High efficiency air filters (EPA, HEPA and ULPA) - Part 5: Determining the efficiency of filter elements

This European Standard applies to efficient particulate air filters (EPA), high efficiency particulate air filters (HEPA) and ultra low penetration air filters (ULPA) used in the field of ventilation and air conditioning and for technical processes, e.g. for clean room
technology or applications in the nuclear and pharmaceutical industry. It establishes a procedure for the determination of the efficiency on the basis of a particle counting method using a liquid test aerosol, and allows a standardized classification of these filters
in terms of their efficiency. Part 5 of the standard deals with measuring the efficiency of filter elements, specifying the conditions and pro-cedures for carrying out tests, describing a specimen test apparatus and its components, and including the method for evaluating test results.

Schwebstofffilter (EPA, HEPA und ULPA) - Teil 5: Abscheidegradprüfung des Filterelements

Diese Europäische Norm gilt für Hochleistungs-Partikelfilter (EPA) Schwebstofffilter (HEPA) und
Hochleistungs-Schwebstofffilter (ULPA) im Bereich der Raum- und Prozesslufttechnik, z. B. Anwendungen in
der Reinraumtechnik oder in der pharmazeutischen Industrie.
Sie legt ein Verfahren zur Prüfung des Abscheidegrades auf Basis von Partikelzählverfahren unter Verwendung
eines flüssigen Prüfaerosols fest und ermöglicht eine einheitliche Klassifizierung der Schwebstofffilter
nach dem Abscheidegrad.
Dieser Teil der Normenreihe EN 1822 behandelt die Abscheidegradprüfung von Filterelementen mit Angabe
der Bedingungen und Verfahren zur Durchführung der Prüfung sowie mit der Beschreibung eines Prüfgerätes
einschließlich ihrer Komponenten und des Verfahrens zur Auswertung der Messergebnisse.

Filtres à air à haute efficacité (EPA, HEPA et ULPA) - Partie 5: Mesure de l'efficacité de l'élément filtrant

La présente Norme européenne est applicable aux filtres à air à haute efficacité (EPA), à très haute efficacité (HEPA) et à très faible pénétration (ULPA), utilisés dans le domaine de la ventilation et de la climatisation ainsi que dans des procédés techniques, tels que les applications en salle blanche ou de l'industrie pharmaceutique.
Elle définit une méthode de détermination de l'efficacité, à partir d'une méthode du comptage de particules à l'aide d'un aérosol d'essai liquide et permet une classification normalisée de ces filtres en fonction de leur efficacité.
Cette partie de la série des EN 1822 traite de la mesure de l'efficacité des éléments filtrants, elle spécifie les conditions et les modes opératoires des essais, décrit un exemple d'appareillage d'essai et ses éléments, et inclut la méthode d'évaluation des résultats d'essai.

Visoko učinkoviti zračni filtri (EPA, HEPA in ULPA) - 5. del: Določanje učinkovitosti filtrskih elementov

Ta evropski standard velja za učinkovite zračne filtre drobnih delcev (EPA), visoko učinkovite zračne filtre drobnih delcev (HEPA) in zračne filtre z ultra nizko penetracijo (ULPA), ki se uporabljajo na področju prezračevanja in klimatizacije ter za tehnične postopke, npr. za naprave v tehnologiji čistega prostora ali farmacevtski industriji. Vzpostavlja postopek za določitev učinkovitosti na osnovi metode štetja delcev z uporabo tekočega testnega aerosola ter omogoča standardizirano klasifikacijo teh filtrov glede na njihovo učinkovitost. Ta del serije EN 1822 obravnava merjenje učinkovitosti filtrskih elementov, določa pogoje in postopke za opravljanje preskusov, opisuje vzorčno opremo za preskušanje in njene komponente ter vključuje metodo za vrednotenje rezultatov preskusa.

General Information

Status
Withdrawn
Public Enquiry End Date
30-Jun-2008
Publication Date
16-Dec-2009
Withdrawal Date
22-Oct-2018
Technical Committee
Current Stage
9900 - Withdrawal (Adopted Project)
Start Date
18-Oct-2018
Due Date
10-Nov-2018
Completion Date
23-Oct-2018

Relations

Buy Standard

Standard
EN 1822-5:2010
English language
28 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.Schwebstofffilter (EPA, HEPA und ULPA) - Teil 5: Abscheidegradprüfung des FilterelementsFiltres à air à haute efficacité (EPA, HEPA et ULPA) - Partie 5: Mesure de l'efficacité de l'élément filtrantHigh efficiency air filters (EPA, HEPA and ULPA) - Part 5: Determining the efficiency of filter elements23.120QDSUDYHVentilators. Fans. Air-conditionersICS:Ta slovenski standard je istoveten z:EN 1822-5:2009SIST EN 1822-5:2010en01-januar-2010SIST EN 1822-5:2010SLOVENSKI
STANDARDSIST EN 1822-5:20011DGRPHãþD



SIST EN 1822-5:2010



EUROPEAN STANDARD NORME EUROPÉENNE EUROPÄISCHE NORM
EN 1822-5
November 2009 ICS 13.040.40 Supersedes EN 1822-5:2000English Version
High efficiency air filters (EPA, HEPA and ULPA) - Part 5: Determining the efficiency of filter elements
Filtres à air à haute efficacité (EPA, HEPA et ULPA) - Partie 5: Mesure de l'efficacité de l'élément filtrant
Schwebstofffilter (EPA, HEPA und ULPA) - Teil 5: Abscheidegradprüfung des Filterelements This European Standard was approved by CEN on 17 October 2009.
CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN Management Centre or to any CEN member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by translation under the responsibility of a CEN member into its own language and notified to the CEN Management Centre has the same status as the official versions.
CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION EUROPÄISCHES KOMITEE FÜR NORMUNG
Management Centre:
Avenue Marnix 17,
B-1000 Brussels © 2009 CEN All rights of exploitation in any form and by any means reserved worldwide for CEN national Members. Ref. No. EN 1822-5:2009: ESIST EN 1822-5:2010



EN 1822-5:2009 (E) 2 Contents
Page Foreword .4Introduction .51Scope .62Normative references .63Terms and definitions .64Description of the method .74.1General .74.2Measurement method using fixed sampling probe .84.3Scan method .84.4Statistical efficiency test method for EPA filters (Group E) .85Test filter .96Test apparatus .96.1General .96.2Test duct .96.2.1Test air conditioning .96.2.2Adjustment of the volume flow rate .96.2.3Measurement of the volume flow rate .96.2.4Aerosol mixing section .96.2.5Test filter mounting assembly .96.2.6Measuring points for the pressure drop . 106.2.7Sampling . 106.3Aerosol generation and measuring instruments . 116.3.1General . 116.3.2Apparatus for testing with a monodisperse test aerosol . 116.3.3Apparatus for testing with a polydisperse test aerosol . 127Conditions of the test air . 178Test procedure . 178.1Preparatory checks . 178.2Starting up the aerosol generator . 178.3Preparation of the test filter . 178.3.1Installation of the test filter . 178.3.2Flushing the test filter . 178.4Testing . 188.4.1Measuring the pressure drop . 188.4.2Testing with a monodisperse test aerosol . 188.4.3Testing with a polydisperse test aerosol . 189Evaluation . 1810Test report . 2011Maintenance and inspection of the test apparatus . 22Annex A (informative)
Testing and classification method for filters with MPPS ≤ 0,1 µm (e.g. membrane medium filters) . 23A.1Background . 23A.2MPPS of filters with Membrane filter medium . 23A.3Penetration consistency and uniformity of Membrane filter medium . 23SIST EN 1822-5:2010



EN 1822-5:2009 (E) 3 A.4Procedure for testing and classification of filters with Membrane filter media . 23A.4.1Integral Penetration . 23A.4.2Classification . 24A.4.3Local Penetration . 24A.5Publication of data and labelling of products with membrane filter media . 24Annex B (normative)
Testing and classification of filters using media with (charged) synthetic fibers . 26B.1Background . 26B.2Scope . 26B.3Procedure for testing and classification of HEPA and ULPA filters using media with (charged) synthetic fibres . 26B.4Publication of data and labelling of products for HEPA and ULPA filters using media with (charged) synthetic fibres . 27Bibliography . 28 SIST EN 1822-5:2010



EN 1822-5:2009 (E) 4 Foreword This document (EN 1822-5:2009) has been prepared by Technical Committee CEN/TC 195 “Air filters for general air cleaning”, the secretariat of which is held by UNI. This European Standard shall be given the status of a national standard, either by publication of an identical text or by endorsement, at the latest by May 2010, and conflicting national standards shall be withdrawn at the latest by May 2010. Attention is drawn to the possibility that some of the elements of this document may be the subject of patent rights. CEN [and/or CENELEC] shall not be held responsible for identifying any or all such patent rights. This document supersedes EN 1822-5:2000. It contains requirements, fundamental principles of testing and the marking for efficient particulate air filters (EPA), high efficiency particulate air filters (HEPA) and ultra low penetration air filters (ULPA). EN 1822, High efficiency air filters (EPA, HEPA and ULPA), consists of the following parts:  Part 1: Classification, performance testing, marking  Part 2: Aerosol production, measuring equipment, particle counting statistics  Part 3: Testing flat sheet filter media  Part 4: Determining leakage of filter element (scan method)  Part 5: Determining the efficiency of filter elements According to the CEN/CENELEC Internal Regulations, the national standards organizations of the following countries are bound to implement this European Standard: Austria, Belgium, Bulgaria, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and the United Kingdom. SIST EN 1822-5:2010



EN 1822-5:2009 (E) 5 Introduction As decided by CEN/TC 195, this European Standard is based on particle counting methods which actually cover most needs of different applications. The difference between this European Standard and previous national standards lies in the technique used for the determination of the integral efficiency. Instead of mass relationships, this technique is based on particle counting at the most penetrating particle size (MPPS), which is for micro-glass filter media usually in the range of 0,12 µm to 0,25 µm. This method also allows the testing test ultra low penetration air filters, which was not possible with the previous test methods because of their inadequate sensitivity. For membrane and synthetic filter media, separate rules apply, see Annexes A and B of this standard.
SIST EN 1822-5:2010



EN 1822-5:2009 (E) 6 1 Scope This European Standard applies to efficient particulate air filters (EPA), high efficiency particulate air filters (HEPA) and ultra low penetration air filters (ULPA) used in the field of ventilation and air conditioning and for technical processes, e.g. for applications in clean room technology or pharmaceutical industry. It establishes a procedure for the determination of the efficiency on the basis of a particle counting method using a liquid test aerosol, and allows a standardized classification of these filters in terms of their efficiency. This part of the EN 1822 series deals with measuring the efficiency of filter elements, specifying the conditions and procedures for carrying out tests, describing a specimen test apparatus and its components, and including the method for evaluating test results. 2 Normative references The following referenced documents are indispensable for the application of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. EN 779:2002, Particulate air filters for general ventilation — Determination of the filtration performance EN 1822-1:2009, High efficiency air filters (EPA, HEPA and ULPA) — Part 1: Classification, performance testing, marking EN 1822-2:2009, High efficiency air filters (EPA, HEPA and ULPA) — Part 2: Aerosol production, measuring equipment, particle counting statistics EN 1822-3, High efficiency air filters (EPA, HEPA and ULPA) — Part 3: Testing flat sheet filter media EN 1822-4, High efficiency air filters (EPA, HEPA and ULPA) — Part 4: Determining leakage of filter element (scan method) EN 14799:2007, Air filters for general air cleaning — Terminology EN ISO 5167-1, Measurement of fluid flow by means of pressure differential devices inserted in circular cross-section conduits running full — Part 1: General principles and requirements (ISO 5167-1:2003) 3 Terms and definitions For the purposes of this document, the terms and definitions given in EN 14799:2007 and the following apply.
3.1 sampling duration time during which the particles in the sampling volume flow are counted (upstream or downstream) 3.2 measuring procedure with fixed sampling probes determination of the integral efficiency using fixed sampling probes upstream and downstream of the test filter SIST EN 1822-5:2010



EN 1822-5:2009 (E) 7 3.3 total particle count method particle counting method in which the overall number of particles – without size classification – can be determined in a certain test volume (e.g. by using a condensation nucleus counter) 3.4 particle counting and sizing method particle counting method which can determine both the number of particles and also their size distribution (e.g. by using an optical particle counter) 4 Description of the method 4.1 General In order to determine the efficiency of the test filter it is fixed in the test filter mounting assembly and subjected to a test air volume flow corresponding to the nominal volume flow rate. After measuring the pressure drop at the nominal volume flow rate, the filter is purged with clean air and the test aerosol produced by the aerosol generator is mixed with the prepared test air along a mixing section, so that it is spread homogeneously over the cross section of the duct. The efficiency is always determined for the most penetrating particle size (MPPS) (see EN 1822-3). The size distribution of the aerosol particles can optionally be measured using a particle size analysis system (for example a differential mobility particle sizer, DMPS). The testing can be carried out using either a monodisperse or polydisperse test aerosol. When testing with (quasi-)monodisperse aerosol the total particle counting method can be used with a condensation nucleus counter (CNC) or an optical particle counter (OPC; for example a laser particle counter). It shall be ensured that the number median particle diameter corresponds to the MPPS, i.e. the particle diameter at which the filter medium has its minimum efficiency. When using a polydisperse aerosol, an optical particle counter shall be used, which in addition to counting the particles is also able to determine their size distribution. It shall be ensured that the median diameter DM of the test aerosol lies in the range: 5,12×<>MPPSDMPPSM In order to determine the integral efficiency, representative partial flows are extracted on the upstream and downstream sides of the filter element and led to the attached particle counter to measure the number of particles. The integral efficiency can be determined using one of two methods, either  with fixed test sampling probes (see 4.2); or  with one or several movable sampling probes downstream (scan method) (see 4.3). In both methods the sample upstream is taken using a fixed sampling probe. The upstream and downstream number concentrations and the integral efficiency are calculated from the particle count, the duration of the sampling and the sampling volume flow rate. SIST EN 1822-5:2010



EN 1822-5:2009 (E) 8 4.2 Measurement method using fixed sampling probe Using this method, the downstream sample used to determine the integral efficiency is taken using a fixed sampling probe. It is necessary to have a mixing section behind the test filter to mix the aerosol homogeneously with the test air over the duct cross section (see 6.2.4). 4.3 Scan method This integral efficiency can be determined by averaging the readings from the result of the leak test (scan method). The test rig for the scan method is described in EN 1822-4. In the scan method the downstream sampling is carried out directly behind the test filter using one or several moveable sampling probes, which can traverse the entire cross sectional area of the filter and its frame in overlapping tracks without any gaps. The test apparatus corresponds largely with that used with stationary sampling probes. The differences in the scanning method are that the downstream mixing section is not included and instead a three-dimensional tracking system is included downstream which moves the probe(s). Since the test duct is usually open, provisions shall be made to prevent the intrusion of contaminated outside air into the test air flow. The arrangement of this test apparatus is described in EN 1822-4. In the scan method all the particles counted during the entire downstream scan in the course of the leak testing are added together. The duration of the sampling is derived from the data of the scanning and the number of probes. The further clauses of this standard refer solely to the measuring method with fixed sampling probes where the integral efficiency is determined independently from the leak test procedure. 4.4 Statistical efficiency test method for EPA filters (Group E) One of the test procedures as described in 4.2 and 4.3 must be used for EPA filters. However for EPA filters the efficiency test does not have to be carried out for each single filter element (as this is mandatory for HEPA [Group H] and ULPA filters [Group U]). The integral efficiency of EPA filters shall be determined by averaging the results of the statistical efficiency tests as described below.
A record of the filter data according to Clause 10 is required in the form of a type test certificate or alternatively a factory test certificate. However, the supplier shall be able to provide documentary evidence to verify the published filter data upon request. This can be done by either:  maintaining a certified quality management system (e.g. EN ISO 9000), which forces him to apply statistically based methods for testing and documenting efficiency for all EPA filters as per EN 1822 (all parts); or  using accepted statistical methods to test all of his production lots of EPA filters. Either the “skip lot procedure” as described in ISO 2859-1 may be used or any equivalent alternative method. NOTE This “skip lot procedure” as described in ISO 2859-1 implies that, at the beginning, the test frequency is high and is in the course of further testing reduced as the production experience grows and the products produced are conform to the target. As an example: the first eight production lots, 100 % of the produced filters are tested. If all the tests are positive, the frequency is reduced to half for the next eight production lots. If all the tests are positive again it is reduced to half again, and so on until only one out of eight lots has to be tested (= minimum test frequency). Each time, one of the tested filters fails; the test frequency is doubled again. In any case the number of samples tested per lot should be more than three filters. SIST EN 1822-5:2010



EN 1822-5:2009 (E) 9 5 Test filter The filter element to be tested shall show no signs of damage or any other irregularities. The filter element shall be handled carefully and shall be clearly and permanently marked with the following details: a) Designation of the filter element; b) Upstream side of the filter element. The temperature of the test filter during the testing shall correspond with that of the test air. 6 Test apparatus 6.1 General A flow sheet showing the arrangement of apparatus comprising a test rig is given in Figure 4 of EN 1822-1:2009. An outline diagram of a test rig is given in Figure 1 of this standard. The fundamentals of aerosol generation and neutralisation with details of suitable types of equipment as well as detailed descriptions of the measuring instruments needed for the testing are contained in EN 1822-2. 6.2 Test duct 6.2.1 Test air conditioning The test air conditioning equipment shall comprise the equipment needed to control the condition of the test air so that it may be brought in compliance with the requirement of Clause 7. 6.2.2 Adjustment of the volume flow rate Filters shall always be tested at their nominal air flow rate. It shall be possible to adjust the volume flow rate by means of a suitable provision (e.g. by changing the speed of the fan, or with dampers) to a value ± 5 % of the nominal flow rate which shall then remain constant within ± 2 % throughout each test. 6.2.3 Measurement of the volume flow rate The volume flow rate shall be measured using a standardized or calibrated method (e.g. measurement of the differential pressure using standardized damper equipment such as orifice plates, nozzles, Venturi tubes in accordance with EN ISO 5167-1). The limit error of measurement shall not exceed 5 % of the measured value. 6.2.4 Aerosol mixing section The aerosol input and the mixing section (see example in Figure 1) shall be so constructed that the aerosol concentration measured at individual points of the duct cross section, directly in front of the test filter, shall not deviate by more than 10 % from the mean value of at least 9 measuring points, over the channel cross section. 6.2.5 Test filter mounting assembly The test filter mounting assembly shall ensure that the test filter can be sealed and subjected to flow in accordance with requirements. SIST EN 1822-5:2010



EN 1822-5:2009 (E) 10 It shall not obstruct any part of the filter cross sectional area.
Key 1 Coarse dust filter 2 Fine dust filte 3 Fan 4 Air heating 5 High efficiency air filter 6 Aerosol inlet to the test duct 7 Temperature measurement 8 Hygrometer 9 Sampler, particle size analysis 10 Sampler, upstream 11 Ring pipe for differential pressure measurement 12 Manometer 13 Test filter mounting assembly 14 Measuring damper in accordance with
EN ISO 5167-1 15 Measurement of absolute pressure 16 Manometer measuring differential pressure 17 Sampler, downstream Figure 1 — Example of a test rig 6.2.6 Measuring points for the pressure drop The measuring points for pressure drop shall be so arranged that the mean value of the static pressure in the flow upstream and downstream of the filter can be measured. The planes of the pressure measurements upstream and downstream shall be positioned in regions of an even flow with a uniform flow profile. In rectangular or square test ducts, smooth holes with a diameter of 1 mm to 2 mm for the pressure measurements shall be bored in the middle of the channel walls, normal to the direction of flow. The four holes shall be interconnected with a circular pipe. 6.2.7 Sampling In order to determine the efficiency, partial flows are extracted from the test volume flow by sampling probes and led to the particle counters. The diameter of the probes shall be chosen so that isokinetic conditions pertain in the duct at the given volume flow rate for the sample. In this way sampling errors can be neglected due to the small size of the particles in the test aerosol. The connections to the particle counter shall be as short as possible. Samples on the upstream side are taken by a fixed sampling probe SIST EN 1822-5:2010



EN 1822-5:2009 (E) 11 in front of the test filter. The sampling shall be representative, which is taken to be the case when the aerosol concentration measured from the sample does not deviate by more than ± 10 % from the mean value determined in accordance with 6.2.4. A fixed sampling probe is also installed downstream, preceded by a mixing section which ensures a representative measurement of the downstream aerosol concentration. This is taken to be the case when, in event of a leak in the test filter according to Clause 5 of EN 1822-1:2009, the aerosol concentration measured does not at any point deviate by more than ± 10 % from the mean value of at least nine measuring points over the duct cross section. The mean aerosol concentrations determined at the upstream and downstream sampling points without the filter in position shall not differ from each other by more than 5 %. 6.3 Aerosol generation and measuring instruments 6.3.1 General The operating parameters of the aerosol generator shall be adjusted to produce a test aerosol whose number median diameter is in the range of the Most Penetrating Particle Size (MPPS) for the sheet filter medium. The median size of the monodisperse test aerosol may not deviate from the MPPS by more than ± 10 %. A deviation of ± 50 % is allowed when using a polydisperse aerosol. The particle output of the aerosol generator shall be adjusted according to the test volume flow rate and the filter efficiency so that the counting rates on the upstream and downstream sides lie under the coincidence limits of the counter (coincidence error max. 5 %), and significantly above the zero count rate of the instruments.
The number distribution concentration of the test aerosol can be determined using a suitable particle size analysis system (e.g. a differential mobility particle sizer - DMPS) or with a laser particle counter suitable for these test purposes. The limit error of the measurement method used to determine the number median value shall not exceed ± 20 % (relative to the measurement value). The number of counted particles measured upstream and downstream shall be sufficiently large to provide statistically meaningful results, without the concentration exceeding the measuring range of the upstream particle counter. If the upstream number concentration exceeds the range of the particle counter (in the counting mode), a dilution system shall be inserted between the sampling point and the counter. The particle counting can be carried out using either a pair of counters operating in parallel on the upstream and downstream sides, or using a single counter to measure the number concentrations on the upstream and downstream sides alternately. If measurements are made with only one counter then it shall be ensured that the relevant properties of the test aerosol (for example, the number concentration, particle size distribution, homogeneous distribution over the channel cross section) remain constant over time. If two counters are used in parallel both should be of the same type and calibrated as dual devices. 6.3.2 Apparatus for testing with a monodisperse test aerosol For technical reasons, the particle size distribution produced by the aerosol generator is usually quasi-monodisperse. When using a monodisperse aerosol for the efficiency testing of the filter element, not only optical particle counters but also condensation nucleus counters may be used. SIST EN 1822-5:2010



EN 1822-5:2009 (E) 12 When using a condensation nucleus counter it shall be ensured that the test aerosol does not contain appreciable numbers of particles which are very much smaller than the MPPS. Such particles, which may be produced, for example, by an aerosol generator which is no longer working properly, are also counted by a condensation nucleus counter and can lead to a considerable error in the determination of the efficiency. One way of checking this is to determine the number distribution of the test aerosol with a measuring device which stretches over a range from the lower range limit of the condensation n
...