Standard Practice for Application of Hose Stream

SIGNIFICANCE AND USE
4.1 This practice is intended to standardize the apparatus used and the method or pattern of application of a standard hose stream to building elements as one part of the assessment and fire resistance of building elements.  
4.1.1 This practice specifies the water pressure and duration of application of the hose stream to the test assembly.  
4.2 This practice is intended to be used only after a test assembly has completed a prescribed standard fire-resistance test.  
4.3 The practice exposes a test assembly to a standard hose stream under controlled laboratory conditions.  
4.3.1 Pass/fail criteria are defined in the appropriate fire test method.  
4.3.2 This exposure is not intended to replicate typical fire fighting operations or all applied or impact loads a system could be subjected to in field use and conditions.  
4.4 Any variation from tested conditions has the potential of substantially changing the performance characteristics determined by this practice.
SCOPE
1.1 This practice is applicable to building elements required to be subjected to the impact, erosion, and cooling effects of a hose stream as part of a fire-test-response standard. Building elements include, but are not limited to, wall and partition assemblies, fire-resistive joint systems, and doors.  
1.2 This practice shall register performance of the building element under specific hose stream conditions. It shall not imply that, either after exposure or under other conditions, the structural capability of the building element is intact or that the building element is suitable for use.  
1.3 The result derived from this practice is one factor in assessing the integrity of building elements after fire exposure. The practice prescribes a standard hose stream exposure for comparing performance of building elements after fire exposure and evaluates various materials and construction techniques under common conditions.  
1.4 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.  
1.5 The text of this standard references notes which provide explanatory material. These notes shall not be considered as requirements of the standard.  
1.6 This fire standard cannot be used to provide quantitative measures.  
1.7 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.

General Information

Status
Historical
Publication Date
31-May-2015
Technical Committee
Drafting Committee
Current Stage
Ref Project

Relations

Buy Standard

Standard
ASTM E2226-15a - Standard Practice for Application of Hose Stream
English language
6 pages
sale 15% off
Preview
sale 15% off
Preview
Standard
REDLINE ASTM E2226-15a - Standard Practice for Application of Hose Stream
English language
6 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)

NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
Designation: E2226 − 15a AnAmerican National Standard
Standard Practice for
1
Application of Hose Stream
This standard is issued under the fixed designation E2226; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
INTRODUCTION
Several fire-test-response standards (such as ASTM E119, E814, E2074, and E1966) in order to
assess the integrity of building elements after exposure to a specified test fire, require test specimens
tobeevaluatedbyexposuretoahosestream.Itisimportanttostandardizecertainelementsofthehose
stream to promote uniformity in requirements. To attain this goal, this practice describes a standard
apparatus for delivering a solid stream of water and prescribes a standard method of subjecting
building elements to a hose stream after fire exposure.
1. Scope 1.7 This standard does not purport to address all of the
safety concerns, if any, associated with its use. It is the
1.1 This practice is applicable to building elements required
responsibility of the user of this standard to establish appro-
to be subjected to the impact, erosion, and cooling effects of a
priate safety and health practices and determine the applica-
hose stream as part of a fire-test-response standard. Building
bility of regulatory limitations prior to use.
elements include, but are not limited to, wall and partition
assemblies, fire-resistive joint systems, and doors.
2. Referenced Documents
1.2 This practice shall register performance of the building
2
2.1 ASTM Standards:
element under specific hose stream conditions. It shall not
E119 Test Methods for Fire Tests of Building Construction
imply that, either after exposure or under other conditions, the
and Materials
structural capability of the building element is intact or that the
E176 Terminology of Fire Standards
building element is suitable for use.
E631 Terminology of Building Constructions
1.3 The result derived from this practice is one factor in
E814 Test Method for Fire Tests of Penetration Firestop
assessing the integrity of building elements after fire exposure.
Systems
The practice prescribes a standard hose stream exposure for
E1966 Test Method for Fire-Resistive Joint Systems
comparing performance of building elements after fire expo-
E2074 Test Method for Fire Tests of Door Assemblies,
sure and evaluates various materials and construction tech-
Including Positive Pressure Testing of Side-Hinged and
3
niques under common conditions.
Pivoted Swinging Door Assemblies (Withdrawn 2007)
1.4 The values stated in inch-pound units are to be regarded 2.2 UL Standard:
as standard. The values given in parentheses are mathematical UL 385 Standard for Safety Play Pipes for Water Supply
4
conversions to SI units that are provided for information only Testing in Fire-Protection Service
and are not considered standard.
3. Terminology
1.5 The text of this standard references notes which provide
3.1 Definitions—For definitions of terms used in this
explanatory material. These notes shall not be considered as
practice, refer to Terminologies E176 and E631.
requirements of the standard.
3.2 Definitions of Terms Specific to This Standard:
1.6 This fire standard cannot be used to provide quantitative
measures.
2
For referenced ASTM standards, visit the ASTM website, www.astm.org, or
contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM
1
This practice is under the jurisdiction of ASTM Committee E05 on Fire Standards volume information, refer to the standard’s Document Summary page on
Standards and is the direct responsibility of Subcommittee E05.11 on Fire the ASTM website.
3
Resistance. The last approved version of this historical standard is referenced on
CurrenteditionapprovedJune1,2015.PublishedJuly2015.Originallyapproved www.astm.org.
4
in 2002. Last previous edition approved in 2015 as E2226–15. DOI: 10.1520/ Available from Underwriters Laboratories (UL), Corporate Progress, 333
E2226-15A. Pfingsten Rd., Northbrook, IL 60062.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
1

---------------------- Page: 1 ----------------------
E2226 − 15a
3.2.1 building element, n—a component or assembly of 4.3 The practice exposes a test assembly to a standard hose
materials using products manufactured as independent units stream under controlled laboratory conditions.
capable of being joined with or placed within other compo-
4.3.1 Pass/fail criteria are defined in the appropriate fire test
nents or assemblies to create a structure. method.
4.3.2 This exposure is not intended to replicate typical fire
3.2.2 exp
...

This document is not an ASTM standard and is intended only to provide the user of an ASTM standard an indication of what changes have been made to the previous version. Because
it may not be technically possible to adequately depict all changes accurately, ASTM recommends that users consult prior editions as appropriate. In all cases only the current version
of the standard as published by ASTM is to be considered the official document.
Designation: E2226 − 15 E2226 − 15a An American National Standard
Standard Practice for
1
Application of Hose Stream
This standard is issued under the fixed designation E2226; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
INTRODUCTION
Several fire-test-response standards (such as ASTM E119, E814, E2074, and E1966) in order to
assess the integrity of building elements after exposure to a specified test fire, require test specimens
to be evaluated by exposure to a hose stream. It is important to standardize certain elements of the hose
stream to promote uniformity in requirements. To attain this goal, this practice describes a standard
apparatus for delivering a solid stream of water and prescribes a standard method of subjecting
building elements to a hose stream after fire exposure.
1. Scope
1.1 This practice is applicable to building elements required to be subjected to the impact, erosion, and cooling effects of a hose
stream as part of a fire-test-response standard. Building elements include, but are not limited to, wall and partition assemblies,
fire-resistive joint systems, and doors.
1.2 This practice shall register performance of the building element under specific hose stream conditions. It shall not imply that,
either after exposure or under other conditions, the structural capability of the building element is intact or that the building element
is suitable for use.
1.3 The result derived from this practice is one factor in assessing the integrity of building elements after fire exposure. The
practice prescribes a standard hose stream exposure for comparing performance of building elements after fire exposure and
evaluates various materials and construction techniques under common conditions.
1.4 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical
conversions to SI units that are provided for information only and are not considered standard.
1.5 The text of this standard references notes which provide explanatory material. These notes shall not be considered as
requirements of the standard.
1.6 This fire standard cannot be used to provide quantitative measures.
1.7 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility
of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory
limitations prior to use.
2. Referenced Documents
2
2.1 ASTM Standards:
E119 Test Methods for Fire Tests of Building Construction and Materials
E176 Terminology of Fire Standards
E631 Terminology of Building Constructions
E814 Test Method for Fire Tests of Penetration Firestop Systems
E1966 Test Method for Fire-Resistive Joint Systems
1
This practice is under the jurisdiction of ASTM Committee E05 on Fire Standards and is the direct responsibility of Subcommittee E05.11 on Fire Resistance.
Current edition approved April 1, 2015June 1, 2015. Published May 2015July 2015. Originally approved in 2002. Last previous edition approved in 20122015 as
E2226–12.–15. DOI: 10.1520/E2226-15.10.1520/E2226-15A.
2
For referenced ASTM standards, visit the ASTM website, www.astm.org, or contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM Standards
volume information, refer to the standard’s Document Summary page on the ASTM website.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
1

---------------------- Page: 1 ----------------------
E2226 − 15a
E2074 Test Method for Fire Tests of Door Assemblies, Including Positive Pressure Testing of Side-Hinged and Pivoted Swinging
3
Door Assemblies (Withdrawn 2007)
2.2 UL Standard:
4
UL 385 Standard for Safety Play Pipes for Water Supply Testing in Fire-Protection Service
3. Terminology
3.1 Definitions—For definitions of terms used in this practice, refer to Terminologies E176 and E631.
3.2 Definitions of Terms Specific to This Standard:
3.2.1 building element, n—a component or assembly of materials using products manufactured as independent units capable of
being joined with or placed within other components or assemblies to create a structure.
3.2.2 exposed area, n—the total surface area of the test assembly that is subjected to the
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.