Abstract

This clause of Part 1 is replaced by the following:
This document applies to temperature sensing controls
– for use in, on, or in association with equipment for household appliance and similar use, including equipment for heating, air-conditioning and similar applications. The equipment can use electricity, gas, oil, solid fuel, solar thermal energy, etc., or a combination thereof.
NOTE 1 Throughout this document, the word "equipment" means "appliance and equipment" and "controls" means "temperature sensing controls".
– for building automation within the scope of ISO 16484 series and IEC 63044 series (HBES/BACS);
EXAMPLE 1 Independently mounted temperature sensing controls, controls in smart grid systems and controls for building automation systems within the scope of ISO 16484-2.
– for equipment that is used by the public, such as equipment intended to be used in shops, offices, hospitals, farms and commercial and industrial applications;
EXAMPLE 2 Controls for commercial catering, heating and air-conditioning equipment.
– that are smart enabled controls;
EXAMPLE 3 Smart grid control, remote interfaces/control of energy-consuming equipment including computer or smart phone.
– that are AC or DC powered controls with a rated voltage not exceeding 690 V AC or 600 V DC;
– used in, on, or in association with equipment that use electricity, gas, oil, solid fuel, solar thermal energy, etc., or a combination thereof;
– utilized as part of a control system or controls which are mechanically integral with multifunctional controls having non-electrical outputs;
– using NTC or PTC thermistors and to discrete thermistors, requirements for which are contained in Annex J;
– that have electrical circuits and control circuits which are, for example, operated by bimetals, magnet coils, memory metals, pressure elements, temperature-sensitive
expansion elements or electronic elements.
– as well as manual controls when such are electrically and/or mechanically integral with automatic controls.
NOTE 2 Requirements for manually actuated mechanical switches not forming part of an automatic control are contained in IEC 61058-1-1.
This document applies to
– the inherent safety of automatic electrical controls, and
– functional safety of temperature sensing controls and safety related systems,
– controls where the performance (for example the effect of EMC phenomena) of the product can impair the overall safety and performance of the controlled system,
– the operating values, operating times, and operating sequences where such are associated with equipment safety and to the testing of automatic electrical temperature sensing control devices used in, or in association with, equipment,
EXAMPLE 4 Boiler thermostats, fan controls, temperature limiters and thermal cut-outs.
– electrical safety of temperature sensing controls with non-electrical outputs such as refrigerant flow and gas controls,
– single-operation devices as defined in this document.
This document specifies the requirements for construction, operation and testing of automatic electrical controls used in, on, or in association with an equipment.
This document does not
– apply to automatic electrical temperature sensing controls intended exclusively for industrial process applications unless explicitly mentioned in the relevant part 2 or the equipment standard. However, this document can be applied to evaluate automatic electrical controls intended specifically for industrial applications in cases where no relevant safety standard exists.
– take into account the response value of an automatic action of a control, if such a response value is dependent upon the method of mounting the control in the equipment. Where a response value is of significant purpose for the protection of the user, or surroundings, the value defined in the appropriate equipment standard or as determined by the manufacturer will apply.
– address the integrity of the output signal to the networ

Status
Published
Publication Date
02-Jul-2026
Current Stage
6060 - Document made available - Publishing
Start Date
03-Jul-2026
Due Date
31-Dec-2025
Completion Date
31-Dec-2025

Buy Documents

Standard

EN IEC 60730-2-9:2026 - BARVE

English language (79 pages)
Preview
Preview
e-Library read for
×1 day

EN IEC 60730-2-9:2026 is a CENELEC European Standard for automatic electrical controls with temperature sensing functions. It specifies particular requirements for the construction, operation and testing of thermostats, temperature limiters, thermal cut-outs and single-operation devices used in appliances, building automation and similar equipment. The standard is aimed at manufacturers, test laboratories, certification bodies, quality teams and equipment designers who need a common basis for selecting and verifying these controls.

What does EN IEC 60730-2-9:2026 specify?

EN IEC 60730-2-9:2026 gives the Part 2-9 requirements for temperature sensing controls and is used together with EN IEC 60730-1. The document adds to, modifies or replaces the corresponding Part 1 clauses so that the general automatic-control rules become specific requirements for temperature sensing applications.

The scope covers controls for household and similar equipment, including heating and air-conditioning equipment, equipment used by the public, building automation within HBES/BACS, smart-enabled controls, AC or DC powered controls up to the stated voltage limits, and controls used with thermistors and other temperature sensing elements. It also covers manual controls when they are electrically and/or mechanically integral with automatic controls.

The document excludes automatic electrical temperature sensing controls intended exclusively for industrial process applications unless a relevant Part 2 or equipment standard explicitly mentions them. It also does not use mounting-related response values as a general basis for the control if that response depends on how the control is installed, and it does not deal with network output signal integrity unless that has been assessed as part of the control system.

The document is organized in the usual IEC Part 1 plus Part 2 format:

  • clauses 1 to 26 cover scope, references, terms, general requirements, technical information, safety, construction, tests, endurance and EMC
  • Annex G, H, J, BB, CC and DD are normative
  • Annex Q, R, S, T, AA and EE are informative
AnnexWhat it covers
GResistance to heat, fire and tracking tests
HFunctional safety and additional information requirements
JThermistor elements and controls using thermistors
QRegional differences for CENELEC member countries
RNational differences for the United States
SNational differences for Japan
TNational differences for Canada
AAMaximum manufacturing deviation and drift
BBTime factor
CCNumber of cycles
DDControls for use in agricultural confinement buildings
EEGuide to the application of temperature sensing controls

What are the key requirements of EN IEC 60730-2-9:2026?

EN IEC 60730-2-9:2026 is mainly about safe temperature control behavior, declared operating values and type testing. The most practical part of the document is that it tells the manufacturer what must be declared, what must be tested, and which extra tests apply to specific control types and applications.

How the Part 2-9 rules work with Part 1

Clause 1 and the foreword make clear that EN IEC 60730-2-9:2026 supplements EN IEC 60730-1. If Part 2-9 says addition, modification or replacement, the corresponding Part 1 requirement is adapted accordingly. If a Part 1 subclause is not mentioned, that Part 1 subclause applies as written.

In practice, this means a user of the standard has to read the two parts together. A control cannot be assessed only against Part 2-9 if the base requirement is in Part 1.

What must be declared about the control

Clause 5 and Table 1 require technical information to be declared for a number of control characteristics, and Table H.1 adds more items for functional safety and EMC-related assessment. Important declarations include maximum sensing element temperature, time factor, SOD reset temperature, number of cycles, minimum current for a test, ambient temperature limits, and the output condition after operation for certain control types.

This matters because the standard uses declared values as the basis for testing and selection. Buyers and test engineers need these declarations to decide whether a control fits the appliance, the installation conditions and the safety function.

Which control types and behaviors are covered

Clause 3 defines the key temperature sensing control types used in the document, including room thermostats, boiler thermostats, voltage maintained thermal cut-outs, agricultural thermostats and the two kinds of SOD. The standard also covers type 1 and type 2 actions, plus special actions such as push-and-turn, pull-and-turn, and several trip-free or safety-related action types in clause 9.

This is important in practice because the action type determines how the control is expected to operate, reset or stay latched after operation. For a designer, the chosen action type drives the mechanical design, the reset mechanism and the control’s role in the safety chain.

What constructional and safety tests apply

Clauses 6 to 15 and 20 to 26 cover the safety backbone of the standard: protection against electric shock, earthing, terminals, creepage and clearance, component behavior, moisture and dust resistance, electric strength, heating, endurance, mechanical strength, resistance to heat/fire/tracking, corrosion, EMC emission and immunity, and abnormal operation tests.

For controls with liquid metal parts, clause 20.102 adds special mechanical and pressure-related tests. For non-bimetallic SODs, clause 9.1.102 and clause 19.15.106.2 add material, ageing and operating tests that reflect their one-time protective role. For voltage maintained thermal cut-outs, clause 16.4.101 and clause 19.15.105 address the thermal and reset behavior tied to supply voltage.

Which special performance checks are important

Clause 9.101 and Annex BB define the time factor and the test methods used to verify it. Clause 19.101 gives the type 2.P cycling test, including thermal cycling, two-bath and temperature-change methods. Annex CC sets cycle counts for independently mounted and in-line cord controls.

In practice, these clauses tell the user how quickly the sensing element responds, how it behaves after thermal cycling, and how many operating cycles the control must endure. That is the data that matters when comparing a thermostat for a cooker, a limiter for a heater or a safety cut-out in a refrigeration or water-heating application.

Which special applications have extra requirements

Annex J covers thermistor elements and controls using thermistors. Annex DD adds a test method for controls intended for agricultural confinement buildings, with exposure to corrosive gases, humidity, disinfectants and dust. Annex EE is a selection and application guide that explains how temperature sensing controls are classified and how they are used in typical appliances.

That means the standard is not just a generic electrical-control document. It also gives extra rules for controls that work in harsh farming environments, and guidance for selecting the right control for domestic, commercial and building applications.

What terms does EN IEC 60730-2-9:2026 define?

  • single-operation device (SOD) - A control with a temperature sensing element intended to operate only once and then be completely replaced.
  • bimetallic single-operation device - An SOD with a bimetallic sensing element that does not reset above the declared temperature.
  • non-bimetallic single-operation device - An SOD with a non-bimetallic thermal element that operates once and then needs complete or partial replacement.
  • room thermostat - A thermostat intended to control the temperature of habitable space.
  • boiler thermostat - A thermostat intended to control boiler or liquid temperature.
  • voltage maintained thermal cut-out - A thermal cut-out that stays operated because of the voltage across it in the operated state.
  • time factor - The transient response of a temperature sensing control to a defined change in the activating quantity.
  • agricultural confinement building - A heated and/or cooled farm structure where waste and feed can create corrosive compounds not normally found in freely ventilated farm buildings.

Who uses EN IEC 60730-2-9:2026?

EN IEC 60730-2-9:2026 is used by control manufacturers, appliance OEMs, building automation designers, test laboratories, certification bodies and quality teams. It is relevant to heating, air-conditioning, cooking, refrigeration, laundry, water-heating, commercial catering, agricultural and smart-enabled equipment.

For manufacturers, the standard supports design and type testing. For buyers and OEMs, it helps specify the right control type, declared operating values and application limits. For labs and certification teams, it gives the test methods and pass/fail basis.

What changed in EN IEC 60730-2-9:2026 from the previous edition?

EN IEC 60730-2-9:2026 is the fifth edition and it supersedes EN IEC 60730-2-9:2019, including amendments A1:2019 and A2:2020. The stated technical revision is the adoption of IEC 60730-1:2022 and the significant changes carried in that Part 1 edition.

Which standards are used with EN IEC 60730-2-9:2026?

  • EN IEC 60730-1 - the base part used together with Part 2-9 for general requirements, tests and definitions.
  • IEC 60216-1 / EN IEC 60216-1 - provides ageing procedures and evaluation of thermal endurance test results for insulating materials.
  • IEC 60691 - referenced for thermal links connected with some SOD-related distinctions.
  • ISO 16484 series and IEC 63044 series - define the building-automation context named in the scope.
  • IEC 60335 series - used in Annex EE for application examples and to show where temperature sensing controls operate in appliance tests.
  • IEC 60079 series - referenced in Annex DD because agricultural-confinement controls are not intended for explosive atmospheres.

What does the EN IEC 60730-2-9:2026 document contain?

The document contains the clause structure for scope, references, terms, safety, construction, environmental and endurance testing, EMC, and abnormal operation. It includes Table 1 and Table H.1 for declared technical information, Table AA.1 for manufacturing deviation and drift, Table BB.1 for time factor values, and Table CC.1 for cycle counts.

It also includes test methods and figures for practical verification, such as the impact tool, the aluminium cylinder for temperature-change testing, and the time-factor diagrams in Annex BB. Annex DD gives the detailed test sequence for agricultural confinement buildings, while Annex EE gives classification guidance, appliance examples and selection tables for common temperature sensing controls.

Relations

Effective Date
14-May-2024
Effective Date
14-May-2024
Effective Date
14-May-2024
Effective Date
16-Jun-2026
Effective Date
25-Aug-2026
Effective Date
07-Jul-2026
Effective Date
07-Jul-2026
Effective Date
07-Jul-2026
Effective Date
07-Jul-2026
Effective Date
07-Jul-2026
Effective Date
07-Jul-2026
Effective Date
07-Jul-2026
Effective Date
07-Jul-2026
Effective Date
07-Jul-2026
Effective Date
07-Jul-2026

Buy Documents

Standard

EN IEC 60730-2-9:2026 - BARVE

English language (79 pages)
Preview
Preview
e-Library read for
×1 day

Frequently Asked Questions

EN IEC 60730-2-9:2026 is a standard published by CLC. Its full title is "Automatic electrical controls - Part 2-9: Particular requirements for temperature sensing controls". This standard covers: This clause of Part 1 is replaced by the following: This document applies to temperature sensing controls – for use in, on, or in association with equipment for household appliance and similar use, including equipment for heating, air-conditioning and similar applications. The equipment can use electricity, gas, oil, solid fuel, solar thermal energy, etc., or a combination thereof. NOTE 1 Throughout this document, the word "equipment" means "appliance and equipment" and "controls" means "temperature sensing controls". – for building automation within the scope of ISO 16484 series and IEC 63044 series (HBES/BACS); EXAMPLE 1 Independently mounted temperature sensing controls, controls in smart grid systems and controls for building automation systems within the scope of ISO 16484-2. – for equipment that is used by the public, such as equipment intended to be used in shops, offices, hospitals, farms and commercial and industrial applications; EXAMPLE 2 Controls for commercial catering, heating and air-conditioning equipment. – that are smart enabled controls; EXAMPLE 3 Smart grid control, remote interfaces/control of energy-consuming equipment including computer or smart phone. – that are AC or DC powered controls with a rated voltage not exceeding 690 V AC or 600 V DC; – used in, on, or in association with equipment that use electricity, gas, oil, solid fuel, solar thermal energy, etc., or a combination thereof; – utilized as part of a control system or controls which are mechanically integral with multifunctional controls having non-electrical outputs; – using NTC or PTC thermistors and to discrete thermistors, requirements for which are contained in Annex J; – that have electrical circuits and control circuits which are, for example, operated by bimetals, magnet coils, memory metals, pressure elements, temperature-sensitive expansion elements or electronic elements. – as well as manual controls when such are electrically and/or mechanically integral with automatic controls. NOTE 2 Requirements for manually actuated mechanical switches not forming part of an automatic control are contained in IEC 61058-1-1. This document applies to – the inherent safety of automatic electrical controls, and – functional safety of temperature sensing controls and safety related systems, – controls where the performance (for example the effect of EMC phenomena) of the product can impair the overall safety and performance of the controlled system, – the operating values, operating times, and operating sequences where such are associated with equipment safety and to the testing of automatic electrical temperature sensing control devices used in, or in association with, equipment, EXAMPLE 4 Boiler thermostats, fan controls, temperature limiters and thermal cut-outs. – electrical safety of temperature sensing controls with non-electrical outputs such as refrigerant flow and gas controls, – single-operation devices as defined in this document. This document specifies the requirements for construction, operation and testing of automatic electrical controls used in, on, or in association with an equipment. This document does not – apply to automatic electrical temperature sensing controls intended exclusively for industrial process applications unless explicitly mentioned in the relevant part 2 or the equipment standard. However, this document can be applied to evaluate automatic electrical controls intended specifically for industrial applications in cases where no relevant safety standard exists. – take into account the response value of an automatic action of a control, if such a response value is dependent upon the method of mounting the control in the equipment. Where a response value is of significant purpose for the protection of the user, or surroundings, the value defined in the appropriate equipment standard or as determined by the manufacturer will apply. – address the integrity of the output signal to the networ

This clause of Part 1 is replaced by the following: This document applies to temperature sensing controls – for use in, on, or in association with equipment for household appliance and similar use, including equipment for heating, air-conditioning and similar applications. The equipment can use electricity, gas, oil, solid fuel, solar thermal energy, etc., or a combination thereof. NOTE 1 Throughout this document, the word "equipment" means "appliance and equipment" and "controls" means "temperature sensing controls". – for building automation within the scope of ISO 16484 series and IEC 63044 series (HBES/BACS); EXAMPLE 1 Independently mounted temperature sensing controls, controls in smart grid systems and controls for building automation systems within the scope of ISO 16484-2. – for equipment that is used by the public, such as equipment intended to be used in shops, offices, hospitals, farms and commercial and industrial applications; EXAMPLE 2 Controls for commercial catering, heating and air-conditioning equipment. – that are smart enabled controls; EXAMPLE 3 Smart grid control, remote interfaces/control of energy-consuming equipment including computer or smart phone. – that are AC or DC powered controls with a rated voltage not exceeding 690 V AC or 600 V DC; – used in, on, or in association with equipment that use electricity, gas, oil, solid fuel, solar thermal energy, etc., or a combination thereof; – utilized as part of a control system or controls which are mechanically integral with multifunctional controls having non-electrical outputs; – using NTC or PTC thermistors and to discrete thermistors, requirements for which are contained in Annex J; – that have electrical circuits and control circuits which are, for example, operated by bimetals, magnet coils, memory metals, pressure elements, temperature-sensitive expansion elements or electronic elements. – as well as manual controls when such are electrically and/or mechanically integral with automatic controls. NOTE 2 Requirements for manually actuated mechanical switches not forming part of an automatic control are contained in IEC 61058-1-1. This document applies to – the inherent safety of automatic electrical controls, and – functional safety of temperature sensing controls and safety related systems, – controls where the performance (for example the effect of EMC phenomena) of the product can impair the overall safety and performance of the controlled system, – the operating values, operating times, and operating sequences where such are associated with equipment safety and to the testing of automatic electrical temperature sensing control devices used in, or in association with, equipment, EXAMPLE 4 Boiler thermostats, fan controls, temperature limiters and thermal cut-outs. – electrical safety of temperature sensing controls with non-electrical outputs such as refrigerant flow and gas controls, – single-operation devices as defined in this document. This document specifies the requirements for construction, operation and testing of automatic electrical controls used in, on, or in association with an equipment. This document does not – apply to automatic electrical temperature sensing controls intended exclusively for industrial process applications unless explicitly mentioned in the relevant part 2 or the equipment standard. However, this document can be applied to evaluate automatic electrical controls intended specifically for industrial applications in cases where no relevant safety standard exists. – take into account the response value of an automatic action of a control, if such a response value is dependent upon the method of mounting the control in the equipment. Where a response value is of significant purpose for the protection of the user, or surroundings, the value defined in the appropriate equipment standard or as determined by the manufacturer will apply. – address the integrity of the output signal to the networ

EN IEC 60730-2-9:2026 is classified under the following ICS (International Classification for Standards) categories: 97.120 - Automatic controls for household use. The ICS classification helps identify the subject area and facilitates finding related standards.

EN IEC 60730-2-9:2026 has the following relationships with other standards: It is inter standard links to EN IEC 60730-2-9:2019, EN IEC 60730-2-9:2019/A1:2019, EN IEC 60730-2-9:2019/A2:2020, EN IEC 60216-1:2026, EN 50465:2015, EN 12897:2016, EN 12977-5:2012, EN 15033:2006, EN 15502-2-2:2014, EN IEC 62933-5-1:2024, EN 13278:2003, EN 12098-5:2017, EN 12828:2012+A1:2014, EN 12098-4:2005, EN 12828:2012. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.

EN IEC 60730-2-9:2026 is associated with the following European legislation: EU Directives/Regulations: 2014/30/EU, 2014/35/EU; Standardization Mandates: M/511, M/552. When a standard is cited in the Official Journal of the European Union, products manufactured in conformity with it benefit from a presumption of conformity with the essential requirements of the corresponding EU directive or regulation.

EN IEC 60730-2-9:2026 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.

Standards Content (Sample)

Contents

  • 1 Scope
  • 2 Normative references
  • 3 Terms and definitions
  • 3.2 Definitions of types of controls according to purpose
  • 3.3 Definitions relating to the function of controls
  • 3.5 Definitions of types of control according to construction
  • 4 General
  • 4.2 General requirements
  • 4.3 General notes on tests
  • 5 Required technical information
  • 5.2 Methods of providing technical information
  • Annex DD
  • 5.3 Class II symbol
  • 6 Protection against electric shock
  • 7 Provision for protective earthing
  • 8 Terminals and terminations
  • 9 Constructional requirements
  • 9.1 Materials
  • 9.3 Actuation and operation
  • 9.4 Actions
  • 9.6 Mounting of controls
  • 10 Threaded parts and connections
  • 11 Creepage distances, clearances and distances through solid insulation
  • 12 Components
  • 13 Fault assessment on electronic circuits
  • 13.1 Fault assessment for inherent safety
  • 14 Moisture and dust resistance
  • 15 Electric strength and insulation resistance
  • 16 Heating
  • 17 Manufacturing deviation and drift
  • 18 Environmental stress
  • 19 Endurance
  • 19.15 Test for particular purpose controls
  • 20 Mechanical strength
  • 21 Resistance to heat, fire and tracking
  • 22 Resistance to corrosion
  • 23 Electromagnetic compatibility (EMC) requirements – Emission
  • 24 Normal operation
  • 25 Electromagnetic compatibility (EMC) requirements – Immunity
  • 26 Abnormal operation tests
  • Annex G
  • Annex H
  • Annex J
  • Annex Q
  • Annex R
  • Annex S
  • Annex T
  • Annex AA
  • Annex BB
  • Annex CC
  • Annex DD
  • Annex DD does not prescribe any requirement for pre-conditioning. However, controls
  • Annex EE
  • Bibliography

1 Scope

This clause of Part 1 is replaced by the following:

This document applies to temperature sensing controls - for use in, on, or in association with equipment for household appliance and similar use, including equipment for heating, air-conditioning and similar applications. The equipment can use electricity, gas, oil, solid fuel, solar thermal energy, etc., or a combination thereof. NOTE 1 Throughout this document, the word "equipment" means "appliance and equipment" and "controls" means "temperature sensing controls".

- for building automation within the scope of ISO 16484 series and IEC 63044 series (HBES/BACS); EXAMPLE 1 Independently mounted temperature sensing controls, controls in smart grid systems and controls for building automation systems within the scope of ISO 16484-2.

- for equipment that is used by the public, such as equipment intended to be used in shops, offices, hospitals, farms and commercial and industrial applications; EXAMPLE 2 Controls for commercial catering, heating and air-conditioning equipment. - that are smart enabled controls; EXAMPLE 3 Smart grid control, remote interfaces/control of energy-consuming equipment including computer or smart phone.

  • that are AC or DC powered controls with a rated voltage not exceeding 690 V AC or 600 V DC;
  • used in, on, or in association with equipment that use electricity, gas, oil, solid fuel, solar thermal energy, etc., or a combination thereof;
  • utilized as part of a control system or controls which are mechanically integral with multifunctional controls having non-electrical outputs;
  • using NTC or PTC thermistors and to discrete thermistors, requirements for which are contained in Annex J;
  • that have electrical circuits and control circuits which are, for example, operated by bimetals, magnet coils, memory metals, pressure elements, temperature-sensitive expansion elements or electronic elements.
  • as well as manual controls when such are electrically and/or mechanically integral with automatic controls.

NOTE 2 Requirements for manually actuated mechanical switches not forming part of an automatic control are contained in IEC 61058-1-1.

This document applies to - the inherent safety of automatic electrical controls, and - functional safety of temperature sensing controls and safety related systems, - controls where the performance (for example the effect of EMC phenomena) of the product can impair the overall safety and performance of the controlled system, - the operating values, operating times, and operating sequences where such are associated with equipment safety and to the testing of automatic electrical temperature sensing control devices used in, or in association with, equipment, EXAMPLE 4 Boiler thermostats, fan controls, temperature limiters and thermal cut-outs. - electrical safety of temperature sensing controls with non-electrical outputs such as refrigerant flow and gas controls, - single-operation devices as defined in this document.

SIST EN IEC 60730-2-9:2026 IEC 60730-2-9:2026  IEC 2026 This document specifies the requirements for construction, operation and testing of automatic electrical controls used in, on, or in association with an equipment. This document does not - apply to automatic electrical temperature sensing controls intended exclusively for industrial process applications unless explicitly mentioned in the relevant part 2 or the equipment standard. However, this document can be applied to evaluate automatic electrical controls intended specifically for industrial applications in cases where no relevant safety standard exists.

  • take into account the response value of an automatic action of a control, if such a response value is dependent upon the method of mounting the control in the equipment. Where a response value is of significant purpose for the protection of the user, or surroundings, the value defined in the appropriate equipment standard or as determined by the manufacturer will apply.
  • address the integrity of the output signal to the network devices, such as interoperability with other devices unless it has been evaluated as part of the control system.

2 Normative references

This clause of Part 1 is applicable except as follows:

Addition:

IEC 60216-1, Electrical insulating materials - Thermal endurance properties - Part 1: Ageing procedures and evaluation of test results

3 Terms and definitions

This clause of Part 1 is applicable except as follows:

3.2 Definitions of types of controls according to purpose

Additional definitions:

3.2.101 single-operation device SOD control having a temperature sensing element which is intended to operate only once and then requires complete replacement 3.2.102 bimetallic single-operation device single-operation device (SOD) having a bimetallic temperature sensing element Note 101 to entry: A bimetallic single-operation device (SOD) does not reset above a declared temperature (see 9.4.103).

Note 102 to entry: Requirements for thermal links (which are not allowed to reset) are contained in IEC 60691.

SIST EN IEC 60730-2-9:2026 IEC 60730-2-9:2026  IEC 2026 3.2.103 non-bimetallic single-operation device single-operation device (SOD) having a temperature sensing element which is part of a combination action control, the operation of which cannot be separated from other functions of the control and having a non-bimetallic thermal element that operates only once and then needs complete or partial replacement Note 101 to entry: When such parts can be tested separately, they are considered to be thermal links within the scope of IEC 60691.

Note 102 to entry: The ageing period and thermal response of the device is dependent on the intended use of the device. As a result, the nature of the testing applicable to the device is representative of the application conditions for which the protective control is intended (see 7.2).

Note 103 to entry: Non-bimetallic SODs provide the equivalent of micro-disconnection. 3.2.104 room thermostat independently mounted or incorporated thermostat intended to control the temperature of habitable space 3.2.105 boiler thermostat thermostat intended to control boiler/liquid temperature 3.2.106 voltage maintained thermal cut-out thermal cut-out which is maintained in its operated condition by the voltage which appears across it in that condition Note 101 to entry: A voltage maintained thermal cut-out control can only be reset if disconnected from the electrical supply.

3.2.107 agricultural thermostat thermostat intended for use in agricultural confinement buildings 3.2.108 agricultural confinement building farm structure characterized by being heated and/or cooled by artificial means, where accumulation of animal food and waste can result in concentrations of corrosive compounds not normally found in freely ventilated farm buildings (e.g. barns) and periodically disinfected prior to subsequent similar use

3.3 Definitions relating to the function of controls

Additional definition:

3.3.101 time factor transient response of temperature sensing controls by defined change of the activating quantity

3.5 Definitions of types of control according to construction

Additional definitions:

3.5.101 push-and-turn actuation two-step actuation accomplished by first pushing, then rotating the actuating member of the control

SIST EN IEC 60730-2-9:2026 IEC 60730-2-9:2026  IEC 2026 3.5.102 pull-and-turn actuation two-step actuation accomplished by first pulling, then rotating the actuating member of the control 3.101 permanent operation continuous monitoring of the protective function during the operation of the appliance or system for longer than 24 h Note 101 to entry: 24 h is considered the typical time interval between a first and a second fault. 3.102 non-permanent operation continuous monitoring of the protective function during the operation of the appliance or system for less than 24 h Note 101 to entry: 24 h is considered the typical time interval between a first and a second fault.

4 General

This clause of Part 1 is applicable except as follows:

4.2 General requirements

Additional note:

NOTE 101 Annex EE can be used as a guide for selecting and carrying out relevant tests as well as establishing test levels and compliance criteria.

4.3 General notes on tests

4.3.2 Conditions of test

Additional subclauses:

4.3.2.101 For the purposes of the tests of this document and unless otherwise indicated, ambient temperature excursions beyond T during abnormal operation as a precursor to the max operation of a manual reset thermal cut-out or a bimetallic SOD are ignored. 4.3.2.102 For manual reset thermal cut-outs and bimetallic SODs which have an operating value above T , the temperature at the sensing element is raised, as necessary, max to achieve any cycling required during the tests.

4.3.3 Samples required

4.3.3.1 Addition:

Six samples of bimetallic SODs are used for the test of Clause 17 and a further six for the test of Clause 19.

SIST EN IEC 60730-2-9:2026 IEC 60730-2-9:2026  IEC 2026

5 Required technical information

This clause of Part 1is applicable except as follows:

5.2 Methods of providing technical information

Table 1 – Required technical information and methods of providing these information Clause or Information Method subclause Additional items:

101 Maximum sensing element temperature (other than relevant to 16.101 X

requirement 105) Controls for use in or on cooking appliances Controls for use in or on ovens of the self-cleaning type Controls for use in or on food-handling appliances Controls having parts containing liquid metal 102 Time factor with or without sheath 3.3.101 X 9.101 BB.2.2 103 3.2.101 X SOD reset temperature (either –35 °C or 0 °C) 9.4.103 19.15.106.1.2 104 Number of cycles for bimetallic SOD with 0 °C reset 19.15.106.1.5 X 105 Maximum sensing element temperature in °C of controls used in self- 19.15.104 D cleaning ovens (T ) e

106 20.102 D Controls having parts containing liquid metal 107 Tensile yield strength 9.1.101 X

108 23.2.2 D Minimum current for the purpose of the test of 23.2.2 109 T is the maximum ambient temperature in which the control may remain 16.4.101 D max.1 continuously in the operated condition so that Table 17 temperatures are not

exceeded 110 Time period t is the maximum time during which the ambient temperature 16.4.101 D

can be higher than T after the control has operated max.1 111 Temperature limit above which automatic reset of a manual reset thermal 3.2.106 X cut-out or a voltage maintained thermal cut-out shall not occur (not higher 9.4.106 than –20 °C) 19.15.105 112 For type 2.P controls, the method of test 19.101 X 113 The click rate N or switching operations per minute for the purposes of 23 X testing to CISPR 14-1

114 Rated functioning temperature (T ) of the sensing element, which causes 19.15.106.2 C f a non-bimetallic SOD to change state of conductivity 105,107 115 19.15.106.2.2 D Ageing temperature for non-bimetallic SOD 106,107 116 19.15.106.2.2 D Rate of rise of temperature for testing non-bimetallic SOD 117 Agricultural thermostat 3.2.107 D 9.4.107 9.6.3.101

Annex DD

SIST EN IEC 60730-2-9:2026 IEC 60730-2-9:2026  IEC 2026 Additional footnotes:

This declaration applies only to temperature sensing controls containing liquid metal. For temperature sensing controls used in or on self-cleaning ovens, this declaration is the temperature for the cooking operation.

Metal is an inclusive term that encompasses chemically metallic elements such as sodium (Na), potassium (K), and others. Mercury (Hg) is generally not allowed.

When no minimum is declared, the test value is 15 mA.

Consideration should be given to the provision of information by the equipment manufacturer relating to the minimum time that the appliance has to be disconnected from the supply to allow a voltage maintained thermal cut-out to reset.

Determined by the control manufacturer based on the opening temperature of the thermal-cut-out.

Determined by the control manufacturer referring to the actual maximum rate of rise probable in the projected end-use equipment.

Non-bimetallic SODs are limited for use in appliances for heating or employing liquids or steam. They are not suitable for instantaneous water heaters and storage water heaters

5.3 Class II symbol

5.3.1 Addition:

The symbol for class II shall be used on controls of class II integrated or incorporated in an assembly utilizing a non-electrical energy source.

6 Protection against electric shock

This clause of Part 1 is applicable.

7 Provision for protective earthing

This clause of Part 1 is applicable.

8 Terminals and terminations

This clause of Part 1 is applicable.

9 Constructional requirements

This clause of Part 1 is applicable except as follows:

9.1 Materials

Additional subclauses:

9.1.101 Parts containing liquid metal Controls containing liquid metal declared under Table 1, requirement 106, and parts of any control that contain sodium (Na), potassium (K), or both, shall be constructed of metal that has a tensile yield strength at least four times the circumferential (hoop) or other stress on the parts at 1,2 times the maximum temperature of the sensing element (T ) in °C. e Compliance is checked by inspection of the manufacturer's declaration and by the test of 20.102.

SIST EN IEC 60730-2-9:2026 IEC 60730-2-9:2026  IEC 2026 9.1.102 Material for non-bimetallic SODs Insulating material used in non-bimetallic SODs as defined in this document shall comply with the requirements of IEC 60216-1 and be suitable for the application.

9.3 Actuation and operation

9.3.9 Pull-cord actuated control

Additional note:

NOTE 101 The Note is not applicable to controls classified as type 1.X or 2.X or type 1.Z or 2.Z.

9.4 Actions

9.4.3 Type 2 action

Addition:

Capacitors shall not be connected across the contacts of a thermal cut-out. Constructions requiring a soldering operation to reset thermal cut-outs are not permitted.

9.4.11 Type 1.H or 2.H action (a trip-free mechanism in which the contacts cannot be

prevented from opening and which can automatically be reset to the "closed" position after normal operation conditions have been restored if the reset means is held in the "reset" position) Modification:

Replace the compliance criteria with the following:

Compliance is checked by inspection and by the tests as given in 9.4.11.101 to 9.4.11.106. Additional subclauses:

9.4.11.101 For this test, the reset mechanism of the control will be held in the reset position for the duration of the test from 9.4.11.102 to 9.4.11.104. The verification of the automatic nonresetting above –35 °C will be carried out by 9.4.11.105 to 9.4.11.106. For SOD, the verification of the automatic non-resetting above either +0 °C or –35 °C will be carried out by 9.4.11.105 to 9.4.11.106, as declared in item 103 of Table 1.

9.4.11.102 With the reset mechanism held in the reset position at room temperature, continuity across contacts is observed by a low-energy circuit, 0,05 A maximum. 9.4.11.103 The control’s sensing element is then installed in an air circulating chamber or a liquid bath and the control’s switch head is installed as in 16.5 a). When the whole control is declared as the sensing element, the whole control is placed in an air-circulating chamber. The control or the control’s sensing element is adjusted for the maximum set point temperature. The chamber or liquid bath temperature shall be determined by positioning a thermocouple wire adjacent to the control under test. The chamber or liquid bath temperature is then raised from room temperature and held at approximately 10 K below the set point until temperatures stabilize. The chamber or liquid bath temperature is then raised at a rate of not more than 0,5 K per minute until the contact operates. Indication of contact separation is observed by applying the method of 9.4.11.104.

SIST EN IEC 60730-2-9:2026 IEC 60730-2-9:2026  IEC 2026 9.4.11.104 After the control has operated and with the reset mechanism still held in the reset position, the temperature of the chamber or liquid bath is then reduced to determine if the control automatically resets. Verification of contact closure is done by applying the method in 9.4.11.102.

9.4.11.105 The whole control or the control’s sensing element is then installed in an air circulating chamber or liquid bath again and the control’s switch head (if applicable) is installed as in 16.5 a) with the reset mechanism in its normal condition. The chamber or liquid bath temperature shall be determined by positioning a thermocouple wire adjacent to the control under test. The chamber or liquid bath temperature is raised from room temperature and held at approximately 10 K below the set point until temperatures stabilize. The chamber or liquid bath temperature is then raised at a rate of not more than 0,5 K per minute until the contact operates. Indication of contact separation is observed by applying the method of 9.4.11.102. 9.4.11.106 After the control has operated, the temperature of the chamber is allowed to cool down to either +0 °C or –35 °C. Indication of contact separation is observed by applying the method of 9.4.11.102.

9.4.12 Type 1.J or 2.J action (a trip-free mechanism in which the contacts cannot be

prevented from opening and the control is not permitted to function as an automatic reset device if the reset means is held in the "reset" or "on" position) Modification:

Replace the compliance criteria with the following:

Compliance is checked by inspection and by the tests as given in 9.4.12.101 to 9.4.12.106. Additional subclauses:

9.4.12.101 For this test, the reset mechanism of the control will be held in the reset position for the duration of the test from 9.4.12.102 to 9.4.12.104. The verification of the automatic nonresetting above –35 °C will be carried out by 9.4.12.105 to 9.4.12.106. For SOD, the verification of the automatic non-resetting above either +0 °C or –35 °C will be carried out by 9.4.12.105 to 9.4.12.106, as declared in item 103 of Table 1.

9.4.12.102 With the reset mechanism held in the reset position at room temperature, contact separation is observed by a low-energy circuit, 0,05 A maximum. 9.4.12.103 The control’s sensing element is then installed in an air circulating chamber or liquid bath and the control’s switch head is installed as in 16.5. When the whole control is declared as the sensing element, the whole control is placed in an air-circulating chamber. The control or the control’s sensing element is adjusted for the maximum set point temperature. The chamber or liquid bath temperature shall be determined by positioning a thermocouple wire adjacent to the control under test. The chamber or liquid bath temperature is raised from room temperature and held at approximately 10 K below the set point until temperatures stabilize. The chamber or liquid bath temperature is then raised at a rate of not more than 0,5 K per minute until 10 K over the operation temperature. Indication of contact separation is still observed by applying the method of 9.4.12.102. 9.4.12.104 After the control has operated and with the reset mechanism still held in the reset position, the temperature of the chamber or liquid bath is then reduced to determine if the control automatically resets. Verification of contact closure is done by applying the method in 9.4.12.102.

...