IEC 60598-2-3:2002+AMD1:2011 CSV
(Main)Luminaires - Part 2-3: Particular requirements - Luminaires for road and street lighting
Luminaires - Part 2-3: Particular requirements - Luminaires for road and street lighting
IEC 60598-2-3:2002+A1:2011 specifies requirements for:
- luminaires for road, street lighting and other public outdoor lighting applications;
- tunnel lighting;
- column-integrated luminaires with a minimum total height above normal ground level of 2,5 m;
- and for use with electrical lighting sources on supply voltages not exceeding 1 000 V.
This publication is to be read in conjunction with IEC 60598-1:2008.
This consolidated version consists of the third edition (2002) and its amendment 1 (2011) and has been prepared for user convenience. Therefore, no need to order amendment in addition to this publication.
Luminaires - Partie 2-3: Règles particulières - Luminaires d'éclairage public
La CEI 60598-2-3:2002+A1:2011 spécifie les prescriptions applicables:
- aux luminaires pour les routes, les rues et les autres applications d'éclairage public à l'extérieur;
- à l'éclairage des tunnels;
- aux luminaires intégrés dans des candélabres d'une hauteur totale minimale au-dessus du sol de 2,5 m,
- à utiliser avec des sources lumineuses électriques dont la tension d'alimentation ne dépasse pas 1 000 V.
Cette publication doit être lue conjointement avec la CEI 60598-1:2008.
Cette version consolidée comprend la troisième édition (2002) et son amendement 1 (2011) et a été préparée par commodité pour l'utilisateur. Il n'est donc pas nécessaire de commander l'amendement avec cette publication.
General Information
Standards Content (Sample)
IEC 60598-2-3 ®
Edition 3.1 2011-11
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE
colour
inside
Luminaires –
Part 2-3: Particular requirements – Luminaires for road and street lighting
Luminaires –
Partie 2-3: Règles particulières – Luminaires d'éclairage public
IEC 60598-2-3:2002+A1:2011
All rights reserved. Unless otherwise specified, no part of this publication may be reproduced or utilized in any form or by
any means, electronic or mechanical, including photocopying and microfilm, without permission in writing from either IEC or
IEC's member National Committee in the country of the requester.
If you have any questions about IEC copyright or have an enquiry about obtaining additional rights to this publication,
please contact the address below or your local IEC member National Committee for further information.
Droits de reproduction réservés. Sauf indication contraire, aucune partie de cette publication ne peut être reproduite
ni utilisée sous quelque forme que ce soit et par aucun procédé, électronique ou mécanique, y compris la photocopie
et les microfilms, sans l'accord écrit de la CEI ou du Comité national de la CEI du pays du demandeur.
Si vous avez des questions sur le copyright de la CEI ou si vous désirez obtenir des droits supplémentaires sur cette
publication, utilisez les coordonnées ci-après ou contactez le Comité national de la CEI de votre pays de résidence.
IEC Central Office
3, rue de Varembé
CH-1211 Geneva 20
Switzerland
Email: inmail@iec.ch
Web: www.iec.ch
About the IEC
The International Electrotechnical Commission (IEC) is the leading global organization that prepares and publishes
International Standards for all electrical, electronic and related technologies.
About IEC publications
The technical content of IEC publications is kept under constant review by the IEC. Please make sure that you have the
latest edition, a corrigenda or an amendment might have been published.
Catalogue of IEC publications: www.iec.ch/searchpub
The IEC on-line Catalogue enables you to search by a variety of criteria (reference number, text, technical committee,…).
It also gives information on projects, withdrawn and replaced publications.
IEC Just Published: www.iec.ch/online_news/justpub
Stay up to date on all new IEC publications. Just Published details twice a month all new publications released. Available
on-line and also by email.
Electropedia: www.electropedia.org
The world's leading online dictionary of electronic and electrical terms containing more than 20 000 terms and definitions
in English and French, with equivalent terms in additional languages. Also known as the International Electrotechnical
Vocabulary online.
Customer Service Centre: www.iec.ch/webstore/custserv
If you wish to give us your feedback on this publication or need further assistance, please visit the Customer Service
Centre FAQ or contact us:
Email: csc@iec.ch
Tel.: +41 22 919 02 11
Fax: +41 22 919 03 00
A propos de la CEI
La Commission Electrotechnique Internationale (CEI) est la première organisation mondiale qui élabore et publie des
normes internationales pour tout ce qui a trait à l'électricité, à l'électronique et aux technologies apparentées.
A propos des publications CEI
Le contenu technique des publications de la CEI est constamment revu. Veuillez vous assurer que vous possédez
l’édition la plus récente, un corrigendum ou amendement peut avoir été publié.
Catalogue des publications de la CEI: www.iec.ch/searchpub/cur_fut-f.htm
Le Catalogue en-ligne de la CEI vous permet d’effectuer des recherches en utilisant différents critères (numéro de référence,
texte, comité d’études,…). Il donne aussi des informations sur les projets et les publications retirées ou remplacées.
Just Published CEI: www.iec.ch/online_news/justpub
Restez informé sur les nouvelles publications de la CEI. Just Published détaille deux fois par mois les nouvelles
publications parues. Disponible en-ligne et aussi par email.
Electropedia: www.electropedia.org
Le premier dictionnaire en ligne au monde de termes électroniques et électriques. Il contient plus de 20 000 termes et
définitions en anglais et en français, ainsi que les termes équivalents dans les langues additionnelles. Egalement appelé
Vocabulaire Electrotechnique International en ligne.
Service Clients: www.iec.ch/webstore/custserv/custserv_entry-f.htm
Si vous désirez nous donner des commentaires sur cette publication ou si vous avez des questions, visitez le FAQ du
Service clients ou contactez-nous:
Email: csc@iec.ch
Tél.: +41 22 919 02 11
Fax: +41 22 919 03 00
IEC 60598-2-3 ®
Edition 3.1 2011-11
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE
colour
inside
Luminaires –
Part 2-3: Particular requirements – Luminaires for road and street lighting
Luminaires –
Partie 2-3: Règles particulières – Luminaires d'éclairage public
INTERNATIONAL
ELECTROTECHNICAL
COMMISSION
COMMISSION
ELECTROTECHNIQUE
PRICE CODE
INTERNATIONALE
CODE PRIX CE
ICS 29.140.40; 93.080.30 ISBN 978-2-88912-737-5
– 2 – 60598-2-3 IEC:2002+A1:2011
CONTENTS
FOREWORD . 3
3.1 Scope . 5
3.2 General test requirements . 5
3.3 Definitions . 5
3.4 Classification of luminaires . 6
3.5 Marking . 7
3.6 Construction . 7
3.7 Creepage distances and clearances . 12
3.8 Provision for earthing . 12
3.9 Terminals . 12
3.10 External and internal wiring . 12
3.11 Protection against electric shock . 12
3.12 Endurance tests and thermal tests . 13
3.13 Resistance to dust and moisture . 13
3.14 Insulation resistance and electric strength . 13
3.15 Resistance to heat, fire and tracking . 13
Annex A (informative) Drag coefficient measurement . 16
Annex B (normative) Schedule of amended clauses containing more serious/critical
requirements which require products to be retested . 17
Figure 1 – Different procedures for the static wind-force test . 14
Figure 2 – Counting particles at the edge of the square . 15
60598-2-3 IEC:2002+A1:2011 – 3 –
INTERNATIONAL ELECTROTECHNICAL COMMISSION
____________
LUMINAIRES –
Part 2-3: Particular requirements –
Luminaires for road and street lighting
FOREWORD
1) The International Electrotechnical Commission (IEC) is a worldwide organization for standardization comprising
all national electrotechnical committees (IEC National Committees). The object of IEC is to promote
international co-operation on all questions concerning standardization in the electrical and electronic fields. To
this end and in addition to other activities, IEC publishes International Standards, Technical Specifications,
Technical Reports, Publicly Available Specifications (PAS) and Guides (hereafter referred to as “IEC
Publication(s)”). Their preparation is entrusted to technical committees; any IEC National Committee interested
in the subject dealt with may participate in this preparatory work. International, governmental and non-
governmental organizations liaising with the IEC also participate in this preparation. IEC collaborates closely
with the International Organization for Standardization (ISO) in accordance with conditions determined by
agreement between the two organizations.
2) The formal decisions or agreements of IEC on technical matters express, as nearly as possible, an international
consensus of opinion on the relevant subjects since each technical committee has representation from all
interested IEC National Committees.
3) IEC Publications have the form of recommendations for international use and are accepted by IEC National
Committees in that sense. While all reasonable efforts are made to ensure that the technical content of IEC
Publications is accurate, IEC cannot be held responsible for the way in which they are used or for any
misinterpretation by any end user.
4) In order to promote international uniformity, IEC National Committees undertake to apply IEC Publications
transparently to the maximum extent possible in their national and regional publications. Any divergence
between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in
the latter.
5) IEC itself does not provide any attestation of conformity. Independent certification bodies provide conformity
assessment services and, in some areas, access to IEC marks of conformity. IEC is not responsible for any
services carried out by independent certification bodies.
6) All users should ensure that they have the latest edition of this publication.
7) No liability shall attach to IEC or its directors, employees, servants or agents including individual experts and
members of its technical committees and IEC National Committees for any personal injury, property damage or
other damage of any nature whatsoever, whether direct or indirect, or for costs (including legal fees) and
expenses arising out of the publication, use of, or reliance upon, this IEC Publication or any other IEC
Publications.
8) Attention is drawn to the Normative references cited in this publication. Use of the referenced publications is
indispensable for the correct application of this publication.
9) Attention is drawn to the possibility that some of the elements of this IEC Publication may be the subject of
patent rights. IEC shall not be held responsible for identifying any or all such patent rights.
This consolidated version of IEC 60598-2-3 consists of the third edition (2002)
[documents 34D/762/FDIS and 34D/772/RVD] and its amendment 1 (2011) [documents
34D/989/FDIS and 34D/1003/RVD]. It bears the edition number 3.1.
The technical content is therefore identical to the base edition and its amendment and
has been prepared for user convenience. A vertical line in the margin shows where the
base publication has been modified by amendment 1. Additions and deletions are
displayed in red, with deletions being struck through.
– 4 – 60598-2-3 IEC:2002+A1:2011
This International Standard IEC 60598-2-3 has been prepared by subcommittee 34D:
Luminaires, of IEC technical committee 34: Lamps and related equipment.
This publication has been drafted in accordance with the ISO/IEC Directives, Part 2.
This standard is to be read in conjunction with IEC 60598-1.
The changes to the text introduced by this new edition introduce requirements for column-
integrated luminaires.
The text introduced by interpretation sheets IS 01 and IS 02 is contained in subclause 3.6.5
Note 1 and subclause 3.12.1, second paragraph, respectively.
The committee has decided that the contents of the base publication and its amendments will
remain unchanged until the stability date indicated on the IEC web site under
"http://webstore.iec.ch" in the data related to the specific publication. At this date, the
publication will be
• reconfirmed,
• withdrawn,
• replaced by a revised edition, or
• amended.
IMPORTANT – The “colour inside” logo on the cover page of this publication indicates
that it contains colours which are considered to be useful for the correct understanding
of its contents. Users should therefore print this publication using a colour printer.
60598-2-3 IEC:2002+A1:2011 – 5 –
LUMINAIRES –
Part 2-3: Particular requirements –
Luminaires for road and street lighting
3.1 Scope
This part of IEC 60598 specifies requirements for
− luminaires for road, street lighting and other public outdoor lighting applications;
− tunnel lighting;
− column-integrated luminaires with a minimum total height above normal ground level of
2,5 m;
and for use with electrical lighting sources on supply voltages not exceeding 1 000 V.
NOTE Column integrated luminaires with a total height below 2,5 m are under consideration.
3.1.1 Normative references
The normative references listed in Section 0 of IEC 60598-1 apply to this part as well as the
following reference:
IEC 60068-3-76:1997, Environmental testing – Part 2-75: Tests – Test Eh: Hammer tests
IEC 60364-7-714, 1996, Electrical installations of buildings – Part 7: Requirements for special
installations or locations – Section 714: External lighting installations
IEC 62262: 2002, Degrees of protection provided by enclosures for electrical equipment
against external mechanical impacts (IK code)
3.2 General test requirements
The provisions of Section 0 of IEC 60598-1 apply.
The tests described in each appropriate section of Part 1 shall be carried out in the order
listed in this section of Part 2.
In order to facilitate testing, and due to the dimensions of the sample, it is allowed to make
use of the appropriate parts of the luminaire only (this is mainly applicable to column-
integrated luminaires).
3.3 Definitions
For the purposes of this section, the definitions of Section 1 of IEC 60598-1 apply together
with the following definitions.
3.3.1
span wire
wire between main supports which carries the weight of the complete installation.
NOTE This may include several luminaires, supply cables and a stay wire.
– 6 – 60598-2-3 IEC:2002+A1:2011
3.3.2
suspension wire
wire attached to the span wire and carrying the weight of the luminaire
3.3.3
stay wire
tensioned wire between main supports to limit lateral and rotary movement of the suspended
luminaires
3.3.4
column-integrated luminaires
lighting systems formed with a luminaire integrated in a lighting column fixed in the ground
3.3.5
reflective or decorative external part of a column-integrated luminaire
device reflecting the light in a fixed direction or with a decorative purpose, mounted outside
the lamp compartment generally at the top of the column-integrated luminaire
NOTE Such devices are referred to in this standard as “external parts”.
3.3.6
lighting column
support intended to hold one or more luminaires, consisting of one or more parts: a post,
possibly an extension piece, and if necessary a bracket. It does not include columns for
catenary lighting
3.3.7
nominal height of a column-integrated luminaire
distance between the centre line of the point of entry of the external part and the intended
ground level, for column-integrated luminaires planted in the ground, or the bottom of the
flange plate, for column-integrated luminaires with a flange plate
3.3.8
door opening of a column-integrated luminaire
opening in the column of a column-integrated luminaire for access to electrical equipment
3.3.9
cable entry slot of a column integrated luminaire
opening in the part of a column-integrated luminaire below ground for the cable entry
3.3.10
connection box of a column integrated luminaire
box containing terminal blocks: protecting devices allowing the connection of a column-
integrated luminaire to the mains and the looping of electricity supply cables
3.3.11
tunnel luminaires
luminaires for lighting tunnels which are mounted direct or on frames to the wall or ceiling of
the tunnel
3.4 Classification of luminaires
Luminaires shall be classified in accordance with the provisions of Section 2 of IEC 60598-1.
NOTE Luminaires for road and street lighting are normally suitable for one or more of the following modes of
installation:
a) on a pipe (bracket) or the like;
b) on a mast (column) arm;
c) on a post top;
60598-2-3 IEC:2002+A1:2011 – 7 –
d) on span or suspension wires;
e) on a wall.
3.5 Marking
The provisions of Section 3 of IEC 60598-1 apply. In addition, the following information shall
be provided in the instruction leaflet supplied with the luminaire:
a) design attitude (normal operating position);
b) weight including control gear if any;
c) overall dimensions;
d) if intended for mounting more than 8 m above ground level, the maximum projected area
subjected to wind force (see 3.6.3.1);
e) the range of cross-sectional areas of suspension wires suitable for the luminaire, if
applicable;
f) suitability for use indoors provided the 10 °C, allowed for the effects of natural air
movement, has not been deducted from measured temperature (see 3.12.1);
g) dimensions of the compartment in which the connection box is placed;
h) the torque setting in newton metres to be applied to any bolts or screws which fix the
luminaire to its support;
i) maximum mounting height relevant to the selected method for protection against the
falling of glass particles.
3.6 Construction
The provisions of Section 4 of IEC 60598-1 apply together with the requirements of 3.6.1
to 3.6.5.
3.6.1 All luminaires shall have protection against ingress of moisture of at least IPX3, except
for tunnel-lighting luminaires and glazing of column-integrated luminaires with an open-sided
external part, for which IPX5 is required.
For column-integrated luminaires, door opening included, the IP classification shall be as
follows:
1) parts below 2,5 m: IP3X (see IEC 60364-7-714)
2) parts above 2,5 m: IP2X (when the external part is open-sided, the IP classification of the
glazing shall be 5X)
3.6.2 Luminaires for suspension on span wires shall be fitted with clamping devices for this
purpose and the range of span-wire sizes for which the clamping devices are suitable shall be
stated in the instruction leaflet supplied with the luminaire. The device shall clamp the span
wire to prevent movement of the luminaire with respect to the span wire.
The suspension devices shall not damage the span wire during installation and during normal
use of the luminaire.
Compliance is checked by inspection after fitting the luminaire to the smallest and largest
span wires in the range stated by the luminaire manufacturer.
NOTE Care should be taken to avoid electrolytic corrosion between the clamping device and the span wire.
3.6.3 The means for attaching the luminaire or external part to its support shall be
appropriate to the weight of the luminaire or external part. The connection shall be designed
to withstand wind speeds of 150 km/h on the projected surface of the assembly without undue
deflection.
– 8 – 60598-2-3 IEC:2002+A1:2011
Fixings which carry the weight of the luminaire or external part and internal accessories shall
be provided with means to prevent the dislodgement of any part of the luminaire or external
part by vibration, either in service or during maintenance.
Parts of luminaires or external parts which are fixed other than with at least two devices, for
example, screws or equivalent means of sufficient strength, shall have such extra protection
as to prevent those parts falling and endangering persons, animals and surroundings, should
a fixing device fail under normal conditions.
Compliance is checked by inspection and, for mast-arm or post-top mounted luminaires or
external parts, by the test of 3.6.3.1.
The wind-force test is not required to be performed on tunnel luminaires.
NOTE In considering the possible effects of vibration, the luminaire should be studied in conjunction with the lamp
and the column with which it may be used.
3.6.3.1 Static load test for mast-arm or post-top mounted luminaires or external parts
The luminaire or external part is mounted in such a way that the most critical surface is
loaded.
The most critical surface is determined by calculating the highest value of Cd × S
where
Cd is the drag coefficient;
S is the area of the surface to be loaded (m ).
The drag coefficient depends on the shape of the surface. For luminaires or external parts for
which the Cd is not measured, the value of 1,2 shall be taken.
NOTE 1 See Annex A for measurement of Cd.
The means of attachment shall be secured in accordance with the manufacturer’s instructions.
A constant evenly distributed load is applied for 10 min on the most critical surface.
NOTE 2 See Figure 1 for methods of equal distribution of the load. In cases where bags are used, these can be
filled with sand, lead shot or small balls.
The load shall be equal to
F = 1/2 Rh × S × Cd × V (N)
where
Rh is equal to 1,225 kg/m (air volumic mass);
V is the wind speed (m/s).
The wind speeds relevant to the mounting heights of luminaires or external parts shall be
V = 45 m/s (163 km/h) for heights up to 8 m;
V = 52 m/s (188 km/h) for heights between 8 m and 15 m;
V = 57 m/s (205 km/h) for heights of more than 15 m.
NOTE 3 In some countries, the wind speed is determined by national rules (for example, Japan).
The drag coefficient is 1,2 (or the exact value measured in Annex A).
60598-2-3 IEC:2002+A1:2011 – 9 –
After the test, there shall be no visible failure impairing the safety, no permanent deformation
from the attachment which exceeds a slope of more than 2 cm/m, and no rotation around the
point of attachment.
3.6.4 If the use of a single lampholder does not ensure the correct position of the lamp, an
adequate supporting device shall be provided.
For adjustable lampholders or optical parts, suitable reference marks shall be provided.
Compliance is checked by inspection.
3.6.5 Glass covers shall either consist of a glass that fractures into small pieces or shall be
provided with a guard of sufficiently small mesh or a film-coated glass that retains glass
fragments.
For flat glass covers compliance is checked by inspection and, if the glass is not provided
with a guard, by the following test.
The glass component is supported over the whole area to ensure that particles will not be
scattered upon fragmentation and that movement of the particles is prevented. Shatter the
glass with a centre punch at a point 30 mm from the mid-point of one of the longer edges of
glass towards the centre. Within 5 min of fracture, count the particles in a 50 mm square,
located approximately at the centre of the area of coarsest fracture but always within the
confines of the glass.
NOTE Where possible, the area of measurement should not be within 30 mm of any edge, hole or machining of
the glass.
A glass is deemed to have passed the test if the number of particles in the 50 mm square is
more than 60; glass splinters and pieces less than the full thickness of the glass being
excluded from the count. For glass of smaller size where a 50 mm × 50 mm area is not
possible, the number of pieces necessary in the count is proportionately reduced.
In the count of the total number of particles in the 50 mm square, the particles in the centre of
the square plus those at the edge shall be taken into account. In order to count particles at
the edge of the square, it is recommended that all pieces intersected by two adjacent sides be
included and all particles intersected by the two other sides be ignored (see Figure 2).
A suitable method of counting the particles is to place a square of 50 mm side, of transparent
material over the glass and mark a spot of ink as each particle within the square is counted.
NOTE 1 When the test sample remains as one sheet, the fragmentation lines would normally be used to indicate
fractures and the size and number of particles would thus be evaluated, unless reinforcing or a film were employed.
NOTE 2 For glass covers formed from a flat plate, a test is under consideration.
3.6.5 In order to reduce the risk of injury caused by breaking glass, the following
requirements, in relation to the intended mounting height of the luminaire, are applicable.
When luminaires are installed below 5 m, no additional requirements are requested on glass
covers.
For tunnel luminaries, the requirements of 3.6.5.1 apply without exception.
When luminaires are installed above 5 m, glass covers shall be:
a) constituted with a glass that fractures into small pieces, or
b) constituted with a glass having a high impact shock resistance, or
– 10 – 60598-2-3 IEC:2002+A1:2011
c) protected by any means to retain glass fragments in case of breakage (e.g. guard, film
coating).
Compliance is checked:
– for a) by test and inspection according to 3.6.5.1;
– for b) by test and inspection according to 3.6.5.2;
– for c) by inspection.
The luminaire manufacturer shall declare to the testing laboratory the method of protection
used.
3.6.5.1 Protection by the use of glass that fractures into small pieces
Preconditioning of the luminaire and glass cover before testing is not required.
For flat glass, the glass component is supported over the whole area to ensure that particles
will not be scattered upon fragmentation and that movement of the particles is prevented.
Shatter the glass with a centre punch at a point 30 mm from the mid-point of one of the longer
edges of glass towards the centre.
NOTE 1 A centre punch is a tool made of steel with a sharp point.
For formed glass, the glass component part shall be supported on all the surfaces (example
of testing method could be the use of material like sand or a mould). The thickness of the
material used as a support surface shall be more than 30 mm. The face of the glass shall be
completely covered with an adhesive film in order to avoid any move of the broken particles.
Shatter the glass (from the inside or the outside) with a centre punch in the middle of the
glass cover.
Within 5 min of fracture, count the particles in a 50 mm square, located approximately at the
centre of the area of the coarsest fracture but always within the confines of the glass.
Compliance: A glass is deemed to have passed the test if the number of particles in the
50 mm square is more than 40; glass splinters and pieces less than the full thickness of the
glass being excluded from the count. For glass of smaller size where a 50 mm × 50 mm area
is not possible, the number of pieces necessary in the count is proportionately reduced. The
size of the particles shall be less than 50 mm for all the dimensions.
In the count of the total number of particles in the 50 mm square, the particles in the centre of
the square plus those at the edge shall be taken into account. In order to count particles at
the edge of the square, it is recommended that all pieces intersected by two adjacent sides be
included and all particles intersected by the two other sides be ignored (see Figure 2).
NOTE 2 A suitable method of counting the particles is to place a square of 50 mm side, of transparent material
over the glass and mark a spot of ink as each particle within the square counted.
NOTE 3 When the test sample remains as one sheet, the fragmentation lines would normally be used to indicate
fractures and the size and number of particles would thus be evaluated, unless reinforcing or a film were employed.
NOTE 4 Where possible, the area of measurement should not be within 30 mm of any edge, hole or machining of
the glass or in a circle of 50 mm around the impact.
3.6.5.2 Protection by the use of high impact resistant glass
3.6.5.2.1 Glass covers shall have high mechanical strength.
The luminaire and glass cover shall be preconditioned by the thermal endurance test of 12.3
of IEC 60598-1.
The test is performed on one sample and on the external face (opposite side of the lamp) of
the glass mounted on the luminaire.
60598-2-3 IEC:2002+A1:2011 – 11 –
The testing procedure shall be in accordance with the IEC 62262, and the test apparatus used
is the pendulum hammer or vertical hammer according to IEC 60068-2-75.
Compliance: The glass shall not be broken after a shock with impact energy of 5 J (IK08).
3.6.5.2.2 Glass covers shall not break into large pieces.
Glass covers shall be tested according the same testing procedure as 3.6.5.1.
Compliance: A glass is deemed to have passed the test if the number of particles in the
50 mm square is more than 20, glass splinters and pieces less than the full thickness of the
glass being excluded from the count. For glass of smaller size where a 50 mm × 50 mm area
is not possible, the number of pieces necessary in the count is proportionately reduced. The
size of the particles shall be less than 50 mm for all the dimensions.
3.6.6 The connection compartment of column-integrated luminaires shall provide adequate
space within the door opening for
– the luminaire terminals;
– the protective devices;
– the termination and looping of electricity supply cables;
– the connection box (if any).
The compartment shall be provided with means for attaching such equipment. Where such
means is of metal, it shall be of corrosion-resistant material or suitably protected against
corrosion.
3.6.7 With regard to load calculation and verification of structural design by testing, column-
integrated luminaires, except for their external part, shall comply with ISO standards, where
available, otherwise regional or national standards, where applicable.
NOTE In Europe the EN 40, in Japan the JIL 1003 and in North America the ANSI C136 series apply
3.6.8 The door of a column-integrated luminaire shall be treated against corrosion in
accordance with the treatment applied to the column-integrated luminaire.
Compliance is checked by inspection and by the test specified in 4.18 of Part 1.
The opening of the door shall be designed in such a way that only authorized persons will be
able to open it.
A type test will be performed on a sample of the door. The test equipment shall be that used
for the pendulum hammer, the vertical fall, spring-operated impact test apparatus specified in
IEC 60068-2-75 or by other suitable means giving equivalent results. An impact energy of
5 Nm shall be applied three times.
Blows will be applied in the centre of the door on the largest side when the door has several
facets.
After the test, the sample shall show no damage, in particular :
– the locking device shall still be operational;
– no visible cracks shall be present on the sample;
– the level of IP protection shall not be reduced (see 3.6.1).
– 12 – 60598-2-3 IEC:2002+A1:2011
3.6.9 For column-integrated luminaires:
− the cable entry slot shall be not less than 50 mm × 150 mm;
− the cable path from the slot to the connection compartment shall be not less than 50 mm,
and shall be free from obstructions, sharp edges, burrs, flashes and the like that might
cause abrasion of the cables.
Compliance is checked by inspection and by measurements.
NOTE In the USA, the size of the cable entry slot has to be in accordance with ANSI C136.
3.7 Creepage distances and clearances
The provisions of Section 11 of IEC 60598-1 apply.
3.8 Provision for earthing
The provisions of Section 7 of IEC 60598-1 apply together with the requirements of 3.8.1.
3.8.1 The attachment of the fixed part of the terminal shall be designed and executed so as to
prevent it from being rotated when the clamping part is moved.
Compliance is checked by inspection and by the mechanical tests specified in Sections 14
and 15 of Part 1.
3.9 Terminals
The provisions of Sections 14 and 15 of IEC 60598-1 apply.
Terminals for supply connection shall allow the connection of conductors having nominal
cross-sectional areas according to Table 14.1 of Section 14 of IEC 60598-1, excluding the
provision of supply cables with cross-sectional areas smaller than 1 mm .
Compliance is checked by fitting conductors of the smallest and largest cross-sectional areas
specified.
3.10 External and internal wiring
The provisions of Section 5 of IEC 60598-1 apply together with the requirements of 3.10.1.
3.10.1 A luminaire for road and street lighting shall be provided with a cord anchorage such
that the conductors for supply cables are relieved from strain where they are connected to the
terminals, if, without the cord anchorage, the weight of the supply cables would exert a strain
on the connections.
Compliance is checked by the relevant test of Section 5 of IEC 60598-1, but with a pull of
60 N and a torque of 0,25 Nm.
The values for the pull and the torque to be applied depend on the weight of the supply
cables. In general, the specified values are adequate, but for luminaires intended to be
mounted higher than 20 m and where the weight of the supply cables affecting the cord
anchorage exceeds 4 kg a pull of 100 N and a torque of 0,35 Nm are applied.
3.11 Protection against electric shock
The provisions of Section 8 of IEC 60598-1 apply.
60598-2-3 IEC:2002+A1:2011 – 13 –
3.12 Endurance tests and thermal tests
The provisions of Section 12 of IEC 60598-1 apply together with the following.
3.12.1 When applying the limits given in the tables of Section 12 of IEC 60598-1, 10 °C
shall be deducted from the temperatures measured on the luminaire in the test enclosure to
allow for the effects of natural air movement which occur in the working environment of the
luminaire.
Products intended for use outdoors only shall be tested at their declared t ± 5 °C. 10 °C can
a
then be deducted from the measured temperature after the test.
3.12.2 Luminaires with an IP classification greater than IP20 shall be subjected to the
relevant tests of 12.4, 12.5 and 12.6 of Section 12 of IEC 60598-1 after the test(s) of 9.2 but
before the test(s) of 9.3 of Section 9 of IEC 60598-1 specified in 3.13 of this section of
IEC 60598-2.
3.12.3 Glass covers shall be used within the thermal limits declared by the glass manufac-
turer. Thermal limits shall include the minimum and maximum temperature and the maximum
∆t allowed on the glass.
3.13 Resistance to dust and moisture
The provisions of Section 9 of IEC 60598-1 apply together with the following.
3.13.1 For luminaires with an IP classification greater than IP20 the order of the tests
specified in Section 9 of IEC 60598-1 shall be as specified in 3.12 of this section
of IEC 60598-2.
3.14 Insulation resistance and electric strength
The provisions of Section 10 of IEC 60598-1 apply.
3.15 Resistance to heat, fire and tracking
The provisions of Section 13 of IEC 60598-1 apply.
– 14 – 60598-2-3 IEC:2002+A1:2011
IEC 2518/2000
Key
1 Sandbag
2 Net
3 Weight
Figure 1 – Different procedures for the static wind-force test
60598-2-3 IEC:2002+A1:2011 – 15 –
50 mm
A
D
B
C
IEC 135/98
Particles counted (intersected by two selected adjacent sides: AB/BC)
Particles not counted (not intersected by two selected adjacent sides: AB/BC)
Figure 2 – Counting particles at the edge of the square
50 mm
– 16 – 60598-2-3 IEC:2002+A1:2011
Annex A
(informative)
Drag coefficient measurement
A.1 Measurement methods
The drag coefficient measurement is performed in the same way as the method used to
determine the drag coefficient values introduced in ISO 4354.
The luminaire measurement is easier than measurement on a complicated structure
(motionless tested luminaire representing the actual size of the luminaire).
The common practice is to place the luminaire as indicated by the manufacturer’s installation
rules in a wind tunnel.
The wind tunnel should be such that the surface S of the luminaire represents 5 % maximum
of the cross-sectional area of the wind tunnel.
The wind speed used in the measurement should represent as far as possible the reality,
according to 3.6.3.1. A speed of 25 m/s should be considered as a minimum.
After the measurement, no visible failure must impair the safety of the luminaire.
A.2 Reference documents
ISO 4354:1997, Wind actions on structures
60598-2-3 IEC:2002+A1:2011 – 17 –
Annex B
(normative)
Schedule of amended clauses containing more serious/critical
requirements which require products to be retested
This new edition of IEC 60598-2-3 broadens the scope of the standard to incorporate
requirements for column-integrated luminaires. For other types of luminaires for road and
street lighting, this new edition introduces no requirements that are more serious or critical.
Consequently, luminaires for road and street lighting which have been shown to comply with
IEC 60598-2-3, second edition, including its amendment 1 (1997) and its amendment 2
(2000), can be accepted as complying with this new edition without retesting.
NOTE Where more serious/critical requirements are introduced in future amendments/editions of this standard,
these clauses will be marked ‘R’ and scheduled in this annex.
___________
– 18 – 60598-2-3 CEI:2002+A1:2011
SOMMAIRE
AVANT-PROPOS . 19
3.1 Domaine d'application . 21
3.2 Règles générales sur les essais . 21
3.3 Définitions . 21
3.4 Classification des luminaires . 23
3.5 Marquage . 23
3.6 Construction . 23
3.7 Lignes de fuite et distances dans l'air . 28
3.8 Dispositions en vue de la mise à la terre . 28
3.9 Bornes. 29
3.10 Câblages externe et interne . 29
3.11 Protection contre les chocs électriques . 29
3.12 Essais d'endurance et d'échauffement . 29
3.13 Résistance aux poussières et à l'humidité . 30
3.14 Résistance d'isolement et rigidité diélectrique . 30
3.15 Résistance à la chaleur, au feu et aux courants de cheminement . 30
Annexe A (informative) Mesure du coefficient de traînée . 33
Annexe B (normative) Récapitulatif des articles modifiés contenant des prescriptions
particulièrement importantes/critiques qui nécessitent de refaire les essais sur les produits . 34
Figure 1 – Différentes procédures pour l’essai statique de résistance à la force du vent . 31
Figure 2 – Comptage des morceaux sur le pourtour du carré . 32
60598-2-3 CEI:2002+A1:2011 – 19 –
COMMISSION ÉLECTROTECHNIQUE INTERNATIONALE
____________
LUMINAIRES –
Partie 2-3: Règles particulières –
Luminaires d’éclairage public
AVANT-PROPOS
1) La Commission Electrotechnique Internationale (CEI) est une organisation mondiale de normalisation
composée de l'ensemble des comités électrotechniques nationaux (Comités nationaux de la CEI). La CEI a
pour objet de favoriser la coopération internationale pour toutes les questions de normalisation dans les
domaines de l'électricité et de l'électronique. A cet effet, la CEI – entre autres activités – publie des Normes
internationales, des Spécifications techniques, des Rapports techniques, des Spécifications accessibles au
public (PAS) et des Guides (ci-après dénommés "Publication(s) de la CEI"). Leur élaboration est confiée à des
comités d'études, aux travaux desquels tout Comité national intéressé par le sujet traité peut participer. Les
organisations internationales, gouvernementales et non gouvernementales, en liaison avec la CEI, participent
également aux travaux. La CEI collabore étroitement avec l'Organisation Internationale de Normalisation (ISO),
selon des conditions fixées par accord entre les deux organisations.
2) Les décisions ou accords officiels de la CEI concernant les questions techniques représentent, dans la mesure
du possible, un accord international sur les sujets étudiés, étant donné que les Comités nationaux de la CEI
intéressés sont représentés dans chaque comité d’études.
3) Les Publications de la CEI se présentent sous la forme de recommandations internationales et sont agréées
comme telles par les Comités nationaux de la CEI. Tous les efforts raisonnables sont entrepris afin que la CEI
s'assure de l'exactitude du contenu technique de ses publications; la CEI ne peut pas être tenue responsable
de l'éventuelle mauvaise utilisation ou interprétation qui en est faite par un quelconque utilisateur final.
4) Dans le but d'encourager l'uniformité internationale, les Comités nationaux de la CEI s'engagent, dans toute la
mesure possible, à appliquer de façon transparente les Publications de la CEI dans leurs publications
nationales et régionales. Toutes divergences entre toutes Publications de la CEI et toutes publications
nationales ou régionales correspondantes doivent être indiquées en termes clairs dans ces dernières.
5) La CEI elle-même ne fournit aucune attestation de conformité. Des organismes de certification indépendants
fournissent des services d'évaluation de conformité et, dans certains secteurs, accèdent aux marques de
conformité de la CEI. La CEI n'est responsable d'aucun des services effectués par les organismes de
certification indépendants.
6) Tous les utilisateurs doivent s'assurer qu'ils sont en possession de la dernière édition de cette publication.
7) Aucune responsabilité ne doit être imputée à la CEI, à ses administrateurs, employés, auxiliaires ou
mandataires, y compris ses experts particuliers et les membres de ses comités d'études et des Comités
nationaux de la CEI, pour tout préjudice causé en cas de dommages corporels et matériels, ou de tout autre
dommage de quelque natur
...








Questions, Comments and Discussion
Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.
Loading comments...