Standard Specification for Fibrous Glass Duct Lining Insulation (Thermal and Sound Absorbing Material)

SCOPE
1.1 This specification covers fibrous glass insulation used as a thermal and sound absorbing liner for interior surfaces of ducts, plenums, and other air handling equipment that handle air up to 250oF (121oC).
1.2 The values stated in inch-pound units are the standard. The SI values in parentheses are for information only.
1.3

General Information

Status
Historical
Publication Date
09-Dec-2000
Current Stage
Ref Project

Relations

Buy Standard

Technical specification
ASTM C1071-00 - Standard Specification for Fibrous Glass Duct Lining Insulation (Thermal and Sound Absorbing Material)
English language
4 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)

NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
Designation: C 1071 – 00
Standard Specification for
Fibrous Glass Duct Lining Insulation (Thermal and Sound
1
Absorbing Material)
This standard is issued under the fixed designation C 1071; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (e) indicates an editorial change since the last revision or reapproval.
2
1. Scope Vapor Sorption of Unfaced Mineral Fiber Insulation
C 1114 Test Method for Steady-StateThermalTransmission
1.1 This specification covers fibrous glass insulation used as
2
Properties by Means of the Thin-Heater Apparatus
a thermal and sound absorbing liner for interior surfaces of
C 1304 Test Method for Assessing the Odor Emission of
ducts, plenums, and other air handling equipment that handle
2
Thermal Insulation Materials
air up to 250°F (121°C).
C 1338 Test Method for Determining Fungi Resistance of
1.2 The values stated in inch-pound units are the standard.
2
Insulation Materials and Facings
The SI values in parentheses are for information only.
E 84 Test Method for Surface Burning Characteristics of
1.3 This standard does not purport to address all of the
3
Building Materials
safety concerns, if any, associated with its use. It is the
E 795 Practices for Mounting Test Specimens During
responsibility of the user of this standard to establish appro-
2
Sound Absorption Tests
priate safety and health practices and determine the applica-
G 21 Practice for Determining Resistance of Synthetic
bility of regulatory limitations prior to use.
4
Polymer Materials to Fungi
2. Referenced Documents G 22 Practice for Determining Resistance of Plastics to
4
Bacteria
2.1 ASTM Standards:
2.2 Other Standards:
C 167 Test Methods for Thickness and Density of Blanket
5
2
NAIMA Fibrous Glass Duct Liner Standard
or Batt Thermal Insulations
6
SMACNA HVAC Duct Construction Standards
C 168 Terminology Relating to Thermal Insulating Materi-
2
UL723 Test for Surface Burning Characteristics of Building
als
7
Materials
C 177 Test Method for Steady-State Heat Flux Measure-
NFPA 255 Standard Method of Test of Surface Burning
ments and Thermal Transmission Properties by Means of
8
2
Characteristics of Building Materials
the Guarded-Hot-Plate Apparatus
NFPA 259 Standard Test Method for Potential Heat of
C 390 Criteria for Sampling and Acceptance of Preformed
8
2
Building Materials
Thermal Insulation Lots
CAN/ULC-S102-M88 Standard Method of Test for Surface
C 411 Test Method for Hot-Surface Performance of High-
2
Burning Characteristics of Building Materials andAssem-
Temperature Thermal Insulation
9
blies
C 423 Test Method for Sound Absorption and Sound Ab-
2
sorption Coefficients by the Reverberation Room Method
3. Terminology
C 518 Test Method for Steady-State Heat Flux Measure-
3.1 For definitions of terms used in this specification, see
ments and Thermal Transmission Properties by Means of
2
Terminology C 168.
the Heat Flow Meter Apparatus
C 665 Specification for Mineral-Fiber Blanket Thermal In-
3
sulation for Light Frame Construction and Manufactured
Annual Book of ASTM Standards, Vol 04.07.
2
4
Housing Annual Book of ASTM Standards, Vol 14.04.
5
Available from North American Insulation Manufacturers Association, 44
C 1104/C 1104M Test Method for Determining the Water
Canal Center Plaza, Suite 310, Alexandria, VA 22314.
6
Available from Sheet Metal and Air Conditioning Contractors National
Association, Inc., 4201 Lafayette Center Drive, Chantilly, VA 22021-1209.
1 7
This specification is under the jurisdiction of ASTM Committee C16 on Available from Underwriters Laboratories Inc., 333 Pfingsten Road, North-
Thermal Insulation and is the direct responsibility of Subcommittee C16.23 on brook, Illinois 60062–2096.
8
Blanket and Loose Fill Insulation. Available from National Fire ProtectionAssociation, 1 Batterymarch Park, PO
Current edition approved Dec. 10, 2000. Published January 2001. Originally Box 9101, Quincy, MA 02269–9101.
9
published as C 1071 – 86. Last previous edition C 1071 – 98. Available from Underwriters Laboratories of Canada, 7 Crouse Road, Scarbor-
2
Annual Book of ASTM Standards, Vol 04.06. ough, Ontario, Canada M1R 3A9.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.
1

---------------------- Page: 1 ----------------------
C 1071
4. Classification shall have a maximum flame spread index of 25 and a
maximum smoke developed index of 50.
4.1 The insulation covered by this specification shall be of
7.8 Apparent Thermal Conductivity—When tested in accor-
the following types:
dance with 12.10, the apparent thermal conductivity (k) of the
4.1.1 Type I—Blanket in roll form up to 200 ft (61 m) in
2
insulation,
...