SIST EN 54-3:2014
(Main)Fire detection and fire alarm systems - Part 3: Fire alarm devices - Sounders
Fire detection and fire alarm systems - Part 3: Fire alarm devices - Sounders
EN 54-3 specifies the requirements, test methods and performance criteria for fire alarm sounders, including voice sounders, in a fixed installation intended to signal an audible warning between the fire detection and fire alarm systems and the occupants of a building (see EN 54-1:2011). This European Standard provides for the assessment and verification of constancy of performance (AVCP) of fire alarm sounders to this EN. This European Standard is not intended to cover: a) loudspeaker type devices primarily intended for emitting emergency voice messages that are generated from an external audio source; b) supervisory sounders, for example, within the control and indicating equipment.
Brandmeldeanlagen - Teil 3: Feueralarmeinrichtungen Akustische Signalgeber
Diese Europäische Norm legt die Anforderungen, Prüfverfahren und Leistungskriterien für akustische Signalgeber, einschließlich Sprachsignalgeber, fest, die in einer ortsfesten Installation für die Abgabe einer akustischen Warnung von einer Brandmeldeanlage an die Personen im Gebäude vorgesehenen sind (siehe EN 54 1:2011).
Diese Europäische Norm sieht die Bewertung und Überprüfung der Leistungsbeständigkeit (AVCP) von akustischen Signalgebern nach dieser EN vor.
Diese Europäische Norm ist nicht dafür vorgesehen, Folgendes abzudecken:
a) Lautsprechereinrichtungen, die primär für die Aussendung von Alarmdurchsagen vorgesehen sind, die in externen Audioquellen erzeugt werden;
b) Statustongeber, die z. B. innerhalb von Brandmelderzentralen vorgesehen sind.
Systèmes de détection et d'alarme incendie - Partie 3: Dispositifs sonores d'alarme feu
La présente Norme européenne spécifie les exigences, les méthodes d'essai et les critères de performance pour les dispositifs sonores d'alarme feu, y compris les alarmes vocales, d’une installation fixe, prévue pour diffuser un signal sonore d'alarme incendie depuis le système de détection et d'alarme incendie vers les occupants d'un bâtiment (voir l'EN 54-1:2011).
La présente Norme européenne prévoit l'évaluation et la vérification de la constance des performances (EVCP) des dispositifs sonores d'alarme feu par rapport à la présente EN.
La présente Norme européenne n'est pas prévue pour traiter :
a) des dispositifs du type à haut-parleurs, dont la fonction première est de diffuser des messages d'urgence générés par une source audio externe ;
b) des bruiteurs installés, par exemple, dans les équipements de contrôle et de signalisation.
Sistemi za odkrivanje in javljanje požara ter alarmiranje - 3. del: Naprave za alarmiranje - Zvočne naprave
Standard EN 54-3 določa zahteve, preskusne metode in merila delovanja za zvočne naprave za alarmiranje, vključno z glasovnimi napravami, v vgrajenih napravah, namenjenih signaliziranju zvočnega opozorila med sistemi za odkrivanje in javljanje požara ter alarmiranje ter uporabniki stavbe (glej standard EN 54-1:2011). Ta evropski standard zagotavlja ocenjevanje in preverjanje nespremenljivosti lastnosti (AVCP) zvočnih naprav za alarmiranje za ta standard. Ta evropski standard ni namenjen obravnavanju: a) naprav, podobnih zvočnikom, namenjenih zlasti oddajanju glasovnih sporočil v sili, ki jih proizvaja zunanji zvočni vir; b) nadzornih zvočnih naprav, ki se na primer nahajajo v nadzorni in indikatorski opremi.
General Information
Relations
Standards Content (Sample)
SLOVENSKI STANDARD
SIST EN 54-3:2014
01-september-2014
1DGRPHãþD
SIST EN 54-3:2001
SIST EN 54-3:2001/A1:2002
SIST EN 54-3:2001/A2:2006
6LVWHPL]DRGNULYDQMHLQMDYOMDQMHSRåDUDWHUDODUPLUDQMHGHO1DSUDYH]D
DODUPLUDQMH=YRþQHQDSUDYH
Fire detection and fire alarm systems - Part 3: Fire alarm devices - Sounders
Brandmeldeanlagen - Teil 3: Feueralarmeinrichtungen Akustische Signalgeber
Systèmes de détection et d'alarme incendie - Partie 3: Dispositifs sonores d'alarme feu
Ta slovenski standard je istoveten z: EN 54-3:2014
ICS:
13.220.20 3RåDUQD]DãþLWD Fire protection
13.320 Alarmni in opozorilni sistemi Alarm and warning systems
SIST EN 54-3:2014 en,fr,de
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
---------------------- Page: 1 ----------------------
SIST EN 54-3:2014
---------------------- Page: 2 ----------------------
SIST EN 54-3:2014
EUROPEAN STANDARD
EN 54-3
NORME EUROPÉENNE
EUROPÄISCHE NORM
July 2014
ICS 13.220.20 Supersedes EN 54-3:2001
English Version
Fire detection and fire alarm systems - Part 3: Fire alarm devices
- Sounders
Systèmes de détection et d'alarme incendie - Partie 3: Brandmeldeanlagen - Teil 3: Feueralarmeinrichtungen
Dispositifs sonores d'alarme feu Akustische Signalgeber
This European Standard was approved by CEN on 8 May 2014.
CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European
Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national
standards may be obtained on application to the CEN-CENELEC Management Centre or to any CEN member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by translation
under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC Management Centre has the same
status as the official versions.
CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,
Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania,
Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and United
Kingdom.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION
EUROPÄISCHES KOMITEE FÜR NORMUNG
CEN-CENELEC Management Centre: Avenue Marnix 17, B-1000 Brussels
© 2014 CEN All rights of exploitation in any form and by any means reserved Ref. No. EN 54-3:2014 E
worldwide for CEN national Members.
---------------------- Page: 3 ----------------------
SIST EN 54-3:2014
EN 54-3:2014 (E)
Contents Page
Foreword .5
Introduction .7
1 Scope .8
2 Normative references .8
3 Terms, definitions and abbreviations .9
3.1 Definitions .9
3.2 Abbreviations . 11
4 Requirements . 11
4.1 Compliance . 11
4.2 Operational reliability . 11
4.2.1 Duration of operation . 11
4.2.2 Provision for external conductors . 11
4.2.3 Flammability of materials . 11
4.2.4 Enclosure protection . 12
4.2.5 Access . 12
4.2.6 Manufacturer's adjustment . 12
4.2.7 On-site adjustment of the operation mode . 12
4.2.8 Software controlled sounders . 13
4.3 Performance parameters under fire conditions . 14
4.3.1 Sound pressure level . 14
4.3.2 Frequencies and sound pattern . 14
4.3.3 Synchronisation . 14
4.3.4 Performance of voice sounders . 15
4.3.5 Voice sounders sequence timing . 15
4.4 Durability of performance parameters under fire conditions . 15
4.4.1 Temperature resistance . 15
4.4.2 Humidity resistance . 15
4.4.3 Shock and vibration resistance . 16
4.4.4 Corrosion resistance . 16
4.4.5 Electrical stability . 16
5 Testing, assessment and sampling methods . 16
5.1 General . 16
5.1.1 Atmospheric conditions for tests . 16
5.1.2 Operating conditions for tests . 17
5.1.3 Mounting arrangements . 17
5.1.4 Tolerances . 17
5.1.5 Provision for tests . 17
5.1.6 Test schedule . 18
5.1.7 Reproducibility . 19
5.2 Operational reliability . 20
5.2.1 Duration of operation . 20
5.2.2 Provision for external conductors . 20
5.2.3 Flammability of materials . 20
5.2.4 Enclosure protection . 21
5.2.5 Access . 22
5.2.6 Manufacturer’s adjustments . 22
5.2.7 On site adjustments of the operating mode . 22
5.2.8 Requirements for software controlled devices . 22
2
---------------------- Page: 4 ----------------------
SIST EN 54-3:2014
EN 54-3:2014 (E)
5.3 Performance parameters under fire conditions . 22
5.3.1 Sound pressure level . 22
5.3.2 Frequencies and sound patterns . 23
5.3.3 Synchronisation . 23
5.3.4 Performance of voice sounders . 24
5.3.5 Voice sounder sequence timing . 25
5.4 Durability of performance parameters under fire conditions . 26
5.4.1 Heat resistance . 26
5.4.2 Humidity resistance . 29
5.4.3 Shock and vibration resistance . 31
5.4.4 Corrosion resistance, SO corrosion (endurance) . 35
2
5.4.5 Electrical stability . 36
6 Assessment and verification of constancy of performance (AVCP) . 37
6.1 General . 37
6.2 Type testing . 37
6.2.1 General . 37
6.2.2 Test samples, testing and compliance criteria . 38
6.2.3 Test reports . 38
6.3 Factory production control (FPC) . 38
6.3.1 General . 38
6.3.2 Requirements . 39
6.3.3 Product specific requirements . 41
6.3.4 Initial inspection of factory and FPC . 42
6.3.5 Continuous surveillance of FPC . 42
6.3.6 Procedure for modifications. 43
6.3.7 One-off products, pre-production products, (e.g. prototypes) and products produced in
very low quantities . 43
7 Classification and designation . 44
8 Marking, labelling and packaging . 44
Annex A (normative) Sound pressure level for fire alarm sounders . 45
A.1 General . 45
A.2 Mounting arrangements . 45
A.3 Instrumentation . 45
A.4 Background noise level . 45
A.5 Measurement of sound pressure level . 45
Annex B (normative) Comparative sound pressure level test during environmental conditioning . 49
B.1 General . 49
B.2 Test chamber . 49
B.2.1 Size . 49
B.2.2 Shape . 49
B.2.3 Rigidity. 50
B.2.4 Surface treatment . 50
B.3 Mounting arrangements . 50
B.4 Instrumentation . 50
B.5 Background noise level . 50
B.6 Test procedure . 50
3
---------------------- Page: 5 ----------------------
SIST EN 54-3:2014
EN 54-3:2014 (E)
B.6.1 Number and positioning of microphones . 50
B.6.2 Measurement of sound pressure level . 51
Annex C (informative) Data supplied with sounders . 54
Annex D (informative) Sound patterns used in some European countries . 55
D.1 Introduction . 55
D.2 Standards references . 55
D.3 Information on sound patterns . 56
D.3.1 Introduction . 56
D.3.2 ISO 8201 Evacuate signal . 56
D.3.3 DIN 33404-3 Unified emergency signal . 56
D.3.4 BS 5839-1 Evacuate signal . 57
D.3.5 BS 5839-1 Alert signal . 57
D.3.6 NF S32-001 Evacuate signal . 57
D.3.7 NEN 2575 Evacuate signal . 58
Annex E (informative) Comparison of flammability test requirements in various standards . 59
E.1 Introduction . 59
E.2 Relevant standards . 59
E.3 Vertical burning tests . 59
E.4 Horizontal burning tests . 60
E.4.1 ISO 1210, IEC 60695-11-10 and UL 94 . 60
E.4.2 ISO 10351, IEC 60695-11-20 and UL 94 . 61
Annex ZA (informative) Clauses of this European Standard addressing the provisions of the EU
Construction Products Regulation . 62
ZA.1 Scope and relevant characteristics . 62
ZA.2 Procedure for assessment and verification of constancy of performance (AVCP) of
sounders . 63
ZA.2.1 System of AVCP . 63
ZA.2.2 Declaration of performance (DoP) . 64
ZA.2.2.1 General . 64
ZA.2.2.2 Content . 64
ZA.2.2.3 Example of DoP . 65
ZA.3 CE marking and labelling . 68
Bibliography . 72
4
---------------------- Page: 6 ----------------------
SIST EN 54-3:2014
EN 54-3:2014 (E)
Foreword
This document (EN 54-3:2014) has been prepared by Technical Committee CEN/TC 72 “Fire detection and
fire alarm systems”, the secretariat of which is held by BSI.
This European Standard shall be given the status of a national standard, either by publication of an identical
text or by endorsement, at the latest by January 2015, and conflicting national standards shall be withdrawn at
the latest by April 2016.
Attention is drawn to the possibility that some of the elements of this document may be the subject of patent
rights. CEN [and/or CENELEC] shall not be held responsible for identifying any or all such patent rights.
This document supersedes EN 54-3:2001.
This document has been prepared under a mandate given to CEN by the European Commission and the
European Free Trade Association, and supports essential requirements of EU Directive(s).
For relationship with EU Directive(s), see informative Annex ZA, which is an integral part of this document.
EN 54-3 has been revised so as to align with the second answer of CEN/TC 72 to Mandate M/109. EN 54-3
includes new clauses and annexes as follows:
— Requirements for software controlled devices (5.2.8);
— Clause 6 Assessment and verification of constancy of performance (AVCP);
— Clause 7 Classification and designation;
— Clause 8 Marking, labelling and packaging;
— Annex C Data supplied with sounders;
— Annex D (informative) Sound patterns used in some European countries;
— Annex E (informative) Comparison of flammability test requirements in various standards.
The previous Annex C dealt with the requirements and test methods for voice sounders. The content of this
annex has been integrated in the main body of the standard, specifically under 4.3.3, 4.3.4, 4.3.5, 5.3.3. 5.3.4
and 5.3.5. In addition, Annex ZA has been revised to align with the Construction Products Regulation (CPR).
EN 54, Fire detection and fire alarm systems, consists of the following parts:
— Part 1: Introduction
— Part 2: Control and indicating equipment
— Part 3: Fire alarm devices – Sounders
— Part 4: Power supply equipment
— Part 5: Heat detectors – Point detectors
— Part 7: Smoke detectors – Point detectors using scattered light, transmitted light or ionization
— Part 10: Flame detector – Point detectors
5
---------------------- Page: 7 ----------------------
SIST EN 54-3:2014
EN 54-3:2014 (E)
— Part 11: Manual call points
— Part 12: Smoke detectors – Line detector using an optical light beam
— Part 13: Compatibility assessment of system components
— Part 14: Guidelines for planning, design, installation, commissioning, use and maintenance
— Part 15: Point detectors using a combination of detected phenomena
— Part 16: Voice alarm control and indicating equipment
— Part 17: Short circuit isolators
— Part 18: Input/output devices
— Part 20: Aspirating smoke detectors
— Part 21: Alarm transmission and fault warning routine equipment
— Part 22: Line-type heat detectors
— Part 23: Fire alarm devices – Visual alarms
— Part 24: Components of voice alarm systems – Loudspeakers
— Part 25: Components using radio links and system requirements
— Part 26: Carbon monoxide detectors – Point detectors
— Part 27: Duct smoke detectors
— Part 28: Non-resettable (digital) line type heat detectors
— Part 29: Multi-sensor fire detectors - Point detectors using a combination of smoke and heat sensors
— Part 30: Multi-sensor fire detectors - Point detectors using a combination of carbon monoxide and heat
sensors
— Part 31: Multi-sensor detector – Point detectors using a combination of smoke, carbon monoxide and
optionally heat sensors
— Part 32: Guidelines for the planning, design, installation, commissioning, use and maintenance of voice
alarm systems
NOTE This list includes standards that are in preparation and other standards may be added. For current status of
published standards refer to www.cen.eu.
According to the CEN-CENELEC Internal Regulations, the national standards organizations of the following
countries are bound to implement this European Standard: Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech
Republic, Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece,
Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal,
Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and the United Kingdom.
6
---------------------- Page: 8 ----------------------
SIST EN 54-3:2014
EN 54-3:2014 (E)
Introduction
The purpose of a fire alarm sounder is to warn person(s) within, or in the vicinity of, a building of the
occurrence of a fire emergency situation in order to enable such a person(s) to take appropriate measures.
This European Standard recognizes that the exact nature of the sound requirements, i.e. its frequency range,
temporal pattern and output level will vary according to the nature of the installation, the type of risk present
and appropriate measures to be taken, the type of signals used by other non-emergency alarms (see, for
example, EN ISO 7731) and national differences in custom and practice. The resulting standard specifies,
therefore, a common method for the testing of the operational performance of sounders against the
specification declared by the manufacturer rather than imposing common requirements.
In some European countries, specific frequencies of sound and sound patterns are used. These may be given
in national codes or standards (see Annex D). Attention is drawn to national safety regulations which may
specify maximum safe sound pressure level received by occupants of a building.
Attention is also drawn to ISO 8201:1987, Acoustics – Audible emergency evacuation signal, the international
standard which specifies the temporal pattern and the required sound pressure level of an audible emergency
evacuation signal.
This European Standard gives common requirements for sounders as well as for their performance under
climatic, mechanical and electrical interference conditions which are likely to occur in the service environment.
This European Standard covers sounders for either an indoor or an outdoor application environment category.
In fire detection and fire alarm systems, voice sounders are used as alarm devices for warning the occupants
of a building of the occurrence of a fire risk, using a combination of an attention-drawing signal and dedicated
voice message(s). The requirements, test methods and performance criteria specified in this standard for
sounders are also applicable to voice sounders. Additional requirements, test methods and performance
criteria specific to voice sounders are also incorporated.
7
---------------------- Page: 9 ----------------------
SIST EN 54-3:2014
EN 54-3:2014 (E)
1 Scope
This European Standard specifies the requirements, test methods and performance criteria for fire alarm
sounders, including voice sounders, in a fixed installation intended to signal an audible warning between the
fire detection and fire alarm systems and the occupants of a building (see EN 54-1:2011).
This European Standard provides for the assessment and verification of constancy of performance (AVCP) of
fire alarm sounders to this EN.
This European Standard is not intended to cover:
a) loudspeaker type devices primarily intended for emitting emergency voice messages that are generated
from an external audio source;
b) supervisory sounders, for example, within the control and indicating equipment.
2 Normative references
The following documents, in whole or in part, are normatively referenced in this document and are
indispensable for its application. For dated references, only the edition cited applies. For undated references,
the latest edition of the referenced document (including any amendments) applies.
EN 54-1:2011, Fire detection and fire alarm systems - Part 1: I
...