Low-voltage electrical installations - Part 5-53: Selection and erection of electrical equipment - Isolation, switching and control - Clause 534: Devices for protection against overvoltages

Gives the requirements for the erection and selection of surge protection devices of installations of buildings to obtain a limitation of transient overvoltages of atmospheric origin transmitted by the supply distribution system and against switching overvoltages generated by the equipment within the installation. Selection and erection of surge protective devices is also necessary for the protection against direct lightning strokes or lightning strokes in the vicinity of buildings.

Errichten von Niederspannungsanlagen - Teil 5-53: Auswahl und Errichtung elektrischer Betriebsmittel - Trennen, Schalten und Steuern - Abschnitt 534: Überspannungs-Schutzeinrichtungen (SPDs)

Installations électriques à basse tension - Partie 5-53: Choix et mise en oeuvre des matériels électriques - Sectionnement, coupure et commande - Article 534: Dispositifs pour la protection contre les surtensions

L’IEC 60364-5-53 traite des prescriptions générales relatives au sectionnement, à la coupure et à la commande, ainsi que des prescriptions relatives au choix et à la mise en œuvre des dispositifs assurant ces fonctions.
L'Article 534 contient des dispositions pour l’application de la limitation de tension afin de réaliser la coordination de l’isolement dans les cas décrits dans le HD 60364-4-44, l'EN 60664-1, l'EN 62305-1, l'EN 62305-4 et la CLC/TS 61643-12.
L'Article 534 porte principalement sur les exigences relatives au choix et à l'installation des parafoudres pour la protection contre les surtensions transitoires conformément aux exigences de l'IEC 60364-4-44:2007, Article 443, de la série EN 62305 ou suivant une spécification contraire.
L'Article 534 ne prend pas en compte:
-   les composants de protection contre les surtensions pouvant être incorporés dans les matériels d'utilisation connectés à l'installation;
-   les parafoudres mobiles.
NOTE   De plus amples informations sont disponibles dans la CLC/TS 61643-12.
L'Article 534 s'applique à des circuits de puissance en courant alternatif. Pour les circuits de puissance en courant continu, les exigences du présent article peuvent s'appliquer autant que possible.

Nizkonapetostne električne inštalacije - 5-53. del: Izbira in namestitev električne opreme - Ločevanje, stikanje in krmiljenje - 534. točka: Naprave za prenapetostno zaščito

Podaja zahteve za postavitev in izbiro naprav za prenapetostno zaščito v inštalacijah stavb za doseganje omejitve začasne prenapetosti atmosferskega izvora, ki jih prenaša distribucijski sistem, in zaščito pred stikalno prenapetostjo, ki jo povzroči oprema v inštalaciji. Izbira in postavitev naprav za prenapetostno zaščito je potrebna tudi za zaščito pred neposrednimi udari strele ali udari strele v bližini stavb.

General Information

Status
Published
Publication Date
14-Mar-2016
Current Stage
6100 - Translation of adopted SIST standards (Adopted Project)
Start Date
16-Nov-2020
Due Date
15-Nov-2021
Completion Date
07-Feb-2023

Relations

Buy Standard

Standardization document
HD 60364-5-534:2016 - BARVE
English language
53 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day
Standard – translation
HD 60364-5-534:2016 - BARVE
Slovenian language
55 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

SLOVENSKI STANDARD
SIST HD 60364-5-534:2016
01-april-2016
1DGRPHãþD
SIST HD 60364-5-534:2008
1L]NRQDSHWRVWQHHOHNWULþQHLQãWDODFLMHGHO,]ELUDLQQDPHVWLWHYHOHNWULþQH
RSUHPH/RþHYDQMHVWLNDQMHLQNUPLOMHQMHWRþND1DSUDYH]DSUHQDSHWRVWQR
]DãþLWR
Low-voltage electrical installations - Part 5-53: Selection and erection of electrical
equipment - Isolation, switching and control - Clause 534: Devices for protection against
overvoltages
Installations électriques à basse tension - Partie 5-53: Choix et mise en oeuvre des
matériels électriques - Sectionnement, coupure et commande - Article 534: Dispositifs
pour la protection contre les surtensions
Ta slovenski standard je istoveten z: HD 60364-5-534:2016
ICS:
29.120.99 'UXJDHOHNWULþQDGRGDWQD Other electrical accessories
RSUHPD
91.140.50 Sistemi za oskrbo z elektriko Electricity supply systems
SIST HD 60364-5-534:2016 en
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

---------------------- Page: 1 ----------------------

SIST HD 60364-5-534:2016

---------------------- Page: 2 ----------------------

SIST HD 60364-5-534:2016


HARMONIZATION DOCUMENT HD 60364-5-534

DOCUMENT D'HARMONISATION

HARMONISIERUNGSDOKUMENT
February 2016
ICS 29.130; 91.140.50 Supersedes HD 60364-5-534:2008
English Version
Low-voltage electrical installations - Part 5-53: Selection and
erection of electrical equipment - Isolation, switching and control -
Clause 534: Devices for protection against transient overvoltages
(IEC 60364-5-53:2001/A2:2015 , modified)
Installations électriques à basse tension - Partie 5-53: Choix Errichten von Niederspannungsanlagen - Teil 5-53:
et mise en oeuvre des matériels électriques - Auswahl und Errichtung elektrischer Betriebsmittel -
Sectionnement, coupure et commande - Article 534: Trennen, Schalten und Steuern - Abschnitt 534:
Dispositifs de protection contre les surtensions transitoires Überspannung-Schutzeinrichtungen (ÜSE)
(IEC 60364-5-53:2001/A2:2015 , modifiée) (IEC 60364-5-53:2001/A2:2015 , modifiziert)
This Harmonization Document was approved by CENELEC on 2015-12-14. CENELEC members are bound to comply with the
CEN/CENELEC Internal Regulations which stipulate the conditions for implementation of this Harmonization Document at national level.
Up-to-date lists and bibliographical references concerning such national implementations may be obtained on application to the CEN-
CENELEC Management Centre or to any CENELEC member.
This Harmonization Document exists in three official versions (English, French, German).
CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus, the Czech Republic,
Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia,
Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland,
Turkey and the United Kingdom.


European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung
CEN-CENELEC Management Centre: Avenue Marnix 17, B-1000 Brussels
© 2016 CENELEC All rights of exploitation in any form and by any means reserved worldwide for CENELEC Members.
 Ref. No. HD 60364-5-534:2016 E

---------------------- Page: 3 ----------------------

SIST HD 60364-5-534:2016
HD 60364-5-534:2016
European foreword
The text of document 64/2031/FDIS, future IEC 60364-5-53:2001/A2 prepared by IEC/TC 64 “Electrical
installations and protection against electric shock” was submitted to the IEC-CENELEC parallel vote and
approved by CENELEC as HD 60364-5-534:2016.
A draft amendment, which covers common modifications to IEC 60364-5-53:2001/A2:2015
(64/2031/FDIS), was prepared by CLC/TC 64 “Electrical installations and protection against electric
shock” and approved by CENELEC.
The following dates are fixed:
• latest date by which the document has to be implemented at (dop) 2016-12-14
national level by publication of an identical national
standard or by endorsement
• latest date by which the national standards conflicting with the (dow) 2018-12-14
document have to be withdrawn
HD 60364-5-534:2016 supersedes HD 60364-5-534:2008.
HD 60364-5-534:2016 includes the following significant technical changes with respect to the previous
edition: this document constitutes a complete structural and technical revision of HD 60364-5-534:2008.
The most significant technical change refers to the selection requirements for the voltage protection level.
Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. CENELEC [and/or CEN] shall not be held responsible for identifying any or all such patent
rights.
Clauses, subclauses, notes, tables, figures and annexes which are additional to those in
IEC 60364-5-53:2001/A2:2015 are prefixed “Z”.
2

---------------------- Page: 4 ----------------------

SIST HD 60364-5-534:2016
HD 60364-5-534:2016
Endorsement notice
The text of the International Standard IEC 60364-5-53:2001/A2:2015 was approved by CENELEC as a
Harmonization Document with agreed common modifications.
COMMON MODIFICATIONS
530.2 Normative references
Replace the text of 530.2 by the following:
The following documents, in whole or in part, are normatively referenced in this document and are
indispensable for its application. For dated references, only the edition cited applies. For undated
references, the latest edition of the referenced document (including any amendments) applies.
EN 60038, CENELEC standard voltages (IEC 60038)
HD 60364-4-41:2007 + corr. Jul. 2007, Low-voltage electrical installations - Part 4-41: Protection for
safety - Protection against electric shock (IEC 60364-4-41:2005, mod.)
HD 60364-4-43:2010, Low-voltage electrical installations - Part 4-43: Protection for safety - Protection
against overcurrent (IEC 60364-4-43:2008, mod. + corr. Oct. 2008)
HD 60364-4-443:2016, Low-voltage electrical installations - Part 4-44: Protection for safety - Protection
against voltage disturbances and electromagnetic disturbances - Clause 443: Protection against transient
overvoltages of atmospheric origin or due to switching (IEC 60364-4-44:2007/A1:2015, mod.)
HD 60364-5-54, Low-voltage electrical installations - Part 5-54: Selection and erection of electrical
equipment - Earthing arrangements and protective conductors (IEC 60364-5-54)
EN 60664-1:2007, Insulation coordination for equipment within low-voltage systems - Part 1: Principles,
requirements and tests (IEC 60664-1:2007)
EN 61643-11:2012, Low-voltage surge protective devices - Part 11: Surge protective devices connected
to low-voltage power systems - Requirements and test methods (IEC 61643-11:2011, mod.)
CLC/TS 61643-12, Low-voltage surge protective devices - Part 12: Surge protective devices connected to
low-voltage power distribution systems - Selection and application principles (IEC 61643-12)
EN 62305-1, Protection against lightning - Part 1: General principles (IEC 62305-1)
EN 62305-2, Protection against lightning - Part 2: Risk management (IEC 62305-2)
EN 62305-4, Protection against lightning - Part 4: Electrical and electronic systems within structures
(IEC 62305-4)
IEC/TR 60664-2-1:2011, Insulation coordination for equipment within low-voltage systems - Part 2-1:
Application guide - Explanation of the application of the IEC 60664 series, dimensioning examples and
dielectric testing
3

---------------------- Page: 5 ----------------------

SIST HD 60364-5-534:2016
HD 60364-5-534:2016
530.3 Terms and definitions
Add Clause 530.3 “Terms and definitions” as follows:
530.3 Terms and definitions
For the purposes of this document, the following terms and definitions apply.
530.3.101
SPD assembly
one SPD or a set of SPDs, in both cases including all SPD disconnectors required by the SPD
manufacturer, providing the required overvoltage protection for a type of system earthing
530.3.102
SPD disconnector
disconnector
device for disconnecting an SPD, or part of an SPD, from the power system
Note 1 to entry: This disconnecting device is not required to have isolating capability for safety purposes. It is to
prevent a persistent fault on the system and is used to give an indication of an SPD’s failure. Disconnectors can be
internal (built in) or external (required by the manufacturer). There may be more than one disconnector function, for
example, an over-current protection function and a thermal protection function. These functions may be in separate
units.
[SOURCE: IEC 61643-11:2011, 3.1.28]
530.3.103
mode of protection of an SPD
intended current path, between terminals that contains protective components, e.g. line-to-line, line-to-
earth, line-to-neutral, neutral-to-earth
[SOURCE: IEC 61643-11:2011, 3.1.8]
530.3.104
follow current interrupt rating
I
fi
prospective short-circuit current that an SPD is able to interrupt without operation of a disconnector
[SOURCE: IEC 61643-11:2011, 3.1.39]
530.3.105
short-circuit current rating

I
SCCR
maximum prospective short-circuit current from the power system for which the SPD, in conjunction with
the disconnector specified, is rated
[SOURCE: IEC 61643-11:2011, 3.1.27]
4

---------------------- Page: 6 ----------------------

SIST HD 60364-5-534:2016
HD 60364-5-534:2016
530.3.106
voltage protection level
U
P
maximum voltage to be expected at the SPD terminals due to an impulse stress with defined voltage
steepness and an impulse stress with a discharge current with given amplitude and waveshape
Note 1 to entry: The voltage protection level is given by the manufacturer and may not be exceeded by:
– the measured limiting voltage determined for front-of-wave sparkover (if applicable) and the measured limiting
voltage determined from the residual voltage measurements at amplitudes corresponding to I and/or I
n imp
respectively for test classes II and/or I;
– the measured limiting voltage at the open circuit voltage (U ) of the combination wave generator, determined
OC
for the combination wave for test class III.
Note 2 to entry: Information on the correlation between SPD Types and test classes according to the product
standard is provided in Annex C.
[SOURCE: IEC 61643-11:2011, 3.1.14, mod. — Note 1 to entry is modified and Note 2 to entry is added.]
530.3.107
rated impulse voltage
U
W
impulse withstand voltage value assigned by the manufacturer to the equipment or to a part of it,
characterizing the specified withstand capability of its insulation against transient overvoltages
[SOURCE: IEC 60664-1:2007, 3.9.2, mod. — The abbreviation 'U ' is added.]
W
530.3.108
maximum continuous operating voltage
U
C
maximum r.m.s. voltage, which may be continuously applied to the SPD's mode of protection
Note 1 to entry: The U value covered by this standard may exceed 1 000 V.
C
[SOURCE: IEC 61643-11:2011, 3.1.11]
530.3.109
nominal discharge current for class II test
I
n
crest value of the current through the SPD having a current waveshape of 8/20
Note 1 to entry: Information on the correlation between SPD Types and test classes according to the product
standard is provided in Annex C.
[SOURCE: IEC 61643-11:2011, 3.1.9, mod. — Note 1 to entry is added.]
530.3.110
impulse discharge current for class I test
I
imp
crest value of a discharge current through the SPD with specified charge transfer Q and specified energy
W/R in the specified time
Note 1 to entry: Information on the correlation between SPD Types and test classes according to the product
standard is provided in Annex C.
[SOURCE: IEC 61643-11:2011, 3.1.10, mod. — Note 1 to entry is added.]
5

---------------------- Page: 7 ----------------------

SIST HD 60364-5-534:2016
HD 60364-5-534:2016
530.3.111
open circuit voltage
U
OC
open circuit voltage of the combination wave generator at the point of connection of the device under test
[SOURCE: IEC 61643-11:2011, 3.1.23]
530.3.112
two-port SPD
SPD having a specific series impedance connected between separate input and output connections
[SOURCE: IEC 61643-11:2011, 3.1.3]
534 Devices for protection against transient overvoltages
534.1 General
Replace the 2 first paragraphs under 534.1 as follows:
This clause contains provisions for the application of voltage limitation in order to obtain insulation
coordination in the cases described in HD 60364-4-44, EN 60664-1, EN 62305-1, EN 62305-4 and
CLC/TS 61643-12.
This clause focuses mainly on the requirements for the selection and erection of SPDs for protection
against transient overvoltages where required by IEC 60364-4-44:2007, Clause 443, the EN 62305
series, or as otherwise specified.
Replace the title of 534.4.1 and all paragraphs before NOTE 3, except NOTE 1, as follows:
534.4.1 SPD location and type of SPD
SPDs shall at least be installed as close as possible to the origin of the installation. For protection against
effects of lightning and against switching overvoltages Type 2 SPDs shall be used.
If the structure is equipped with an external lightning protection system or protection against effects of
direct lightning is otherwise specified, Type 1 SPDs shall be used.
Where the structure is not equipped with an external lightning protection system and where the
occurrence of direct lightning strike to the overhead lines between the last pole and the entrance of the
installation is to be taken into consideration, Type 1 SPDs at or near the origin of the electrical installation
may be also selected according to Annex B.
Following the product standard, the marking of the product is as follows:
– for Type 1 SPDs: either “Type 1” and/or “T1“ (T1 in a square);
– for Type 2 SPDs: either “Type 2” and/or “T2“ (T2 in a square);
– for Type 3 SPDs: either “Type 3” and/or “T3” (T3 in a square).
NOTE 2 Information on the correlation between SPD Types and test classes according to the product standard is
provided in Annex C.
Additional Type 2 or Type 3 SPDs may be needed to sufficiently protect the installation according to
534.4.4.1 and shall be located downstream in the fixed electrical installation, for example in the sub-
distribution boards or at socket outlets. These SPDs shall not be used without SPDs being installed at the
origin of the installation and shall be coordinated with SPDs located upstream (see 534.4.4.5).
6

---------------------- Page: 8 ----------------------

SIST HD 60364-5-534:2016
HD 60364-5-534:2016
If a Type 1 SPD is not able to provide protection according to 534.4.4.2, it shall be accompanied by a
coordinated Type 2 or Type 3 SPD to ensure the required voltage protection level.
Additional Type 2 SPDs or Type 3 SPDs may be needed close to sensitive equipment to sufficiently
protect the equipment according to 534.4.4.2 and shall be coordinated with SPDs located upstream.
Replace Figure 534.1 and its title as follows:

Type 1 SPD Type 2 SPD Type 2 SPD
and/or or or
Type 2 SPD Type 3 SPD Type 3 SPD
Figure 534.1 — Example of installation of Type 1, Type 2 and Type 3 SPDs
534.4.4.2 Selection of voltage protection level (U ) as a function of equipment rated impulse
p
voltage (U )
W
Replace the introductory paragraph for the four indents as follows:
This recommendation may not be considered where one of the following cases applies:
7

---------------------- Page: 9 ----------------------

SIST HD 60364-5-534:2016
HD 60364-5-534:2016
Replace Table 534.1 as follows:
Table 534.1 — Required rated impulse voltage of equipment (U )
W
b
Nominal voltage of Nominal voltage of
Voltage line to Required rated impulse voltage (U ) of equipment
W
the supply the supply
neutral from
a a
Overvoltage category II Overvoltage category I
system system nominal a.c. or d.c.
(equipment with normal (equipment with reduced
voltages up to and
Three-phase Single-phase

rated impulse voltage) rated impulse voltage)
including
systems systems
V V V kV kV
 50 0,5 0,33
 100 0,8 0,5
120/240 150 1,5 0,8
230/400
300 2,5 1,5
277/480
400/690 600 4 2,5
1 000 1 000 6 4
c c
 1 500 d.c.
8 6
a
According to EN 60038.
b
The rated impulse voltage applies between live conductor and PE.
c
Recommended values based on IEC/TR 60664–2-1:2011, Annex D.
Replace the paragraph after Table 534.1 as follows:
Additional SPDs between live conductors may be needed to avoid equipment malfunctions. An
appropriate voltage protection level needs to be evaluated based on equipment immunity and availability
requirements (see CLC/TS 61643-12).
534.4.4.4 Selection of SPDs with regard to nominal discharge current (I ) and impulse discharge
n
current (I )
imp
Replace the title of Subclause 534.4.4.4.1 and the first paragraph under as follows:
534.4.4.4.1 Type 2 SPDs
Where Type 2 SPDs are required at or near the origin of installation, their nominal discharge current shall
be not less than that given in Table 534.3.
8

---------------------- Page: 10 ----------------------

SIST HD 60364-5-534:2016
HD 60364-5-534:2016
Replace the title of Subclause 534.4.4.4.2 and the first 2 paragraphs under as follows:
534.4.4.4.2 Type 1 SPDs
Where Type 1 SPDs are required at or near the origin of the installation, one of the following cases
applies:
a) Where no risk analysis according to EN 62305-2 has been carried out, the impulse discharge current
(I ) shall be not less than as given in Table 534.4.
imp
Replace the indent b) as follows:
b) Where the risk analysis according to EN 62305-2 has been carried out, the impulse discharge current
(I ) shall be determined according to the EN 62305 series.
imp
534.4.4.5 Coordination of two or several SPDs
Replace the paragraph under 534.4.4.5 as follows:
Coordination of SPDs in the installation needs to be ensured. The manufacturer's instructions on how to
achieve coordination between SPDs shall be followed with reference CLC/TS 61643-12.
534.4.4.6 Selection of SPDs with regard to the short-circuit current rating I
SCCR
Replace the second paragraph under 534.4.4.6 as follows:
This requirement does not apply to SPDs connected between neutral conductor and PE in TN or TT
systems, for which this is already covered by the product standard EN 61643-11.
534.4.4.7 Selection of SPDs with regard to the follow current interrupting rating
Replace the second paragraph under 534.4.4.7 as follows:
This requirement does not apply to SPDs connected between neutral conductor and PE conductor in TN
or TT systems, for which this is already covered by the product standard EN 61643-11.
534.4.5.3 Selectivity between overcurrent protective devices
Replace the first paragraph under 534.4.5.3 as follows:
Where required, the need for selectivity between overcurrent protective devices shall be considered
according to the installation conditions at the point of installation of the SPD and the information provided
by the manufacturer (See HD 60364-5-53:2014, Clause 536).
534.4.6 Fault protection
Replace the first paragraph under 534.4.6 as follows:
Fault protection, as defined in HD 60364-4-41, shall remain effective in the protected installation even in
the event of SPD failures.
9

---------------------- Page: 11 ----------------------

SIST HD 60364-5-534:2016
HD 60364-5-534:2016
Replace the indent b) as follows:
b) the installation of SPDs upstream of the main RCD. Because of the possibility of a failure of an SPD
connected between neutral conductor and PE, the conditions of HD 60364-4-41:2007, 411.4.1, shall be
met and the SPDs shall be installed in accordance with connection type CT2.
534.4.7 SPDs installation in conjunction with RCDs
Replace NOTE 1 and the last paragraph under 534.4.7 as follows:
NOTE 1 S-type RCDs in accordance with EN 61008–1 and EN 61009–1 satisfy this requirement.
Installation of Type 1 SPDs downstream of an RCD is not recommended.
534.4.10 Connecting conductors of SPDs
Replace the 2 indents after the first paragraph under 534.4.10 as follows:
2
– 6 mm copper or equivalent for Type 2 SPDs installed at or near the origin of the installation;
2
– 16 mm copper or equivalent for Type 1 SPDs installed at or near the origin of the installation.
Replace the last 2 indents as follows:
2
– 2,5 mm copper or equivalent for Type 2 SPDs installed at or near the origin of the installation;
2
– 6 mm copper or equivalent for Type 1 SPDs installed at or near the origin of the installation.
10

---------------------- Page: 12 ----------------------

SIST HD 60364-5-534:2016
HD 60364-5-534:2016
Annex B
(informative)

Installations supplied by overhead lines
Replace the first 2 paragraphs as follows:
Where overvoltage protection according to HD 60364-4-443:2016, Clause 443, is required, where the
lines entering the building are overhead and where the case of lightning strike to the last pole of the
overhead lines close to the building is taking into account, SPDs at the origin of the installation shall be
selected according to Table B.1.
Further information can be found in EN 62305 series.
11

---------------------- Page: 13 ----------------------

SIST HD 60364-5-534:2016
HD 60364-5-534:2016
Replace Annex C by the following new Annex C:
Annex C
(informative)

Correlation between SPD Types and test classes
according to the product standard EN 61643-11
Table C.1 — Type 1, Type 2 and Type 3 SPDs and
corresponding test classes I, II and III
Reference
Type of SPD Test class
parameter
I
Type 1 test class I
imp
I
Type 2 test class II
n
U
Type 3 test class III
oc
12

---------------------- Page: 14 ----------------------

SIST HD 60364-5-534:2016
HD 60364-5-534:2016
Add Annex ZA and Annex ZB as follows:
Annex ZA
(normative)

Special national conditions
Special national condition: National characteristic or practice that cannot be changed even over a long
period, e.g. climatic conditions, electrical earthing conditions.
NOTE If it affects harmonization, it forms part of Harmonization Document.
For the countries in which the relevant special national conditions apply these provisions are normative,
for other countries they are informative.
Clause Special national condition
534.4.1 France
The following content:
Where the structure is not equipped with an external lightning protection system and
where the occurrence of direct lightning strike to the overhead lines between the last
pole and the entrance of the installation is to be taken into consideration, Type 1
SPDs at or near the origin of the electrical installation may be also selected according
to Annex B.
is not applied in France
534.4.1 Germany
In Germany, where the installation of a building is supplied by overhead lines, SPDs
shall be Type 1 according Annex B.
534.4.3 Germany
In Germany, the restriction to a maximum distance of 0,5 m is the only requirement to
be considered.
534.4.4.2 Norway
In Norway, where the installation is galvanic connected to a public IT-distribution
network, the minimum required U for a SPD located at the origin of the installations
c
shall be at least 350 V.
13

---------------------- Page: 15 ----------------------

SIST HD 60364-5-534:2016
HD 60364-5-534:2016
Clause Special national condition
534.4.4.4.1 Germany
Add the following text and additional table:
The nominal discharge current of Type 2 SPDs installed at or near the origin of
installations with increased safety level, shall not be less than given in Table 534.3
below:
Table 534.3 — Nominal discharge current (I ) in kA depending on supply
n
system and connection type for installations with increased safety level
Supply system
Single-phase Three-phase
Connection
Connection Connection Connection Connection

type 1 type 2 type 1 type 2
L – N 10 10
L – PE 10 10
N – PE 10 20 10 40

534.4.4.4.2 Germany
In Germany, where the installation of a building is supplied by overhead lines, SPDs
shall be Type 1 according Annex B.
534.4.4.5 Norway
In Norway, where the installation is galvanically connected to a public IT-distribution
network, and where a second SPD is installed downstream of the SPD located in the
main distribution board, the maximum continuous operating voltage, U , for the
c
second SPD shall be at least 440 V between line conductors and PE, and at least
275 V between line conductors.
534.4.6 Germany
In order to avoid false tripping or welding of the RCDs contacts the flow of high
impulses currents or partial lightning currents should be avoided. Therefore, SPDs
Type 1 or Type 2 at or near the origin of installation should be installed on the line
side of an RCD. If the surge is expected from the load side, e.g. due to external
mounted equipment, not protected by a LPS, SPDs Type 1 or Type 2 should be
installed on the load side of an RCD.
14

---------------------- Page: 16 ----------------------

SIST HD 60364-5-534:2016
HD 60364-5-534:2016
Clause Special national condition
534.4.6 Norway
In Norway, where the installation is galvanically connected to a public IT or TT
distribution network without the provision of a distributed PE conductor (i.e.
installation supplied by overhead lines), protection against fire caused by a failure of
the SPD located in the main distribution board shall be ensured by:
– locating the SPD in a separate enclosure of non-combustible materials; or
– protecting the SPD by a time-delayed RCD (S-type or similar) with a rated
residual operating current not exceeding 300 mA; or
– using an SPD constructed so as to minimize the risk of damage and fire due to an
earth failure in the high-voltage distribution network.
534.4.7 Germany
It should be ensured that lightning currents or high impulse currents will not flow
through the RCD. Therefore, the installation of class I tested SPDs downstream the
RCD is not admissible, except partial lightning currents may be expected from the
load side of the RCD.
The installation of class II tested SPDs downstream of the RCD is admissible, only if
already a class II tested SPD is installed upstream of the RCD or if impulse currents
are expected from the load side of the RCD.
In case of surge currents higher than 3 kA 8/20, the RCD may trip causing
interruption of the power supply.
Annex A Germany
In Germany, earthing connections 5a and 5b are required for SPDs installed at the
origin of installation.
Annex B France
Annex B is not applied in France.
Annex B Germany
Annex B is normative in Germany.
15

---------------------- Page: 17 ----------------------

SIST HD 60364-5-534:2016
HD 60364-5-534:2016
Annex ZB
(informative)

A-deviations
A-deviation: National deviation due to regulations, the alteration of which is for the time being outside the
competence of the CEN-CENELEC national member.
This Harmonization Document does not fall under any Directive of the EU.
In the relevant CEN–CENELEC countries, these A-deviations are valid instead of the provisions of the
Harmonization Document until they have been removed.
Clause Deviation
534.4.6 Austria
534.4.7 Electrotechnical Ordinance 2002 - Federal gazette Part II No. 222/2002
amended by
Electrotechnical Ordinance 2002/A1 - Federal gazette Part II No. 33/2006
amended by
Electrotechnical Ordinance 2002/A2 - Federal gazette Part II No. 223/2010):
In Austria, the SPD assembly at or near the origin of the installation may not be
installed downstream of any RCD.
534.4.11AT Austria
Electrotechnical Ordinance 2002 - Federal gazette Part II No. 222/2002
amended by
Electrotechnical Ordinance 2002/A1 - Federal gazette Part II No. 33/2006
amended by
Electrotechnical Ordinance 2002/A2 - Federal gazette Part II No. 223/2010):
Addition:
534.4.11AT Measurement of the insulation resistance
If SPDs mounted in a distribution board may significantly influence the insulation
resistance measurement of the installation, they shall be clearly labelled:
e.g. SPDs shall be disconnected for insulation measurements!
SPDs not incorporated in a distribution board, which are connected to the PE
conductor, shall withstand the insulation resistance measurement without a significant
influence on the measurement results.
16

---------------------- Page: 18 ----------------------

SIST HD 60364-5-534:2016
HD 60364-5-534:2016
Replace the bibliography as follows:
Bibliography
EN 61008-1, Residual current operated circuit-breakers without integral overcurrent protection for
household and similar uses (RCCBs) - Part 1: General rules (IEC 61008-1)
EN 61009-1, Residual current operated circuit-breakers with integral overcurrent protection for household
and similar uses (RCBOs) - Part 1: General rules (IEC 61009-1)

17

---------------------- Page: 19 ----------------------

SIST HD 60364-5-534:2016

---------------------- Page: 20 ----------------------

SIST HD 60364-5-534:2016




IEC 60364-5-53

®


Edition 3.0 2015-09




INTERNATIONAL



STANDARD




NORME



INTERNATIONALE
colour

inside



A MENDMENT 2

AM ENDEMENT 2





Electrical installations of buildings –

Part 5-53: Selection and erection of electrical equipment – Isolation, switching

and control




Installations électriques des bâtiments –

Partie 5-53: Choix et mise en oeuvre des matériels électriques – Sectionnement,


coupure et commande














INTERNATIONAL

ELECTROTECHNICAL

COMMISSION


COMMISSION

ELECTROTECHNIQUE


INTERNATIONALE




ICS 29.130; 91.140.50 ISBN 978-2-8322-2883-8



Warning! Make sure that you obtained this publication from an authorized distributor.

Attention! Veuillez vous assurer que
...

S L O V E N S K I SIST HD 60364-5-534
S T A N D A R D april 2016
Nizkonapetostne električne inštalacije – 5-53. del: Izbira in namestitev
električne opreme – Ločevanje, stikanje in krmiljenje –
534. točka: Naprave za prenapetostno zaščito
Low-voltage electrical installations – Part 5-53: Selection and erection of electrical
equipment – Isolation, switching and control – Clause 534: Devices for protection
against overvoltages
Installations électriques à basse tension – Partie 5-53: Choix et mise en oeuvre
des matériels électriques – Sectionnement, coupure et commande – Article 534:
Dispositifs pour la protection contre les surtensions
Errichten von Niederspannungsanlagen – Teil 5-53: Auswahl und Errichtung
elektrischer Betriebsmittel – Trennen, Schalten und Steuern – Abschnitt 534:
Überspannung-Schutzeinrichtungen (ÜSE)
Referenčna oznaka
ICS 29.130; 91.140.50 SIST HD 60364-5-534:2016 (sl)
Nadaljevanje na straneh II in III ter od 1 do 53
© 2023-03. Slovenski inštitut za standardizacijo. Razmnoževanje ali kopiranje celote ali delov tega dokumenta ni dovoljeno.

---------------------- Page: 1 ----------------------
SIST HD 60364-5-534 : 2016

NACIONALNI UVOD

Standard SIST HD 60364-5-534 (sl), Nizkonapetostne električne inštalacije – 5-53. del: Izbira in
namestitev električne opreme – Ločevanje, stikanje in krmiljenje – 534. točka: Naprave za
prenapetostno zaščito, 2016, ima status slovenskega standarda in je istoveten evropskemu standardu
HD 60364-5-534 (en), Low-voltage electrical installations – Part 5-53: Selection and erection of electrical
equipment – Isolation, switching and control – Clause 534: Devices for protection against transient
overvoltages, 2016.

Ta standard nadomešča SIST HD 60364-5-534:2008.

NACIONALNI PREDGOVOR

Evropski standard HD 60364-5-534:2016 je pripravil tehnični odbor CLC/TC 64 Električne inštalacije in
zaščita pred električnim šokom.

Slovenski standard SIST HD 60364-5-534:2016 je prevod evropskega standarda HD 60364-5-
534:2016. V primeru spora glede besedila slovenskega prevoda v tem standardu je odločilen izvirni
evropski standard v angleškem jeziku. Slovensko izdajo standarda je potrdil tehnični odbor SIST/TC ELI
Nizkonapetostne in komunikacijske električne inštalacije.

Odločitev za privzem tega standarda je aprila 2016 sprejel tehnični odbor SIST/TC ELI Nizkonapetostne
in komunikacijske električne inštalacije.

ZVEZA Z NACIONALNIMI STANDARDI

S privzemom tega evropskega standarda veljajo za omejeni namen referenčnih standardov vsi
standardi, navedeni v izvirniku, razen tistih, ki so že sprejeti v nacionalno standardizacijo:
SIST EN 60038 Standardne napetosti CENELEC
SIST HD 60364-4-41:2007 + popravek 2007 Nizkonapetostne električne inštalacije – 4-41. del:
Zaščitni ukrepi – Zaščita pred električnim udarom
SIST HD 60364-4-43:2011 Nizkonapetostne električne inštalacije – 4-43. del: Zaščitni
ukrepi – Zaščita pred nadtoki
SIST HD 60364-4-443:2016 Nizkonapetostne električne inštalacije – 4-44. del: Zaščitni
ukrepi – Zaščita pred napetostnimi in elektromagnetnimi
motnjami – 443. točka: Zaščita pred atmosferskimi in stikalnimi
prenapetostmi
SIST HD 60364-5-54 Nizkonapetostne električne inštalacije – 5-54. del: Izbira in
namestitev električne opreme – Ozemljitve in zaščitni vodniki
SIST EN 60664-1:2007 Uskladitev izolacije za opremo v okviru nizkonapetostnih
sistemov – 1. del: Načela, zahteve in preskusi
SIST EN 61643-11:2012 Nizkonapetostne naprave za zaščito pred prenapetostnimi
udari – 11. del: Naprave za zaščito pred prenapetostnimi udari
za nizkonapetostne napajalne sisteme – Zahteve in preskus
SIST-TS CLC/TS 61643-12 Nizkonapetostne naprave za zaščito pred prenapetostnimi
udari – 12. del: Naprave za zaščito pred prenapetostnimi udari
za nizkonapetostne napajalne sisteme – Izbira in načela za
uporabo
SIST EN 62305-1 Zaščita pred delovanjem strele – 1. del: Splošna načela
SIST EN 62305-2 Zaščita pred delovanjem strele – 2. del: Vodenje rizika
SIST EN 62305-4 Zaščita pred delovanjem strele – 4. del: Električni in elektronski
sistemi v zgradbah
II

---------------------- Page: 2 ----------------------
SIST HD 60364-5-534 : 2016

OSNOVA ZA IZDAJO STANDARDA

– privzem standarda HD 60364-5-534:2016

PREDHODNA IZDAJA

– SIST HD 60364-5-534:2008, Nizkonapetostne električne inštalacije – 5-53. del: Izbira in namestitev
električne opreme - Ločevanje, stikanje in krmiljenje – 534. točka: Naprave za prenapetostno
zaščito

OPOMBE

– Povsod, kjer se v besedilu standarda uporablja izraz “evropski standard“ ali »mednarodni
standard«, v SIST HD 60364-5-534:2016 to pomeni “slovenski standard”.

– Nacionalni uvod in nacionalni predgovor nista sestavni del standarda.

– Ta nacionalni dokument je istoveten HD 60364-5-534:2016 in je objavljen z dovoljenjem

CEN-CENELEC
Upravni center
Avenue Marnix 17
B-1000 Bruselj

This national document is identical with HD 60364-5-534:2016 and is published with the permission
of

CEN-CENELEC
Management Centre
Avenue Marnix 17
B-1000 Brussels





III

---------------------- Page: 3 ----------------------
SIST HD 60364-5-534 : 2016
























(prazna stran)
IV

---------------------- Page: 4 ----------------------
HARMONIZACIJSKI DOKUMENT HD 60364-5-534
HARMONIZATION DOCUMENT

DOCUMENT D'HARMONISATION
februar 2016
HARMONISIERUNGSDOKUMENT

ICS 29.130; 91.140.50 Nadomešča HD 60364-5-534:2008






Slovenska izdaja

Nizkonapetostne električne inštalacije – 5-53. del: Izbira in namestitev
električne opreme – Ločevanje, stikanje in krmiljenje – 534. točka: Naprave za
prenapetostno zaščito


Low-voltage electrical installations Installations électriques à basse Errichten von Nieders-
– Part 5-53: Selection and erection tension – Partie 5-53: Choix et pannungsanlagen – Teil 5-53:
of electrical equipment – Isolation, mise en oeuvre des matériels Auswahl und Errichtung
switching and control – Clause électriques – Sectionnement, elektrischer Betriebsmittel –
534: Devices for protection against coupure et commande – Article Trennen, Schalten und Steuern –
overvoltages (IEC 60364-5- 534: Dispositifs de protection Abschnitt 534: Überspannung-
53:2001/A2:2015, modified) contre les surtensions transitoires Schutzeinrichtungen (ÜSE)
(IEC 60364-5-53:2001/A2:2015, (IEC 60364-5-53:2001/A2:2015,
modifiée) modifiziert)




Ta harmonizacijski dokument je CENELEC sprejel 14. decembra 2015. Člani CENELEC morajo
izpolnjevati notranje predpise CEN/CENELEC, ki določajo pogoje, pod katerimi dobi ta evropski
standard status nacionalnega standarda.

Najnovejši seznami teh nacionalnih standardov in njihovi bibliografski podatki se na zahtevo lahko dobijo
pri Upravnem centru CEN-CENELEC ali kateremkoli članu CENELEC.

Ta harmonizacijski dokument obstaja v treh izvirnih izdajah (angleški, francoski, nemški).

Člani CENELEC so nacionalni elektrotehniški komiteji Avstrije, Belgije, Bolgarije, Cipra, Češke
republike, Danske, Estonije, Finske, Francije, Grčije, Hrvaške, Islandije, Irske, Italije, Latvije, Litve,
Luksemburga, Madžarske, Malte, Nekdanje jugoslovanske republike Makedonije, Nemčije,
Nizozemske, Norveške, Poljske, Portugalske, Romunije, Slovaške, Slovenije, Španije, Švedske, Švice
in Združenega kraljestva.
,







CENELEC
Evropski komite za standardizacijo v elektrotehniki
European Committee for Electrotechnical Standardisation
Europäisches Komitee für Elektrotechnische Normung
Comité Européen de Normalisation Electrotechnique
Upravni center CEN-CENELEC: Avenue Marnix 17, B - 1000 Bruselj

© 2016 CENELEC Vse pravice do izkoriščanja v kakršnikoli obliki in na kakršenkoli Ref. št. HD 60364-5-534:2016 E
način imajo nacionalni člani CENELEC.

---------------------- Page: 5 ----------------------
SIST HD 60364-5-534 : 2016
Evropski predgovor

Besedilo dokumenta 64/2031/FDIS, poznejšega standarda IEC 60364-5-53:2001/A2, ki ga je pripravil
tehnični odbor IEC/TC 64 "Električne inštalacije in zaščita pred električnim udarom", je bilo predloženo
v vzporedno glasovanje CENELEC in ga je CENELEC odobril kot HD 60364-5-53.

Osnutek dopolnila, ki obsega skupne popravke k IEC 60364-5-53:2001/A2:2015 (64/2031/FDIS), je
pripravil tehnični odbor CLC/TC 64 "Električne inštalacije in zaščita pred električnim udarom" in ga je
odobril CENELEC.

Določena sta bila naslednja datuma:

‒ zadnji datum, do katerega mora dokument dobiti status (dop) 2016-12-14
nacionalnega standarda bodisi z objavo istovetnega besedila
ali z razglasitvijo
‒ zadnji datum, do katerega je treba razveljaviti nacionalne (dow) 2018-12-14
standarde, ki so v nasprotju s HD

HD 60364-5-534:2016 nadomešča HD 60364-5-534:2008.

HD 60364-5-534:2016 vključuje naslednje pomembne tehnične spremembe glede na prejšnjo izdajo: ta
dokument obsega celotno zgradbo in tehnično revizijo standarda HD 60364-5-534:2008.
Najpomembnejša tehnična sprememba se nanaša na izbiro zahtev za napetostni zaščitni nivo.

Upoštevati je treba, da so nekateri elementi tega dokumenta lahko predmet patentnih pravic. CENELEC
[in/ali CEN] ni odgovoren za identifikacijo katerekoli ali vseh teh pravic.

Točke, podtočke, opombe, preglednice, številke in dodatki, ki so dodani tistim v IEC 60364-5-
53:2001/A2:2015, imajo predznak "Z".


2

---------------------- Page: 6 ----------------------
SIST HD 60364-5-534 : 2016

Razglasitvena objava

Besedilo mednarodnega standarda IEC 60364-5-53:2001/A2:2015 je odobril CENELEC kot
harmonizacijski dokument z dogovorjenimi splošnimi spremembami.


SPLOŠNE SPREMEMBE

530.2 Zveze s standardi

Besedilo v 530.2 se zamenja z naslednjim:

Za uporabo tega standarda so nujno potrebni, v celoti ali delno, naslednji referenčni dokumenti. Pri
datiranih sklicevanjih velja samo navedena izdaja. Pri nedatiranih sklicevanjih se uporablja zadnja izdaja
navedenega dokumenta (vključno z dopolnili).
EN 60038 Standardne napetosti CENELEC (IEC 60038)
HD 60364-4-41:2007 + corr. jul. 2007 Nizkonapetostne električne inštalacije – 4-41. del: Zaščitni ukrepi
– Zaščita pred električnim udarom om (IEC 60364-4-41:2005, mod.)
HD 60364-4-43:2010 Nizkonapetostne električne inštalacije – 4-43. del: Zaščitni ukrepi –
Zaščita pred nadtoki (IEC 60364-4-43:2008, mod. + corr. okt. 2008)
HD 60364-4-443:2016 Nizkonapetostne električne inštalacije – 4-44. del: Zaščitni ukrepi –
Zaščita pred napetostnimi in elektromagnetnimi motnjami – 443. točka:
Zaščita pred atmosferskimi in stikalnimi prenapetostmi (IEC 60364-4-
44:2007/A1:2015, mod.)
HD 60364-5-54 Nizkonapetostne električne inštalacije – 5-54. del: Izbira in namestitev
električne opreme – Ozemljitve in zaščitni vodniki (IEC 60364-5-54)
EN 60664-1:2007 Uskladitev izolacije za opremo v okviru nizkonapetostnih sistemov – 1.
del: Načela, zahteve in preskusi (IEC 60664-1:2007)
EN 61643-11:2012 Nizkonapetostne naprave za zaščito pred prenapetostnimi udari – 11.
del: Naprave za zaščito pred prenapetostnimi udari za nizkonapetostne
napajalne sisteme – Zahteve in preskus (IEC 61643-11:2011, mod.)
CLC/TS 61643-12 Nizkonapetostne naprave za zaščito pred prenapetostnimi udari – 12.
del: Naprave za zaščito pred prenapetostnimi udari za nizkonapetostne
napajalne sisteme – Izbira in načela za uporabo (IEC 61643-12)
EN 62305-1 Zaščita pred delovanjem strele – 1. del: Splošna načela (IEC 62305-1)
EN 62305-2 Zaščita pred delovanjem strele – 2. del: Vodenje rizika (IEC 62305-2)
EN 62305-4 Zaščita pred delovanjem strele – 4. del: Električni in elektronski sistemi
v zgradbah (IEC 62305-4)
IEC/TR 60664-2-1:2011 Koordinacija izolacije za opremo v nizkonapetostnih sistemih – 2-1. del:
Navodilo za uporabo – Pojasnitev uporabe v skupini IEC 60664, primeri
dimenzioniranja in dielektrično preskušanje


3

---------------------- Page: 7 ----------------------
SIST HD 60364-5-534 : 2016

530.3 Izrazi in definicije

Doda se točka 530.3 "Izrazi in definicije", kot sledi:

530.3 Izrazi in definicije

V tem dokumentu se uporabljajo naslednji izrazi in definicije:

530.3.101
sestav SPD (sestav prenapetostne zaščitne naprave)
en SPD ali niz SPD, v obeh primerih vključno z vsemi ločilniki SPD, ki jih zahteva proizvajalec SPD in
ki zagotavljajo zahtevano prenapetostno zaščito danega tipa ozemljitve omrežja

530.3.102
ločilnik SPD
ločilnik
naprava za izklop SPD ali dela SPD iz elektroenergetskega sistema

OPOMBA: Za to napravo za ločitev se ne zahteva, da ima izolacijsko sposobnost za zaščitne namene. Namenjena je
preprečitvi nastanka trajne okvare v sistemu in indikaciji odpovedi SPD. Ločilniki so lahko notranji (vgrajeni) ali
zunanji (na zahtevo proizvajalca). Imajo lahko več kot eno izklopno funkcijo, npr. nadtokovno in toplotno zaščitno
funkcijo. Te funkcije so lahko v ločenih enotah.

[VIR: IEC 61643-11:2011, 3.1.28]

530.3.103
način zaščite s prenapetostno zaščitno napravo (SPD)
predvidena pot toka med priključki, ki vključuje zaščitne komponente, npr. za medfazno zaščito, zaščito
faza proti zemlji, med fazo in nevtralnim vodnikom ter med nevtralnim vodnikom in zemljo

[VIR: IEC 61643-11:2011, 3.1.8]

530.3.104
naznačena vrednost toka po prekinitvi
Ifi
pričakovani kratkostični tok, ki ga SPD lahko prekine brez delovanja ločilnika

[VIR: IEC 61643-11:2011, 3.1.39]

530.3.105
naznačeni kratkostični tok
I
SCCR
največji pričakovani kratkostični tok iz elektroenergetskega sistema, za katerega je predviden SPD
skupaj z določenim ločilnikom

[VIR: IEC 61643-11:2011, 3.1.27]

530.3.106
napetostni zaščitni nivo
U
p
najvišja napetost, ki jo je mogoče pričakovati na sponkah SPD zaradi udarne preobremenitve z
napetostjo z določeno strmino in udarne preobremenitve z razelektritvenim tokom z določeno amplitudo
in valovno obliko

OPOMBA 1: Napetostni zaščitni nivo poda proizvajalec naprave in ga ne smejo presegati:

– izmerjena mejna napetost, določena za čelni preplaz (če je to primerno), in izmerjena mejna napetost,
določena iz merjenj preostale napetosti pri amplitudi, ki ustreza toku I oziroma I glede na preskusna
n imp
razreda II oziroma I,

4

---------------------- Page: 8 ----------------------
SIST HD 60364-5-534 : 2016

– izmerjena mejna napetost pri napetosti odprtega tokokroga (U ) generatorja kombiniranih valov, določenega
OC
za kombinirani val za preskusni razred III.

OPOMBA 2: Podatki o soodvisnosti med tipi SPD in preskusnimi razredi v skladu s standardom za proizvod so navedeni v
dodatku C.

[VIR: IEC 61643-11:2011, 3.1.14, spremenjen – spremenjena je opomba 1 in dodana opomba 2]

530.3.107
naznačena udarna napetost
UW
vrednost udarne vzdržne napetosti, ki jo proizvajalec določi napravi ali delu naprave in ki podaja
določeno vzdržno zmogljivost njene izolacije proti prehodnim prenapetostim

[VIR: IEC 60664-1:2007, 3.9.2, spremenjen – dodana je okrajšava U ]
W

530.3.108
najvišja stalna obratovalna napetost
UC
najvišja efektivna napetost, ki je lahko trajno priključena v načinu zaščite s SPD

OPOMBA: Vrednost U , ki jo obravnava ta standard, lahko preseže 1 000 V.
C

[VIR: IEC 61643-11:2011, 3.1.11]

530.3.109
nazivni razelektritveni tok za preskus razreda II
In
temenska vrednost toka skozi SPD, ki ima valovno obliko 8/20

OPOMBA: Informacije o soodvisnosti med tipi SPD in preskusnimi razredi v skladu s standardom za proizvod so navedene
v dodatku C.

[VIR: IEC 61643-11:2011, 3.1.9, spremenjen – dodana je opomba]

530.3.110
udarni razelektritveni tok za preskus razreda I
I
imp
temenska vrednost toka skozi SPD z določeno vrednostjo prenesenega naboja Q in določeno vrednostjo
energije W/R v določenem času

OPOMBA: Informacije o soodvisnosti med SPD in preskusnimi razredi v skladu s standardom za proizvod so navedene v
dodatku C.

[VIR: IEC 61643-11:2011, 3.1.10, spremenjen – dodana je opomba]

530.3.111
napetost na odprtih sponkah
U
OC
napetost na odprtih sponkah generatorja kombiniranih valov v točki, kjer je nanj priključen preskušanec

[VIR: IEC 61643-11:2011, 3.1.23]

530.3.112
dvoportna prenapetostna zaščitna naprava (SPD)
SPD, ki ima med ločenima vhodnim in izhodnim priključkom vezano posebno zaporedno impedanco

[VIR: IEC 61643-11:2011, 3.1.3]


5

---------------------- Page: 9 ----------------------
SIST HD 60364-5-534 : 2016

534 Naprave za zaščito pred prehodnimi prenapetostmi

534.1 Splošno

Zamenjata se prva dva odstavka v 534.1, kot sledi:

Točka vsebuje določila za uporabo napetostne meje, da se doseže koordinacija izolacije v primerih,
opisanih v HD 60364-4-44, EN 60664-1, EN 62305-1, EN 62305-4 in CLC/TS 61643-12.

Ta točka se osredotoča predvsem na zahteve za izbiro in namestitev SPD za zaščito pred prehodnimi
prenapetostmi, če se to zahteva v IEC 60364-4-44:2007, točka 443, skupini standardov EN 62305 ali
če je določeno drugače.

Zamenjajo se naslov točke 534.4.1 in odstavki pred OPOMBO 3, razen OPOMBE 1, kakor sledi

534.4.1 Lokacija in tip SPD

SPD mora biti nameščen čim bližje je mogoče začetku inštalacije. Za zaščito pred delovanjem strele in
stikalnimi prenapetostmi je treba uporabiti SPD tipa 2.

Če je zgradba opremljena z zunanjim sistemom zaščite pred delovanjem strele ali je zaščita pred učinki
neposrednega udara strele določena drugače, se uporabijo SPD tipa 1.

Kadar zgradba ni opremljena z zunanjim sistemom zaščite pred delovanjem strele in kadar je treba
upoštevati možnost neposrednega udara strele v nadzemne vode med zadnjim drogom in vhodom v
inštalacijo, se lahko izberejo SPD tipa 1 na začetku inštalacije ali blizu njega v skladu z dodatkom B.

Na podlagi standarda za proizvod se uporabijo naslednje oznake proizvodov:

– za tip 1 SPD: "tip 1" in/ali "T1" (T1 v okvirju),

– za tip 2 SPD: "tip 2" in/ali "T2" (T2 v okvirju),

– za tip 3 SPD: "tip 3" in/ali "T3" (T3 v okvirju).

OPOMBA 2: Informacije o soodvisnosti med tipi SPD in preskusnimi razredi v skladu s standardom za proizvod so podane v
dodatku C.

Za zadovoljivo zaščito inštalacije v skladu s 534.4.4.1 bodo morda potrebni dodatni SPD tipa 2 ali tipa
3, ki jih je treba namestiti za njimi v fiksni električni inštalaciji, npr. na podrejenih razdelilnikih ali na
vtičnicah. Ti SPD ne smejo biti uporabljeni brez SPD, nameščenih na začetku inštalacije, in morajo biti
usklajeni s SPD, vgrajenimi pred njimi (glej 534.4.4.5).

Če tip 1 SPD ne more zagotavljati zaščite v skladu s 534.4.4.2, mu je treba dodati usklajeni SPD tipa 2
ali tipa 3, da se zagotovi zahtevani napetostni zaščitni nivo.

Tik ob občutljivi opremi bodo morda potrebni SPD tipa 2 ali tipa 3, da bo oprema zadovoljivo zaščitena
v skladu s 534.4.4.2, ki pa morajo biti usklajeni z višje umeščenimi SPD.

Zamenjata se slika 534.1 in njen naslov, kot sledi:

6

---------------------- Page: 10 ----------------------
SIST HD 60364-5-534 : 2016

Na začetku inštalacije ali blizu njega,
npr. glavni razdelilnik


SPD tipa 1 in/ali SPD tipa 2 SPD tipa 2 ali SPD tipa 3 SPD tipa 2 ali SPD tip 3

Slika 534.1: Primer namestitve prenapetostnih zaščitnih naprav SPD tipa 1, tipa 2 in tipa 3

534.4.4.2 Izbira napetostnega zaščitnega nivoja (Up) kot funkcije naznačenega napetostnega
udara opreme (UW)

Zamenja se uvodni odstavek za štiri alineje, kot sledi:

Tega priporočila ni treba upoštevati, če ne pride do nobenega od naštetih primerov:

Zamenja se preglednica 534.1, kot sledi:

Preglednica 534.1: Zahtevana naznačena udarna napetost opreme (UW)

Nazivna napetost Nazivna napetost Napetostni vodnik Zahtevana naznačena udarna
a a b
napajalnega sistema napajalnega sistema proti nevtralni točki iz napetost (UW) opreme
nazivnih izmeničnih
Trifazni sistemi Enofazni sistemi
Prenapetostna Prenapetostna
ali enosmernih
kategorija II kategorija I
napetosti do vključno
(oprema z (oprema z
normalno znižano
naznačeno naznačeno
udarno udarno
napetostjo napetostjo
V V kV kV
 50 0,5 0,33
 100 0,8 0,5
120/240 150 1,5 0,8
230/400 300 2,5 1,5
277/480
400/690 600 4 2,5
1 000 1 000 6 4
c c
 1 500 enosmerno 8 6
a
V skladu z EN 60038.
b
Naznačena udarna napetost velja za napetost med vodnikom pod napetostjo in PE.
c
Priporočene vrednosti na podlagi IEC/TR 60664–2-1:2011, dodatek D.
7

---------------------- Page: 11 ----------------------
SIST HD 60364-5-534 : 2016

Zamenja se odstavek po preglednici 534.1, kot sledi:

Zaradi izogibanja nepravilnemu delovanju opreme bodo morda potrebni dodatni SPD med vodniki pod
napetostjo. Na podlagi zahtev za odpornost in razpoložljivost opreme je treba oceniti ustrezni napetostni
zaščitni nivo (glej IEC 61643-12).

534.4.4.4 Izbira SPD glede na nazivni razelektritveni tok (In) in udarni razelektritveni tok (Iimp)

Zamenjata se naslov točke 534.4.4.4.1 in njen prvi odstavek, kot sledi:

534.4.4.4.1 SPD tipa 2

Kjer je zahtevano, da so SPD tipa 2 na začetku inštalacije ali blizu njega, mora biti njihov nazivni
razelektritveni tok najmanj enak toku, navedenemu v preglednici 534.3.

Zamenjajo se naslov točke 534.4.4.4.2 in njena prva dva odstavka, kakor sledi:

534.4.4.4.2 SPD tipa 1

Kjer je zahtevano, da so SPD tipa 1 na začetku inštalacije ali blizu njega, velja eden od naslednjih
primerov:

a) če ni bila izvedena analiza tveganja po IEC 62305-2, udarni razelektritveni tok (I ) ne sme biti
imp
manjši od toka, navedenega v preglednici 534.4,

Zamenja se alineja b), kakor sledi:

b) če je bila izvedena analiza tveganja po IEC 62305-2, se vrednost udarnega razelektritvenega toka
(I ) določi v skladu s skupino standardov IEC 62305.
imp

534.4.4.5 Usklajevanje dveh ali več SPD

Zamenja se odstavek v 534.4.5, kakor sledi:

Zagotoviti je treba usklajenost SPD v inštalaciji. Navodila proizvajalca SPD, kako doseči usklajenost
med SPD, morajo upoštevati referenčni dokument CLC/TS 61643-12.

534.4.4.6 Izbira SPD glede na naznačeni kratkostični tok I
SCCR

Zamenja se drugi odstavek v 534.4.4.6, kakor sledi:

Ta zahteva ne velja za SPD, priključene med nevtralnim in PE-vodnikom v omrežjih TN ali TT, za katere
je to že zajeto v standardu za proizvod IEC 61643-11.

534.4.4.7 Izbira SPD glede na naznačeno vrednost toka po prekinitvi

Zamenja se drugi odstavek v 534.4.4.7, kakor sledi:

Ta zahteva ne velja za SPD, priključene med nevtralnim in PE-vodnikom v omrežjih TN ali TT, za katere
je to že zajeto v standardu za proizvod IEC 61643-11.

534.4.5.3 Selektivnost med nadtokovnimi zaščitnimi napravami

Zamenja se prvi odstavek v 534.4.5.3, kakor sledi:

Kjer je to zahtevano, je treba skladno z inštalacijskimi pogoji na mestu inštalacije SPD in informacijami,
ki jih zagotovi proizvajalec, upoštevati selektivnost med nadtokovnimi zaščitnimi napravami (glej IEC
60364-5-53:2014, točka 536).

8

---------------------- Page: 12 ----------------------
SIST HD 60364-5-534 : 2016

534.4.6 Okvarna zaščita

Zamenja se prvi odstavek v 534.4.6, kakor sledi:

Okvarna zaščita, kot je opredeljena v IEC 60464-4-41, mora v ščitenih inštalacijah ostati učinkovita tudi
v primeru odpovedi SPD.

Zamenja se alineja b), kakor sledi:

b) namestitev SPD pred glavnim RCD. Zaradi možnosti odpovedi SPD, povezanega med nevtralnim
in PE-vodnikom, morajo biti izpolnjeni pogoji iz HD 60364-4-41:2007, točka 411.4.1, in SPD morajo
biti nameščeni v skladu s priključnim tipom CT2.

534.4.7 Namestitev SPD v povezavi z RCD

Zamenjata se OPOMBA 1 in zadnji odstavek v 534.4.7, kakor sledi:

OPOMBA 1: RCD tipa S v skladu z IEC 61008-1 in IEC 61009-1 izpolnjujejo to zahtevo.

Namestitev SPD tipa 1 nižje od namestitve RCD ni priporočljiva.

534.4.10 Priključni vodniki SPD

Zamenjata se dve alineji za prvim odstavkom v 534.4.10, kakor sledi:

2
‒ 6 mm iz bakra ali enakovrednega materiala, za SPD tipa 2 na začetku inštalacije ali blizu njega,

2
‒ 16 mm iz bakra ali enakovrednega materiala, za SPD tipa 1 na začetku inštalacije ali blizu njega.

Zamenjata se zadnji dve alineji, kakor sledi:

2
‒ 2,5 mm iz bakra ali enakovrednega materiala za SPD tipa 2 na začetku inštalacije ali blizu njega,

2
‒ 6 mm iz bakra ali enakovrednega materiala, za SPD tipa 1 na začetku inštalacije ali blizu njega.


9

---------------------- Page: 13 ----------------------
SIST HD 60364-5-534 : 2016

Dodatek B
(informativni)




Inštalacije, ki jih napajajo nadzemni vodi


Zamenjata se prva dva odstavka, kakor sledi:

Kjer je zahtevana prenapetostna zaščita v skladu s HD 60364-4-44:2016, točka 443, in kjer nadzemni
vodi vstopajo v stavbo ter kjer je treba upoštevati možnost neposrednega udara strele v drog nadzemnih
vodov v bližini stavbe, je treba SPD na začetku inštalacije izbrati v skladu s preglednico B.1.

Več informacij je na voljo v skupini standardov IEC 62305.


10

---------------------- Page: 14 ----------------------
SIST HD 60364-5-534 : 2016

Zamenja se dodatek C z naslednjim novim dodatkom C:

Dodatek C
(informativni)




Soodvisnost med tipi SPD in preskusnimi razredi v skladu s standardom za
proizvod EN 61643-11

Preglednica C.1: SPD tipa 1, tipa 2 in tipa 3 ter ustrezni preskusni razredi I, II in III

Tip naprave SPD Preskusni razred Referenčni
parameter
Tip 1 Preskusni razred I I
imp
Tip 2 Preskusni razred II I
n
Tip 3 Preskusni razred III Uoc


11

---------------------- Page: 15 ----------------------
SIST HD 60364-5-534 : 2016

Dodata se dodatka ZA in ZB, kakor sledi:

Dodatek ZA
(informativni)




Posebni nacionalni pogoji

Posebni nacionalni pogoji: nacionalne karakteristike ali prakse, ki jih ni mogoče spremeniti niti po
dolgem obdobju, npr. podnebne razmere, pogoji za električne ozemljitve.
OPOMBA: Če to vpliva na harmonizacijo, je to del evropskega standarda.
Za države, na katere se relevantni posebni nacionalni pogoji nanašajo, so te določbe normativne, za
druge države pa so informativne.

Točka Posebni nacionalni pogoj
534.4.1 Francija
Naslednja vsebina:
Kadar zgradba ni opremljena z zunanjim sistemom zaščite pred delovanjem strele in
kadar je treba upoštevati možnost neposrednega udara strele v nadzemne vode med
zadnjim drogom in vhodom v inštalacijo, se lahko izberejo SPD tipa 1 na začetku
inštalacije ali blizu njega v skladu z dodatkom B.

v Franciji ne velja.
534.4.1 Nemčija
V Nemčiji morajo biti tam, kjer je inštalacija zgradb izvedena z nadzemnimi vodi, SPD
tipa 1 v skladu z dodatkom B.
Nemčija
534.4.3
V Nemčiji je edina zahteva, ki jo je treba upoštevati, omejitev dolžine do največ 0,5 m.
Norveška
534.4.4.2
Na Norveškem mora biti tam, kjer je inštalacija galvansko povezana na IT-javno
omrežje, najnižja zahtevana U za SPD na začetku inštalacije najmanj 350 V.
c
534.4.4.4.1 Nemčija
Dodata se naslednje besedilo in dodatna preglednica:
Nazivni razelektritveni tok SPD tipa 2, vgrajenih na začetku inštalacij ali blizu njega, s
povečanim varnostnim nivojem, ne sme biti manjši od toka, navedenega v spodnji
preglednici 534.3.




12

---------------------- Page: 16 ----------------------
SIST HD 60364-5-534 : 2016

Točka Posebni nacionalni pogoj
Preglednica 534.3: Nazivni razelektritveni tok (I ) v kA, odvisen od napajalnega
n
sistema in vrste povezave za inštalacije s povečanim varnostnim nivojem
Povezava Napajalni sistem
Enofazni Trifazni
Povezava Povezava Povezava Povezava
tipa 1 tipa 2 tipa 1 tipa 2
L – N 10 10
L – PE 10 10
N – PE 10 20 10 40


534.4.4.4.2 Nemčija
V Nemčiji morajo biti tam, kjer je napajanje inštalacije zgradbe izvedeno z nadzemnimi
vodi, SPD tipa 1 v skladu z dodatkom B.
534.4.4.5 Norveška
Na Norveškem mora imeti tam, kjer je inštalacija galvansko povezana na javno IT-
omrežje in kjer je drugi SPD nameščen za SPD, ki je v glavnem razdelilniku, drugi
SPD najvišjo stalno obratovalno napetost U najmanj 440 V med linijskimi vodniki in
c
PE, in najmanj 275 V med linijskimi vodniki.

534.4.6 Nemčija
Zaradi izogibanja nepotrebnim odklopom ali lepljenju/mehanskim poškodbam
kontaktov RCD se je treba izogibati pretoku velikih ali delnih udarnih tokov strele. Zato
naj bodo SPD preskusnega razreda I ali II nameščeni na linijski strani RCD. Če je
mogoče pričakovati prenapetostni udar na bremenski strani RCD, npr. zaradi zunaj
vgrajene opreme, ki ni zaščitena z LPS (sistemom zaščite pred delovanjem strele), naj
se na bremenski strani RCD namesti SPD preskusnega razreda I ali II.
534.4.6 Norveška
Na Norveškem je treba tam, kjer je inštalacija galvansko povezana z javnim IT-
omrežjem ali TT-distribucijskim omrežjem brez zagotovljenega ločenega vodnika PE
(npr. napajanje inštalacije iz nadzemnih vodov), zaščito pred požarom, nastalim zaradi
odpovedi SPD, zagotoviti z:
– umestitvijo SPD v ločena ohišja iz negorljivih materialov ali
– zaščito SPD s časovno zakasnjenim RCD (tip S ali podobno) s preostalim
naznačenim tokom, ki ne presega 300 mA, ali
z uporabo SPD, zasnovanega tako, da kar najbolj zmanjša tveganje poškodbe in
požara zaradi zemeljskega stika v visokonapetostnem distribucijskem omrežju.
534.4.7 Nemčija
Zagotovi naj se, da tokovi strele ali veliki udarni toki ne bodo tekli skozi RCD. Zato
SPD preskusnega razreda I ni dopustno nameščati za RCD, razen če je mogoče
pričakovati delne tokove strele tudi na bremenski strani RCD.

13

---------------------- Page: 17 ----------------------
SIST HD 60364-5-534 : 2016

Točka Posebni nacionalni pogoj
Namestitev SPD preskusnega razreda II za RCD je dopustna le, če je pred RCD že
nameščen SPD preskusnega razreda II ali če se pričakujejo udarni toki na bremenski
strani RCD.
Pri udarnih tokih, večjih od 3 kA 8/20, se RCD lahko sproži in povzroči prekinitev
napajanja.
Dodatek A Nemčija
V Nemčiji so zahtevani ozemljitveni priključki 5a in 5
...

Questions, Comments and Discussion