Emergency escape lighting systems

This document specifies electrical installation requirements specific for emergency escape lighting systems
together with verification, operation and maintenance documentation and test requirements for such systems.
NOTE 1 Emergency escape lighting includes escape route lighting, open area (anti-panic) lighting and high-risk task
area lighting. Escape route safety signs are part of emergency escape lighting.
NOTE 2 Emergency escape lighting systems include adaptive and non-adaptive systems, as well as high and lowmounted
systems.
This document does not cover stand-by lighting requirements.
NOTE 3 Systems used for stand-by lighting can also be used for emergency escape lighting, given the corresponding
requirements are fulfilled, see EN 1838.

Sicherheitsbeleuchtungsanlagen

Systèmes d'éclairage de sécurité

Le présent document spécifie les exigences en matière d'installation électrique spécifiques aux systèmes d'éclairage de sécurité, ainsi que les exigences d'essai et de documentation relatives à la vérification, à l'exploitation et à la maintenance de tels systèmes.
NOTE 1   L'éclairage de sécurité englobe l'éclairage des chemins d'évacuation, l'éclairage d'ambiance (antipanique), l'éclairage d'une zone spécifique et l'éclairage des emplacements de travaux dangereux. Les signaux de sécurité des chemins d'évacuation font partie de l'éclairage de sécurité.
NOTE 2   Les systèmes d'éclairage de sécurité incluent les systèmes adaptatifs et non adaptatifs, ainsi que les systèmes installés en position haute et en position basse.
Le présent document ne s'applique pas à l'éclairage de remplacement.
NOTE 3   Les systèmes utilisés pour l'éclairage de remplacement peuvent également être utilisés pour l'éclairage de sécurité, sous réserve que les exigences correspondantes soient respectées (voir le prEN 1838:2022, Article 4).

Sistemi za zasilno razsvetljavo evakuacijskih poti

Ta dokument določa posebne zahteve glede električne napeljave sistemov za zasilno razsvetljavo evakuacijskih poti, skupaj z dokumentacijo o preverjanju, delovanju in vzdrževanju ter zahtevami glede preskušanja takšnih sistemov.
OPOMBA 1: Zasilna razsvetljava evakuacijskih poti vključuje razsvetljavo zasilnih izhodov, razsvetljavo na odprtem območju (za preprečevanje panike) in razsvetljavo delovnega območja z visokim tveganjem. Varnostni znaki za evakuacijske poti so del zasilne razsvetljave evakuacijskih poti.
OPOMBA 2: Sistemi za zasilno razsvetljavo evakuacijskih poti vključujejo prilagodljive in neprilagodljive sisteme ter sisteme za visoko in nizko montažo.
Ta dokument ne obravnava zahtev glede nadomestne razsvetljave.
OPOMBA 3: Sisteme, ki se uporabljajo za nadomestno razsvetljavo, je mogoče uporabiti tudi za zasilno razsvetljavo evakuacijskih poti, če so izpolnjene ustrezne zahteve (glej standard EN 1838).

General Information

Status
Published
Public Enquiry End Date
31-Jul-2022
Publication Date
13-Aug-2024
Current Stage
6060 - National Implementation/Publication (Adopted Project)
Start Date
24-Jul-2024
Due Date
28-Sep-2024
Completion Date
14-Aug-2024

Relations

Buy Standard

Standard
EN 50172:2024
English language
29 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)


SLOVENSKI STANDARD
01-september-2024
Sistemi za zasilno razsvetljavo evakuacijskih poti
Emergency escape lighting systems
Sicherheitsbeleuchtungsanlagen
Systèmes d'éclairage de sécurité
Ta slovenski standard je istoveten z: EN 50172:2024
ICS:
91.160.10 Notranja razsvetljava Interior lighting
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

EUROPEAN STANDARD EN 50172
NORME EUROPÉENNE
EUROPÄISCHE NORM July 2024
ICS 91.160 Supersedes EN 50172:2004
English Version
Emergency escape lighting systems
Systèmes d'éclairage de sécurité Sicherheitsbeleuchtungsanlagen
This European Standard was approved by CENELEC on 2024-05-27. CENELEC members are bound to comply with the CEN/CENELEC
Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration.
Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN-CENELEC
Management Centre or to any CENELEC member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by translation
under the responsibility of a CENELEC member into its own language and notified to the CEN-CENELEC Management Centre has the
same status as the official versions.
CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus, the Czech Republic,
Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, the
Netherlands, Norway, Poland, Portugal, Republic of North Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland,
Türkiye and the United Kingdom.

European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung
CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Brussels
© 2024 CENELEC All rights of exploitation in any form and by any means reserved worldwide for CENELEC Members.
Ref. No. EN 50172:2024 E
Contents Page
European foreword . 4
Introduction . 5
1 Scope . 6
2 Normative references . 6
3 Terms and definitions . 7
4 General . 9
4.1 Normal lighting failures . 9
4.2 Minimum requirements . 9
4.3 Permanently occupied buildings . 10
4.4 Electrical installation . 10
5 Emergency escape lighting system design . 10
5.1 Plan of premises and documentation . 10
5.2 Emergency escape lighting equipment . 10
5.3 Identification marking . 11
6 Handover of the emergency escape lighting systems . 11
6.1 Responsibilities . 11
6.2 Handover documentation . 12
7 Maintenance and verification . 12
7.1 General . 12
7.2 Logbook (Reporting) . 13
7.3 Initial verification . 13
7.4 Periodic inspection and testing . 14
Annex A (informative) System durations and activation times . 16
A.1 System durations . 16
A.2 Activation times . 16
Annex B (informative) On-site luminance and illuminance measurements . 18
B.1 Introduction . 18
B.2 General . 18
B.3 Illuminance and luminance meters . 18
B.4 Measurement of emergency lighting illuminance levels . 19
B.5 Illuminance measurements on site . 22
B.6 Safety signs . 24
B.7 Conformity assessment . 25
Annex C (informative) Considerations for emergency lighting systems during and after a
premises lockdown or prolonged periods where power is disconnected . 26
C.1 Introduction . 26
C.2 Disconnection of power . 26
C.3 Servicing and testing . 26
C.4 Reoccupation . 26
Annex D (normative) Wiring system . 27
D.1 Introduction . 27
D.2 General . 27
Annex E (informative) A-deviations . 28
Bibliography . 29
European foreword
This document (EN 50172:2024) has been prepared by CLC/TC 34” Lighting”.
The following dates are fixed:
• latest date by which this document has to be (dop) 2025-05-27
implemented at national level by publication of
an identical national standard or by
endorsement
• latest date by which the national standards (dow) 2027-05-27
conflicting with this document have to be
withdrawn
This document supersedes EN 50172:2004 and all of its amendments and corrigenda (if any).
— Requirements for emergency escape lighting equipment have been added
— Requirements for the initial verification have been added
— Requirements for the handover documentation have been added
— Requirements to the logbook have been added
— Requirements to maintenance and verification of emergency escape lighting systems have been modified
— Guidance for the selection of appropriate system durations and activation times for various use cases
have been added as Annex A
— Recommendations how the onsite measurement should be carried out have been added as Annex B
— Considerations for emergency lighting systems during and after a premises lockdown or prolonged
periods where power is disconnected have been added as Annex C
— Requirements how the system wiring should be carried out have been added as Annex D
Attention is drawn to the possibility that some of the elements of this document may be the subject of patent
rights. CENELEC shall not be held responsible for identifying any or all such patent rights.
This document is read in conjunction with EN 1838.
Any feedback and questions on this document should be directed to the users’ national committee. A
complete listing of these bodies can be found on the CENELEC website.
Introduction
Table 1 shows an overview of the different forms of emergency lighting. For more details see EN 1838.
Table 1 — Forms of emergency lighting
Emergency lighting
Emergency escape lighting
Escape route Open area (anti- High-risk task area Local area Standby
lighting panic) lighting lighting lighting lighting
Safety signs including adaptive safety signs
While EN 1838 includes luminous requirements for emergency escape lighting systems (and stand-by lighting
systems), this document provides electrical installation requirements specific for emergency escape lighting
systems together with verification, operation and maintenance documentation and test requirements for such
systems. Emergency lighting is a key element of building safety and of utmost importance to prevent harm
and save lives in emergency situations. Such situations are rare, but their rarity is also the reason why issues
may remain undetected and the functionality of the emergency lighting system may thus be impaired just in
the very moment that emergency lighting is actually required. Such issues may be related to building layout
updates or changes in use pattern, or simply the ageing of emergency lighting equipment over time, for
instance. Therefore, maintenance of emergency lighting systems is just as essential as its initial proper
installation.
Hence, this document does contain detailed requirements not only for the initial verification of emergency
escape lighting systems, but also for its continuous monitoring and maintenance which is the only way to
ensure that emergency escape lighting will adequately be provided whenever required.
Note that legal requirements throughout Europe are not limited to the initial installation of emergency lighting,
but also comprise requirements related to continuous monitoring and maintenance.
1 Scope
This document specifies electrical installation requirements specific for emergency escape lighting systems
together with verification, operation and maintenance documentation and test requirements for such systems.
NOTE 1 Emergency escape lighting includes escape route lighting, open area (anti-panic) lighting and high-risk task
area lighting. Escape route safety signs are part of emergency escape lighting.
NOTE 2 Emergency escape lighting systems include adaptive and non-adaptive systems, as well as high and low-
mounted systems.
This document does not cover stand-by lighting requirements.
NOTE 3 Systems used for stand-by lighting can also be used for emergency escape lighting, given the corresponding
requirements are fulfilled, see EN 1838.
2 Normative references
The following documents are referred to in the text in such a way that some or all of their content constitutes
requirements of this document. For dated references, only the edition cited applies. For undated references,
the latest edition of the referenced document (including any amendments) applies.
EN 1838:—, Lighting applications - Emergency lighting
ISO 8528-12, Reciprocating internal combustion engine driven alternating current generating sets — Part 12:
Emergency power supply to safety services
EN 50171:2021, Central safety power supply systems
HD 60364-5-51:2009, Electrical installations of buildings - Part 5-51: Selection and erection of electrical
equipment - Common rules
HD 60364-5-56:2018, Low-voltage electrical installations - Part 5-56: Selection and erection of electrical
equipment - Safety services
HD 60364-6:2016, Low-voltage electrical installations - Part 6: Verification
EN IEC 60598-2-22:2022, Luminaires - Part 2-22: Particular requirements - Luminaires for emergency lighting
(IEC 60598-2-22)
EN 62034, Automa
...

Questions, Comments and Discussion