(Main)Heat exchangers - Hydronic room fan coil units - Test procedures for establishing the performance
Heat exchangers - Hydronic room fan coil units - Test procedures for establishing the performance
This European Standard applies to hydronic fan coil units (FCU) as factory-made single assemblies which provide the functions of cooling and/or heating but do not include the source of cooling or heating.
The standard covers both air free delivery and air ducted units with a maximum external static pressure due to duct resistance of 120 Pa max.
The standard applies to all types of fan speed control of a fan coil unit (variable speed, multispeed).
This standard deals with the cooling and heating functions of the FCU considered as an emitter for cooling/heating of a room/space. It does not cover any ventilation function of the unit.
If the FCU can also provide fresh air, this function is not considered and the fresh air inlet closed during testing.
This European Standard provides a method for the determination of the thermal performance of fan coil units in standard conditions, for the use with hot or chilled water or water mixtures. The test procedures given in this standard may additionally be used for determining performance at other conditions.
It also provides the method for the determination of the air flow rate supplied by the fan coil unit.
The standard does not cover the rating of heating or cooling from direct expansion coils or heating from electric resistance elements.
The standard does not cover acoustic performance of fan coil units which is dealt with in EN 16583.
It is not the purpose of this standard to specify the tests used for production or field testing.
NOTE For the purpose of remaining clauses, the term “unit” is used to mean “fan coil unit” as defined in 3.1.
Wärmeübertrager - Wasser-Luft-Ventilatorkonvektoren - Prüfverfahren zur Leistungsfeststellung
Diese Europäische Norm gilt für fabrikmäßig gefertigte einzelne Baueinheiten von Wasser-Luft-Ventilator-konvektoren (Ventilatorkonvektor, FCU, en: fan coil unit), die eine Kühl- und/oder Heizfunktion bieten, jedoch keine eigene Kühl- oder Heizquelle enthalten.
Diese Europäische Norm deckt sowohl Geräte mit ungehinderter Luftabgabe als auch solche mit Luftkanalanschluss ab, die aufgrund des Kanalwiderstands einen maximalen statischen Außendruck von höchstens 120 Pa aufweisen.
Diese Europäische Norm gilt für alle Arten der Drehzahlregelung für den Ventilator einer Ventilator-Rohrschlange (variable Drehzahl, mehrere Drehzahlen).
Diese Europäische Norm behandelt die Kühl- und die Heizfunktion des für das Kühlen/Heizen eines Raumes als Strahler angesehenen FCU. Die Lüftungsfunktion der Geräte wird nicht behandelt.
Sofern der FCU auch Frischluft bereitstellen kann, wird diese Funktion nicht berücksichtigt und der Frischlufteintritt bleibt während der Prüfung geschlossen.
Diese Europäische Norm enthält ein Verfahren zur Bestimmung des wärmetechnischen Verhaltens von Ventilatorkonvektoren unter Normbedingungen, bei Anwendung mit heißem oder gekühltem Wasser oder Wassergemischen. Die in dieser Norm angegebenen Prüfverfahren dürfen darüber hinaus zur Bestimmung des Verhaltens unter weiteren Bedingungen genutzt angewendet werden.
Die Norm enthält auch das Verfahren zur Bestimmung des durch den Ventilatorkonvektor bereitgestellten Luftvolumenstroms.
Diese Norm behandelt nicht die Bemessung der Heiz- oder Kühlleistung von Direktverdampfungsregistern bzw. der Heizleistung von elektrischen Widerstandsheizelementen.
Die vorliegende Norm deckt nicht das akustische Verhalten von Ventilatorkonvektoren ab; dieses wird in EN 16583 behandelt.
Die Festlegung von Produktions- oder Einsatzprüfungen ist nicht Zweck dieser Norm.
ANMERKUNG In den folgenden Abschnitten steht die Benennung 'Gerät' für 'Ventilatorkonvektor' entsprechend der Definition nach 3.1.
Échangeurs thermiques - Ventilo-convecteurs à eau - Procédures d'essai pour la détermination des performances
La présente Norme européenne s'applique aux ventilo-convecteurs à eau en tant qu'ensembles autonomes fabriqués en usine, assurant des fonctions de refroidissement et/ou de chauffage, mais n'incluant pas la source de refroidissement ou de chauffage.
La présente Norme européenne concerne les unités à soufflage libre et les unités raccordées sur l’air conçues pour une pression statique externe due à la résistance du circuit de 120 Pa maximum.
La présente Norme européenne s'applique à tous les types de régulation de vitesse du ventilateur d'un ventilo-convecteur (vitesse variable, multi-vitesse).
La présente Norme européenne traite des fonctions de refroidissement et de chauffage des ventilo-convecteurs à eau considérés comme source d’émission de refroidissement et de chauffage d'une salle ou d'un espace. Elle ne s'applique pas à la fonction ventilation de l’unité.
Si le ventilo-convecteur peut également délivrer de l'air neuf, cette fonction n'est pas prise en compte et l'arrivée d'air neuf doit être obturée pendant les essais.
La présente Norme européenne définit une méthode pour déterminer les performances thermiques de ventilo-convecteurs dans des conditions nominales de fonctionnement avec de l'eau chaude ou glacée, ou des solutions aqueuses. Les modes opératoires d'essai qui figurent dans la présente norme peuvent, en outre, être utilisés pour déterminer les performances dans d'autres conditions.
La présente norme définit également la méthode de détermination du débit d'air fourni par le ventilo-convecteur.
La présente norme ne traite pas de l’évaluation des caractéristiques de chauffage ou de refroidissement par batterie à détente directe ou de chauffage par éléments à résistances électriques.
La présente norme ne traite pas des performances acoustiques des ventilo-convecteurs. Celles-ci sont traitées dans l'EN 16583.
La présente norme n'a pas pour objet de spécifier les types d'essais utilisés en production ou sur site.
NOTE Pour les besoins des articles ci-après, le terme « unité » est utilisé pour désigner un « ventilo-convecteur » tel que défini en 3.1.
Prenosniki toplote - Ventilatorski konvektorji voda/zrak - Postopki preskušanja za ugotavljanje tehničnih karakteristik
This European Standard applies to hydronic fan coil units (FCU) as factory-made single assemblies which provide the functions of cooling and/or heating but do not include the source of cooling or heating.
The standard covers both air free delivery and air ducted units with a maximum external static pressure due to duct resistance of 120 Pa max.
The standard applies to all types of fan speed control of a fan coil (variable speed, multispeed).
This standard deals with the cooling and heating functions of the FCU considered as an emitter for cooling/heating of a room/space. It does not cover any ventilation function of the unit.
If the FCU can also provide fresh air, this function is not considered and the fresh air inlet closed during testing.
This European Standard provides a method for the determination of the thermal performance of fan coil units in standard conditions, for the use with hot or chilled water or water mixtures. The test procedures given in this standard may additionally be used for determining performance at other conditions.
It also provides the method for the determination of the air flow rate supplied by the fan coil unit. The standard does not cover the rating of heating or cooling from direct expansion coils or heating from electric resistance elements.
The standard does not cover acoustic performance of fan coil units which is dealt with in EN 16583. It is not the purpose of this standard to specify the tests used for production or field testing.
NOTE For the purpose of remaining clauses, the term “unit” is used to mean “fan coil unit” as defined in 3.1.
General Information
Relations
Standards Content (Sample)
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.Wärmeübertrager - Wasser-Luft-Ventilatorkonvektoren - Prüfverfahren zur LeistungsfeststellungÉchangeurs thermiques - Ventilo-convecteurs à eau - Procédures d'essai pour la détermination des performancesHeat exchangers - Hydronic room fan coil units - Test procedures for establishing the performance27.060.30Grelniki vode in prenosniki toploteBoilers and heat exchangersICS:Ta slovenski standard je istoveten z:EN 1397:2015SIST EN 1397:2015en,fr,de01-oktober-2015SIST EN 1397:2015SLOVENSKI
STANDARDSIST EN 1397:19991DGRPHãþD
EUROPEAN STANDARD NORME EUROPÉENNE EUROPÄISCHE NORM
EN 1397
August 2015 ICS 27.060.30 Supersedes EN 1397:1998English Version
Heat exchangers - Hydronic room fan coil units - Test procedures for establishing the performance
Échangeurs thermiques - Ventilo-convecteurs à eau - Procédures d'essai pour la détermination des performances Wärmeübertrager - Wasser-Luft-Ventilatorkonvektoren - Prüfverfahren zur Leistungsfeststellung This European Standard was approved by CEN on 3 July 2015.
CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN-CENELEC Management Centre or to any CEN member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC Management Centre has the same status as the official versions.
CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and United Kingdom.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION EUROPÄISCHES KOMITEE FÜR NORMUNG
CEN-CENELEC Management Centre:
Avenue Marnix 17,
B-1000 Brussels © 2015 CEN All rights of exploitation in any form and by any means reserved worldwide for CEN national Members. Ref. No. EN 1397:2015 ESIST EN 1397:2015
European foreword .3 1 Scope .4 2 Normative references .4 3 Terms and definitions .4 4 Designation of fan coil units .6 5 Symbols .6 6 Air flow rate test for ducted units .7 6.1 General conditions .7 6.2 Test installation .7 6.3 Pressure settings .8 6.4 Standard rating conditions .9 6.5 Test procedure .9 6.6 Data to be recorded . 10 7 Capacity rating tests . 10 7.1 General conditions . 10 7.2 Test room . 10 7.3 Installation of the test object . 11 7.4 Standard rating conditions . 11 7.5 Test method . 12 7.6 Measurements criteria . 13 7.7 Uncertainties of measurement from indicated values . 15 7.8 Test duration . 15 7.9 Data to be recorded . 16 8 Performance tests. 17 8.1 General . 17 8.2 Test conditions . 17 8.3 Sweat test . 17 8.4 Condensate disposal test . 17 9 Test report . 18 9.1 General information . 18 9.2 Additional information . 18 9.3 Test results . 18 10 Manufacturer's data . 19 Annex A (informative)
Drawings of the different types of configurations of fan coil units . 20 Annex B (informative)
Air flow rate test for non-ducted units . 23 Annex C (normative)
Design of separation partition for testing of cassette type fan coil units . 25
to entry: This device includes at least a liquid-to-air heat exchanger and a fan, and may be designed for free or ducted intake air and/or for free or ducted delivery of supply air. SIST EN 1397:2015
...