This document specifies the requirements and tests methods concerning the construction, safety, fitness for purpose, and rational use of energy, as well as the classification and marking of hybrid units.
A hybrid unit is composed of:
-   a gas boiler as a heat generator which is able to supply the heat demand in all operating conditions;
-   an electrical air-to-water heat pump, as a heat generator, which does not have to meet the heat demand in all operating conditions;
-   a control unit (see definition 3.1.10).
A hybrid unit can include the facility to produce hot water, either by the instantaneous or storage principle, the whole being marketed as a single unit.
A gas boiler as part of a hybrid unit covered by this document is a gas-fired central heating boiler from the types C1 up to C9 and the types B2, B3 and B5, according to the classification in EN 1749:2020:
a)   that have a nominal heat input (on the basis of gross calorific value) not exceeding 400 kW;
b)   that use one or more combustible gases of the three gas families at the pressures stated in EN 437:2021;
c)   where the temperature of the heat transfer fluid does not exceed 105 °C during normal operation;
d)   where the maximum operating pressure in the water circuit does not exceed 6 bar;
e)   which are classified as a gas-fired central heating boiler;
f)   which are intended to be installed either indoors or outdoors in a partially protected place;
g)   which are designed for either sealed water systems or for open water systems.
This document provides requirements for boilers with known constructions.
NOTE 1   For boilers with any alternative constructions, which might not fully be covered by this document, the risk associated with this alternative construction needs to be assessed.
NOTE 2   An example of an assessment methodology, based upon risk assessment and which covers the essential requirements of the Gas Appliance Regulation UE/426/2016, is given in Clause 11.
This document does not cover all the requirements for:
aa)   appliances that are intended to be connected to gas grids where the quality of the distributed gas is likely to vary to a large extent over the lifetime of the appliance (see EN 15502-1:2021, Annex AB);
ab)   appliances using flue dampers;
ac)   appliances of the types B21, B31, B51, C21, C41, C51, C61, C71 and C81;
ad)   appliances incorporating flexible plastic flue liners;
ae)   appliances designed to become connected to a combined flue duct system.
af)   appliances of the types C(10),C(11), C(12) and C(13);
ag)   C7 appliances that have a nominal heat input (on the basis of net calorific value) exceeding 70 kW;
ah)   appliances intended to be connected to a flue having mechanical extraction;
ai)   surface temperatures of external parts particular to children and elderly people;
aj)   appliances that are intended to burn natural gases of the second family where hydrogen is added to the natural gas;
ak)   appliances equipped with an adaptive combustion control function (ACCF);
al)   boilers intended to be installed in areas accessible to elderly people and children.
This document specifies minimum operating requirements which ensure that the products are fit for the use designated by the technical instructions when used for space heating and/or DHW production.
This document is intended to be used in conjunction with:
ba)   the gas-fired boiler, the generic part EN 15502-1:2021 and specific parts FprEN 15502-2-1:2022 and FprEN 15502-2-2:2022;
bb)   the electrical heat pump, EN 14511-4:2018, EN 378-1:2016+A1:2020, EN 378-2:2016 and EN 14825:2022;
bc)   electrical safety, EN 60335-1:2012 , EN 60335-2-102:2016 and IEC 60335-2-40:2018;
bd)   for domestic hot water production, EN 13203-5:2022.

  • Standard
    42 pages
    English language
    sale 10% off
    e-Library read for
    1 day
  • Draft
    42 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This document is applicable to gas-fired appliances producing domestic hot water. It applies to sorption heat pumps connected to or including a domestic hot water storage tank. It applies to a package marketed as single unit or fully specified that have:
-   a heat input not exceeding 400 kW;
-   a hot water storage tank capacity (if any) not exceeding 2 000 l.
In the case of gas-fired sorption heat pumps, with or without storage tank, domestic hot water production is integrated or coupled, the whole being marketed as a single unit.
EN 13203-1:2015 sets out in qualitative and quantitative terms the performance in delivery of domestic hot water for a selected variety of uses. It also gives a system for presenting the information to the user. The present document sets out a method for assessing the energy performance of the appliances. It specifies a number of daily load profiles for each domestic hot water use, kitchen, shower, bath and a combination of these, together with corresponding test procedures, enabling the energy performances of different gas-fired appliances to be compared and matched to the needs of the user. Where other technologies are combined with a gas-fired sorption heat to produce domestic hot water, specific parts of EN 13203 apply.
Horizontal ground heat sources are not covered by the scope of the present document.

  • Standard
    32 pages
    English language
    sale 10% off
    e-Library read for
    1 day
  • Draft
    29 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This document is applicable to gas-fired appliances producing domestic hot water. It applies to condensing combination boilers with passive flue heat recovery device (PFHRD) that have:
-   a heat input not exceeding 400 kW;
-   a hot water storage tank capacity (if any) not exceeding 2 000 l;
-   a declared load profile between M to 4XL.
In the case of combination boilers, with or without storage tank, domestic hot water production is integrated or coupled, the whole being marketed as a single unit.
For this document, some tests and calculation results of EN 13203-2:2022 are used to calculate the energy consumptions.

  • Standard
    26 pages
    English language
    sale 10% off
    e-Library read for
    1 day
  • Draft
    17 pages
    English language
    sale 10% off
    e-Library read for
    1 day
  • Draft
    21 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This document is applicable to gas-fired appliances producing domestic hot water. It applies to both instantaneous and storage tank appliances; waters-heaters and combination boilers that have:
-   a heat input not exceeding 400 kW;
-   a hot water storage tank capacity (if any) not exceeding 2 000 l.
In the case of combination boilers, with or without storage tank, domestic hot water production is integrated or coupled, the whole being marketed as a single unit.
The water heaters covered by the present standard are considered "conventional water heaters" as defined by the Transitional Methods (Commission Communication 2014/C 207/03) then in the calculation formula for the Annual Electricity Consumption (AEC), Qcor is equal to zero.
In case of the boiler is equipped with an internal or external Passive Flue Heat Recovery Device (PFHRD), the boiler efficiency can be assessed by applying EN 13203-2:2022 in combination with EN 13203-7:2022. In case of a PFHRD, where the technology has the ability to recover energy out of flue gasses during central heating production to be able to preheat the domestic hot water (indirect contribution), to assess this indirect contribution EN 13203-7:2022 applies. EN 13203-2:2022 is applicable for measuring and calculating the direct efficiency (direct contribution) while combining the measuring results of EN 13203-7:2022 the overall efficiency (direct and indirect) can be calculated. EN 13203-1:2015 sets out in qualitative and quantitative terms the performance in delivery of domestic hot water for a selected variety of uses. It also gives a system for presenting the information to the user. The present document sets out a method for assessing the energy performance of the appliances. It specifies a few daily load profiles for each domestic hot water use, kitchen, shower, bath and a combination of these, together with corresponding test procedures, enabling the energy performances of different gas-fired appliances to be compared and matched to the needs of the user. Where other technologies are combined with a gas-fired boiler or a water heater to produce domestic hot water, specific parts of EN 13203 apply.

  • Standard
    43 pages
    English language
    sale 10% off
    e-Library read for
    1 day
  • Draft
    43 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This document is applicable to gas-fired mCHP appliances producing domestic hot water and electricity. The electricity is generated in a process linked to the production of useful heat.
It applies to a mCHP appliances marketed as single unit or as a package fully specified by a manufacturer that have:
-   a gas heat input not exceeding 400 kW;
-   an electrical output not exceeding 50 kW;
-   a hot water storage capacity (if any) not exceeding 2 000 l.
EN 13203-1:2015 sets out in qualitative and quantitative terms the performance in delivery of domestic hot water for a variety of uses. It also gives a system for presenting the information to the user.
The present document sets out a method for assessing the energy performance of gas fired mCHP appliances. It defines several daily tapping cycles for each domestic hot water use, kitchen, shower, bath and a combination of these, together with corresponding test procedures, enabling the energy performances of different gas-fired appliances to be compared and matched to the needs of the user.
When the mCHP generator does not supply domestic hot water in the summer period, the present standard is not applicable. EN 13203-2:2022 is used for performance assessment of these generators.

  • Standard
    26 pages
    English language
    sale 10% off
    e-Library read for
    1 day
  • Draft
    25 pages
    English language
    sale 10% off
    e-Library read for
    1 day
  • Draft
    26 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This document is applicable to solar supported gas-fired appliances producing domestic hot water. It applies to a system marketed as single unit or a fully specified system that:
-   has a gas heat input not exceeding 70 kW;
-   has a hot water storage tank capacity not exceeding 500 l;
-   is equipped with at least one solar collector;
-   is, with regard to the solar hydraulic circuit, considered as a forced circulation system (definition according to EN ISO 9488:1999).
The appliances covered by this document are described in Annex E (normative).
This document does not apply to thermo-siphon or integral collector storage tank systems according to definitions given by EN ISO 9488:1999.
NOTE   In principle, the energy consumption of thermo-siphon solar preheat systems and integral collector storage tank preheat systems can also be assessed based on this document. One appropriate procedure for that purpose is to calculate the temperature level of the domestic hot water withdrawn from the thermal solar system for the reference conditions specified in this standard by using the numerical system model and the thermal solar system performance parameters according to ISO 9459-5. Based on the temperature level of the hot water withdrawn from the store the energy consumption of the gas appliance is determined. This determination can either be done by means of calculations or by performing a test according to EN 13203 2:2022 and using instead of the cold water inlet temperature the hot water temperature withdrawn from the store.
This document is not intended to assess the performance:
-   of the solar collector(s), which should comply with EN 12975-1:2006+A1:2010 and EN 12975-2:2006;
-   of thermal solar systems and components, which should comply with EN 12976-1:2021 and EN 12976-2:2019.
EN 13203-1:2015 sets out in qualitative and quantitative terms the performance in delivery of domestic hot water for a selected variety of uses. It also gives a presenting the information to the user.
The present document sets out a method for assessing the energy performance of a solar supported appliance. It specifies a few daily tapping cycles for each domestic hot water use, kitchen, shower, bath and a combination of these, together with corresponding test procedures including information about the available solar radiation. It enables the energy performances of different gas-fired appliances to be compared and matched to the needs of the user.

  • Standard
    22 pages
    English language
    sale 10% off
    e-Library read for
    1 day
  • Draft
    22 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This document is applicable to gas-fired appliances producing domestic hot water. It applies to both instantaneous and storage gas-fired combined with electric heat pump.
It applies to a package marketed as single unit or fully specified by the manufacturer that have:
-   a heat input not exceeding 400 kW;
-   a hot water storage tank capacity (if any) not exceeding 2 000 l.
EN 13203-1:2015 sets out in qualitative and quantitative terms the performance in delivery of domestic hot water for a selected variety of uses. It also gives a system for presenting the information to the user. The present document sets out a method for assessing the energy performance of gas fired appliances combined with heat pump with electrically driven compressor according to EN 16147. It specifies a number of daily load profiles for each domestic hot water use, kitchen, shower, bath and a combination of these, together with corresponding test procedures, enabling the energy performances of different gas-fired appliances to be compared and matched to the needs of the user. Where other technologies are combined with a gas-fired boiler or a water heater to produce domestic hot water, specific parts of EN 13203 apply.
The present document does not apply for gas boilers with recovery systems using combustion products as heat source for the electrical heat pump.
When the electrical heat pump does not work for domestic hot water production in the summer period, the present standard is not applicable for energy performances assessing, instead EN 13203-2:2022 is applicable.

  • Standard
    37 pages
    English language
    sale 10% off
    e-Library read for
    1 day
  • Draft
    33 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This European Standard specifies, the requirements and test methods concerning, in particular the construction, safety, fitness for purpose, and rational use of energy, as well as the classification and marking of gas-fired central heating boilers that are fitted with atmospheric burners, fan assisted atmospheric burners and are hereafter referred to as boilers.
Where the word boiler is used, this is to be read as the boiler including its connecting ducts, ducts and terminals, if any.
This European Standard covers gas-fired central heating boilers type B11, B11BS, B12, B12BS, B13, B13BS according to the classification in CEN/TR 1749:2009:
a)   that have a nominal heat input (on the basis of net calorific value) not exceeding 70 kW;
b)   that use one or more combustible gases of the three gas families at the pressures stated in EN 437;
c)   where the temperature of the heat transfer fluid does not exceed 105 °C during normal operation;
d)   where the maximum operating pressure in the water circuit does not exceed 6 bar;
e)   which are declared in the technical instructions to be either a low temperature boiler or a standard boiler. If no declaration is given the boiler is to be considered a standard boiler;
f)   which are intended to be installed either indoors or in a partially protected place;
g)   which are either not intended to produce hot water, or are intended to produce hot water either by the instantaneous or storage principle, the whole being marketed as a single unit.
h)   which are designed for either sealed water systems or for open water systems.
This European Standard is to be used in conjunction with the General Requirements Standard EN 15502 1.
For applications within the scope of the PED further requirements may be necessary (e.g. situations where the maximum allowable temperature exceeds 110 °C, or where volume times maximum allowable pressure is over 50 bar x litres).
This standard provides requirements for boilers with known constructions. For boilers with any alternative constructions, which might not fully be covered by this standard, the risk associated with this alternative construction shall be assessed.
An example of an assessment methodology, based upon risk assessment and which covers the essential requirements of the Gas Appliance Directive, is given in Clause 11.
This standard does not cover all the requirements for:
i)   appliances that are intended to be connected to gas grids where the quality of the distributed gas is likely to vary to a large extent over the lifetime of the appliance (see Annex DD of EN 15502 2 1:2012);
j)   appliances using flue dampers;
k)   appliances that have a nominal heat input (on the basis of net calorific value) exceeding 70 kW;
l)   appliances of the types A, B14, B2, B3, B4, B5 and C;
m)   appliances intended to be connected to a (common) flue having mechanical extraction;
n)   appliances with gas/air ratio control;
o)   modular boilers;
p)   boilers which can give rise to condensation under certain circumstances;
q)   boilers intended to be installed in a room with a foreseeable negative pressure relative to the pressure in the flue system.
NOTE   Negative pressure relative to the pressure in the flue system can for example be caused by mechanical or thermal ventilation in airtight buildings.

  • Standard
    46 pages
    English language
    sale 10% off
    e-Library read for
    1 day
  • Draft
    45 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This European Standard is applicable to gas-fired appliances producing domestic hot water. It applies to both instantaneous and storage appliances; water-heaters and combination boilers that have:
-   heat input not exceeding 70 kW; and
-   hot water storage capacity (if any) not exceeding 500 l.
In the case of combination boilers, with or without storage tank, domestic hot water production is integrated or coupled, the whole being marketed as a single unit.
This European Standard sets out in qualitative and quantitative terms the performance in delivery of domestic hot water for a selected variety of uses. It also gives a system for presenting the information to the user.

  • Standard
    32 pages
    English language
    sale 10% off
    e-Library read for
    1 day
  • Draft
    32 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This European Standard specifies the requirements and test methods for the construction, the safety and the rational energy usage for gas-fired central heating boilers equipped with a forced draught burner. These boilers are formed of the assembly of a boiler body and a forced draught gas burner achieved on the production site of the manufacturer, the whole being designed and marketed as a complete boiler. The boiler body shall be in accordance with EN 303-1. The construction of the forced draught gas burner shall be in accordance with EN 676.

  • Standard
    61 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This European Standard specifies the requirements and test methods concerning, in particular, the construction, safety, fitness for purpose, and rational use of energy, as well as the classification and marking of gas-fired central heating boilers that are fitted with atmospheric burners, fan assisted atmospheric burners or fully premixed burners, and are hereafter referred to as “boilers”.
This European Standard applies to boilers of type B, as listed in 4.2:
¾   that use one or more combustible gases of the three gas families at the pressures stated in Tables 16 and 17;
¾   that have a nominal heat input (on the basis of net calorific value) exceeding 300 kW, but not exceeding 1  000 kW, including modular boilers;
¾   where the temperature of the heat transfer fluid does not exceed 105 °C during normal operation;
¾   where the maximum operating pressure in the water circuit does not exceed 6 bar;
¾   that can give rise to condensation under certain circumstances;
¾   of the standard and low-temperature types.
This European Standard applies to boilers designed for sealed water systems or for open water systems.
This European Standard does not contain all the requirements necessary for boilers:
¾   intended to be installed in the open or in living rooms;
¾   permanently fitted with more than one flue outlet;
¾   where the combustion circuit is sealed with respect to the room where the boiler is installed;
¾   of the condensing type;
¾   intended to be connected to a common flue having mechanical extraction;
¾   fitted with a forced draught burner in accordance with EN 676 (see EN 303-7);
¾   producing hot water for domestic purposes.
This standard only covers type testing.
Matters related to quality assurance systems, tests during production, and certificates of conformity of auxiliary devices are not dealt with in this European Standard.

  • Standard
    138 pages
    English language
    sale 10% off
    e-Library read for
    1 day

Replace the second paragraph by the following text :
"This European Standard applies to standard boilers and low-temperature boilers with a nominal heat output not exceeding 1000 kW and with a water temperature at normal operation not exceeding 105 °C."
Replace the 2nd dash of the third paragraph by the following text :
"- condensing boilers;"
Delete the last but one paragraph of EN 303-3 :
"This European Standard does not contain all the necessary requirements for low temperature boilers. Nevertheless, the testing methods defined by this European Standard for the determination of useful efficiencies can be used for low temperature boilers, after being adapted in accordance with annex H."

  • Amendment
    10 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This European Standard specifies the requirements and test methods for the construction, the safety and the rational energy usage of an assembly made up of a boiler body complying with EN 303- 11) and a forced draught gas burner complying with EN 676, using combustible gases, hereafter referred to as a "boiler".  This European Standard applies to a boiler:  - with a nominal output not exceeding 1 000 kW.  This European Standard does not contain all the necessary requirements for:  - assemblies designed as units;  - condensing boilers and low temperature boilers;  - boilers intended to be installed in the open;  - boilers permanently fitted with more than one flue outlet;  - boilers fitted with a draught diverter;  -  boilers intended to be connected to a common flue having mechanical    extraction.  This European Standard does not apply to living-space dedicated boilers   If the boiler body has already been tested with a liquid fuel burner, in accordance with EN 303-1, EN 303-2 and EN 304, only the tests described in annex G need to be performed.  In the case of a range of boilers, see annex F.  This European Standard does not contain all the necessary requirements for low temperature boilers. Nevertheless, the testing methods defined by this European Standard for the determination of useful efficiencies can be used for low temperature boilers, after being adapted in accordance with annex H.  This European Standard only covers type testing.

  • Standard
    47 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This European Standard specifies, the requirements and test methods concerning the classification and marking of gas-fired central heating boilers that are fitted with atmospheric burners, fan assisted atmospheric burners and are hereafter referred to as 'boilers'.
Where the word boiler is used, this is to be read as the boiler including its connecting ducts, ducts and terminals, if any.
This document is to be used in conjunction with FprEN 15502-1:2021
This European Standard covers gas-fired central heating boilers type B11, B11BS, B12, B12BS, B13, B13BS:
NOTE For further background information on appliance types see EN 1749:2020
a)   that have a nominal heat input (on the basis of net calorific value) not exceeding 70 kW;
b)   that use one or more combustible gases of the three gas families at the pressures stated in EN 437:2018;
c)   where the temperature of the heat transfer fluid does not exceed 105 °C during normal operation;
d)   where the maximum operating pressure in the water circuit does not exceed 6 bar;
e)   which are declared in the technical instructions to be either a 'low temperature boiler' or a 'standard boiler'. If no declaration is given the boiler is to be considered a 'standard boiler';
f)   which are intended to be installed inside a building or in a partially protected place;
g)   which are intended to produce also hot water either by the instantaneous or storage principle, as a single unit.
h)   which are designed for either sealed water systems or for open water systems.
For applications within the scope of the PED further requirements may be necessary (e.g. situations where the maximum allowable temperature exceeds 110 °C, or where volume times maximum allowable pressure is over 50 bar x litres).
NOTE This standard provides requirements for boilers with known constructions. For boilers with any alternative constructions, which might not fully be covered by this standard, the risk associated with this alternative construction needs to be assessed.
An example of an assessment methodology, based upon risk assessment, is given in Clause 11.
This standard does not cover all the requirements for:
i)   appliances that are intended to be connected to gas grids where the quality of the distributed gas is likely to vary to a large extent over the lifetime of the appliance (see Annex AB);
j)   appliances using flue dampers;
k)   appliances that have a nominal heat input (on the basis of net calorific value) exceeding 70 kW;
l)   appliances of the types A, B14, B2, B3, B4, B5 and C;
m)   appliances intended to be connected to a (common) flue having mechanical extraction;
n)   appliances with gas/air ratio control;
o)   modular boilers;
p)   boilers which can give rise to condensation under certain circumstances;
q)   boilers intended to be installed in a room with a foreseeable negative pressure relative to the pressure in the flue system;
r)   surface temperatures of external parts particular to children and elderly people;
s)   appliances that are intended to burn natural gases of the second family where hydrogen is added to the natural gass;
t)   boilers intended to be installed in areas accessible to elderly people and children.
NOTE   Negative pressure relative to the pressure in the flue system can for example be caused by mechanical or thermal ventilation in airtight buildings.

  • Draft
    64 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This document is applicable to gas-fired appliances producing domestic hot water. It applies to both instantaneous and storage appliances; water-heaters and combination boilers that have:
-   heat input not exceeding 70 kW; and
-   hot water storage capacity (if any) not exceeding 500 l.
In the case of combination boilers, with or without storage tank, domestic hot water production is integrated or coupled, the whole being marketed as a single unit.
This document sets out in qualitative and quantitative terms the performance in delivery of domestic hot water for a selected variety of uses. It also gives a system for presenting the information to the user.

  • Draft
    35 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This European Standard is applicable to gas-fired appliances producing domestic hot water. It applies to both instantaneous and storage gas-fired appliances combined with electrical heat pump. It applies to a package marketed as single unit or fully specified by a manufacturer that have:   - a gas heat input not exceeding 70 kW;  - a hot water storage capacity not exceeding 500 litres.  This European Standard EN 13203 is formed in several parts which cover aspects of domestic hot water production.  Standard EN 13203-1 sets out in qualitative and quantitative terms the performance in delivery of domestic hot water for a selected variety of uses. It also gives a system for presenting the information to the user. This first part complements EN 26, EN 89 and EN 625.  This Part 5 sets out a method for assessing the energy performance of gas fired appliances combined with heat pump with electrically driven compressor according to EN 16417.  This European standard does not apply for gas boilers with recovery systems using combustion products as heat source for the electrical heat pump.  When the electrical heat pump does not work for domestic hot water production in the summer period, the present standard is not applicable for energy performances assessing, EN 13203-2 must be used for energy performances assessing.

  • Draft
    29 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This European Standard is applicable to gas-fired micro CHP appliances producing domestic hot water and electricity. The electricity is generated in a process linked to the production of useful heat.
It applies to a system marketed as single unit or a system fully specified by a manufacturer that have:
- a gas heat input not exceeding 70 kW;
- an electrical output not exceeding 50 kWe; and
- a hot water storage capacity not exceeding  500 litres.
This European Standard EN 13203 is formed in four parts which cover aspects of domestic hot water production.
Standard EN 13203-1 sets out in qualitative and quantitative terms the performance in delivery of domestic hot water for a selected variety of uses. It also gives a system for presenting the information to the user. This first part complements EN 26, EN 89 and EN 625.
Standard EN 13203-2 sets out a method for assessing the energy performance of the appliances. It defines a number of daily tapping cycles for each domestic hot water use, kitchen, shower, bath and a combination of these, together with corresponding test procedures, enabling the energy performances of different gas-fired appliances to be compared and matched to the needs of the user.
Standard EN 13203-3 deals with solar systems.
Note : a draft standard prEN 13203-5 for "Gas-fired domestic appliance producing hot water - Part 5 : Assessment of energy consumption of gas fired appliances combined with electrical heat pump not exceeding 70 kW heat input and 300 l water storage capacity" is also under preparation by CEN/TC109/WG4.
All standards and drafts series EN 13203 are worked out under Mandate M324 against Energy Labelling Directive 92/75/EC under revision.

  • Draft
    26 pages
    English language
    sale 10% off
    e-Library read for
    1 day

When final draft in CCMC - Double check that a decision (to submit to FV) is taken both by CEN/TC 166 and CEN/TC 109 - See CEN/BT Decision 72/2014

  • Draft
    27 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This standard specifies the requirements and test methods concerning, in particular the construction, safety, fitness for purpose, and rational use of energy, as well as the classification and marking of gas-fired central heating boilers that are fitted with atmospheric burners, fan assisted atmospheric burners or fully premixed burners, and are hereafter referred to as "boilers".This standard applies to boilers of type C:- that use one or more combustible gases of the three gas families;- that have a nominal heat input (on the basis of net caloric value)exceeding 70 kW, but not exceeding 1000 kW, including modular boilers;- where the temperature of the heat transfer fluid does not exceed 105°C during normal operation;- where the maximum operating pressure in the water circuit does not exceed 6 bar;- which can give rise to condensation under certain circumstances.The standard applies to boilers designed for sealed water systems or for open water systems.The standard does not contain all the requirements necessary for boilers:- intended to be installed in the open or in living rooms;- permanently fitted with more than one flue outlet;- of the condensing type;- intended to be connected to a common flue having mechanical extraction;- type C41, C51, C61, C7, and C81 boilers;- fitted with a forced draught burner in accordance with EN 676;- producing hot water for domestic purposes.This standard only covers type testing.

  • Draft
    164 pages
    English language
    sale 10% off
    e-Library read for
    1 day

Amendment for the addition of ecodesign requirements (Regulation No 813/2013)
and energy labelling requirements (Regulation No 811/2013)
This European Standard specifies the common requirements and test methods concerning, in particular the construction, safety, fitness for purpose, and rational use of energy, as well as the classification, marking and energy labelling of gas-fired central heating boilers that are fitted with atmospheric burners, fan assisted atmospheric burners or fully premixed burners, and are hereafter referred to as “boilers”.
This European Standard is to be used in conjunction with the specific Parts 2 (Part 2-1 and following ones).
This European Standard applies to boilers of types B and C, according to CEN/TR 1749:2014:
a)   that use one or more combustible gases of the three gas families at the pressures stated in EN 437;
b)   where the temperature of the heat transfer fluid does not exceed 105 °C during normal operation;
c)   where the maximum operating pressure in the water circuit does not exceed 6 bar;
d)   which can give rise to condensation under certain circumstances;
e)   which are declared in the installation instructions to be either a “condensing” boiler or a "low temperature boiler" or a “standard boiler”. If no declaration is given the boiler is to be considered a “standard boiler”
f)   which are intended to be installed inside a building or in a partially protected place;
g)   which are intended to produce hot water either by the instantaneous or storage principle, the whole being marketed as a single unit.
This European Standard applies to boilers designed for sealed water systems or for open water systems.
This general standard and the specific standards (see Part 2) provide requirements for boilers with known constructions. For boilers with any alternative constructions, which might not fully be covered by this standard or a specific standard, the risk associated with this alternative construction will need to be assessed.
An example of an assessment methodology, based upon risk assessment, is given in Clause 11.
This European Standard is not intended to cover appliances intended for connection to gas grids where the quality of the distributed gas is likely to vary to a large extent over the lifetime of the appliance.

  • Draft
    43 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This document specifies the requirements and test methods, as well as the classification and marking of gas-fired central heating boilers that are fitted with atmospheric burners, fan assisted atmospheric burners or fully premixed burners, and are hereafter referred to as "boilers".
This document is intended to be used in conjunction with EN 15502-1:2021.
This document covers gas-fired central heating boilers from the types C1 up to C(11) and the types B2, B3 and B5:
NOTE 1   For further background information on appliance types see EN 1749:2020.
a)   that have a nominal heat input (on the basis of net calorific value) not exceeding 1 000 kW;
b)   that use one or more combustible gases of the three gas families at the pressures stated in EN 437:2021;
c)   where the temperature of the heat transfer fluid does not exceed 105 °C during normal operation;
d)   where the maximum operating pressure in the water circuit does not exceed 6 bar;
e)   which can give rise to condensation under certain circumstances;
f)   which are declared in the instructions for installation to be either a "condensing" boiler or a "low temperature boiler" or a "standard boiler"; if no declaration is given the boiler is to be considered a "standard boiler";
g)   which are intended to be installed inside a building or in a partially protected place;
h)   which are intended to produce also hot water either by the instantaneous or storage principle as a single unit;
i)   which are designed for either sealed water systems or for open water systems;
j)   which are either modular boilers, or non-modular boilers.
k)   which are from the types C(10) that are equipped with a gas-air ratio control and that have a ∆pmax, saf(min) of 25 Pa, and C(11) that have condensing boiler modules that are equipped with a gas-air ratio control and that have a ∆pmax, saf(min) of 25 Pa.
NOTE 2   This document provides requirements for boilers with known constructions. For boilers with any alternative constructions, which might not fully be covered by this standard, the risk associated with this alternative construction needs to be assessed.
An example of an assessment methodology, based upon risk assessment, is given in Clause 11.
This document does not cover all the requirements for:
aa)   appliances above 1 000 kW;
ab)   appliances that are intended to be connected to gas grids where the quality of the distributed gas is likely to vary to a large extent over the lifetime of the appliance (see Annex AB of EN 15502-1:2021);
ac)   appliances using flue dampers;
ad)   appliances of the types B21, B31, B51, C21, C41, C51, C61, C71, C81, C(12) and C(13);
ae)   C7 appliances that have a nominal heat input (on the basis of net calorific value) exceeding 70 kW;
af)   appliances incorporating flexible plastic flue liners;
ag)   C(10) boilers:
1)   without a gas-air ratio control, or
2)   which are non-condensing appliances, or
3)   which have a maximum safety pressure difference at minimum heat input not equal to 25 Pa (∆pmax, saf(min));
ah)   C(11) boilers that have boiler modules:
1)   without a gas-air ratio control, or
2)   which are non-condensing appliances, or
3)   which have a maximum safety pressure difference at minimum heat input not equal to 25 Pa (∆pmax, saf(min));
ai)   appliances intended to be connected to a flue having mechanical extraction;
aj)   surface temperatures of external parts particular to children and elderly people;
ak)   appliances that are intended to burn natural gases of the second family where hydrogen is added to the natural gas;
al)   appliances equipped with an adaptive combustion control function (ACCF);
am)   boilers intended to be installed in areas accessible to elderly people and children.

  • Standard
    107 pages
    English language
    sale 10% off
    e-Library read for
    1 day
  • Draft
    109 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This European Standard specifies the common requirements and test methods, as well as the classification, marking and energy labelling of gas-fired central heating boilers that are fitted with atmospheric burners, fan assisted atmospheric burners or fully premixed burners, and are hereafter referred to as “boilers”.
This European Standard is to be used in conjunction with the specific Parts 2 (Part 2-1 and following ones).
This European Standard applies to boilers of types B and C.
NOTE For further background information on appliance types see CEN/TR 1749:2014 [1].
a) that use one or more combustible gases of the three gas families at the pressures stated in EN 437;
b) where the temperature of the water is below or above 105 °C during normal operation;
c) where the maximum operating pressure in the water circuit does not exceed 6 bar;
d) which can give rise to condensation under certain circumstances;
e) which are declared in the instructions for installation to be either a "condensing" boiler or a "low temperature boiler" or a "standard boiler" or an "other boiler". If no declaration is given the boiler is to be considered both a "standard boiler" and an "other boiler";
NOTE The Ecodesign Directive defines "other boilers", "low temperature boilers" and "condensing boilers". The Boiler Efficiency Directive defines "standard boilers", "low temperature boilers" and "condensing boilers". Depending on the legislation applied, a boiler can be both "a standard boiler" and an "other boiler"."
f) which are intended to be installed inside a building or in a partially protected place;
g) which are intended to produce also hot water either by the instantaneous or storage principle as a single unit.
This European Standard applies to boilers designed for sealed water systems or for open water systems.
NOTE This general standard and the specific standards (see Part 2) provide requirements for boilers with known constructions. For boilers with any alternative constructions, which might not fully be covered by this standard or a specific standard, the risk associated with this alternative construction will need to be assessed.
An example of an assessment methodology, based upon risk assessment, is given in Clause 11.
This European Standard is not intended to cover appliances intended for connection to gas grids where the quality of the distributed gas is likely to vary to a large extent over the lifetime of the appliance (see Annex EE).
This European Standard is not intended to cover appliances designed and constructed to burn gas containing toxic components.

  • Corrigendum
    3 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This European Standard specifies the common requirements and test methods, as well as the classification, marking and energy labelling of gas-fired central heating boilers that are fitted with atmospheric burners, fan assisted atmospheric burners or fully premixed burners, and are hereafter referred to as “boilers”.
This European Standard is to be used in conjunction with the specific Parts 2 (Part 2-1 and following ones).
This European Standard applies to boilers of types B and C.
NOTE For further background information on appliance types see CEN/TR 1749:2014 [1].
a) that use one or more combustible gases of the three gas families at the pressures stated in EN 437;
b) where the temperature of the water is below or above 105 °C during normal operation;
c) where the maximum operating pressure in the water circuit does not exceed 6 bar;
d) which can give rise to condensation under certain circumstances;
e) which are declared in the instructions for installation to be either a "condensing" boiler or a "low temperature boiler" or a "standard boiler" or an "other boiler". If no declaration is given the boiler is to be considered both a "standard boiler" and an "other boiler";
NOTE The Ecodesign Directive defines "other boilers", "low temperature boilers" and "condensing boilers". The Boiler Efficiency Directive defines "standard boilers", "low temperature boilers" and "condensing boilers". Depending on the legislation applied, a boiler can be both "a standard boiler" and an "other boiler"."
f) which are intended to be installed inside a building or in a partially protected place;
g) which are intended to produce also hot water either by the instantaneous or storage principle as a single unit.
This European Standard applies to boilers designed for sealed water systems or for open water systems.
NOTE This general standard and the specific standards (see Part 2) provide requirements for boilers with known constructions. For boilers with any alternative constructions, which might not fully be covered by this standard or a specific standard, the risk associated with this alternative construction will need to be assessed.
An example of an assessment methodology, based upon risk assessment, is given in Clause 11.
This European Standard is not intended to cover appliances intended for connection to gas grids where the quality of the distributed gas is likely to vary to a large extent over the lifetime of the appliance (see Annex EE).
This European Standard is not intended to cover appliances designed and constructed to burn gas containing toxic components.

  • Standard
    213 pages
    English language
    sale 10% off
    e-Library read for
    1 day
  • Draft
    215 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This European Standard specifies, the requirements and test methods concerning, in particular, the construction, safety, fitness for purpose, and rational use of energy, as well as the classification and marking of gas-fired central heating boilers that are fitted with atmospheric burners, fan assisted atmospheric burners or fully premixed burners, and are hereafter referred to as boilers.
Where the word boiler is used, it needs to be read as the boiler including its connecting ducts, ducts and terminals, if any.
This European Standard covers gas-fired central heating boilers from the types C1 up to C9 and the types B2, B3 and B5:
NOTE   For further background information on appliance types see CEN/TR 1749:2014.
a)   that have a nominal heat input (on the basis of net calorific value) not exceeding 1 000 kW;
b)   that use one or more combustible gases of the three gas families at the pressures stated in EN 437;
c)   where the temperature of the heat transfer fluid does not exceed 105 °C during normal operation;
d)   where the maximum operating pressure in the water circuit does not exceed 6 bar;
e)   which may or may not give rise to condensation under certain circumstances;
f)   which are declared in the installation instructions to be either a condensing boiler or a "low temperature boiler" or a standard boiler; if no declaration is given the boiler is to be considered a standard boiler;
g)   which are intended to be installed either indoors or outdoors in a partially protected place;
h)   which may include the facility to produce hot water, either by the instantaneous or storage principle, the whole being marketed as a single unit;
i)   which are designed for either sealed water systems or for open water systems;
j)   which are either modular boilers, or non- modular boilers.
This European Standard also covers gas-fired condensing central heating boilers from the types C(10) that are equipped with a gas-air ratio control and that have a ∆pmax, saf(min) of 25 Pa, ).and C(11) boilers that have condensing boiler modules that are equipped with a gas-air ratio control and that have a ∆pmax, saf(min) of 25 Pa.
This European Standard provides requirements for boilers with known constructions. For boilers with any alternative constructions, which might not fully be covered by this standard, the risk associated with this alternative construction needs to be assessed.
An example of an assessment methodology, based upon risk assessment and which covers the essential requirements of the Gas Appliance Directive, is given in Clause 11.
This European Standard does not cover all the requirements for:
k)   Appliances that are intended to be connected to gas grids where the quality of the distributed gas is likely to vary to a large extent over the lifetime of the appliance (see Annex XC);
l)   Appliances using flue dampers;
m)   Appliances of the types B21, B31, B51, C21, C41, C51, C61, C71, C81 ,C(12) and C(13);
n)   C7 appliances that have a nominal heat input (on the basis of net calorific value) exceeding 70 kW;
o)   Appliances incorporating flexible plastic flue liners;
p)   C(10) boilers:
1)    without a gas-air ratio control, or
2)    which are non-condensing appliances, or
3)    which have a maximum safety pressure difference at minimum heat input not equal to 25 Pa (∆pmax, saf(min)), - ;
q)   C(11) boilers that have boiler modules:
1)    without a gas-air ratio control, or
2)    which are non-condensing appliances, or
3)    which have a maximum safety pressure difference at minimum heat input not equal to 25 Pa (∆pmax, saf(min));
r)   Appliances intended to be connected to a (common) flue having mechanical extraction.

  • Standard
    106 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This European Standard is applicable to gas-fired appliances producing domestic hot water. It applies to both instantaneous and storage gas-fired combined with electrical heat pump.
It applies to a package marketed as single unit or fully specified by the manufacturer that have:
- a heat input not exceeding 400 kW; and
- a hot water storage tank capacity (if any) not exceeding 2000 l.
EN 13203-1 sets out in qualitative and quantitative terms the performance in delivery of domestic hot water for a selected variety of uses. It also gives a system for presenting the information to the user. The present document sets out a method for assessing the energy performance of gas fired appliances combined with heat pump with electrically driven compressor according to EN 16147. It defines a number of daily load profiles for each domestic hot water use, kitchen, shower, bath and a combination of these, together with corresponding test procedures, enabling the energy performances of different gas-fired appliances to be compared and matched to the needs of the user. Where other technologies are combined with a gas-fired boiler or a water heater to produce domestic hot water, specific parts of EN 13203 apply.
The present document does not apply for gas boilers with recovery systems using combustion products as heat source for the electrical heat pump.
When the electrical heat pump does not work for domestic hot water production in the summer period, the present standard is not applicable for energy performances assessing, EN 13203-2 should be used.

  • Standard
    51 pages
    English language
    sale 10% off
    e-Library read for
    1 day
  • Draft
    49 pages
    English language
    sale 10% off
    e-Library read for
    1 day
  • Draft
    52 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This document is applicable to gas-fired appliances producing domestic hot water. It applies to both instantaneous and storage tank appliances; waters-heaters and combination boilers that have:
- a heat input not exceeding 400 kW; and
- a hot water storage tank capacity (if any) not exceeding 2000 l.
In the case of combination boilers, with or without storage tank, domestic hot water production is integrated or coupled, the whole being marketed as a single unit.
EN 13203-1 sets out in qualitative and quantitative terms the performance in delivery of domestic hot water for a selected variety of uses. It also gives a system for presenting the information to the user. The present document sets out a method for assessing the energy performance of the appliances. It defines a number of daily load profiles for each domestic hot water use, kitchen, shower, bath and a combination of these, together with corresponding test procedures, enabling the energy performances of different gas-fired appliances to be compared and matched to the needs of the user. Where other technologies are combined with a gas-fired boiler or a water heater to produce domestic hot water, specific parts of EN 13203 apply.

  • Standard
    41 pages
    English language
    sale 10% off
    e-Library read for
    1 day
  • Standard
    41 pages
    English language
    sale 10% off
    e-Library read for
    1 day
  • Draft
    40 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This European Standard is applicable to gas-fired appliances producing domestic hot water. It applies to sorption heat pumps connected to or including a domestic hot water storage tank. It applies to a package marketed as single unit or fully specified that have:
-   a heat input not exceeding 400 kW; and
-   a hot water storage tank capacity (if any) not exceeding 2000 l.
In the case of combination boilers, with or without storage tank, domestic hot water production is integrated or coupled, the whole being marketed as a single unit.
EN 13203 1 sets out in qualitative and quantitative terms the performance in delivery of domestic hot water for a selected variety of uses. It also gives a system for presenting the information to the user. The present document sets out a method for assessing the energy performance of the appliances. It defines a number of daily load profiles for each domestic hot water use, kitchen, shower, bath and a combination of these, together with corresponding test procedures, enabling the energy performances of different gas-fired appliances to be compared and matched to the needs of the user. Where other technologies are combined with a gas-fired boiler or a water heater to produce domestic hot water, specific parts of EN 13203 apply.
Horizontal ground heat sources are not covered by the scope of the present European Standard.

  • Standard
    47 pages
    English language
    sale 10% off
    e-Library read for
    1 day
  • Draft
    38 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This European Standard is applicable to gas-fired mCHP appliances producing domestic hot water and electricity. The electricity is generated in a process linked to the production of useful heat.
It applies to a mCHP appliances marketed as single unit or as a package fully specified by a manufacturer that have:
-   a gas heat input not exceeding 70 kW;
-   an electrical output not exceeding 50 kW and
-   a hot water storage capacity not exceeding 500 l.
EN 13203 1 sets out in qualitative and quantitative terms the performance in delivery of domestic hot water for a variety of uses. It also gives a system for presenting the information to the user.
The present document sets out a method for assessing the energy performance of gas fired mCHP appliances. It defines a number of daily tapping cycles for each domestic hot water use, kitchen, shower, bath and a combination of these, together with corresponding test procedures, enabling the energy performances of different gas-fired appliances to be compared and matched to the needs of the user.
When the mCHP generator does not supply domestic hot water in the summer period, the present standard is not applicable. EN 13203 2 will be used for performance assessment of these generators.

  • Standard
    45 pages
    English language
    sale 10% off
    e-Library read for
    1 day
  • Draft
    42 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This European Standard is applicable to solar supported gas-fired appliances producing domestic hot water. It applies to a system marketed as single unit or a system fully specified by a manufacturer that:
-   has a gas heat input not exceeding 70 kW; and
-   has a hot water storage capacity not exceeding 500 l; and
-   is equipped with at least one solar collector; and
-   is, with regard to the solar hydraulic circuit, considered as a forced circulation system (definition according to EN ISO 9488:1999).
The appliances covered by this European Standard are described in Annex C.
This European Standard does not apply to thermo-siphon or integral collector storage systems (definitions according to EN ISO 9488:1999).
NOTE   In principle, the energy consumption of thermo-siphon solar preheat systems and integral collector storage preheat systems can also be assessed on the basis of this standard. One appropriate procedure for that purpose is to calculate the temperature level of the domestic hot water withdrawn from the thermal solar system for the reference conditions defined in this standard by using the numerical system model and the thermal solar system performance parameters according to ISO 9459-5. Based on the temperature level of the hot water withdrawn from the store the energy consumption of the gas appliance should be determined. This determination can either be done by means of calculations or by performing a test according to EN 13203-2 and using instead of the cold water inlet temperature the hot water temperature withdrawn from the store.
This standard is not intended to assess the performance:
-   of the solar collector(s), which should comply with EN 12975-1 and EN 12975-2; and
-   thermal solar systems and components, which should comply with EN 12976-1 and EN 12976-2.
(...)

  • Standard
    32 pages
    English language
    sale 10% off
    e-Library read for
    1 day

Add to the first list of indents:
-   of the standard type possibly producing condensation in certain circumstances;
-   of the low-temperature type;"
Delete in the second list of indents:
-   of the low-temperature type;

  • Amendment
    15 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This standard specifies the requirements and test methods concerning, in particular the construction, safety, fitness for purpose, and rational use of energy, as well as the classification and marking of gas-fired central heating boilers that are fitted with atmospheric burners, fan assisted atmospheric burners or fully premixed burners, and are hereafter referred to as "boilers".  This standard applies to boilers of type B, as listed in 4.2:   ð that use one or more combustible gases of the three gas families at the pressures stated in Tables 14 and 15;  ð that have a nominal heat input (net CV basis) exceeding 70 kW, but not exceeding 300 kW, including modular boilers;  ð where the temperature of the heat transfer fluid does not exceed 105 øC during normal operation;  ð where the maximum operating pressure in the water circuit does not exceed 6 bar.  The standard applies to boilers designed for sealed water systems or for open water systems.  The standard does not contain all the requirements necessary for boilers:   ð intended to be installed in the open or in living rooms;  ð permanently fitted with more than one flue outlet;  ð where the combustion circuit is sealed with respect to the room where the boiler is installed;  ð of the condensing type;  ð of the low temperature type;  ð intended to be connected to a common flue having mechanical extraction;  ð fitted with a forced draught burner in accordance with EN 676;  ð producing hot water for domestic purposes.  This standard only covers type testing.

  • Standard
    117 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This European Standard specifies the common requirements and test methods concerning, in particular the construction, safety, fitness for purpose, and rational use of energy, as well as the classification, marking and energy labelling of gas-fired central heating boilers that are fitted with atmospheric burners, fan assisted atmospheric burners or fully premixed burners, and are hereafter referred to as boilers.
This European Standard is to be used in conjunction with the specific Parts 2 (Part 2-1 and following ones).
This European Standard applies to boilers of types B and C, according to CEN/TR 1749:2014
a)   that use one or more combustible gases of the three gas families at the pressures stated in EN 437 ;
b)   where the temperature of the heat transfer fluid does not exceed 105 °C during normal operation;
c)   where the maximum operating pressure in the water circuit does not exceed 6 bar;
d)   which can give rise to condensation under certain circumstances;
e)   !which are declared in the installation instructions to be either a "condensing" boiler or a "low temperature boiler" or a "standard boiler" or an "other boiler". If no declaration is given the boiler is to be considered both a "standard boiler" and an "other boiler";
NOTE   The Ecodesign Directive defines "other boilers", "low temperature boilers" and "condensing boilers". The Boiler Efficiency Directive defines "standard boilers", "low temperature boilers" and "condensing boilers". Depending on the legislation applied, a boiler can be both "a standard boiler" and an "other boiler"."
f)   which are intended to be installed inside a building or in a partially protected place;
g)   which are intended to produce hot water either by the instantaneous or storage principle, the whole being marketed as a single unit.
This European Standard applies to boilers designed for sealed water systems or for open water systems.
This general standard and the specific standards (see Part 2) provide requirements for boilers with known constructions. For boilers with any alternative constructions, which might not fully be covered by this standard or a specific standard, the risk associated with this alternative construction will need to be assessed.
An example of an assessment methodology, based upon risk assessment, is given in Clause 11.
This European Standard is not intended to cover appliances intended for connection to gas grids where the quality of the distributed gas is likely to vary to a large extent over the lifetime of the appliance.

  • Standard
    188 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This European Standard is applicable to gas-fired appliances producing domestic hot water. It applies to both instantaneous and storage tank appliances; waters-heaters and combination boilers that have:
-   a heat input not exceeding 70 kW; and
-   a hot water storage tank capacity (if any) not exceeding 500 l.
In the case of combination boilers, with or without storage tank, domestic hot water production is integrated or coupled, the whole being marketed as a single unit.
EN 13203-1 sets out in qualitative and quantitative terms the performance in delivery of domestic hot water for a selected variety of uses. It also gives a system for presenting the information to the user. The present document sets out a method for assessing the energy performance of the appliances. It defines a number of daily tapping cycles for each domestic hot water use, kitchen, shower, bath and a combination of these, together with corresponding test procedures, enabling the energy performances of different gas-fired appliances to be compared and matched to the needs of the user. Where other technologies are combined with a gas-fired boiler or a water heater to produce domestic hot water, specific parts of EN 13203 apply.

  • Standard
    38 pages
    English language
    sale 10% off
    e-Library read for
    1 day
  • Draft
    38 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This European Standard specifies, the requirements and test methods concerning, in particular, the construction, safety, fitness for purpose, and rational use of energy, as well as the classification and marking of gas-fired central heating boilers that are fitted with atmospheric burners, fan assisted atmospheric burners or fully premixed burners, and are hereafter referred to as "boilers".
Where the word boiler is used, it needs to be read as the boiler including its connecting ducts, ducts and terminals, if any.
This European Standard covers gas-fired central heating boilers from the types C1 up to C9 and the types B2, B3 and B5, according to the classification in CEN/TR 1749:
a)   that have a nominal heat input (on the basis of net calorific value) not exceeding 1 000 kW;
b)   that use one or more combustible gases of the three gas families at the pressures stated in EN 437;
c)   where the temperature of the heat transfer fluid does not exceed 105 °C during normal operation;
d)   where the maximum operating pressure in the water circuit does not exceed 6 bar;
e)   which may or may not give rise to condensation under certain circumstances;
f)   which are declared in the installation instructions to be either a "condensing" boiler or a "low temperature boiler" or a "standard boiler"; if no declaration is given the boiler is to be considered a "standard boiler";
g)   which are intended to be installed either indoors or outdoors in a partially protected place;
h)   which may include the facility to produce hot water, either by the instantaneous or storage principle, the whole being marketed as a single unit;
i)   which are designed for either sealed water systems or for open water systems;
j)   which are either modular boilers, or non- modular boilers.
This European Standard will be used in conjunction with the General Requirements Standard EN 15502-1.
This European Standard provides requirements for boilers with known constructions. For boilers with any alternative constructions, which might not fully be covered by this standard, the risk associated with this alternative construction needs to be assessed.
An example of an assessment methodology, based upon risk assessment and which covers the essential requirements of the Gas Appliance Directive, is given in Clause 11.
This European Standard does not cover all the requirements for:
k)   Appliances that are intended to be connected to gas grids where the quality of the distributed gas is likely to vary to a large extent over the lifetime of the appliance (see Annex DD);
l)   Appliances using flue dampers;
m)   Appliances of the types B21, B31, B51, C21, C41, C51, C61, C71 and C81;
n)   C7 appliances that have a nominal heat input (on the basis of net calorific value) exceeding 70 kW;
o)   Appliances incorporating flexible plastic flue liners;
p)   Appliances designed to become connected to a combined flue duct system that is designed to operate under overpressure (for example Ca));
q)   Appliances incorporating a combined combustion products circuit that is designed to operate under overpressure (for example Cb));
r)   Appliances intended to be connected to a (common) flue having mechanical extraction.

  • Standard
    85 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This document is applicable to gas-fired appliances producing domestic hot water. It applies to both instantaneous and storage appliances; water-heaters and combination boilers that have:
¾   heat input not exceeding 70 kW; and
¾   hot water storage capacity (if any) not exceeding 300 l.
In the case of combination boilers, with or without storage, domestic hot water production is integrated or coupled, the whole being marketed as a single unit.
This document is formed in two parts, which cover two aspects of domestic hot water production.
EN 13203-1 sets out in qualitative and quantitative terms the performance in delivery of domestic hot water for a selected variety of uses. It also gives a system for presenting the information to the user. This first part complements EN 26, EN 89 and EN 625.
EN 13203-2 sets out a method for assessing the energy performance of the appliances. It defines a number of daily delivery programmes for each domestic hot water use, kitchen, shower, bath and a combination of these, together with corresponding test procedures, enabling the energy performances of different gas-fired appliances to be compared and matched to the needs of the user.

  • Standard
    31 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This European Standard specifies, the common requirements and test methods concerning, in particular the construction, safety, fitness for purpose, and rational use of energy, as well as the classification and marking of gas-fired central heating boilers that are fitted with atmospheric burners, fan assisted atmospheric burners or fully premixed burners, and are hereafter referred to as “boilers”.
This European Standard is to be used in conjunction with the specific Parts 2 (Part 2-1 and following ones).
This European Standard applies to boilers of types B and C, according to CEN/TR 1749:
a)   that use one or more combustible gases of the three gas families at the pressures stated in EN 437;
b)   where the temperature of the heat transfer fluid does not exceed 105 °C during normal operation;
c)   where the maximum operating pressure in the water circuit does not exceed 6 bar;
d)   which can give rise to condensation under certain circumstances;
e)   which are declared in the installation instructions to be either a “condensing” boiler or a "low temperature boiler" or a “standard boiler”. If no declaration is given the boiler is to be considered a “standard boiler”
f)   which are intended to be installed in a partially protected place;
g)   which are intended to produce hot water either by the instantaneous or storage principle, the whole being marketed as a single unit.
This European Standard applies to boilers designed for sealed water systems or for open water systems.
For applications within the scope of the PED further requirements may be necessary (e.g. situations where the maximum allowable temperature exceeds 110 °C, or where volume times maximum allowable pressure is over 50 bar r litres).
This general standard and the specific standards (see Part 2) provide requirements for boilers with known constructions. For boilers with any alternative constructions, which might not fully be covered by this standard or a specific standard, the risk associated with this alternative construction shall be assessed.
An example of an assessment methodology, based upon risk assessment and which covers the essential requirements of the Gas Appliance Directive, is given in Clause 11.
This European Standard is not intended to cover appliances intended to being connected to gas grids where the quality of the distributed gas is likely to vary to a large extend over the lifetime of the appliance.

  • Standard
    152 pages
    English language
    sale 10% off
    e-Library read for
    1 day
  • Draft
    140 pages
    English language
    sale 10% off
    e-Library read for
    1 day
  • Draft
    150 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This European Standard is applicable to gas-fired appliances producing domestic hot water. It applies to both instantaneous and storage appliances; waters-heaters and combination boilers that have:
¾    heat input not exceeding 70 kW, and
¾    hot water storage capacity (if any) not exceeding 300 l.
In the case of combination boilers, with or without storage, domestic hot water production is integrated or coupled, the whole being marketed as a single unit.
This European Standard EN 13203 is formed in two parts, which cover two aspects of domestic hot water production.
EN 13203-1 sets out in qualitative and quantitative terms the performance in delivery of domestic hot water for a selected variety of uses. It also gives a system for presenting the information to the user. This first part complements EN 26, EN 89 and EN 625.
The present European Standard EN 13203-2 sets out a method for assessing the energy performance of the appliances. It defines a number of daily tapping cycles for each domestic hot water use, kitchen, shower, bath and a combination of these, together with corresponding test procedures, enabling the energy performances of different gas-fired appliances to be compared and matched to the needs of the user.

  • Standard
    28 pages
    English language
    sale 10% off
    e-Library read for
    1 day
  • Draft
    26 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This document applies to gas-fired central heating boilers, which are declared by the manufacturer to be "condensing boilers":
¾   of types C (excluding appliances without a fan) and B,
¾   using one or more gases corresponding to the three gas families, and
¾   for which the nominal heat input is greater than 70 kW but not exceeding 1 000 kW. This document only covers type testing.
This document completes or modifies the standards EN 656, EN 13836, and prEN 15420 hereafter called "boiler standards". It specifies supplementary requirements for condensing boilers.

  • Standard
    17 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This amendment extends the original field of application of EN 297 that was restricted to type B-boilers with atmospheric burners, to type B boilers with fan-assisted burners.

  • Amendment
    40 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This amendment 6 will extend the field of application of EN 297 to boilers intended to be installed in the open air in a partially protected place.

  • Amendment
    10 pages
    English language
    sale 10% off
    e-Library read for
    1 day

Migrated from Progress Sheet (TC Comment) (2000-07-10): Need of a BT C for allowing more amendments than foreseen in IR ++ Exceptional derogation from IR granted in case of EN 297, allowing more than ++ 3 Amd. (but not more than 5) (BT 27/1996)

  • Amendment
    5 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This European standard applies to gas-fired central heating boilers, which are declared by the manufacturer to be "condensing boilers":  - of types B (excluding appliances without a fan) and C, - using one or more gases corresponding to the three gas families, and - for which the nominal heat input is less than or equal to 70 kW.  This European standard only covers type testing.  This European standard completes or modifies the standards EN 297, prEN 483 and EN 625, hereafter called "boiler standards". It specifies supplementary requirements for condensing boilers.

  • Standard
    15 pages
    English language
    sale 10% off
    e-Library read for
    1 day

Migrated from Progress Sheet (TC Comment) (2000-07-10): "SPECIAL CASE " !! ++ Exceptional derogation from IR granted in case of EN 297, allowing more than ++ 3 Amd. (but not more than 5) (BT 27/1996) ++ Combination of Amd. for final publ. (A2+A3) to be disc. with the Secretary.

  • Amendment
    10 pages
    English language
    sale 10% off
    e-Library read for
    1 day

Migrated from Progress Sheet (TC Comment) (2000-07-10): Has to consider also Directive 92/42 on efficiency of boilers !! ++ Exceptional derogation from IR granted in case of EN 297, allowing more than ++ 3 Amd. (but not more than 5) (BT 27/1996)

  • Amendment
    15 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This standard supplements standards EN 297, prEN 483 and prEN 677, hereafter called 'boiler standards'. It specifies the supplementary requirements and tests for the construction, safety, rational use of energy, fitness for purpose, classification and marking related to the domestic hot water operation of combination boilers.   The domestic hot water is produced on either the instantaneous or storage principle. The domestic hot water production is integrated or coupled, the whole being marketed as a single unit.  This standard does not apply to two appliances included in the same case which operate independently of each other - a boiler and a water heater - even if they have a common flue.  This standard only covers type testing.

  • Standard
    23 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This European Standard specifies the requirements and test methods for the construction, safety, fitness for purpose, rational use of energy, classification and marking of gas-fired central heating boilers, hereafter referred to as 'boilers'.  This standard applies to type B11 and BB11BS boilers:  - fitted with atmospheric burners; - that use gases corresponding to the three gas families and to the pressures   stated in 4.1.4; - that have a nominal heat input not exceeding 70 kW (on net calorific value); - where the temperature of the water does not exceed 95 øC during normal   operation; - where the maximum water-side operating pressure does not exceed 6 bar.  This standard does not contain all the necessary requirements for:  boilers:  - intended to be installed in the open; - having multiple heating units with a single draught diverter; - with fan-assisted combustion; - of the condensing type; i- ntended to be connected to a common flue having mechanical extraction; - fitted with manual or automatic means of adjusting the air supply and/or   adjusting the evacuation of the combustion products; - of the combination type (central heating and domestic hot water production);  appliances:  - combining the functions of an independent space heater and a hot water   generator for central heating.  This standard only covers type testing.

  • Standard
    131 pages
    English language
    sale 10% off
    e-Library read for
    1 day

This document specifies the requirements and test methods concerning, in particular, the construction, safety, fitness for purpose, and rational use of energy, as well as the classification and marking of gas-fired central heating boilers that are fitted with atmospheric burners, fan-assisted atmospheric burners or fully premixed burners, and are hereafter referred to as "boilers".
This document applies to boilers of type C, as listed in 4.2:
-   that use one or more combustible gases of the three gas families at the pressures stated in Tables 14 and 15;
-   that have a nominal heat input (on the basis of net calorific value) exceeding 70 kW, but not exceeding 1 000 kW, including modular boilers;
-   where the temperature of the heat transfer fluid does not exceed 105 °C during normal operation;
-   where the maximum operating pressure in the water circuit does not exceed 6 bar;
-   which can give rise to condensation under certain circumstances.
The document applies to boilers designed for sealed water systems or for open water systems.
The document does not contain all the requirements necessary for boilers:
-   intended to be installed in the open or in living rooms;
-   permanently fitted with more than one flue outlet;
-   of the condensing type;
-   intended to be connected to a common flue having mechanical extraction;
-   type C21, C41, C51, C61, C7 and C81 boilers;
-   fitted with a forced draught burner in accordance with EN 676;
-   producing hot water for domestic purposes.
This document only covers type testing.

  • Standard
    168 pages
    English language
    sale 10% off
    e-Library read for
    1 day
  • Draft
    170 pages
    English language
    sale 10% off
    e-Library read for
    1 day

Delete the footnote no.1.

  • Amendment
    22 pages
    English language
    sale 10% off
    e-Library read for
    1 day
  • Amendment
    25 pages
    English language
    sale 10% off
    e-Library read for
    1 day