SIST EN 15269-5:2014+A1:2017
(Main)Extended application of test results for fire resistance and/or smoke control for door, shutter and openable window assemblies, including their elements of building hardware - Part 5: Fire resistance of hinged and pivoted metal framed glazed doorsets and openable windows
Extended application of test results for fire resistance and/or smoke control for door, shutter and openable window assemblies, including their elements of building hardware - Part 5: Fire resistance of hinged and pivoted metal framed glazed doorsets and openable windows
This European Standard covers hinged and pivoted steel (any kind) and aluminium based framed, glazed
doorsets or openable windows.
This European Standard prescribes the methodology for extending the application of test results obtained
from resistance to fire test(s) conducted in accordance with EN 1634-1.
Subject to the completion of the appropriate test or tests selected from those identified in Clause 4 the
extended application may cover all or some of the following examples:
- integrity (E), integrity/radiation (EW) or integrity/insulation (EI1 or EI2) classifications;
- doorsets and openable windows;
- door / window leaf (leaves);
- glazing and non-glazed panels in doorset and openable window;
- items of building hardware;
- decorative finishes;
- intumescent, smoke, draught or acoustic seals;
- alternative supporting construction(s).
Erweiterter Anwendungsbereich von Prüfergebnissen zur Feuerwiderstandsfähigkeit und/oder Rauchdichtigkeit von Türen, Toren und Fenstern einschließlich ihrer Baubeschläge - Teil 5: Feuerwiderstandsfähigkeit von verglasten Drehflügeltüren und zu öffnenden Fenstern mit Metall(rohr)rahmen
Application étendue des résultats d'essais en matière de résistance au feu et/ou d'étanchéité à la fumée des blocs-portes, blocs-fermetures et ouvrants de fenêtre, y compris leurs éléments de quincaillerie intégrés - Partie 5: Résistance au feu des blocs-portes vitrés battants et pivotants, à ossature métallique, et des fenêtres vitrées à ossature métallique
La présente Norme européenne couvre les blocs-portes vitrés battants et pivotants et les fenêtres, à ossature en acier (de toute sorte) et en aluminium.
La présente Norme européenne prescrit la méthodologie d'extension de l'application des résultats d'essai obtenus suite aux essais de résistance au feu réalisés conformément à l’EN 1634-1.
Sous réserve de la réalisation de l'essai ou des essais appropriés choisis parmi ceux identifiés à l'Article 4, l'application étendue peut couvrir tout ou partie des exemples suivants :
- classements d'étanchéité au feu (E), d'étanchéité au feu/rayonnements (EW) ou étanchéité au feu/isolation thermique (EI1 ou EI2) ;
- blocs-portes et fenêtres ;
- vantail (vantaux) de bloc-porte/fenêtre ;
- vitrages et panneaux non vitrés d'un bloc-porte ou d'une fenêtre ;
- éléments de quincaillerie de bâtiment ;
- finitions décoratives ;
- joints intumescents, joints d'étanchéité aux fumées, joints d'étanchéité à l'air ou joints acoustiques ;
- autre(s) construction(s) support(s).
Razširjena uporaba rezultatov preskusov požarne odpornosti in/ali dimotesnosti za vrata, zaporne elemente in okna, ki se odpirajo, vključno z njihovim okovjem - 5. del: Požarna odpornost zastekljenih vrat v kovinskih okvirjih in oken, ki se odpirajo
Ta evropski standard zajema jeklena vrata z vrtljivim krilom (katere koli vrste) in zastekljena vrata v aluminijastem okvirju ali okna, ki se odpirajo. Ta evropski standard predpisuje metodologijo za razširitev uporabe rezultatov preskusa, pridobljenih iz preskusov požarne odpornosti, izvedenih v skladu s standardom EN 1634-1. Razširjena uporaba lahko (glede na opravljene ustrezne preskuse, izbrane med preskusi, opredeljenimi v točki 4) pokriva vse naslednje primere ali nekatere od njih: – razvrstitve integriteta (E), integriteta/sevanje (EW) ali integriteta/izolacija (EI1 ali EI2); – vrata in okna, ki se odpirajo; – vratno/okensko krilo (krila); – steklo in nesteklene plošče za vrata in okna, ki se odpirajo; – elementi stavbnega okovja; – okrasni zaključki; – intumescentna, dimna, akustična tesnila in tesnila za preprečevanje prepiha; – druge podporne gradbene enote.
General Information
Relations
Standards Content (Sample)
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.RGSLUDMRErweiterter Anwendungsbereich von Prüfergebnissen zur Feuerwiderstandsfähigkeit und/oder Rauchdichtigkeit von Türen, Toren und Fenstern einschließlich ihrer Baubeschläge - Teil 5: Feuerwiderstandsfähigkeit von verglasten Drehflügeltüren und zu öffnenden Fenstern mit Metall(rohr)rahmenExtended application of test results for fire resistance and/or smoke control for door, shutter and openable window assemblies, including their elements of building hardware - Part 5: Fire resistance of hinged and pivoted metal framed glazed doorsets and openable windows01-januar-2017SIST EN 15269-5:2014+A1:2017SLOVENSKI
STANDARDSIST EN 15269-5:20141DGRPHãþD
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.Application étendue des résultats d'essais en matière de résistance au feu et/ou d'étanchéité à la fumée des blocs-portes, blocs-fermetures et ouvrants de fenêtre, y compris leurs éléments de quincaillerie intégrés - Partie 5: Résistance au feu des blocs-portes vitrés battants et pivotants, à ossature métallique, et des fenêtres vitrées à ossature métallique91.190Stavbna opremaBuilding accessories91.060.50Vrata in oknaDoors and windows13.220.50Požarna odpornost gradbenih materialov in elementovFire-resistance of building materials and elementsICS:SIST EN 15269-5:2014+A1:2017en,fr,deTa slovenski standard je istoveten z:EN 15269-5:2014+A1:2016SIST EN 15269-5:2014+A1:2017
EUROPEAN STANDARD NORME EUROPÉENNE EUROPÄISCHE NORM
EN 15269-5:2014+A1
October
t r s x ICS
s uä t t rä w râ
{ sä r x rä w r Supersedes EN
s w t x {æ wã t r s vEnglish Version
Extended application of test results for fire resistance oorá shutter and openable window assembliesá including their elements of building hardware æ Part
wã Fire resistance of hinged and pivoted metal framed glazed doorsets and openable windows Application étendue des résultats d 5essais en matière blocsæportesá blocsæfermetures et ouvrants de fenêtreá y compris leurs éléments de quincaillerie intégrés æ Partie
wã Résistance au feu des blocsæportes vitrés battants et pivotantsá à ossature métalliqueá et des fenêtres vitrées à ossature métallique
Erweiterter Anwendungsbereich von Prüfergebnissen Rauchdichtigkeit von Türená Toren und Fenstern einschließlich ihrer Baubeschläge æ Teil
wã Feuerwiderstandsfähigkeit von verglasten Drehflügeltüren und zu öffnenden Fenstern mit This European Standard was approved by CEN on
s y April
t r s v and includes Amendment
s approved by CEN on
s u March
t r s xä egulations which stipulate the conditions for giving this European Standard the status of a national standard without any alterationä Upætoædate lists and bibliographical references concerning such national standards may be obtained on application to the CENæCENELEC Management Centre or to any CEN memberä
translation under the responsibility of a CEN member into its own language and notified to the CENæCENELEC Management Centre has the same status as the official versionsä
CEN members are the national standards bodies of Austriaá Belgiumá Bulgariaá Croatiaá Cyprusá Czech Republicá Denmarká Estoniaá Finlandá Former Yugoslav Republic of Macedoniaá Franceá Germanyá Greeceá Hungaryá Icelandá Irelandá Italyá Latviaá Lithuaniaá Luxembourgá Maltaá Netherlandsá Norwayá Polandá Portugalá Romaniaá Slovakiaá Sloveniaá Spainá Swedená Switzerlandá Turkey and United Kingdomä
EUROPEAN COMMITTEE FOR STANDARDIZATION COMITÉ EUROPÉEN DE NORMALISATION EUROPÄISCHES KOMITEE FÜR NORMUNG
CEN-CENELEC Management Centre:
Avenue Marnix 17,
B-1000 Brussels
t r s x CEN All rights of exploitation in any form and by any means reserved worldwide for CEN national Membersä Refä Noä EN
s w t x {æ wã t r s v ªA sã t r s x ESIST EN 15269-5:2014+A1:2017
Construction parameter variations . 9 Annex B (normative)
Arrangements for doorsets incorporating side and / or over panels . 122 Annex C (normative)
Relationship showing the relevant Parts of EN 15269 that which should be used depending upon the type of doorset . 126 Bibliography . 131
Figure 1 — Effective rebate depth-2 SIST EN 15269-5:2014+A1:2017
Construction parameter variations Table A.1 is designed to be used in the field of fire resistance testing of hinged and pivoted metal framed glazed doorsets and openable windows. The table shall only be used to evaluate a field of extended application when at least one positive fire resistance test to EN 1634-1 has resulted in a classification according to EN 13501-2. The first two columns identify possible variations to the construction details of the specimen tested. The Influence of variation on performance characteristic is identified from column 3 as, integrity, insulation or radiation (E, I or W respectively). For some parameters, it is necessary to evaluate whether the specimen displayed a high, medium or low level of distortion during the test. Where this is the case the following levels shall be used to establish high, medium and low distortion doorsets: as measured using the maximum relative movement at any position between the edge of the door leaf and door frame or between the meeting edges of door leaves. The measurements shall be taken from the start of the test at any time during the complete required classification period (suggested measuring positions are given in EN 1634-1): — low distortion doorsets: maximum relative movement is < 40 % of effective rebate depth-2; — medium distortion doorsets: maximum relative movement is between 40 % and 60 % effective rebate depth-2; — high distortion doorsets: maximum relative movement is > 60 % of effective rebate depth-2. The effect of the change in each parameter is evaluated for each characteristic in column 3 under E for effects on integrity, I for effects on insulation (whether an I1 or I2 class) and W for the effects on radiation. These evaluations lead to the judgement of the possibility of extending the field of application the results of which are given in column 4. In certain cases in column 4, it is a requirement to achieve Category B, the requirements for which are given in EN 1634-1. Where additional tests are deemed to be necessary the type of specimen approved for incorporation of the changed parameter is defined in column 5. Where it is possible to use information from tests performed on one configuration for evidence on a different configuration, this allowance has been made in order to reduce the overall number of tests required for extended application evaluation e.g. single action doorsets to double action doorsets. Where an additional test is required in column 5 the test is a full scale test with the specimen opening outwards (away from the furnace) unless it is otherwise specified. In order to maximize the possible field of extended application from a minimum number of tests the parameter changes have been spread over a series of test specimens. The recommended tests for each parameter depends on the classification required and the preferred direction of testing indicated in column 5. Where more than a single parameter variation is required, the influence on other variations shall also be taken into account. SIST EN 15269-5:2014+A1:2017
Construction parameter Variation Influence of variation on performance characteristic Possibility of extension Additional evidence required (1) (2) (3) (4) (5)
E I W
A Door leaf For double leaf doorsets, both leaves shall be of the same basic construction. A.1.1 Number of leaves — See Figure A.1 Single leaf from double leaf test
¶
· -
· Not possible without an additional test- Additional test single leaf doorset with glazing bead in fire side A.1.2 Number of leaves Double leaf from single leaf test
¶
¶
¶ Not possible without an additional test Additional test (s) double leaf doorset open outwards and inwards for doors with insulated profiles with glazing bead in fire side
Open outwards for doors with un-insulated profiles with glazing bead in fire side A.1.3 Intumescent seals between frame and door leaf / leaves- See Figure A.2a Location towards the > / = / < > / = / < > / = / < Not possible without an additional test Additional test single leaf or double leaf doorset SIST EN 15269-5:2014+A1:2017
E I W
frame rebate (open outwards) A.1.4 Intumescent seals between frame and door leaf / leaves – See Figure A.2b Location away from the frame rebate > / = / < > / = / < > / = / < Not possible without an additional test Additional test single leaf or double leaf doorset (open outwards) A.1.5 Intumescent seals between meeting edges of the door leaves - See Figure A.3a Location > / = / < > / = / < > / = / < Not possible without additional test (s) Additional test (s) double leaf doorset open outwards for E and EW doors
For EI aluminium doors: test both directions
For EI-steel doors: one test, with fire on opposite side of the operated direction. See Figure A.3b A.1.6 Non intumescent seals between frame and door leaf / leaves (draught / smoke / acoustic etc.) - (Reaction to fire class A1) e.g. ceramic products(fitted in leaf or frame). See Figure A.4 Location = = = Any movement possible providing no modifications of the construction are required otherwise not possible without an additional test Additional test single or double leaf doorset if the seal is positioned between the meeting edges of the door leaves the additional test shall be a double leaf doorset A.1.7 Non intumescent seals between meeting edges of the door leaves (draught / smoke / acoustic etc.) - (Reaction to fire class A1) Location > / = / < > / = / < > / = / < No movement possible without an additional test Additional test double leaf doorset A.1.8 Non intumescent seals between door leaves and / or frames (draught /smoke / acoustic etc.) – < Reaction to fire class A1 (fitted in leaf or frame) - See Figure A.4a Location > / = / < > / = / < > / = / < No movement possible without an additional test Additional test (s) double leaf doorset open outwards for E and W doors SIST EN 15269-5:2014+A1:2017
E I W
For EI aluminium doors: test both directions
For EI-steel doors: one test, with fire on opposite side of the operated direction
See Figure A.4b A.1.9 Non intumescent seals between door leaves and / or frames (draught / smoke / acoustic etc.) - (Reaction to fire class A1), e.g. ceramic products (fitted in leaf or frame) - See Figure A.5a Add = = = Possible for doors without intumescent seals and providing the gap between door leaf and door frame is not increased otherwise not possible without an additional test Additional test single or double leaf doorset, if the seal is positioned between the meeting edges of the door leaves the additional test shall be a double leaf doorset A.1.10 Non intumescent seals between door leaves and / or frames (draught / smoke / acoustic etc.) - (Reaction to fire class A1), e.g. ceramic products (fitted in leaf or frame) - See Figure A.6 Remove
¶
¶
¶ Not possible without an additional test Additional test single or double leaf doorset, if the seal is positioned between the meeting edges of the door leaves the additional test shall be a double leaf doorset A.1.11 Non intumescent seals between door leaves and / or frames (draught / smoke / acoustic etc.) – < Reaction to fire class A1 (fitted in leaf or frame) - See Figure A.5a Add
¶
¶
¶ Not possible without an additional test Additional test single or double leaf doorset, if the seal is positioned between the meeting edges of the door leaves the additional test shall be a double leaf doorset. Fireside opposite the position where the seal is added. See Figure A.5b SIST EN 15269-5:2014+A1:2017
E I W
A.1.12 Non intumescent seals between door leaves and / or frames (draught / smoke / acoustic etc. – < Reaction to fire class A1 (fitted in leaf or frame) – See Figure A.6 Remove > / = / < > / = / < = Not possible without an additional test Additional test single or double leaf doorset, if the seal is positioned between the meeting edges of the door leaves the additional test shall be a double leaf doorset A.1.13 Ventilation grilles (louvres) in door leaf tested without ventilation grille - See Figure A.7a Add
¶
¶
¶ Not possible without an additional test Additional test single or double leaf doorset A.1.14 Ventilation grilles (louvres) in door leaf - See Figure A.7b Remove > / = / <
·
· Possible providing the cut out is less than 50 % of the infill otherwise not possible without an additional test Additional test single or double leaf doorset A.1.15 Ventilation grilles (louvres) in the infill of the door leaf tested with ventilation grille Location in vertical direction
¶
¶
¶ Possible for lower location than tested otherwise not possible without an additional test Additional test single or double leaf doorset A.1.16 Ventilation grilles (louvres) in door leaf tested with ventilation grille - See Figure A.8 Location in horizontal direction = = = Possible providing the distance between the edge of the louvre and the perimeter of the infill is not decreased and providing any internal stiffening elements are not affected otherwise not possible without an additional test Additional test single or double leaf doorset A.1.17 Ventilation grilles (louvres) in the profile of the door leaf tested with ventilation grille Location in horizontal and/or vertical direction > / = / < > / = / < > / = / < Not possible without an additional test Additional test single or double leaf doorset SIST EN 15269-5:2014+A1:2017
E I W
A.1.18 Ventilation grilles (louvres) in door leaf tested with ventilation grille - See Figure A.9a Smaller size
·
·
· Possible for one or more louvres smaller than that tested specimen providing the location is inside the perimeter of the tested louvre and minimum spacing between cut outs is not less than 100 mm otherwise not possible without an additional test Additional test single or double leaf doorset A.1.19 Ventilation grilles (louvres) in door leaf tested with ventilation grille- See Figure A.9b Larger size
¶
¶
¶ Possible for doorsets have achieved category B, size increase of ventilation grilles in the infill of the door leaf up to 20 % in height and width and increase up to 21 % In area
otherwise not possible without an additional test Additional test single or double leaf doorset A.1.20 Rebate (door leaves to frames) - See Figure A.10 Add
¶
¶
· Insulated profiles: Not possible without an additional test unless the original test had additional thermocouples positioned on the profile maximum 100 mm and/or 25 mm from the edge of the notional rebate (i.e. 100-x) where x means the width of the added rebate and dimension y shall not be reduced, otherwise not possible without an additional test Un-insulated profiles: Not possible without an additional test Additional test single doorset for single doors, double doorset for double doors SIST EN 15269-5:2014+A1:2017
E I W
A.1.21 Rebate (meeting edges) - See Figure A.11 Add (one rebate)
¶
¶
· Insulated profiles:
Not possible without an additional test unless the original test had additional thermocouples positioned on the profile maximum 100 mm and/or 25 mm from the edge of the notional rebate (i.e. 100-x) where x means the width of the added rebate and dimension y shall not be reduced. Otherwise not possible without an additional test Un-insulated profiles: Not possible without an additional test Additional test single leaf doorset for single doorsets, double leaf doorset for double leaf doorsets (added rebate away from the fire) A.1.22 Rebate (door leaves to frames and meeting edges) - See Figure A.12 Remove
¶
¶
¶ Not possible without an additional test Additional test single or double leaf doorset (open inwards) A.1.23 Latched condition for single and double leaf doorsets Change in latching condition > / = / < = = Possible in line with the following relationship: Additional test to include the required latching condition
tested without a lock tested with a latch/lock but unlatched tested with a latch/lock latched
extension to: without a lock/latch — possible not possible
E I W
extension to: lock with lock/latch but unlocked/ unlatched not possible for EI doors. possible for E or EW doors if latch/lock is all metal construction — not possible
extension to: with a lock/latch, latched not possible for EI doors. possible for E or EW doors if latch/lock is all metal construction possible —
E I W
A.1.24 Latching / locking Remove from door leaf tested with latching / locking
¶
·
· Not possible without an additional test For single leaf doorsets additional test single leaf doorset (open inwards for EI doors, open outwards for E or W doors) for double leaf doorsets additional test double leaf doorset (open inwards for EI doors, open outwards for E or W doors A.2 Size variations A.2.1 Size (area, width, height) all distortions Decrease
·
¶
· E and EW unlimited reduction is Possible For single leaf doorsets additional test single leaf or double leaf doorset, for double leaf doorsets additional test double leaf doorset
EI: possible to decrease to a minimum dimension of the glass as it is mentioned in rule F.1.4
otherwise not possible without an additional test A.2.2 Height – all distortions Increase
¶ =
¶ Possible for doorsets have achieved category B up to 15 % For single leaf doorsets additional test single leaf SIST EN 15269-5:2014+A1:2017
E I W
or possible for doorsets which have achieved category B and medium and low distortion up to 20 % providing overlap of door leaf to frame header is not reduced and distance between top hinge and top of door leaf is equal to or less than tested and additional for EW a thermal emission calculation in accordance with EN 15254–4 within the 15 KW limit (Rule F.1.3 applies)
otherwise not possible without an additional test or double leaf doorset, for double leaf doorsets additional test double leaf doorset A.2.3 Width - all distortions Increase
¶ =
¶ Possible for doorsets which have achieved category B up to 15 % or possible for doorsets which have achieved category B and medium and low distortion up to 20 %
providing overlap of door leaf to frame jamb is not reduced and additional (for EW) thermal emission calculation in accordance with EN 15254–4 within the 15 KW limit Rule F.1.3 applies
Otherwise not possible without an additional test For single leaf doorsets additional test single leaf or double leaf doorset, for double leaf doorsets additional test double leaf doorset (open outwards) SIST EN 15269-5:2014+A1:2017
E I W
A.2.4 Area - all distortions Increase
¶ =
¶ Possible for doorsets which have achieved category B up to 20 %
or possible for doorsets which have achieved category B and medium and low distortion up to 21 %
providing overlap of door leaf to frame header is not reduced and distance between top hinge and top of the door leaf is equal to or less than tested)
and additional (for EW)
a thermal emission calculation in accordance with EN 15254–4 within the 15 KW limit Rule F.1.3 applies
Otherwise not possible without an additional test Additional test see A.2.2 and/or A.2.3 A.3. Materials and constructions A.3.1 Density of infill of profile or core-material in the panel (organic or Reaction to fire class A1) – all distortions Increase > / = / <
·
· Possible by a maximum of 15 % (nominal value) of each core material of the door leaf above 15 % not possible without an additional test Additional test single or double leaf doorset A.3.2 Density of infill of profile of core material (organic or Reaction to fire class A1) – all distortions Decrease > / = / <
¶
¶ E possible to reduce with 50 % EI, EW not possible without an additional test Additional test single or double leaf doorset SIST EN 15269-5:2014+A1:2017
E I W
A.3.3 Type of infill of profile of core material (single thickness or in combination of different layers) Change of supplier / manufacturer of identical material with identical composition and properties = = = Possible
A.3.4 Type of core material (single thickness or in combination of different layers) Alternative composition > / = / < > / = / < > / = / < Not possible without an additional test Additional test single or double leaf doorset A.3.5 Amount of adhesive / m2 – organic based (
¶ = = Not possible without an additional test Additional test single or double leaf doorset A.3.6 Amount of adhesive / m2 – organic based ( = = = Possible
A.3.7 Amount of adhesive / m2 – inorganic based (Reaction to fire class A1) Increase = = = Possible
A.3.8 amount of adhesive / m2 – inorganic based (Reaction to fire class A1) Decrease = = = Not possible without an additional test Additional test single or double leaf doorset A.3.9 Type of adhesive Change of manufacturer for identical composition = = = Possible for identical chemical composition otherwise not possible without an additional test Additional test single or double leaf doorset A.3.10 Type of adhesive Alternative composition > / = / < > / = / < > / = / < Not possible without an additional test Additional test single or double leaf doorset SIST EN 15269-5:2014+A1:2017
E I W
A.3.11 Additional overlapping edge at the bottom of the door leaf - See Figure A.13a Add
·
¶ > / = / < Possible providing the tested overlapping edge at the top of the leaf is added at the bottom of the leaf and providing a fourth frame member is added otherwise not possible without an additional test Additional test single or double leaf doorset A.3.12 Overlapping edge at the bottom of the door leaf - See Figure A.13b Remove
¶
· > / = / < Possible providing the gap between the bottom of the door leaf and the floor remains the same as the original test specimen and in line with direct application otherwise not possible without an additional test Additional test single or double leaf doorset A.3.14 Dimension of intumescent seals (leaf or frame fitted) - See Figure A.14a Increase > / = / < > / = / < > / = / < Not possible without an additional test Additional test single or double leaf doorset A.3.15 Dimension of intumescent seals (leaf or frame fitted) - See Figure A.14b Decrease
¶
¶
¶ Not possible without an additional test Additional test single or double leaf doorset A.3.16 Type of intumescent seals (leaf or frame fitted) Change of supplier / manufacturer > / = / < > / = / < > / = / < Possible but only for identical composition otherwise not possible without an additional test Additional test single or double leaf doorset A.3.17 Type of intumescent seals (leaf or frame fitted) Alternative material > / = / < > / = / < > / = / < Not possible without an additional test Additional test single or double leaf doorset A.3.18 Dimension of draught / smoke seals (Reaction to fire class A1); e.g. ceramic products (leaf or frame fitted) - See Figure A.15a Increase
· = = Possible providing the gap between door leaf and door frame is not increased otherwise not possible without an additional test Additional test single or double leaf doorset SIST EN 15269-5:2014+A1:2017
E I W
A.3.19 Dimension of draught / smoke seals (Reaction to fire class A1); e.g. ceramic products (leaf or frame fitted) - See Figure A.15b Decrease
¶ = = Not possible without an additional test Additional test single or double leaf doorset A.3.20 Dimension of draught / smoke seals (
¶
¶
¶ Not possible without an additional test. Additional test single or double leaf doorset A.3.21 Dimension of draught / smoke seals (
·
·
· Possible in any cross sectional dimension providing the same material and the same manufacturer otherwise not possible without an additional test
A.3.22 Type of draught / smoke seals (leaf or frame fitted) Change of supplier / manufacturer > / = / < = = Possible for Reaction to fire class A1 material or for identical chemical composition otherwise not possible without an additional test Additional test single or double leaf doorset A.3.23 Type of draught / smoke seals (leaf or frame fitted) Alternative material (changing to higher Reaction to fire class) = = = Possible
A.3.24 Type of draught / smoke seals (leaf or frame fitted) Alternative material (changing to a equal or a lower Reaction to fire class)
¶
¶
¶ Not possible without an additional test Additional test single or double leaf doorset SIST EN 15269-5:2014+A1:2017
E I W
A4. Decorative and / or protective finishes A.4.1 Paints without contribution to fire resistance (on leaf or frame) Addition = = = Possible in line with direct application beyond the field of direct application rules not possible without an additional test Additional test single or double leaf doorset A.4.2 Paints without contribution to fire resistance (on leaf or frame) Interchange = = = Possible
A.4.3 Thickness of paints with positive contribution to fire resistance (on leaf or frame) Increase
·
·
· Possible up to a maximum of 25 % in mass per m2 otherwise not possible without an additional test Additional test single or double leaf doorset A.4.4 Thickness of paints with positive contribution to fire resistance (on leaf or frame) Decrease
¶
¶
¶ Not possible without an additional test Additional test single or double leaf doorset A.4.5 type of paints with positive contribution to fire resistance (on leaf or frame) change of supplier / manufacturer > / = / < > / = / < = Possible but only for identical composition
Otherwise not possible without an additional test Additional test single or double leaf doorset A.4.6 Type of paints with positive contribution to fire resistance (on leaf or frame) Alternative material > / = / < > / = / < > / = / < Not possible without an additional test Additional test single or double leaf doorset A.4.7 Decorative laminates and timber veneers on the face (on leaf or frame) - See Figure A.17 Add > / = / <
·
· Possible in line with direct application
Otherwise not possible without additional test Additional test single or double leaf doorset SIST EN 15269-5:2014+A1:2017
E I W
A.4.8 Decorative laminates and timber veneers on the face (on leaf or frame) - See Figure A.18 Remove
...