INTERNATIONAL ISO
STANDARD 9652-2
First edition
2000-04-01
Masonry —
Part 2:
Unreinforced masonry design by simple
rules
Maçonnerie —
Partie 2: Conception de la maçonnerie non armée par des règles
simplifiées
Reference number
ISO 9652-2:2000(E)
©
ISO 2000
---------------------- Page: 1 ----------------------
ISO 9652-2:2000(E)
PDF disclaimer
This PDF file may contain embedded typefaces. In accordance with Adobe's licensing policy, this file may be printed or viewed but shall not
be edited unless the typefaces which are embedded are licensed to and installed on the computer performing the editing. In downloading this
file, parties accept therein the responsibility of not infringing Adobe's licensing policy. The ISO Central Secretariat accepts no liability in this
area.
Adobe is a trademark of Adobe Systems Incorporated.
Details of the software products used to create this PDF file can be found in the General Info relative to the file; the PDF-creation parameters
were optimized for printing. Every care has been taken to ensure that the file is suitable for use by ISO member bodies. In the unlikely event
that a problem relating to it is found, please inform the Central Secretariat at the address given below.
© ISO 2000
All rights reserved. Unless otherwise specified, no part of this publication may be reproduced or utilized in any form or by any means, electronic
or mechanical, including photocopying and microfilm, without permission in writing from either ISO at the address below or ISO's member body
in the country of the requester.
ISO copyright office
Case postale 56 � CH-1211 Geneva 20
Tel. + 41 22 749 01 11
Fax + 41 22 734 10 79
E-mail copyright@iso.ch
Web www.iso.ch
Printed in Switzerland
ii © ISO 1999 – All rights reserved
---------------------- Page: 2 ----------------------
ISO 9652-2:2000(E)
Contents Page
Foreword.iv
Introduction.v
1 Scope .1
2 Normative references .2
3 Terms and definitions .3
4 Symbols .3
5 Stability and robustness .3
6 Limiting loads, strengths and dimensions .4
6.1 General.4
6.2 Limits in respect of walls (but see Table 1) .4
6.3 Limits on sizes of openings.5
6.4 Limits on positions of openings .6
7 Thickness of walls .7
7.1 External and separating walls .7
7.2 Internal walls .8
7.3 Basement walls.8
8 Rules for stiffening walls, piers and chimneys .9
8.1 General.9
8.2 Internal stiffening walls providing restraint.9
8.3 Piers and chimneys providing restraint .9
9 Walls subjected mainly to wind load .10
10 Non-loadbearing internal walls .15
11 Chases and recesses .15
Annex A (normative) Rules for seismic zones .17
Annex B (normative) External walls of certain small single-storey buildings and annexes.19
© ISO 2000 – All rights reserved iii
---------------------- Page: 3 ----------------------
ISO 9652-2:2000(E)
Foreword
ISO (the International Organization for Standardization) is a worldwide federation of national standards bodies (ISO
member bodies). The work of preparing International Standards is normally carried out through ISO technical
committees. Each member body interested in a subject for which a technical committee has been established has
the right to be represented on that committee. International organizations, governmental and non-governmental, in
liaison with ISO, also take part in the work. ISO collaborates closely with the International Electrotechnical
Commission (IEC) on all matters of electrotechnical standardization.
International Standards are drafted in accordance with the rules given in the ISO/IEC Directives, Part 3.
Draft International Standards adopted by the technical committees are circulated to the member bodies for voting.
Publication as an International Standard requires approval by at least 75 % of the member bodies casting a vote.
Attention is drawn to the possibility that some of the elements of this part of ISO 9652 may be the subject of patent
rights. ISO shall not be held responsible for identifying any or all such patent rights.
International Standard ISO 9652-2 was prepared by Technical Committee ISO/TC 179, Masonry, Subcommittee
SC 1, Unreinforced masonry.
ISO 9652 consists of the following parts, under the general title Masonry:
� Part 1: Unreinforced masonry design by calculation
� Part 2: Unreinforced masonry design by simple rules
� Part 3: Reinforced masonry design by calculation
� Part 4: Test methods
� Part 5: Vocabulary
Annexes A and B form a normative part of this part of ISO 9652.
iv © ISO 2000 – All rights reserved
---------------------- Page: 4 ----------------------
ISO 9652-2:2000(E)
Introduction
The rules in this part of ISO 9652 are intended to provide certain masonry designs without the need for structural
calculations. ISO 9652-1 and some national standards will be more restrictive in certain circumstances.
Annex A gives additional rules for use in seismic zones. Annex B gives rules for certain small single-storey
buildings and annexes.
© ISO 2000 – All rights reserved v
---------------------- Page: 5 ----------------------
INTERNATIONAL STANDARD ISO 9652-2:2000(E)
Masonry —
Part 2:
Unreinforced masonry design by simple rules
1 Scope
This part of ISO 9652 gives limited rules for the structural design and construction of unreinforced masonry for
which calculations of loading and strength criteria are not required. This part of ISO 9652 is applicable to masonry
built with Group 1, 2, or 3 masonry units [see 5.2.1 of ISO 9652-1:—] of clay, calcium silicate, concrete (including
autoclaved aerated concrete), and manufactured stone units. The field of application is defined in Table 1 and is
subject to the limitations of normative annex A.
NOTE Clauses 5, 6, 7 and 8 should be taken together; clauses 9 and 10 may be applied separately; clause 11 applies to
all walls covered by this part of ISO 9652.
For masonry designed by calculation, see ISO 9652-1.
Table 1 — Field of application
Type of wall Type of building Location Type of loading
Loadbearing Low-rise dwelling of not Sheltered coastal sites Vertical and wind loads
more than two floor and inland sites except (for limits see clause 6)
levels in addition to any very exposed hills and
basement crests
Other small single-storey
buildings
Basement walls All buildings All sites Earth pressure and
vertical loads
External All buildings up to and Site with many Wind load. No significant
non-loadbearing including four storeys windbreaks, such as city, vertical load
except low-rise dwellings town or well-wooded
of not more than two areas
floor levels in addition to
any basement
Internal All buildings Inside buildings without No significant vertical or
non-loadbearing large openings wind loads
© ISO 2000 – All rights reserved 1
---------------------- Page: 6 ----------------------
ISO 9652-2:2000(E)
The following are not covered by this part of ISO 9652:
a) foundations as shown in Figure 1;
b) free-standing walls;
c) retaining walls other than basement walls;
d) basement walls subjected to hydrostatic pressure;
2
e) masonry in seismic areas with expected ground accelerations in excess of 1,0 m/s (see normative annex A).
Key
1Withinscope
2 Outside scope
Figure 1 — Foundations
2 Normative references
The following normative documents contain provisions which, through reference in this text, constitute provisions of
this part of ISO 9652. For dated references, subsequent amendments to, or revisions of, any of these publications
do not apply. However, parties to agreements based on this part of ISO 9652 are encouraged to investigate the
possibility of applying the most recent editions of the normative documents indicated below. For undated
references, the latest edition of the normative document referred to applies. Members of ISO and IEC maintain
registers of currently valid International Standards.
1)
ISO 9652-1:— , Masonry — Part 1: Unreinforced masonry design by calculation.
1)
ISO 9652-3:— , Masonry — Part 3: Reinforced masonry design by calculation.
1)
ISO 9652-4:— , Masonry — Part 4: Test methods.
ISO 9652-5:2000, Masonry — Part 5: Vocabulary.
1) To be published.
2 © ISO 2000 – All rights reserved
---------------------- Page: 7 ----------------------
ISO 9652-2:2000(E)
3 Terms and definitions
For the purposes of this part of ISO 9652, the terms and definitions given in ISO 9652-5 apply.
4 Symbols
2
A Permitted area of opening, in square metres (m )
o
a , a , a Lengths of wall between one opening and another or between an opening and a buttressing wall or
1 2 3
pier
d Maximum dimension of an opening (height or width) in a wall, which relates to the distance of the
opening from the main restraints or roof
H Height of a wall
h Height of a masonry unit, in millimetres (mm)
u
h Height of the ground above the basement floor
t
l or L Length of a wall
l , l Widths of openings in a wall
1 2
t Wall thickness (whether of solid or cavity construction), in millimetres (mm)
t Thickness of the outer leaf of a cavity wall, in millimetres (mm)
1
t Thickness of the inner leaf of a cavity wall, in millimetres (mm)
2
t , t Thickness of restraining wall and wall to be restrained respectively, in millimetres (mm)
a b
u Minimum overlap between the perpend in a course of masonry and the perpend in the course
immediately above or below it, in millimetres (mm)
x Depth of a chimney or pier (direction perpendicular to the plane of the wall), in millimetres (mm),
X A factor which governs the relationship between the widths of openings in a wall and
a) the lengths of wall between one opening and another,
b) the lengths of wall between an opening and a buttressing wall or pier
y Depth of a pier (direction perpendicular to the plane of the wall), in millimetres (mm).
5 Stability and robustness
For a robust and stable structure, it will be necessary to provide a layout of walls which will enable all lateral forces
to be resisted in the two main directions. Such a design can be achieved most satisfactorily when the walls are
arranged in a cellular form in which the loadbearing walls are provided with substantial returns, piers or chimneys.
The connections between interacting walls and between walls, roofs or floors should be capable of transmitting
lateral forces to the foundations; one way of achieving this is by the use of ring beams. The design should also
ensure that any foreseeable negative loads, particularly suction loads on flat or shallow pitched-roof structures are
resisted by suitable connections.
© ISO 2000 – All rights reserved 3
---------------------- Page: 8 ----------------------
ISO 9652-2:2000(E)
Connections may be achieved by the bonding of masonry or, in some cases, by friction at floor and beam bearings
on masonry. Alternatively, strong, durable, creep-resistant straps, ties, hangers, brackets and angles may be used
as connections between walls and restraining walls and between walls and floors or roofs acting as buttresses.
Ring beams at the head of each storey may also be used to provide horizontal supports.
6 Limiting loads, strengths and dimensions
6.1 General
If loads, strengths or dimensions fall outside the limits given in this clause then calculations should be made for that
part of the structure affected.
6.2 Limits in respect of walls (but see Table 1)
2
6.2.1 The imposed load on any roof, for example snow load, should not exceed 0,9 kN/m , excluding wind load.
6.2.2 The imposed load on any suspended floor, excluding the load from internal walls, should not exceed
2
2,0 kN/m .
2
6.2.3 The imposed load on any floor due to any internal walls should not exceed 1,2 kN/m .
2
6.2.4 The wind load, including internal and external pressures, should not exceed 1,2 kN/m .
2
6.2.5 Floors and roofs should not have a mass greater than 550 kg/m , including any screed or concrete topping.
6.2.6 The minimum normalized compressive strength of masonry units measured in accordance with ISO 9652-4
2
should be 4,0 N/mm unless otherwise required by the rules (normative annex A and Table 2). If the minimum wall
2
thickness of 100 mm is increased to 240 mm then the minimum normalized strength may be reduced to 3,0 N/mm .
Linear interpolation is permitted. The minimum mortar class in accordance with ISO 9652-1 should be M2, except
where the web thickness of units that have more than 50 % voids is 20 mm or less. In that case, the minimum
mortar class should be M10.
6.2.7 The thickness of the loadbearing leaf of a cavity wall may be reduced to 90 mm provided that the minimum
normalized compressive strength given in 6.2.6 is increased by 10 %.
6.2.8 The clear span of floors or concrete roof members should not exceed 6 m.
6.2.9 The clear span of timber roofs should not exceed 12 m when the reaction of the timber roof on the
loadbearing leaf is sensibly axial, otherwise the clear span should not exceed 9 m.
6.2.10 The clear span of lintels over openings should not exceed 3 m (see Figure 2 and 6.3).
6.2.11 In the absence of calculations, the length of lintel bearings (see Figure 2) should be not less than the
following for masonry built from units of Group 1:
2)
a) for timber floors spanning at right angles to the lintel, one tenth of the length of the opening; or
b) for concrete floors spanning at right angles to the lintel, one sixth of the length of the opening
but, in any case not less than 150 mm except where the length of masonry between openings is less than 300 mm
in accordance with 6.3, when the bearing length should be not less than 120 mm and the bearing area should be
2
not less than 15 000 mm .
2) For a single-leaf wall or the inner leaf of a cavity wall of thickness greater than 100 mm, the minimum length of bearing
given here may be multiplied by the ratio: 100 / leaf thickness (in millimetres)
4 © ISO 2000 – All rights reserved
---------------------- Page: 9 ----------------------
ISO 9652-2:2000(E)
For masonry built from units of Groups 2 or 3, the length of lintel bearing shown above should be increased by 1/3.
6.2.12 The bearing for floors spanning on walls should be not less than 85 mm.
Key
1 Bearing length (see 6.2.11 and 6.2.12)
2 Opening (see 6.2.10)
Figure 2 — Length of lintel bearing
6.2.13 For single-leaf construction, masonry units should have a normalized compressive strength equal to or
greater than that for the inner leaf of a cavity wall in the same position.
6.2.14 To ensure adequate bonding, masonry units should overlap by a length of at least 0,4� the height of the
unit when looking at the face of the wall, or 45 mm, whichever is the greatest (see Figure 3).
Key
u Minimum overlap which should be greater than or equal to 0,4 h and greater than or equal to 45 mm
h Height of a masonry unit, in millimetres
Figure 3 — Bonding of units; minimum overlap
6.3 Limits on sizes of openings
The sizes of openings should be determined in accordance with the following rules:
2l
� l + l should not exceed
1 2
3
� l or l should not exceed 3 m
1 2
© ISO 2000 – All rights reserved 5
---------------------- Page: 10 ----------------------
ISO 9652-2:2000(E)
l
1
� a should be greater than
...