onThermalInsulationandisthedirectresponsibilityofSubcommitteeC16.23onBlanketandLoose
Fill Insulation.
Current edition approved Dec. 10, 2000. Published January 2001. Originally published as C1071–86. Last previous edition C1071–98.
Current edition approved April 1, 2005. Published April 2005. Originally approved in 1986. Last previous edition approved in 2000 as C 1071 – 00.
2
For referencedASTM standards, visit theASTM website, www.astm.org, or contactASTM Customer Service at service@astm.org. For Annual Book of ASTM Standards
, Vol 04.06.volume information, refer to the standard’s Document Summary page on the ASTM website.
3
Annual Book of ASTM Standards, Vol 04.07.
3
Available from North American Insulation Manufacturers Association, 44 Canal Center Plaza, Suite 310, Alexandria, VA 22314.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.
1

---------------------- Page: 1 ----------------------
e1
C1071–05
4
SMACNA HVAC Duct Construction Standards
5
UL 723 Test for Surface Burning Characteristics of Building Materials
6
NFPA 255 Standard Method of Test of Surface Burning Characteristics of Building Materials
6
NFPA 259 Standard Test Method for Potential Heat of Building Materials
CAN/ULC-S102-M88 StandardCAN/ULC-S102 Method of Test for Surface Burning Characteristics of Buildin
...