kSIST FprEN 14511-1:2022
(Main)Air conditioners, liquid chilling packages and heat pumps for space heating and cooling and process chillers, with electrically driven compressors - Part 1: Terms and definitions
Air conditioners, liquid chilling packages and heat pumps for space heating and cooling and process chillers, with electrically driven compressors - Part 1: Terms and definitions
This European Standard specifies the terms and definitions for the rating and performance of air conditioners, liquid chilling packages and heat pumps using either air, water or brine as heat transfer media, with electrically driven compressors when used for space heating and/or cooling.
It also specifies the terms and definitions for the rating and performance of process chillers.
This European Standard does not apply to heat pumps for domestic hot water, although certain definitions can be applied to these.
This European Standard applies to:
- factory-made units that can be ducted,
- factory-made liquid chilling packages with integral condensers or for use with remote condensers,
- factory-made units of either fixed capacity or variable capacity by any means, and
- air-to-air air conditioners which can also evaporate the condensate on the condenser side.
Packaged units, single split and multisplit systems are covered by this standard. Single duct and double duct units are covered by the standard.
In the case of units consisting of several parts, this European Standard applies only to those designed and supplied as a complete package, except for liquid chilling packages with remote condenser.
This European Standard is primarily intended for water and brine chilling packages but can be used for other liquid subject to agreement.
The units having their condenser cooled by air and by the evaporation of external additional water should have their performance in the cooling mode determined in accordance to EN 15218. For those which can also operate in the heating mode, the EN 14511 series applies for the determination of their performance in the heating mode.
NOTE 1 Part load testing of units is dealt with in EN 14825.
NOTE 2 All the symbols given in this text are used regardless of the language.
Luftkonditionierer, Flüssigkeitskühlsätze und Wärmepumpen für die Raumbeheizung und -kühlung und Prozess-Kühler mit elektrisch angetriebenen Verdichtern - Teil 1: Begriffe
Dieses Dokument legt die Begriffe für die Einstufung und Leistung von Luftkonditionierern, Flüssigkeits-kühlsätzen und Wärmepumpen, die Luft, Wasser oder Sole als Wärmeträger nutzen, mit elektrisch angetriebenen Verdichtern für die Raumbeheizung und/oder -kühlung fest.
Es legt außerdem die Begriffe für die Einstufung und Leistung von Prozess-Kühlern fest.
Dieses Dokument gilt nicht für Wärmepumpen zum Erwärmen von Brauchwasser, obwohl bestimmte Definitionen auf diese angewendet werden können.
Dieses Dokument gilt für:
- werksseitig hergestellte Geräte, die mit Kanalanschlüssen versehen sein können;
- werksseitig hergestellte Flüssigkeitskühlsätze mit eingebauten Verflüssigern oder für den Betrieb mit getrennt angeordneten Verflüssigern und
- Luft-Luft-Luftkonditionierer, die das Kondensat auch auf der Verflüssigerseite verdampfen können.
Kompaktgeräte, Einzelgeräte in Split-Bauweise und Multi-Split-Systeme fallen in den Anwendungsbereich dieses Dokument. Geräte mit Einkanal- und Zweikanal-Systemen werden ebenfalls in diesem Dokument behandelt.
Wenn die Geräte aus mehreren Teilen bestehen, gilt dieses Dokument mit der Ausnahme von Flüssigkeitskühlsätzen mit getrennt angeordnetem Verflüssiger nur für solche, die als vollständige Funktionseinheit konstruiert und geliefert werden.
Dieses Dokument gilt hauptsächlich für Wasser- und Solekühlsätze, kann jedoch nach Vereinbarung auf weitere Flüssigkeiten angewendet werden.
Die Leistung im Kühlbetrieb von Geräten, deren Verflüssiger durch Belüftung und durch Verdampfung von zusätzlichem, von außen zugeführtem Wasser gekühlt wird, wird nach EN 15218 ermittelt. Bei solchen Geräten, die auch im Heizbetrieb arbeiten können, gilt EN 14511 für die Ermittlung der Leistung im Heizbetrieb.
ANMERKUNG 1 Die Prüfung von Geräten unter Teillastbedingungen ist in EN 14825 festgelegt.
ANMERKUNG 2 Sämtliche in diesem Text enthaltenen Symbole werden unabhängig von der verwendeten Sprache verwendet.
Climatiseurs, groupes refroidisseurs de liquide et pompes à chaleur pour le chauffage et le refroidissement des locaux et refroidisseurs industriels avec compresseur entraîné par moteur électrique - Partie 1 : Termes et définitions
Le présent document spécifie les termes et définitions relatifs à la détermination des caractéristiques et des performances des climatiseurs, des groupes refroidisseurs de liquide et des pompes à chaleur utilisant l'air, l'eau ou l'eau glycolée comme fluide caloporteur, avec compresseur entraîné par moteur électrique, lorsqu'ils sont utilisés pour le chauffage et/ou le refroidissement des locaux.
Il spécifie également les termes et définitions relatifs à la détermination des caractéristiques et des performances des refroidisseurs industriels.
Le présent document ne s'applique pas spécifiquement aux pompes à chaleur utilisées pour l'eau chaude sanitaire, bien que certaines définitions puissent leur être applicables.
Le présent document s'applique :
- aux appareils fabriqués en usine qui peuvent être raccordés ;
- aux groupes refroidisseurs de liquide autonomes fabriqués en usine ou conçus pour être utilisés avec des condenseurs fournis séparément ; et
- aux climatiseurs air/air qui peuvent également évaporer les condensats du côté condenseur.
Le présent document couvre les systèmes monoblocs, à deux éléments séparés et multi-split. Le présent document couvre également les appareils à simple et à double raccordement.
Dans le cas d'appareils à éléments séparés, le présent document ne s'applique qu'aux appareils conçus et fournis comme un ensemble, sauf pour ce qui concerne les groupes refroidisseurs de liquide avec condenseur séparé.
Le présent document est principalement destiné aux groupes refroidisseurs d'eau et d'eau glycolée mais peut être utilisé, après accord, pour d'autres liquides.
La performance en mode refroidissement des appareils ayant leur condenseur refroidi par air et par évaporation d'eau extérieure supplémentaire est déterminée conformément à l’EN 15218. Pour ceux qui peuvent également fonctionner en mode chauffage, la série des EN 14511 s’applique pour la détermination de leur performance en mode chauffage.
NOTE 1 Les essais à charge partielle des appareils sont traités dans l’EN 14825.
NOTE 2 Tous les symboles spécifiés dans le présent document sont utilisés quelle que soit la langue.
Klimatske naprave, enote za hlajenje kapljevine, toplotne črpalke za ogrevanje in hlajenje prostora ter procesne hladilne naprave z električnimi kompresorji - 1. del: Izrazi in definicije
General Information
RELATIONS
Standards Content (sample)
SLOVENSKI STANDARD
oSIST prEN 14511-1:2021
01-april-2021
Klimatske naprave, enote za hlajenje kapljevine, toplotne črpalke za ogrevanje in
hlajenje prostora ter procesne hladilne naprave z električnimi kompresorji - 1. del:
Izrazi in definicijeAir conditioners, liquid chilling packages and heat pumps for space heating and cooling
and process chillers, with electrically driven compressors - Part 1: Terms and definitions
Luftkonditionierer, Flüssigkeitskühlsätze und Wärmepumpen für die Raumbeheizung und
-kühlung und Prozess-Kühler mit elektrisch angetriebenen Verdichtern - Teil 1: Begriffe
Climatiseurs, groupes refroidisseurs de liquide et pompes à chaleur pour le chauffage et
le refroidissement des locaux et refroidisseurs industriels avec compresseur entraîné par
moteur électrique - Partie 1 : Termes et définitionsTa slovenski standard je istoveten z: prEN 14511-1
ICS:
01.040.23 Tekočinski sistemi in sestavni Fluid systems and
deli za splošno rabo (Slovarji) components for general use
(Vocabularies)
23.120 Zračniki. Vetrniki. Klimatske Ventilators. Fans. Air-
naprave conditioners
27.080 Toplotne črpalke Heat pumps
91.140.30 Prezračevalni in klimatski Ventilation and air-
sistemi conditioning systems
oSIST prEN 14511-1:2021 en,fr,de
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
---------------------- Page: 1 ----------------------oSIST prEN 14511-1:2021
---------------------- Page: 2 ----------------------
oSIST prEN 14511-1:2021
DRAFT
EUROPEAN STANDARD
prEN 14511-1
NORME EUROPÉENNE
EUROPÄISCHE NORM
March 2021
ICS Will supersede EN 14511-1:2018
English Version
Air conditioners, liquid chilling packages and heat pumps
for space heating and cooling and process chillers, with
electrically driven compressors - Part 1: Terms and
definitions
Climatiseurs, groupes refroidisseurs de liquide et Luftkonditionierer, Flüssigkeitskühlsätze und
pompes à chaleur pour le chauffage et le Wärmepumpen für die Raumbeheizung und -kühlung
refroidissement des locaux et refroidisseurs industriels und Prozess-Kühler mit elektrisch angetriebenen
avec compresseur entraîné par moteur électrique - Verdichtern - Teil 1: BegriffePartie 1 : Termes et définitions
This draft European Standard is submitted to CEN members for enquiry. It has been drawn up by the Technical Committee
CEN/TC 113.If this draft becomes a European Standard, CEN members are bound to comply with the CEN/CENELEC Internal Regulations
which stipulate the conditions for giving this European Standard the status of a national standard without any alteration.
This draft European Standard was established by CEN in three official versions (English, French, German). A version in any other
language made by translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC
Management Centre has the same status as the official versions.CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,
Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway,
Poland, Portugal, Republic of North Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and
United Kingdom.Recipients of this draft are invited to submit, with their comments, notification of any relevant patent rights of which they are
aware and to provide supporting documentation.Warning : This document is not a European Standard. It is distributed for review and comments. It is subject to change without
notice and shall not be referred to as a European Standard.EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION
EUROPÄISCHES KOMITEE FÜR NORMUNG
CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Brussels
© 2021 CEN All rights of exploitation in any form and by any means reserved Ref. No. prEN 14511-1:2021 E
worldwide for CEN national Members.---------------------- Page: 3 ----------------------
oSIST prEN 14511-1:2021
prEN 14511-1:2021 (E)
Contents
European foreword ....................................................................................................................................................... 3
1 Scope .................................................................................................................................................................... 4
2 Normative references .................................................................................................................................... 4
3 Terms and definitions ................................................................................................................................... 5
4 Symbols, abbreviated terms and units ................................................................................................. 13
5 Denomination ................................................................................................................................................ 14
---------------------- Page: 4 ----------------------oSIST prEN 14511-1:2021
prEN 14511-1:2021 (E)
European foreword
This document (prEN 14511-1:2021) has been prepared by Technical Committee CEN/TC 113 “Heat
pumps and air conditioning units”, the secretariat of which is held by UNE.This document is currently submitted to the Enquiry.
This document will supersede EN 14511-1:2018.
This document has been prepared in the frame of:
— the Commission Regulation (EU) No 206/2012 implementing Directive 2009/125/EC with regard to
ecodesign requirements for air conditioners;— the Commission Regulation (EU) n° 626/2011 supplementing Directive 2010/30/EU with regard to
energy labelling for air conditioners;— the Commission Regulation (EU) No 813/2013 implementing Directive 2009/125/EC with regard to
ecodesign requirements for air-to-water and water-to-water heat pump space heaters;
— the Commission Regulation (EU) n° 811/2013 supplementing Directive 2010/30/EU with regard to
energy labelling for air-to-water and water-to-water heat pump space heaters;— the Commission Regulation (EU) n° 2015/1095 implementing Directive 2009/125/EC of the
European Parliament and of the Council with regard to ecodesign requirements for process chillers;
— Commission Regulation (EU) 2016/2281 implementing Directive 2009/125/EC of the European
Parliament and of the Council with regard to ecodesign requirements for air heating products,
cooling products, high temperature process chillers and fan coil units.EN 14511, Air conditioners, liquid chilling packages and heat pumps for space heating and cooling and
process chillers, with electrically driven compressors currently comprises the following parts:
— Part 1: Terms and definitions— Part 2: Test conditions
— Part 3: Test methods
— Part 4: Requirements
---------------------- Page: 5 ----------------------
oSIST prEN 14511-1:2021
prEN 14511-1:2021 (E)
1 Scope
This document specifies the terms and definitions for the rating and performance of air conditioners,
liquid chilling packages and heat pumps using either air, water or brine as heat transfer media, with
electrically driven compressors when used for space heating and/or cooling.It also specifies the terms and definitions for the rating and performance of process chillers.
This document does not apply to heat pumps for domestic hot water, although certain definitions can be
applied to these.This document applies to:
— factory-made units that can be ducted,
— factory-made liquid chilling packages with integral condensers or for use with remote condensers,
— factory-made units of either fixed capacity or variable capacity by any means, and
— air-to-air air conditioners which can also evaporate the condensate on the condenser side.
Packaged units, single split and multisplit systems are covered by this document. Single duct and double
duct units are covered by the document.In the case of units consisting of several parts, this document applies only to those designed and supplied
as a complete package, except for liquid chilling packages with remote condenser.
This document is primarily intended for water and brine chilling packages but can be used for other liquid
subject to agreement.The units having their condenser cooled by air and by the evaporation of external additional water will
have their performance in the cooling mode determined in accordance to EN 15218. For those which can
also operate in the heating mode, the EN 14511 series applies for the determination of their performance
in the heating mode.NOTE 1 Part load testing of units is dealt with in EN 14825.
NOTE 2 All the symbols given in this text are used regardless of the language.
2 Normative references
There are no normative references in this document.
---------------------- Page: 6 ----------------------
oSIST prEN 14511-1:2021
prEN 14511-1:2021 (E)
3 Terms and definitions
For the purposes of this document, the following terms and definitions apply.
ISO and IEC maintain terminological databases for use in standardization at the following addresses:
— IEC Electropedia: available at http://www.electropedia.org/— ISO Online browsing platform: available at http://www.iso.org/obp
3.1
air conditioner
device capable of cooling or heating, or both, indoor air, using a vapour compression cycle driven by an
electric compressor, including air conditioners that provide additional functionalities such as
dehumidification, air purification, ventilation or supplemental air heating by means of electric resistance
heating, as well as appliances that may use water (either condensate water that is formed onthe
evaporator side or externally added water) for evaporation on the condenser, provided that the device is
also able to function without the use of additional water, using air onlyNote 1 to entry: Appliances using additional external water are rated according to EN 15218.
3.2heat pump
encased assembly or assemblies designed as a unit, using a vapour compression cycle driven by an
electric compressor, to provide delivery of heatNote 1 to entry: It can have means for cooling, circulating, cleaning and dehumidifying the air. The cooling is by
means of reversing the refrigerating cycle.Note 2 to entry: Also known as a reverse cycle air conditioner, when cooling and heating air.
3.3comfort air conditioner or heat pump
air conditioner or heat pump to satisfy the comfort requirements of the occupants of the air conditioned
room3.4
close control air conditioner
air conditioner to satisfy the requirements of the process carried out in the air conditioned room
3.5control cabinet air conditioner
air conditioner to satisfy the requirements of the control cabinet
3.6
packaged unit
factory assembly of components of refrigeration system fixed on a common mounting to form a discrete
unit3.7
single split unit
factory assembly of components of refrigeration system fixed on two mountings to form a discrete
matched functional unit---------------------- Page: 7 ----------------------
oSIST prEN 14511-1:2021
prEN 14511-1:2021 (E)
3.8
single-duct air conditioner
air conditioner in which, during cooling or heating, the condenser (or evaporator) intake air is introduced
from the space containing the unit and discharged outside this space3.9
double-duct air conditioner
air conditioner in which, during cooling or heating, the condenser (or evaporator) intake air is introduced
from the outdoor environment to the unit by a duct and rejected to the outdoor environment by a second
duct, and which is placed wholly inside the space to be conditioned, near a wall3.10
liquid chilling package
factory-made unit designed to cool liquid, using an evaporator, a refrigerant compressor, an integral or
remote condenser and appropriate controlsNote 1 to entry: It may have means for heating which can be reversing the refrigerating cycle, such as a heat
pump.3.11
comfort chiller
liquid chilling package whose indoor heat exchanger extracts heat from a water-based cooling system
designed to operate at leaving chilled water temperatures greater than or equal to 2° C
3.12process chiller
factory-made product integrating at least one compressor and one evaporator, capable of cooling down
and continuously maintaining the temperature of a liquid in order to provide cooling to a refrigerated
appliance or to a process cooling systemNote 1 to entry: It may or may not integrate the condenser, the coolant circuit hardware and other ancillary
equipment.3.13
low temperature process chiller
process chiller that is capable of delivering its rated cooling capacity at an indoor heat exchanger outlet
temperature of −25 °C, at standard rating conditions3.14
medium temperature process chiller
process chiller that is capable of delivering its rated cooling capacity at an indoor heat exchanger outlet
temperature of −8 °C, at standard rating conditions3.15
high temperature process chiller
process chiller that is capable of delivering its rated cooling capacity at an outlet chilled water
temperature of 7 °C3.16
heat recovery liquid chilling package
factory-made liquid chilling package designed for the purpose of chilling liquid and recovering of heat
---------------------- Page: 8 ----------------------oSIST prEN 14511-1:2021
prEN 14511-1:2021 (E)
3.17
heat recovery
recovery of heat rejected by the unit whose primary control is in the cooling mode by means of either an
additional heat exchanger (e.g. a liquid chiller with an additional condenser) or by transferring the heat
through the refrigerating system for use to unit whose primary control remains in the heating mode (e.g.
variable refrigerant flow)3.18
indoor heat exchanger
heat exchanger which is designed to transfer heat between the refrigerant and the indoor heat transfer
mediumNote 1 to entry: In the case of an air conditioner or heat pump operating in the cooling mode, this is the
evaporator. In the case of an air conditioner or heat pump operating in the heating mode, this is the condenser.
3.19outdoor heat exchanger
heat exchanger which is designed to transfer heat between any available heat source and the refrigerant
Note 1 to entry: In the case of an air conditioner or heat pump operating in the cooling mode, this is the
condenser. In the case of an air conditioner or heat pump operating in the heating mode, this is the evaporator.
3.20heat recovery heat exchanger
heat exchanger assembly which is designed to transfer heat to the heat recovery medium
3.21heat transfer medium
medium (water, air...) used for the transfer of the heat without change of state
EXAMPLES Cooled liquid circulating in the evaporator; cooling medium circulating in the condenser; heat
recovery medium circulating in the heat recovery heat exchanger.3.22
exhaust air
air from the air conditioned space entering the outdoor heat exchanger
3.23
recycled air
air from the air conditioned space entering the indoor heat exchanger
3.24
outdoor air
air from the outdoor environment
3.25
water loop
closed circuit of water maintained within a temperature range on which the units in cooling mode reject
heat and the units in heating mode take heat---------------------- Page: 9 ----------------------
oSIST prEN 14511-1:2021
prEN 14511-1:2021 (E)
3.26
cooling capacity
heat given off from the heat transfer medium to the unit per unit of time, corrected from any fan or pump
heat where applicableNote 1 to entry: Expressed in kW.
Note 2 to entry: For air to air, water/brine to air units, cooling capacity is the total cooling capacity i.e. sum of
latent and sensible cooling capacities.3.27
latent cooling capacity
capacity of the unit for removing latent heat from the evaporator intake air
Note 1 to entry: Expressed in kW.
3.28
sensible cooling capacity
capacity of the unit for removing sensible heat from the evaporator intake air
Note 1 to entry: Expressed in kW.
3.29
heating capacity
heat given off by the unit to the heat transfer medium per unit of time, corrected from
...