Extended application of test results for fire resistance and/or smoke control for door, shutter and openable window assemblies, including their elements of building hardware - Part 5: Fire resistance of hinged and pivoted metal framed glazed doorsets and openable windows

EN 15269-5 covers hinged and pivoted steel (any kind) and aluminium based framed, glazed doorsets or openable windows. This European Standard prescribes the methodology for extending the application of test results obtained from resistance to fire test(s) conducted in accordance with EN 1634-1. Subject to the completion of the appropriate test or tests selected from those identified in Clause 4 the extended application may cover all or some of the following examples: - integrity (E), integrity/radiation (EW) or integrity/insulation (EI1 or EI2) classifications; - doorsets and openable windows; - door / window leaf (leaves); - glazing and non-glazed panels in doorset and openable window; - items of building hardware; - decorative finishes; - intumescent, smoke, draught or acoustic seals; - alternative supporting construction(s).

Erweiterter Anwendungsbereich von Prüfergebnissen zur Feuerwiderstandsfähigkeit und/oder Rauchdichtigkeit von Türen, Toren und Fenstern einschließlich ihrer Baubeschläge - Teil 5: Feuerwiderstandsfähigkeit von verglasten Drehflügeltüren mit Metallrahmen und zu öffnenden Fenstern

Dieser Teil von prEN 15269 gilt in Verbindung mit prEN 15269-1 und deckt ein- und zweiflügelige verglaste Drehflügeltüren mit Metallrahmen oder zu öffnende Fenster ab.
Dieses Dokument legt die Methodologie zur Erweiterung der Anwendung von Ergebnissen aus Prüfungen nach EN 1634-1 fest.
In Abhängigkeit von der Durchführung der entsprechenden Prüfung oder Prüfungen, die aus den in Abschnitt 4 aufgeführten auszuwählen sind, kann der erweiterte Anwendungsbereich einige oder alle der nachstehend aufgeführten Bereiche abdecken, wobei diese Liste nicht vollständig ist:
   Klassifizierung von nicht wärmegedämmten Abschlüssen (E), sowie solchen mit Anforderungen an die Strahlung (EW) oder wärmegedämmten Abschlüssen (EI1 oder EI2);
-   Türen und zu öffnende Fenster;
-   Tür-/Fensterflügel;
-   an der Wand/Decke befestigte Elemente (Zarge/Aufhängungssysteme);
-   Verglasungen und unverglaste Paneele in Türen und zu öffnenden Fenstern;
-   Baubeschläge;
-   dekorative Beschichtungen;
-   dämmschichtbildende Dichtungen, sowie Dichtungen zur Behinderung von Rauchdurchtritt (Rauchschutzdichtungen), Durchzug oder der Schallübertragung (Schallschutzdichtungen);
-   alternative Tragkonstruktion(en).

Application étendue des résultats d'essais en matière de résistance au feu et/ou d'étanchéité à la fumée des blocs-portes, blocs-fermetures et fenêtres, y compris leurs éléments de quincaillerie - Partie 5: Résistance au feu des blocs-portes vitrés battants et pivotants, à ossature métallique, et des fenêtres vitrées à ossature métallique

La présente Partie du prEN 15269, qu'il convient de lire conjointement au prEN 15269-1, couvre les blocs-portes vitrés battants et pivotants et les fenêtres vitrées, à ossature métallique et à simple ou à double vantail.
Le présent document prescrit la méthodologie permettant d'étendre l'application des résultats d'essai obtenus suite à un (des) essai(s) réalisés conformément à l'EN 1634-1.
Sous réserve de la réalisation de l'essai ou des essais appropriés choisis parmi ceux identifiés à l'Article 4, l'application étendue peut couvrir tout ou partie de la liste non exhaustive suivante :
-   classement d'étanchéité au feu (E), de rayonnement (EW) ou d'isolation thermique (EI1 ou EI2) ;
-   blocs-portes et fenêtres ;
-   vantail de porte/fenêtre ;
-   éléments fixés au mur/plafond (dormant/système de suspension) ;
-   vitrage et panneaux non vitrés d'un bloc-porte et d'une fenêtre ;
-   éléments de quincaillerie de bâtiment ;
-   finitions décoratives ;
-   joints intumescents, joints d'étanchéité à la fumée, joints d'étanchéité à l'air ou joints acoustiques ;
-   autre(s) construction(s) support.

Razširjena uporaba rezultatov preskusov požarne odpornosti in/ali dimotesnosti za vrata, zaporne elemente in okna, ki se odpirajo, vključno z njihovim okovjem - 5. del: Požarna odpornost zastekljenih vrat v kovinskih okvirjih in oken, ki se odpirajo

Standard EN 15269-5 zajema zastekljena vrata v jeklenih (vse vrste) ali aluminijastih okvirjih ali okna, ki se odpirajo. Ta evropski standard predpisuje metodologijo za razširitev uporabe rezultatov preskusa, pridobljenih iz preskusov požarne odpornosti, izvedenih v skladu s standardom EN 1634-1. Razširjena uporaba lahko (glede na opravljene ustrezne preskuse, izbranih med preskusi, opredeljenimi v točki 4) pokriva vse naslednje primere ali nekatere od njih: – razvrstitve integriteta (E), integriteta/sevanje (EW) ali integriteta/izolacija (EI1 ali EI2); – vrata in okna, ki se odpirajo; – vratno/okensko krilo (krila); – steklo in nesteklene plošče za vrata in okna, ki se odpirajo; – elementi stavbnega okovja; – okrasni zaključki; – intumescentna, dimna, akustična tesnila in tesnila za preprečevanje prepiha; – druge podporne gradbene enote.

General Information

Status
Withdrawn
Public Enquiry End Date
30-Jul-2012
Publication Date
10-Aug-2014
Withdrawal Date
27-Nov-2016
Technical Committee
Current Stage
9900 - Withdrawal (Adopted Project)
Start Date
21-Nov-2016
Due Date
14-Dec-2016
Completion Date
28-Nov-2016

Relations

Buy Standard

Standard
EN 15269-5:2014
English language
130 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.RGSLUDMRErweiterter Anwendungsbereich von Prüfergebnissen zur Feuerwiderstandsfähigkeit und/oder Rauchdichtigkeit von Türen, Toren und Fenstern einschließlich ihrer Baubeschläge - Teil 5: Feuerwiderstandsfähigkeit von verglasten Drehflügeltüren mit Metallrahmen und zu öffnenden FensternApplication étendue des résultats d'essais en matière de résistance au feu et/ou d'étanchéité à la fumée des blocs-portes, blocs-fermetures et fenêtres, y compris leurs éléments de quincaillerie - Partie 5: Résistance au feu des blocs-portes vitrés battants et pivotants, à ossature métallique, et des fenêtres vitrées à ossature métalliqueExtended application of test results for fire resistance and/or smoke control for door, shutter and openable window assemblies, including their elements of building hardware - Part 5: Fire resistance of hinged and pivoted metal framed glazed doorsets and openable windows91.190Stavbna opremaBuilding accessories91.060.50Vrata in oknaDoors and windows13.220.50Požarna odpornost gradbenih materialov in elementovFire-resistance of building materials and elementsICS:Ta slovenski standard je istoveten z:EN 15269-5:2014SIST EN 15269-5:2014en,fr,de01-september-2014SIST EN 15269-5:2014SLOVENSKI
STANDARD



SIST EN 15269-5:2014



EUROPEAN STANDARD NORME EUROPÉENNE EUROPÄISCHE NORM
EN 15269-5
June 2014 ICS 13.220.50; 91.060.50 English Version
Extended application of test results for fire resistance and/or smoke control for door, shutter and openable window assemblies, including their elements of building hardware - Part 5: Fire resistance of hinged and pivoted metal framed glazed doorsets and openable windows
Application étendue des résultats d'essais en matière de résistance au feu et/ou d'étanchéité à la fumée des blocs-portes, blocs-fermetures et ouvrants de fenêtre, y compris leurs éléments de quincaillerie intégrés - Partie 5: Résistance au feu des blocs-portes vitrés battants et pivotants, à ossature métallique, et des fenêtres vitrées à ossature métallique
Erweiterter Anwendungsbereich von Prüfergebnissen zur Feuerwiderstandsfähigkeit und/oder Rauchdichtigkeit von Türen, Toren und Fenstern einschließlich ihrer Baubeschläge - Teil 5: Feuerwiderstandsfähigkeit von verglasten Drehflügeltüren und zu öffnenden Fenstern mit Metall(rohr)rahmen This European Standard was approved by CEN on 17 April 2014.
CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN-CENELEC Management Centre or to any CEN member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC Management Centre has the same status as the official versions.
CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and United Kingdom.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION EUROPÄISCHES KOMITEE FÜR NORMUNG
CEN-CENELEC Management Centre:
Avenue Marnix 17,
B-1000 Brussels © 2014 CEN All rights of exploitation in any form and by any means reserved worldwide for CEN national Members. Ref. No. EN 15269-5:2014 ESIST EN 15269-5:2014



EN 15269-5:2014 (E) 2 Contents Page Foreword .3 Introduction .4 1 Scope .5 2 Normative references .5 3 Terms and definitions .6 4 Determination of the field of extended application .6 4.1 General .6 4.2 How to use extended application rules in Annex A .6 4.3 Procedure for maximum field of extended application .7 4.4 Analysis of resistance to fire test results .8 5 Extended application report .8 6 Classification report .8 Annex A (normative)
Construction parameter variations .9 Annex B (normative)
Arrangements for doorsets incorporating side and / or over panels . 121 Annex C (normative)
Relationship showing the relevant Parts of EN 15269 that which should be used depending upon the type of doorset . 125 Bibliography . 130
SIST EN 15269-5:2014



EN 15269-5:2014 (E) 3 Foreword This document (EN 15269-5:2014 has been prepared by Technical Committee CEN/TC 127 “Fire safety in buildings”, the secretariat of which is held by BSI. This European Standard shall be given the status of a national standard, either by publication of an identical text or by endorsement, at the latest by November 2014 and conflicting national standards shall be withdrawn at the latest by November 2014. Attention is drawn to the possibility that some of the elements of this document may be the subject of patent rights. CEN [and/or CENELEC] shall not be held responsible for identifying any or all such patent rights. This document has been prepared under a mandate given to CEN by the European Commission and the European Free Trade Association, and supports basic work requirements of Regulation (EU) 305/2011. According to the CEN-CENELEC Internal Regulations, the national standards organizations of the following countries are bound to implement this European Standard: Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and the United Kingdom. SIST EN 15269-5:2014



EN 15269-5:2014 (E) 4 Introduction This document is one of a series of standards listed below and intended to be used for the purpose of producing an extended application report based on the evaluation of one or more fire resistance and/or smoke control tests. These standards may also be used to identify the best selection of test specimens required to cover a wide range of product variations. EN 15269 ,Extended application of test results for fire resistance and/or smoke control for door, shutter and openable window assemblies including their elements of building hardware, currently consists of: — Part 1: General requirements; — Part 2: Fire resistance of hinged and pivoted steel doorsets; — Part 3: Fire resistance of hinged and pivoted timber doorsets and openable timber framed windows; — Part 4: Fire resistance of hinged and pivoted glass doorsets (in preparation); — Part 5: Fire resistance of hinged and pivoted metal framed glazed doorsets and openable windows; — Part 6: Fire resistance of sliding timber doorsets; — Part 7: Fire resistance of sliding steel doorsets; — Part 8: Fire resistance of horizontally folding timber doorsets (in preparation); — Part 9: Fire resistance of horizontally folding steel doorsets (in preparation); — Part 10: Fire resistance of steel rolling shutter assemblies; — Part 11: Fire resistance of operable fabric curtains; — Part 20: Smoke control for hinged and pivoted steel, timber and metal framed glazed doorsets. SIST EN 15269-5:2014



EN 15269-5:2014 (E) 5 1 Scope This European Standard covers hinged and pivoted steel (any kind) and aluminium based framed, glazed doorsets or openable windows. This European Standard prescribes the methodology for extending the application of test results obtained from resistance to fire test(s) conducted in accordance with EN 1634-1. Subject to the completion of the appropriate test or tests selected from those identified in Clause 4 the extended application may cover all or some of the following examples: — integrity (E), integrity/radiation (EW) or integrity/insulation (EI1 or EI2) classifications; — doorsets and openable windows; — door / window leaf (leaves); — glazing and non-glazed panels in doorset and openable window; — items of building hardware; — decorative finishes; — intumescent, smoke, draught or acoustic seals; — alternative supporting construction(s). 2 Normative references The following documents, in whole or in part, are normatively referenced in this document and are indispensable for its application. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. EN 1363-1, Fire resistance tests - Part 1: General Requirements EN 1634-1, Fire resistance and smoke control tests for door and shutter assemblies, openable windows and elements of building hardware - Part 1: Fire resistance test for door and shutter assemblies and openable windows EN 1634-2, Fire resistance and smoke control tests for door, shutter and openable window assemblies and elements of building hardware - Part 2: Fire resistance characterisation test for elements of building hardware EN 13501-2:2007+A1:2009, Fire classification of construction products and building elements - Part 2: Classification using data from fire resistance tests, excluding ventilation services EN 15269-1, Extended application of test results for fire resistance and/or smoke control for door, shutter and openable window assemblies, including their elements of building hardware - Part 1: General requirements EN ISO 13943, Fire safety - Vocabulary (ISO 13943) SIST EN 15269-5:2014



EN 15269-5:2014 (E) 6 3 Terms and definitions For the purposes of this document, the terms and definitions given in EN 1363-1, EN ISO 13943, EN 1634-1, EN 1634-2 and EN 15269-1 together with the following apply. 3.1 full scale test test of a full scale doorset in accordance with EN 1634-1 3.2 small scale test test on elements of building hardware in accordance with EN 1634-2 and where the decision process given in EN 1634-2 permits its use 3.3 effective rebate depth-2 dimension of the door leaf thickness of overlapping adjacent edges of door leaf relative to the door frame, transom or side panel or flush overpanel Note 1 to entry: At the meeting edges and for rebated leaves the dimension is the depth of the largest rebate. See Figure 1. Note 2 to entry: The effective rebate depth-2 is different from the effective rebate depth definition given on other standards of the series EN 15269. 3.4 opening outwards means opening the doorleaf away from the fireside 4 Determination of the field of extended application 4.1 General 4.1.1 Before there can be any consideration for extended application the doorset shall have been tested and classified in accordance with EN 1634-1 and EN 13501-2 respectively in order to establish a classification for the doorset. 4.1.2 A review of the construction parameters can indicate that one or more characteristics may be improved by a particular parameter variation. All evaluations shall be made on the basis of retaining the classifications obtainable from testing to EN 1634-1, including those lower than the test duration. However, this shall never lead to an increased classification for any specific parameter beyond that achieved by one resistance to fire test unless specifically identified in the relevant Construction Parameter Variation tables. 4.1.3 If, by following the ensuing procedure, any part of the classification cannot be achieved by extended application rules that part of classification shall be omitted from the subsequent extended application report and classification report. 4.2 How to use extended application rules in Annex A 4.2.1 Identify the variations from the original resistance to fire test specimen(s) which are required to be covered by an extended application report. 4.2.2 Locate the variations in the appropriate parameter variation by reference to columns (1) and (2) of Table A.1. SIST EN 15269-5:2014



EN 15269-5:2014 (E) 7 4.2.3 Review the type of classification to be retained from column (3) and establish from the contents of column (4) whether any extended application is available beyond the direct application rules in EN 1634-1 without the need for further testing. 4.2.4 Where this is deemed to be possible this can be recorded in the extended application report together with any appropriate restrictions and the stated rules from column (4) of Table A.1. 4.2.5 Where the variations required can only be achieved from additional testing, the additional resistance to fire test can be made on a similar specimen type i.e. a doorset of the same or more onerous configuration where the leaf construction is fundamentally the same as tested. Alternatively, column (5) identifies an option for alternative testing and relevant resistance to fire test parameters. 4.3 Procedure for maximum field of extended application 4.3.1 It is possible to provide an extended field of application from a single resistance to fire test. However, where a manufacturer intends to produce a range of doors incorporating single doors and also double doors, with or without side, transom or flush over panels, with or without glazing, with or without louvres or ventilation grilles, with alternative elements of building hardware, etc., it is recommended that careful consideration is given to the complete range of doorset designs and options in order to minimise the testing required before testing commences. 4.3.2 Establish all the parameter variations which are required to be part of the product range. 4.3.3 Determine which are the most important specification requirements and incorporate as many as possible into the specimen(s) for the first resistance to fire tests in the series. 4.3.4 Conduct the first resistance to fire test or a series of tests and then establish which of the original desired parameter variations have not been covered by the resistance to fire tests, including direct application possibilities. 4.3.5 Identify these parameter variations in Annex A and establish if any extended application is possible without further testing. 4.3.6 Record this for the extended application report together with any restrictions and rules given in column (5) in Table A.1. 4.3.7 Evaluate which, if any, of the desired parameter variations have not been covered by the field of direct application or the initial field of extended application derived from 4.3.5. 4.3.8 Determine if the product range is to include only single leaf doorsets or if the range is to also include double leaf configurations. Where only single doorsets are to be part of the product range then the outstanding construction parameter variations shall only be incorporated into specimens for the single leaf doorset. Where single leaf and double leaf doorsets are to be included in the product range, the outstanding construction parameter variations for the extended application of single leaf doorsets may be incorporated into either repeated single leaf doorset resistance to fire tests or in the weakest option, as defined in column 5 of Table A.1, double leaf doorset configurations. 4.3.9 Select the required outstanding parameter variations from column (1) and column (2) of Table A.1 and observe from column (5) of Table A.1 which are the most appropriate weakest specimen options for further testing. 4.3.10 If the complete selection of required parameter variations has not been covered by the resistance to fire tests completed in accordance with 4.3.8 and 4.3.9 above, then an appropriate resistance to fire test or tests may be repeated with the additional product variations incorporated. SIST EN 15269-5:2014



EN 15269-5:2014 (E) 8 4.4 Analysis of resistance to fire test results 4.4.1 In order to maximize the extended field of application, it is important that the test reports shall record details of any premature integrity and / or insulation failure also record details of any distortion to evaluate low, medium and high distortion (see Annex A). 4.4.2 Where a series of resistance to fire tests have been conducted, the extended field of application shall be based on the lowest performance achieved from the complete series of resistance to fire tests unless premature failure has been attributed to one or more specific construction parameter variation. 4.4.3 Where it has been possible, to identify specific parameter failures, the extended application for all other construction parameter variations can be based on the performance achieved after isolating the premature failure(s). 5 Extended application report Prepare an extended application report in accordance with the requirements of Clause 6 of EN 15269-1, based on the results of evaluations in accordance with the above. 6 Classification report The classification report shall be determined from the results of the extended application report and presented in accordance with Annex A of EN 13501-2:2007+A1:2009.
Figure 1 — Effective rebate depth-2 SIST EN 15269-5:2014



EN 15269-5:2014 (E) 9 Annex A (normative)
Construction parameter variations Table A.1 is designed to be used in the field of fire resistance testing of hinged and pivoted metal framed glazed doorsets and openable windows. The table shall only be used to evaluate a field of extended application when at least one positive fire resistance test to EN 1634-1 has resulted in a classification according to EN 13501-2. The first two columns identify possible variations to the construction details of the specimen tested. The Influence of variation on performance characteristic is identified from column 3 as, integrity, insulation or radiation (E, I or W respectively). For some parameters, it is necessary to evaluate whether the specimen displayed a high, medium or low level of distortion during the test. Where this is the case the following levels shall be used to establish high, medium and low distortion doorsets: as measured using the maximum relative movement at any position between the edge of the door leaf and door frame or between the meeting edges of door leaves. The measurements shall be taken from the start of the test at any time during the complete required classification period (suggested measuring positions are given in EN 1634-1): — low distortion doorsets: maximum relative movement is < 40 % of effective rebate depth-2; — medium distortion doorsets: maximum relative movement is between 40 % and 60 % effective rebate depth-2; — high distortion doorsets: maximum relative movement is > 60 % of effective rebate depth-2. The effect of the change in each parameter is evaluated for each characteristic in column 3 under E for effects on integrity, I for effects on insulation (whether an I1 or I2 class) and W for the effects on radiation. These evaluations lead to the judgement of the possibility of extending the field of application the results of which are given in column 4. In certain cases in column 4, it is a requirement to achieve Category B, the requirements for which are given in EN 1634-1. Where additional tests are deemed to be necessary the type of specimen approved for incorporation of the changed parameter is defined in column 5. Where it is possible to use information from tests performed on one configuration for evidence on a different configuration, this allowance has been made in order to reduce the overall number of tests required for extended application evaluation e.g. single action doorsets to double action doorsets. Where an additional test is required in column 5 the test is a full scale test with the specimen opening outwards (away from the furnace) unless it is otherwise specified. In order to maximize the possible field of extended application from a minimum number of tests the parameter changes have been spread over a series of test specimens. The recommended tests for each parameter depends on the classification required and the preferred direction of testing indicated in column 5. Where more than a single parameter variation is required, the influence on other variations shall also be taken into account. SIST EN 15269-5:2014



EN 15269-5:2014 (E) 10 All the rules in Table A.1, with exception are applicable to doorsets and openable windows. However, in the text only the word “doorset” is used. The word “doorset” can be replaced by “openable windows” in every rule. All the rules in Table A.1 influencing glass dimensions shall respect the rules for changing them, as mentioned in Table A.1 part F. SIST EN 15269-5:2014



EN 15269-5:2014 (E) 11 Table A.1 — Construction parameter variations Key symbols in column 3 (which is informative only): > -
higher performance anticipated < -
lower performance anticipated
= -
no significant change in performance anticipated _ -
equal or higher performance anticipated _ -
equal or lower performance anticipated > / = / < -
the influence on performance could be worse, equal or better hence variations not possible unless specific, limited conditions are identified
Construction parameter Variation Influence of variation on performance characteristic Possibility of extension Additional evidence required (1) (2) (3) (4) (5)
E I W
A Door leaf For double leaf doorsets, both leaves shall be of the same basic construction. A.1.1 Number of leaves — See Figure A.1 Single leaf from double leaf test ≤ ≥ - ≥ Not possible without an additional test- Additional test single leaf doorset with glazing bead in fire side A.1.2 Number of leaves Double leaf from single leaf test ≤ ≤ ≤ Not possible without an additional test Additional test (s) double leaf doorset open outwards and inwards for doors with insulated profiles with glazing bead in fire side
Open outwards for doors with un-insulated profiles with glazing bead in fire side A.1.3 Intumescent seals between frame and Location towards the > / = / > / = / <
> / = / <
Not possible without an additional test Additional test single leaf or double leaf doorset SIST EN 15269-5:2014



EN 15269-5:2014 (E) 12 Construction parameter Variation Influence of variation on performance characteristic Possibility of extension Additional evidence required (1) (2) (3) (4) (5)
E I W
door leaf / leaves- See Figure A.2a frame rebate <
(open outwards) A.1.4 Intumescent seals between frame and door leaf / leaves – See Figure A.2b Location away from the frame rebate > / = / <
> / = / <
> / = / <
Not possible without an additional test Additional test single leaf or double leaf doorset (open outwards) A.1.5 Intumescent seals between meeting edges of the door leaves - See Figure A.3a Location > / = / <
> / = / <
> / = / <
Not possible without additional test (s) Additional test (s) double leaf doorset open outwards for E and EW doors
For EI aluminium doors: test both directions
For EI-steel doors: one test, with fire on opposite side of the operated direction. See Figure A.3b A.1.6 Non intumescent seals between frame and door leaf / leaves (draught / smoke / acoustic etc.) - (Reaction to fire class A1) e.g. ceramic products(fitted in leaf or frame). See Figure A.4 Location
=
=
=
Any movement possible providing no modifications of the construction are required otherwise not possible without an additional test Additional test single or double leaf doorset if the seal is positioned between the meeting edges of the door leaves the additional test shall be a double leaf doorset A.1.7 Non intumescent seals between meeting edges of the door leaves (draught / smoke / acoustic etc.) - (Reaction to fire class A1) Location > / = / <
> / = / <
> / = / <
No movement possible without an additional test Additional test double leaf doorset A.1.8 Non intumescent seals between door leaves and / or frames (draught /smoke / acoustic etc.) – < Reaction to fire class A1 Location > / = / <
> / = / <
> / = / <
No movement possible without an additional test Additional test (s) double leaf doorset open outwards for E and W SIST EN 15269-5:2014



EN 15269-5:2014 (E) 13 Construction parameter Variation Influence of variation on performance characteristic Possibility of extension Additional evidence required (1) (2) (3) (4) (5)
E I W
(fitted in leaf or frame) - See Figure A.4a doors
For EI aluminium doors: test both directions
For EI-steel doors: one test, with fire on opposite side of the operated direction
See Figure A.4b A.1.9 Non intumescent seals between door leaves and / or frames (draught / smoke / acoustic etc.) - (Reaction to fire class A1), e.g. ceramic products (fitted in leaf or frame) - See Figure A.5a Add
=
=
=
Possible for doors without intumescent seals and providing the gap between door leaf and door frame is not increased otherwise not possible without an additional test Additional test single or double leaf doorset, if the seal is positioned between the meeting edges of the door leaves the additional test shall be a double leaf doorset A.1.10 Non intumescent seals between door leaves and / or frames (draught / smoke / acoustic etc.) - (Reaction to fire class A1), e.g. ceramic products (fitted in leaf or frame) - See Figure A.6 Remove ≤ ≤ ≤ Not possible without an additional test Additional test single or double leaf doorset, if the seal is positioned between the meeting edges of the door leaves the additional test shall be a double leaf doorset SIST EN 15269-5:2014



EN 15269-5:2014 (E) 14 Construction parameter Variation Influence of variation on performance characteristic Possibility of extension Additional evidence required (1) (2) (3) (4) (5)
E I W
A.1.11 Non intumescent seals between door leaves and / or frames (draught / smoke / acoustic etc.) – < Reaction to fire class A1 (fitted in leaf or frame) - See Figure A.5a Add ≤ ≤ ≤ Not possible without an additional test Additional test single or double leaf doorset, if the seal is positioned between the meeting edges of the door leaves the additional test shall be a double leaf doorset. Fireside opposite the position where the seal is added. See Figure A.5b A.1.12 Non intumescent seals between door leaves and / or frames (draught / smoke / acoustic etc. – < Reaction to fire class A1 (fitted in leaf or frame) – See Figure A.6 Remove > / = / <
> / = / <
=
Not possible without an additional test Additional test single or double leaf doorset, if the seal is positioned between the meeting edges of the door leaves the additional test shall be a double leaf doorset A.1.13 Ventilation grilles (louvres) in door leaf tested without ventilation grille - See Figure A.7a Add ≤ ≤ ≤ Not possible without an additional test Additional test single or double leaf doorset A.1.14 Ventilation grilles (louvres) in door leaf - See Figure A.7b Remove > / = / <
≥ ≥ Possible providing the cut out is less than 50 % of the infill otherwise not possible without an additional test Additional test single or double leaf doorset A.1.15 Ventilation grilles (louvres) in the infill of the door leaf tested with ventilation grille Location in vertical direction ≤ ≤ ≤ Possible for lower location than tested otherwise not possible without an additional test Additional test single or double leaf doorset SIST EN 15269-5:2014



EN 15269-5:2014 (E) 15 Construction parameter Variation Influence of variation on performance characteristic Possibility of extension Additional evidence required (1) (2) (3) (4) (5)
E I W
A.1.16 Ventilation grilles (louvres) in door leaf tested with ventilation grille - See Figure A.8 Location in horizontal direction
=
=
=
Possible providing the distance between the edge of the louvre and the perimeter of the infill is not decreased and providing any internal stiffening elements are not affected otherwise not possible without an additional test Additional test single or double leaf doorset A.1.17 Ventilation grilles (louvres) in the profile of the door leaf tested with ventilation grille Location in horizontal and/or vertical direction > / = / <
> / = / <
> / = / <
Not possible without an additional test Additional test single or double leaf doorset A.1.18 Ventilation grilles (louvres) in door leaf tested with ventilation grille - See Figure A.9a Smaller size ≥ ≥ ≥ Possible for one or more louvres smaller than that tested specimen providing the location is inside the perimeter of the tested
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.