EN 1456-1:2001
(Main)Plastics piping systems for buried and above-ground drainage and sewerage under pressure - Unplasticized poly(vinyl chloride) (PVC-U) - Part 1: Specifications for piping components and the system
Plastics piping systems for buried and above-ground drainage and sewerage under pressure - Unplasticized poly(vinyl chloride) (PVC-U) - Part 1: Specifications for piping components and the system
This European Standard specifies requirements for unplasticized poly(vinyl chloride) (PVC-U) piping systems in the field of buried and above-ground drainage and sewerage under pressure.
In conjunction with one or more of Parts 1 to 5 of EN 1452 and ENV 1452-6, it is applicable to PVC-U pipes, fittings, valves and ancillary equipment, their joints and to joints with components of other plastics and non-plastics materials intended to be used for the conveyance of sewage and drainage under pressure at approximately 20 °C as follows:
a) buried in the ground;
b) sea outfalls;
c) laid in inland waters and/or in ducts;
d) suspended below bridges.
This standard is also applicable to components for the continuous conveyance of sewage and drainage up to and including 45 °C as required in EN 773 [1].
NOTE 1 In this case the pressure derating factors given in EN 1452-2:1999, Figure A.1 apply.
NOTE 2 No pressure reduction is necessary for the drainage of waste waters at short-term peak temperatures up to 45 °C (cumulated for 2 years during a service life of 50 years).
Kunststoff-Rohrleitungssysteme für erdverlegte und nicht erdverlegte Abwasserdruckleitungen - Weichmacherfreies Polyvinylchlorid (PVC-U) - Teil 1: Anforderungen an Rohrleitungsbauteile und das Rohrleitungssystem
Diese Norm legt die Rahmenbedingungen für Rohrleitungssysteme aus weichmacherfreiem Polyvinylchlorid (PVC-U) fest, die für erdverlegte und nicht erdverlegte Abwasserdruckleitungen eingesetzt werden.
Zusammen mit Teil 1 bis Teil 5 der EN 1452 und ENV 1452-6 gilt diese Norm für Rohre, Formstücke, Armaturen und Zubehör aus PVC-U, ihre Verbindungen untereinander sowie mit Rohren und Rohrleitungsteilen aus anderen Kunststoffen oder Rohrwerkstoffen, die für die Fortleitung von Abwasser von etwa 20 °C unter Druck für die folgenden Anwendungen vorgesehen sind:
a) Verlegung im Rohrgraben;
b) Entwässerung ins Meer (Siele);
c) Überlandleitungen in Binnengewässern oder in Kanälen;
d) Düker und Brückenleitungen.
Darüber hinaus ist diese Norm anwendbar auf Rohre und Rohrleitungsteile für die Fortleitung von Abwasser bis 45 °C im Dauerbetrieb gemäß den Anforderungen nach EN 773 [1].
ANMERKUNG 1 Im solchen Fall gelten die Minderungsfaktoren gemäß Bild A.1 in der EN 1452-2:1999.
ANMERKUNG 2 Für die Fortleitung von Abwasser mit kurzzeitigen Temperaturspitzen bis 45 °C (kumuliert auf 2 Jahre während einer Betriebsdauer von 50 Jahren) ist keine Druckminderung erforderlich.
Systèmes de canalisations en plastique pour branchements et collecteurs d'assainissement enterrés et aériens avec pression - Poly(chlorure de vinyle) non plastifié (PVC-U) - Partie 1: Spécifications pour les composants et le système
La présente norme européenne spécifie les aspects généraux des systèmes de canalisations en poly(chlorure de vinyle) non plastifié (PVC-U) dans le domaine de l'assainissement enterré et aérien avec pression.
Conjointement à l'une des parties 1 à 5 de l'EN 1452 et de l'ENV 1452-6, elle s'applique aux tubes, raccords, robinets et équipements auxiliaires en PVC-U ainsi qu'à leurs assemblages, et aux assemblages avec des composants faits en d'autres matériaux, plastiques ou non plastiques, destinés à être utilisés pour le transport avec pression des eaux usées à 20 °C environ comme suit:
a) en enterré;
b) en émissaire en mer;
c) dans les cours d'eau et/ou sous fourreau;
d) en suspension sous les ponts.
La présente norme s'applique aussi aux composants pour le transport continu d'eaux usées jusqu'à 45 °C inclus, comme exigé par l'EN 733 [1].
NOTE 1 Dans ce cas, les coefficients de détimbrage donnés à la Figure A.1 de l'EN 1452-2:1999 s'appliquent.
NOTE 2 Pour des températures de pointe de courte durée jusqu'à 45 °C (cumulées jusqu'à 2 ans pendant 50 ans de service) il n'y a pas besoin de réduire la pression des eaux usées.
Cevni sistemi iz polimernih materialov za odpadno vodo in kanalizacijo pod tlakom, položeni v zemljo ali nad njo - Nemehčan polivinilklorid (PVC-U) - 1. del: Specifikacije za cevne elemente in sistem
General Information
Relations
Standards Content (Sample)
SLOVENSKI STANDARD
SIST EN 1456-1:2002
01-junij-2002
&HYQLVLVWHPLL]SROLPHUQLKPDWHULDORY]DRGSDGQRYRGRLQNDQDOL]DFLMRSRG
WODNRPSRORåHQLY]HPOMRDOLQDGQMR1HPHKþDQSROLYLQLONORULG39&8GHO
6SHFLILNDFLMH]DFHYQHHOHPHQWHLQVLVWHP
Plastics piping systems for buried and above-ground drainage and sewerage under
pressure - Unplasticized poly(vinyl chloride) (PVC-U) - Part 1: Specifications for piping
components and the system
Kunststoff-Rohrleitungssysteme für erdverlegte und nicht erdverlegte
Abwasserdruckleitungen - Weichmacherfreies Polyvinylchlorid (PVC-U) - Teil 1:
Anforderungen an Rohrleitungsbauteile und das Rohrleitungssystem
Systemes de canalisations en plastique pour branchements et collecteurs
d'assainissement enterrés et aériens avec pression - Poly(chlorure de vinyle) non
plastifié (PVC-U) - Partie 1: Spécifications pour les composants et le systeme
Ta slovenski standard je istoveten z: EN 1456-1:2001
ICS:
23.040.01 Deli cevovodov in cevovodi Pipeline components and
na splošno pipelines in general
93.030 Zunanji sistemi za odpadno External sewage systems
vodo
SIST EN 1456-1:2002 en
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
---------------------- Page: 1 ----------------------
SIST EN 1456-1:2002
---------------------- Page: 2 ----------------------
SIST EN 1456-1:2002
EUROPEAN STANDARD
EN 1456-1
NORME EUROPÉENNE
EUROPÄISCHE NORM
July 2001
ICS 23.040.01; 93.030
English version
Plastics piping systems for buried and above-ground drainage
and sewerage under pressure - Unplasticized poly(vinyl chloride)
(PVC-U) - Part 1: Specifications for piping components and the
system
Systèmes de canalisations en plastique pour branchements Kunststoff-Rohrleitungssysteme für erdverlegte und nicht
et collecteurs d'assainissement enterrés et aériens avec erdverlegte Abwasserdruckleitungen - Weichmacherfreies
pression - Poly(chlorure de vinyle) non plastifié (PVC-U) - Polyvinylchlorid (PVC-U) - Teil 1: Anforderungen an
Partie 1: Spécifications pour les composants et le système Rohrleitungsbauteile und das Rohrleitungssystem
This European Standard was approved by CEN on 10 August 2000.
CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European
Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national
standards may be obtained on application to the Management Centre or to any CEN member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by translation
under the responsibility of a CEN member into its own language and notified to the Management Centre has the same status as the official
versions.
CEN members are the national standards bodies of Austria, Belgium, Czech Republic, Denmark, Finland, France, Germany, Greece,
Iceland, Ireland, Italy, Luxembourg, Netherlands, Norway, Portugal, Spain, Sweden, Switzerland and United Kingdom.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION
EUROPÄISCHES KOMITEE FÜR NORMUNG
Management Centre: rue de Stassart, 36 B-1050 Brussels
© 2001 CEN All rights of exploitation in any form and by any means reserved Ref. No. EN 1456-1:2001 E
worldwide for CEN national Members.
---------------------- Page: 3 ----------------------
SIST EN 1456-1:2002
EN 1456-1:2001 (E)
Contents
Page
Foreword .4
1 Scope.5
2 Normative references.5
3 General .6
3.1 Definitions, symbols and abbreviations .6
3.2 Material.6
4 Pipes .7
4.1 Pipe material.7
4.2 General characteristics.7
4.3 Geometrical characteristics .7
4.4 Classification and selection .11
4.5 Mechanical characteristics .11
4.6 Physical characteristics .11
4.7 Sealing rings.11
4.8 Adhesives .11
4.9 Performance requirements.12
4.10 Marking.12
4.11 Allowable operating pressures .12
5 Fittings.12
5.1 Material.12
5.2 General characteristics.12
5.3 Geometrical characteristics of fittings.12
5.4 Mechanical characteristics .12
5.5 Physical characteristics .13
5.6 Sealing rings.13
5.7 Adhesives .13
5.8 Performance requirements.13
5.9 Marking.13
6 Valve bodies and ancillary components .13
6.1 Material.13
6.2 General characteristics.13
6.3 Geometrical characteristics .13
6.4 Classification and operating conditions .13
6.5 Mechanical characteristics .14
6.6 Physical characteristics .14
6.7 Sealing rings.14
6.8 Adhesives .14
6.9 Performance requirements.14
6.10 Marking.14
7 Fitness for purpose of the system.14
2
---------------------- Page: 4 ----------------------
SIST EN 1456-1:2002
EN 1456-1:2001 (E)
Annex A (informative) Guidance for installation.15
A.1 Definitions, symbols and abbreviations .15
A.2 Parameters influencing the design .15
A.3 Hydraulic properties.15
A.4 Assembly methods .15
A.5 Cold bending on site.16
A.6 Storage, handling and transport of pipes.16
A.7 Storage, handling and transport of fittings, valves and ancillaries.16
A.8 Installation.16
A.9 Site pressure testing.20
A.10 Corrosion protection .22
A.11 Pressure surge .22
A.12 Repairs .22
A.13 Pipeline detection .22
3
---------------------- Page: 5 ----------------------
SIST EN 1456-1:2002
EN 1456-1:2001 (E)
Foreword
This European Standard has been prepared by Technical Committee CEN/TC 155 "Plastics piping
systems and ducting systems", the secretariat of which is held by NEN.
This European Standard shall be given the status of a national standard, either by publication of an
identical text or by endorsement, at the latest by January 2002, and conflicting national standards shall
be withdrawn at the latest by July 2003.
According to the CEN/CENELEC Internal Regulations, the national standards organizations of the
following countries are bound to implement this European Standard: Austria, Belgium, Czech
Republic, Denmark, Finland, France, Germany, Greece, Iceland, Ireland, Italy, Luxembourg,
Netherlands, Norway, Portugal, Spain, Sweden, Switzerland and the United Kingdom.
This standard is a Part of a System Standard for plastics piping systems of a particular material for a
specified application. There are a number of such System Standards.
System Standards are based on the results of the work undertaken in ISO/TC 138 "Plastics pipes,
fittings and valves for the transport of fluids", which is a Technical Committee of the International
Organization for Standardization (ISO).
They are supported by separate standards on test methods to which references are made throughout
the System Standard.
The System Standards are consistent with general standards on functional requirements and on
recommended practice for installation.
EN 1456 consists of the following parts, under the general title Plastics piping systems for buried and
above-ground drainage and sewerage under pressure Unplasticized poly(vinyl chloride) (PVC-U):
Part 1: Specifications for piping components and the system (the present standard)
Part 2: Guidance for the assessment of conformity (ENV)
This standard includes the following:
Annex A (informative): Guidance for installation
Bibliography
At the date of publication of this standard, System Standards for piping systems of other plastics
materials used for the same application are the following:
NOTE All listed System Standards are under preparation.
Plastics piping systems for pressure and non-pressure underground drainage and sewerage -
Glass-reinforced thermosetting plastics (GRP) based on polyester resin (UP)
EN 13244 Plastics piping systems for buried and above-ground pressure systems for water for
general purposes, drainage and sewerage - Polyethylene (PE)
Introduction
This standard specifies the requirements for a piping system and its components made from
unplasticized poly(vinyl chloride) (PVC-U). The piping system is intended to be used for buried and
above-ground drainage and sewerage under pressure.
Since the differences between requirements for piping components according to EN 1452 and this
standard are slight, this standard gives only specific requirements, which are applicable to drainage
4
---------------------- Page: 6 ----------------------
SIST EN 1456-1:2002
EN 1456-1:2001 (E)
and sewerage under pressure. For all aspects common to water supply, reference is made to
EN 1452.
This standard is therefore complementary to, and can only be used in conjunction with, EN 1452,
Parts 1 to 5 and ENV 1452-6.
When EN 1452 is taken into account, the medium "water" for the pipes, fittings, valves and ancillary
equipment needs to be read as "sewage and drainage".
Clause 3 of this standard covers the general aspects of the plastics piping system. Components,
requirements and test methods are specified in clauses 4, 5 and 6 of this standard. Characteristics for
fitness for purpose (mainly for joints) are covered in clause 7. Guidance for installation is given in
Annex A.
1 Scope
This European Standard specifies requirements for unplasticized poly(vinyl chloride) (PVC-U) piping
systems in the field of buried and above-ground drainage and sewerage under pressure.
In conjunction with one or more of Parts 1 to 5 of EN 1452 and ENV 1452-6, it is applicable to PVC-U
pipes, fittings, valves and ancillary equipment, their joints and to joints with components of other
plastics and non-plastics materials intended to be used for the conveyance of sewage and drainage
under pressure at approximately 20 °C as follows:
a) buried in the ground;
b) sea outfalls;
c) laid in inland waters and/or in ducts;
d) suspended below bridges.
This standard is also applicable to components for the continuous conveyance of sewage and
[1]
drainage up to and including 45 °C as required in EN 773 .
NOTE 1 In this case the pressure derating factors given in EN 1452-2:1999, Figure A.1 apply.
NOTE 2 No pressure reduction is necessary for the drainage of waste waters at short-term peak temperatures up to 45 °C
(cumulated for 2 years during a service life of 50 years).
2 Normative references
This European Standard incorporates by dated or undated reference, provisions from other
publications. These normative references are cited at the appropriate places in the text and the
publications are listed hereafter. For dated references, subsequent amendments to or revisions of any
of these publications apply to this European Standard only when incorporated in it by amendment or
revision. For undated references the latest edition of the publication referred to applies (including
amendments).
EN 578, Plastics piping systems Plastics pipes and fittings Determination of the opacity
EN 921, Plastics piping systems Thermoplastics pipes Determination of resistance to internal
pressure at constant temperature
EN 1452-1:1999, Plastics piping systems for water supply Unplasticized poly(vinyl chloride)
(PVC-U) Part 1: General
5
---------------------- Page: 7 ----------------------
SIST EN 1456-1:2002
EN 1456-1:2001 (E)
EN 1452-2:1999, Plastics piping systems for water supply Unplasticized poly(vinyl chloride)
(PVC-U) Part 2: Pipes
EN 1452-3:1999, Plastics piping systems for water supply Unplasticized poly(vinyl chloride)
(PVC-U) Part 3: Fittings
EN 1452-4:1999, Plastics piping systems for water supply Unplasticized poly(vinyl chloride)
(PVC-U) Part 4: Valves and ancillary equipment
EN 1452-5:1999, Plastics piping systems for water supply Unplasticized poly(vinyl chloride)
(PVC-U) Part 5: Fitness for purpose of the system
prEN ISO 3126:1999, Plastics piping systems Plastics components Mesurement and
determination of dimensions (ISO/DIS 3126:1999)
EN ISO 12162:1995, Thermoplastics materials for pipes and fittings for pressure applications
Classification and designation Overall service (design) coefficient (ISO 12162:1995)
ISO 1183:1987, Plastics Methods for determining the density and relative density of non-cellular
plastics
1)
ISO/TR 9080:1992 , Thermoplastics pipes for the transport of fluids Methods of extrapolation of
hydrostatic stress rupture data to determine the long-term hydrostatic strength of thermoplastics pipe
materials
3 General
3.1 Definitions, symbols and abbreviations
For the purposes of this standard, the definitions, symbols and abbreviations given in parts 1 to 5 of
EN 1452:1999 apply, as applicable.
3.2 Material
3.2.1 PVC-U compound
The material from which the pipes, fittings and valves are made shall be an unplasticized poly(vinyl
chloride) compound. This compound shall consist of PVC-U resin, to which are added those additives
that are needed to facilitate the manufacture of pipes, fittings and valves conforming to this standard.
None of these additives shall be used separately or together in quantities sufficient to impair the
fabrication or solvent cementing properties of the product or to impair the chemical and physical or
mechanical properties (in particular long-term mechanical strength and impact strength) as specified
in this standard.
3.2.2 Reprocessable and recyclable materials
The use of the manufacturer's own reprocessable material obtained during the production and works
testing of products conforming to this standard is permitted in addition to the use of virgin material.
Reprocessable material obtained from external sources and recyclable material shall not be used.
3.2.3 Chemical resistance
In cases where piping systems conforming to this standard will be used for chemically contaminated
waste waters, such as industrial discharges, chemical and temperature resistance shall be taken into
account.
1) In ISO/TC138/SC5 a new extrapolation method is under development, which is intended to replace
[2]
ISO/TR 9080. It is currently available as prEN ISO 9080:1998 .
6
---------------------- Page: 8 ----------------------
SIST EN 1456-1:2002
EN 1456-1:2001 (E)
NOTE PVC-U materials are resistant to corrosion by water with a wide range of pH-values such as domestic waste
water, rainwater, surface water and ground water. For information about the chemical resistance of PVC-U materials guidance
[3]
is given in ISO/TR 10358:1993 .
4 Pipes
4.1 Pipe material
4.1.1 General
The material used shall conform to 3.2 and to the requirements given in 4.1.2 and 4.1.3.
4.1.2 Density
The density, , at 23 °C of the pipe, when measured in accordance with ISO 1183:1987, shall be
between the following limits:
3 3
1350 kg/m 1460 kg/m .
4.1.3 MRS-value
The pipe material shall have a minimum required strength, MRS, as defined in EN 1452-1:1999, of at
least 25 MPa.
2)
The pipe material shall be evaluated in accordance with method II of ISO/TR 9080:1992 , where the
pressure test shall be conducted in accordance with EN 921, to find the LCL. This evaluation shall be
made with an end cap type a) or b) and using a pipe series S 12,5. The MRS-value shall be derived
from the LCL in accordance with EN ISO 12162:1995.
The pipe material shall be classified by the compound manufacturer.
NOTE Where there is available long-term experience with the effect of a change in material/compound, it is not
necessary to re-evaluate the MRS. In this case the values determined with five test pieces at 20 °C and 60 °C during 1000 h to
5000 h are located on or above the 97,5 % LCL long-term characteristic curve established prior to the material/compound
change.
4.2 General characteristics
4.2.1 Appearance
The appearance shall conform to EN 1452-2:1999.
4.2.2 Colour
The colour of the pipes shall be grey or brown and uniform throughout.
4.2.3 Opacity
The wall of the pipe shall not transmit more than 0,2 % of visible light when measured in accordance
with EN 578.
4.3 Geometrical characteristics
4.3.1 General
Metric-sized pipes shall conform to 4.3.2 to 4.3.6 (inclusive). Imperial(inch)-sized pipes shall conform
to EN 1452-2:1999, Annex B.
2) In ISO/TC138/SC5 a new extrapolation method is under development, which is intended to replace
[2]
ISO/TR 9080. It is currently available as prEN ISO 9080:1998 .
7
---------------------- Page: 9 ----------------------
SIST EN 1456-1:2002
EN 1456-1:2001 (E)
Dimensions shall be measured in accordance with prEN ISO 3126:1999.
4.3.2 Nominal outside diameters
The nominal outside diameter, d , of a pipe shall conform to Table 1.
n
Table 1 Nominal outside diameters and tolerances
Dimensions in millimetres
Nominal outside Tolerance for mean Tolerance for out-of-roundness of the
1) 2)
diameter
outside diameter d outside diameter d
em e
d x S 20 to S 16 S 12,5 to S 8
n
25 0,2 0,5
32 0,2 0,5
40 0,2 1,4 0,5
50 0,2 1,4 0,6
63 0,3 1,5 0,8
75 0,3 1,6 0,9
90 0,3 1,8 1,1
110 0,4 2,2 1,4
125 0,4 2,5 1,5
140 0,5 2,8 1,7
160 0,5 3,2 2,0
180 0,6 3,6 2,2
200 0,6 4,0 2,4
225 0,7 4,5 2,7
250 0,8 5,0 3,0
280 0,9 6,8 3,4
315 1,0 7,6 3,8
355 1,1 8,6 4,3
400 1,2 9,6 4,8
450 1,4 10,8 5,4
500 1,5 12,0 6,0
560 1,7 13,5 6,8
630 1,9 15,2 7,6
710 2,0 17,1 8,6
800 2,0 19,2 9,6
900 2,0 21,6
1000 2,0 24,0
1) The requirement for the tolerance for the mean outside diameter is only applicable prior to storage.
2) The requirement for out-of-roundness is only applicable prior to the pipe leaving the manufacturer's premises.
[4]
NOTE 1 The tolerance for d conforms to grade D of ISO 11922-1:1997 for d 50 mm and to grade C for d
em n n
+X
x
50 mm. The tolerance is expressed in the form mm, where is the value of the tolerance.
0
NOTE 2 The tolerance for out-of-roundness is expressed as the difference between the measurement of the largest and
the smallest outside diameter in a cross-section of the pipe (i.e. d d ).
e,max e,min
[4]
NOTE 3 For d 250 mm, the tolerance for pipe series S 20 to S 16 conforms to grade N of ISO 11922-1:1997 . For
n
[4]
d 250 mm, the tolerance conforms to grade M of ISO 11922-1:1997 .
n
[4]
d
NOTE 4 For a 25 mm, the tolerance for pipe series S 12,5 to S 8 conforms to 0,5 grade M of ISO 11922-1:1997 .
n
8
---------------------- Page: 10 ----------------------
SIST EN 1456-1:2002
EN 1456-1:2001 (E)
4.3.3 Mean outside diameters and their tolerances
The mean outside diameter, d , of a pipe shall conform to the applicable nominal outside diameter,
em
d , within the tolerance given in Table 1.
n
The tolerance for out-of-roundness shall conform to Table 1.
4.3.4 Wall thicknesses and their tolerances
The nominal wall thickness, e , shall conform to Table 2, as appropriate to the pipe series.
n
NOTE The nominal wall thickness is classified with the pipe series S. The nominal wall thickness corresponds to the
minimum allowable wall thickness and has a positive tolerance (see note 1 to Table 3).
The tolerance for mean wall thickness, e , shall conform to Table 3.
m
9
---------------------- Page: 11 ----------------------
SIST EN 1456-1:2002
EN 1456-1:2001 (E)
Table 2 Nominal (minimum) wall thicknesses
Dimensions in millimetres
Nominal Nominal (minimum) wall thicknesses
outside
for pipe series S
diameter
S 20 (S 16,7) S 16 S 12,5 S 10 S 8
(SDR 41) (SDR 34,4) (SDR 33) (SDR 26) (SDR 21) (SDR 17)
for nominal pressure PN based on service (design) coefficient C = 2,5
d
PN 6 PN 6 PN 8 PN 10 PN 12,5
n
25 1,5
32 1,5 1,6 1,9
40 1,5 1,6 1,9 2,4
50 1,5 1,6 2,0 2,4 3,0
63 1,9 2,0 2,5 3,0 3,8
75 2,2 2,3 2,9 3,6 4,5
90 2,7 2,8 3,5 4,3 5,4
1)
for nominal pressure PN based on service (design) coefficient C = 2,0
PN 6 PN 7,5 PN 8 PN 10 PN 12,5 PN 16
110 2,7 3,2 3,4 4,2 5,3 6,6
125 3,1 3,7 3,9 4,8 6,0 7,4
140 3,5 4,1 4,3 5,4 6,7 8,3
160 4,0 4,7 4,9 6,2 7,7 9,5
180 4,4 5,3 5,5 6,9 8,6 10,7
200 4,9 5,9 6,2 7,7 9,6 11,9
225 5,5 6,6 6,9 8,6 10,8 13,4
250 6,2 7,3 7,7 9,6 11,9 14,8
280 6,9 8,2 8,6 10,7 13,4 16,6
315 7,7 9,2 9,7 12,1 15,0 18,7
355 8,7 10,4 10,9 13,6 16,9 21,1
400 9,8 11,7 12,3 15,3 19,1 23,7
450 11,0 13,2 13,8 17,2 21,5 26,7
500 12,3 14,6 15,3 19,1 23,9 29,7
560 13,7 16,4 17,2 21,4 26,7
630 15,4 18,4 19,3 24,1 30,0
710 17,4 20,7 21,8 27,2
800 19,6 23,3 24,5 30,6
900 22,0 26,3 27,6
1000 24,5 29,2 30,6
1) To apply an overall service (design) coefficient of 2,5 (instead of 2,0) for pipes with nominal diameters
above 90 mm, the next higher pressure rating, PN, shall be chosen.
[5]
NOTE 1 The nominal wall thicknesses conform to ISO 4065:1996 .
NOTE 2 The PN 6 values for S 20 and S 16 are calculated with the preferred number 6,3.
NOTE 3 The pipe series S 16,7 is intended to be phased out by the end of [DAV + 2 years].
10
---------------------- Page: 12 ----------------------
SIST EN 1456-1:2002
EN 1456-1:2001 (E)
Table 3 Tolerance on wall thicknesses
Dimensions in millimetres
Nominal (minimum) Tolerance for mean Nominal (minimum) Tolerance for mean
wall thickness wall thickness wall thickness wall thickness
e x e x
n n
1,0 2,0 0,4 16,0 17,0 1,9
2,0 3,0 0,5 17,0 18,0 2,0
3,0 4,0 0,6 18,0 19,0 2,1
4,0 5,0 0,7 19,0 20,0 2,2
5,0 6,0 0,8 20,0 21,0 2,3
6,0 7,0 0,9 21,0 22,0 2,4
7,0 8,0 1,0 22,0 23,0 2,5
8,0 9,0 1,1 23,0 24,0 2,6
9,0 10,0 1,2 24,0 25,0 2,7
10,0 11,0 1,3 25,0 25,0 2,8
11,0 12,0 1,4 26,0 27,0 2,9
12,0 13,0 1,5 27,0 28,0 3,0
13,0 14,0 1,6 28,0 29,0 3,1
14,0 15,0 1,7 29,0 30,0 3,2
15,0 16,0 1,8 30,0 31,0 3,3
+X
NOTE The tolerance applies to the nominal (minimum) wall thickness and is expressed in the form mm, where x is
0
[4]
the value of tolerance for the mean wall thickness, e . It conforms to grade W of ISO 11922-1:1997 .
m
4.3.5 Length of pipe
The length of pipe shall conform to EN 1452-2:1999.
4.3.6 Sockets
For the applicable nominal pipe diameters (see Table 1), the sockets shall conform to
EN 1452-2:1999.
4.4 Classification and selection
For the classification and selection of pipes EN 1452-2:1999 shall apply.
4.5 Mechanical characteristics
The mechanical characteristics of pipes shall conform to EN 1452-2:1999.
4.6 Physical characteristics
The physical characteristics of pipes shall conform to EN 1452-2:1999.
4.7 Sealing rings
Sealing rings shall conform to EN 1452-2:1999.
4.8 Adhesives
Adhesives shall conform to EN 1452-2:1999.
11
---------------------- Page: 13 ----------------------
SIST EN 1456-1:2002
EN 1456-1:2001 (E)
4.9 Performance requirements
For the performance, the requirements given in EN 1452-2:1999 shall apply.
4.10 Marking
4.10.1 General
The presentation of the marking of pipes shall conform to 14.1 of EN 1452-2:1999.
4.10.2 Minimum required marking
For pipes conforming to this standard, the minimum required marking shall conform to 14.2 of
EN 1452-2:1999, with the exception of the marking with the number of the standard, which shall be
marked with "EN 1456".
4.10.3 Additional marking
4.10.3.1 Pipes which conform to this standard, and also conform to other standard(s) may be marked
additionally with the number(s) of the other standard(s), together with the minimum required marking
in accordance with the other standard(s).
4.10.3.2 Pipes which conform to this standard and which are third party certified may be marked
accordingly.
NOTE Attention is drawn to the possible need to include CE marking when required for legislative purposes.
4.11 Allowable operating pressures
For the allowable operating pressure annex A of EN 1452-2:1999 shall apply.
5 Fittings
5.1 Material
The fitting material shall conform to EN 1452-3:1999.
5.2 General characteristics
5.2.1 Appearance
The appearance shall conform to EN 1452-3:1999.
5.2.2 Colour
The colour of injection-moulded fittings shall be grey throughout the wall.
The colour of fittings made from pipes shall be grey or brown throughout the wall.
5.2.3 Opacity
The wall of the fittings shall not transmit more than 0,2 % of visible light when measured in accordance
with EN 578.
5.3 Geometrical characteristics of fittings
The geometrical characteristics of fit
...
Questions, Comments and Discussion
Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.