SIST EN 60730-2-5:2002
(Main)Automatic electrical controls for household and similar use -- Part 2-5: Particular requirements for automatic electrical burner control systems
Automatic electrical controls for household and similar use -- Part 2-5: Particular requirements for automatic electrical burner control systems
Applies to automatic electrical burner control systems for the automatic control of burners for oil, gas, coal or other combustibles for household and similar use including heating, air conditioning and similar use. To be used in conjunction with EN 60730-1 (second edition).
Automatische elektrische Regel- und Steuergeräte für den Hausgebrauch und ähnliche Anwendungen -- Teil 2-5: Besondere Anforderungen an automatische elektrische Brenner-Steuerungs- und Überwachungssysteme
Dispositifs de commande électrique automatiques à usage domestique et analogue -- Partie 2-5: Règles particulières pour les systèmes de commande électrique automatiques des brûleurs
S'applique aux systèmes de commande électrique automatiques de brûleurs pour la commande automatique de brûleurs pour fioul, gaz, charbon ou autres combustibles à usage domestique et analogue, y compris le chauffage, la climatisation et usages analogues. Cette deuxième édition doit être utilisée conjointement avec la EN 60730-1 (deuxième édition).
Automatic electrical controls for household and similar use -- Part 2-5: Particular requirements for automatic electrical burner control systems
Uporablja se za avtomatske električne krmilne sisteme (regulatorje) gorilnikov, za avtomatsko krmiljenje gorilnikov za olje, plin, premog ali druga goriva za uporabo v gospodinjstvu in za podobno uporabo, vključno z ogrevanjem, klimatizacijo in podobno uporabo. Ta del se uporablja za celotne krmilne sisteme (regulatorje) gorilnikov in za posamezne enote za programiranje. Uporablja se tudi za posamezne elektronske visokonapetostne vire vžiga in za posamezne plamenske javljalnike.
General Information
Relations
Standards Content (Sample)
SLOVENSKI STANDARD
SIST EN 60730-2-5:2002
01-december-2002
1DGRPHãþD
SIST EN 60730-2-5:1996
SIST EN 60730-2-5:1996/A1:1997
SIST EN 60730-2-5:1996/A2:1999
Automatic electrical controls for household and similar use -- Part 2-5: Particular
requirements for automatic electrical burner control systems
Automatic electrical controls for household and similar use -- Part 2-5: Particular
requirements for automatic electrical burner control systems
Automatische elektrische Regel- und Steuergeräte für den Hausgebrauch und ähnliche
Anwendungen -- Teil 2-5: Besondere Anforderungen an automatische elektrische
Brenner-Steuerungs- und Überwachungssysteme
Dispositifs de commande électrique automatiques à usage domestique et analogue --
Partie 2-5: Règles particulières pour les systèmes de commande électrique
automatiques des brûleurs
Ta slovenski standard je istoveten z: EN 60730-2-5:2002
ICS:
97.120 Avtomatske krmilne naprave Automatic controls for
za dom household use
SIST EN 60730-2-5:2002 en
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
---------------------- Page: 1 ----------------------
SIST EN 60730-2-5:2002
---------------------- Page: 2 ----------------------
SIST EN 60730-2-5:2002
EUROPEAN STANDARD EN 60730-2-5
NORME EUROPÉENNE
EUROPÄISCHE NORM May 2002
ICS 97.120 Supersedes EN 60730-2-5:1995 + A1:1996 + A2:1998
English version
Automatic electrical controls for household and similar use
Part 2-5: Particular requirements for automatic
electrical burner control systems
(IEC 60730-2-5:2000, modified)
Dispositifs de commande électrique Automatische elektrische Regel- und
automatiques à usage domestique Steuergeräte für den Hausgebrauch
et analogue und ähnliche Anwendungen
Partie 2-5: Règles particulières pour Teil 2-5: Besondere Anforderungen
les systèmes de commande électrique an automatische elektrische Brenner-
automatiques des brûleurs Steuerungs- und Überwachungssysteme
(CEI 60730-2-5:2000, modifiée) (IEC 60730-2-5:2000, modifiziert)
This European Standard was approved by CENELEC on 2001-12-04. CENELEC members are bound to
comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this
European Standard the status of a national standard without any alteration.
Up-to-date lists and bibliographical references concerning such national standards may be obtained on
application to the Central Secretariat or to any CENELEC member.
This European Standard exists in three official versions (English, French, German). A version in any
other language made by translation under the responsibility of a CENELEC member into its own
language and notified to the Central Secretariat has the same status as the official versions.
CENELEC members are the national electrotechnical committees of Austria, Belgium, Czech Republic,
Denmark, Finland, France, Germany, Greece, Iceland, Ireland, Italy, Luxembourg, Malta, Netherlands,
Norway, Portugal, Spain, Sweden, Switzerland and United Kingdom.
CENELEC
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung
Central Secretariat: rue de Stassart 35, B - 1050 Brussels
© 2002 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members.
Ref. No. EN 60730-2-5:2002 E
---------------------- Page: 3 ----------------------
SIST EN 60730-2-5:2002
EN 60730-2-5:2002 - 2 -
Foreword
The text of the International Standard IEC 60730-2-5:2000, prepared by IEC TC 72, Automatic controls
for household use, together with the common modifications prepared by the Technical Committee
CENELEC TC 72, Automatic controls for household use, was submitted to the formal vote and was
approved by CENELEC as EN 60730-2-5 on 2001-12-04.
This European Standard supersedes EN 60730-2-5:1995 + corrigendum July 1997 + A1:1996 +
A1:1996/corrigendum July 1997 + A2:1998 + A2:1998/corrigendum January 1998.
The following dates were fixed:
- latest date by which the EN has to be implemented
at national level by publication of an identical
national standard or by endorsement dop 2002-12-01
- latest date by which the national standards conflicting
with the EN have to be withdrawn dow 2008-12-01
This Part 2-5 is to be used in conjunction with EN 60730-1:1995, Automatic electrical controls for
household and similar use - Part 1: General requirements, and its amendments. Consideration may be
given to future editions of EN 60730-1.
This Part 2-5 supplements or modifies the corresponding clauses of EN 60730-1 so as to convert it into
the European Standard: Particular requirements for automatic electrical burner control systems.
Where a particular clause or subclause of Part 1 is not mentioned in this Part 2-5, that clause or
subclause applies as far as is reasonable. Where this Part 2-5 states “addition”, “modification” or
“replacement”, the relevant text of Part 1 is to be adapted accordingly.
Where reference is made to other international or harmonized standards, the edition of that standard
quoted in annex ZA (normative) is applicable.
There are no special national conditions (snc) causing a deviation from this European Standard other
than those listed in annex ZB of EN 60730-1.
National deviations from this European Standard are listed in annex ZC (informative) and are in addition
to those in EN 60730-1:1995.
In this standard:
1) The following print types are used:
- Requirements proper: in roman type;
- Test specifications: in italic type;
- Explanatory matter: in small roman type.
2) Subclauses, notes, tables and figures which are additional to those in Part 1 are numbered starting
from 101, additional annexes are lettered AA, BB, etc.
Annexes designated "normative" are part of the body of the standard.
Annexes designated "informative" are given for information only.
In this standard, annexes H, AA and ZA are normative and annexes BB and ZC informative.
Annexes ZA and ZC have been added by CENELEC.
__________
---------------------- Page: 4 ----------------------
SIST EN 60730-2-5:2002
- 3 - EN 60730-2-5:2002
Endorsement notice
The text of the International Standard IEC 60730-2-5:2000 was approved by CENELEC as a European
Standard with agreed common modifications as given below.
COMMON MODIFICATIONS
Foreword Delete
6 Classification
6.11 Replace the text of the addition by the following:
The minimum value is 250 000 automatic cycles.
Replace “6.11.4 to 6.11.12 Not applicable” by “6.11.1 to 6.11.12 Not applicable”.
11 Constructional requirements
11.3.105 Delete the ‘in some countries’ clauses following 11.3.105.6.
15 Manufacturing deviation and drift
15.7 Delete the ‘in some countries’ note.
17 Endurance
17.16.102.1a) Delete the ‘in some countries’ note.
Annexes
Annex H
H.26.9 Delete the ‘in some countries’ note.
H.26.10 Replace with ‘H 26.10 Void’.
H.26.11 Delete the ‘in some countries’ note.
H.27.1.3a) Delete the note.
H.26.12.5 Replace the table by:
Frequency Severity level
12
Under consideration
9 kHz to � 27 MHz
� 27 MHz to � 500 MHz 3 V/m 10 V/m
Under consideration
� 500 MHz to � 1 GHz
Annex J
J.20 Delete
---------------------- Page: 5 ----------------------
SIST EN 60730-2-5:2002
EN 60730-2-5:2002 - 4 -
Annex ZA
(normative)
Normative references to international publications
with their corresponding European publications
Additions to annex ZA of EN 60730-1:1995
Add under IEC publications:
Publication Year Title EN/HD Year
IEC 60068-2-6 1995 Environmental testing – EN 60068-2-6 1995
+ corr. March 1995 Part 2: Tests – Test Fc: Vibration (sinusoidal)
IEC 60384-16 1982 Fixed capacitors for use in electronic equipment –
Part 16: Sectional specification: Fixed metallized
polypropylene film dielectric d.c. capacitors
IEC 60989 1991 Separating transformers, autotransformers,
variable transformers and reactors
_____________
---------------------- Page: 6 ----------------------
SIST EN 60730-2-5:2002
- 5 - EN 60730-2-5:2002
Annex ZB
(normative)
Special national conditions
There are no special conditions (snc) causing a deviation from this European Standard other than those
listed in annex ZB to EN 60730-1.
_____________
Annex ZC
(informative)
A-deviations
Addition:
Clause Deviation
Annex H Austria: Bundesgesetzblatt 19. Verordnung: Luftreinhalteverordnung 1989 (LVR-K 1989,
air clean keeping decree for vessel equipment), last valid modification Nov. 4, 1997 by
324. Verordnung: Änderung der Luftreinhalteverordnung für Kesselanlagen 1989
(modification of LVR-K 1989, air clean keeping decree for vessel equipment):
§ 8(1) Werden Dampfkesselanlagen mit Brennern ausgerüstet, die in den
Anwendungsbereich nachstehender ÖNORMen fallen, so sind diese ÖNORMen
verbindlich anzuwenden:
(Whenever steam boilers are equipped with burners concerned by the following
standards, these standards have to be applied:)
- ÖNORM EN 267/1991: Atomizing oil burners of monobloc type-Testing;
- ÖNORM M 7540-1/1994: Atomizing oil burners of monobloc type for the heating fuels
"fuel oil light", "fuel oil medium" and "fuel oil heavy" - Terminology, requirements,
testing, marking of conformty;
- ÖNORM M 7445/1984: Forced-air gasburners;
- ÖNORM M 7445/1990: Fan-assisted gas burners with low NOx-emission; nitrogen
oxide measurement."
_____________
---------------------- Page: 7 ----------------------
SIST EN 60730-2-5:2002
---------------------- Page: 8 ----------------------
SIST EN 60730-2-5:2002
NORME CEI
INTERNATIONALE IEC
60730-2-5
INTERNATIONAL
Troisième édition
STANDARD
Third edition
2000-04
Dispositifs de commande électrique automatiques
à usage domestique et analogue –
Partie 2-5:
Règles particulières pour les systèmes
de commande électrique automatiques
des brûleurs
Automatic electrical controls for household
and similar use –
Part 2-5:
Particular requirements for automatic electrical
burner control systems
IEC 2000 Droits de reproduction réservés Copyright - all rights reserved
Aucune partie de cette publication ne peut être reproduite ni No part of this publication may be reproduced or utilized in
utilisée sous quelque forme que ce soit et par aucun procédé, any form or by any means, electronic or mechanical,
électronique ou mécanique, y compris la photocopie et les including photocopying and microfilm, without permission in
microfilms, sans l'accord écrit de l'éditeur. writing from the publisher.
International Electrotechnical Commission 3, rue de Varembé Geneva, Switzerland
Telefax: +41 22 919 0300 e-mail: inmail@iec.ch IEC web site http://www.iec.ch
CODE PRIX
Commission Electrotechnique Internationale
X
PRICE CODE
International Electrotechnical Commission
Pour prix, voir catalogue en vigueur
For price, see current catalogue
---------------------- Page: 9 ----------------------
SIST EN 60730-2-5:2002
60730-2-5 IEC:2000 – 3 –
CONTENTS
Page
FOREWORD . 5
Clause
1 Scope and normative references . 9
2 Definitions. 13
3 General requirements. 25
4 General notes on tests . 25
5 Rating . 27
6 Classification . 27
7 Information. 31
8 Protection against electric shock . 37
9 Provision for protective earthing . 37
10 Terminals and terminations . 39
11 Constructional requirements. 39
12 Moisture and dust resistance. 51
13 Electric strength and insulation resistance . 51
14 Heating . 53
15 Manufacturing deviation and drift. 55
16 Environmental stress. 59
17 Endurance .59
18 Mechanical strength . 65
19 Threaded parts and connections. 65
20 Creepage distances, clearances and distances through insulation . 67
21 Resistance to heat, fire and tracking. 67
22 Resistance to corrosion. 67
23 Radio interference suppression . 67
24 Components. 67
25 Normal operation. 67
26 Operation with mains-borne perturbations, magnetic, and electromagnetic disturbances . 67
27 Abnormal operation . 67
28 Guidance on the use of electronic disconnection. 67
Annex H (normative) Requirements for electronics. 69
Annex J (normative) Requirements for controls using thermistors . 91
Annex AA (normative) Failure modes of electrical/electronic components. 93
Annex BB (informative) Functional characteristics of burner control systems
to be specified by the relevant appliance standards, as applicable. 97
Figure 101. . 37
Table 7.2. . 33
Table H.101 – Criteria for compliance with voltage dip tests in each operating condition. 75
Table H.102 – Criteria for compliance with voltage interruption tests in each
operating condition . . 75
---------------------- Page: 10 ----------------------
SIST EN 60730-2-5:2002
60730-2-5 IEC:2000 – 5 –
INTERNATIONAL ELECTROTECHNICAL COMMISSION
____________
AUTOMATIC ELECTRICAL CONTROLS FOR HOUSEHOLD
AND SIMILAR USE –
Part 2-5: Particular requirements for automatic electrical
burner control systems
FOREWORD
1) The IEC (International Electrotechnical Commission) is a worldwide organization for standardization comprising
all national electrotechnical committees (IEC National Committees). The object of the IEC is to promote
international co-operation on all questions concerning standardization in the electrical and electronic fields. To
this end and in addition to other activities, the IEC publishes International Standards. Their preparation is
entrusted to technical committees; any IEC National Committee interested in the subject dealt with may
participate in this preparatory work. International, governmental and non-governmental organizations liaising
with the IEC also participate in this preparation. The IEC collaborates closely with the International Organization
for Standardization (ISO) in accordance with conditions determined by agreement between the two
organizations.
2) The formal decisions or agreements of the IEC on technical matters express, as nearly as possible, an
international consensus of opinion on the relevant subjects since each technical committee has representation
from all interested National Committees.
3) The documents produced have the form of recommendations for international use and are published in the form
of standards, technical specifications, technical reports or guides and they are accepted by the National
Committees in that sense.
4) In order to promote international unification, IEC National Committees undertake to apply IEC International
Standards transparently to the maximum extent possible in their national and regional standards. Any
divergence between the IEC Standard and the corresponding national or regional standard shall be clearly
indicated in the latter.
5) The IEC provides no marking procedure to indicate its approval and cannot be rendered responsible for any
equipment declared to be in conformity with one of its standards.
6) Attention is drawn to the possibility that some of the elements of this International Standard may be the subject
of patent rights. The IEC shall not be held responsible for identifying any or all such patent rights.
International Standard IEC 60730-2-5 has been prepared by IEC technical committee 72:
Automatic controls for household use.
This third edition cancels and replaces the second edition published in 1993, amendment 1
(1996) and amendment 2 (1997) and constitutes a technical revision.
The text of this standard is based on the second edition, amendments 1 and 2 and the
following documents:
FDIS Report on voting
72/430/FDIS 72/447/RVD
Full information on the voting for the approval of this standard can be found in the report on
voting indicated in the above table.
This publication has been drafted in accordance with the ISO/IEC Directives, Part 3.
---------------------- Page: 11 ----------------------
SIST EN 60730-2-5:2002
60730-2-5 IEC:2000 – 7 –
This part 2-5 is intended to be used in conjunction with IEC 60730-1. It was established on the
basis of the second edition (1993) of IEC 60730-1 and its amendments 1 (1994) and 2 (1997).
Consideration may be given to future editions of, or amendments to, IEC 60730-1.
This part 2-5 supplements or modifies the corresponding clauses in IEC 60730-1 so as to
convert that publication into the IEC standard: Safety requirements for automatic electrical
burner control systems.
Where this part 2-5 states "addition", "modification", or "replacement", the relevant
requirement, test specification or explanatory matter in part 1 should be adapted accordingly.
Where no change is necessary, this part 2-5 indicates that the relevant clause or subclause
applies.
In the development of a fully international standard, it has been necessary to take into
consideration the differing requirements resulting from practical experience in various parts of
the world and to recognize the variation in national electrical systems and wiring rules.
The "in some countries" notes regarding differing national practice are contained in the
following subclauses:
–6.11
– 15.7
– 17.16.102.1
– H.26.9
– H.26.10
– H.26.11
In this publication:
1) The following print types are used:
– Requirements proper: in roman type;
– Test specifications: in italic type;
– Explanatory matter; in small roman type.
2) Subclauses, notes, tables and figures which are additional to those in part 1 are numbered
starting from 101, additional annexes are lettered AA, BB, etc.
The committee has decided that the contents of this publication will remain unchanged until
2002-04. At this date, the publication will be:
• reconfirmed;
• withdrawn;
• replaced by a revised edition, or
• amended.
---------------------- Page: 12 ----------------------
SIST EN 60730-2-5:2002
60730-2-5 IEC:2000 – 9 –
AUTOMATIC ELECTRICAL CONTROLS FOR HOUSEHOLD
AND SIMILAR USE –
Part 2-5: Particular requirements for automatic electrical
burner control systems
1 Scope and normative references
This clause of part 1 is applicable except as follows:
1.1 Replacement:
This part of IEC 60730 applies to automatic electrical burner control systems for the automatic
control of burners for oil, gas, coal or other combustibles for household and similar use
including heating, air conditioning and similar use.
This part 2-5 is applicable to a complete burner control system and to a separate programming
unit. This part 2-5 is also applicable to a separate electronic high-voltage ignition source and to
a separate flame detector.
Separate ignition devices (electrodes, pilot burners, etc.) are not covered by this part 2-5 unless they are submitted
as part of a burner control system.
Requirements for separate ignition transformers are contained in IEC 60989.
Throughout this part 2-5, where it can be used unambiguously, the word "system" means
"burner control system" and "systems" means "burner control systems".
Systems utilizing thermoelectric flame supervision are not covered by this part 2-5.
1.1.1 This part 2-5 applies to the inherent safety, to the manufacturer's declared operating
values, operating times and operating sequences where such are associated with burner safety
and to the testing of automatic electrical burner control systems used in, on, or in association
with, burners.
Requirements for specific operating values, operating times and operating sequences are given in the standards for
appliances and equipment.
Systems for equipment not intended for normal household use, but which nevertheless may be
used by the public, such as equipment intended to be used by laymen in shops, in light industry
and on farms, are within the scope of this part 2-5.
This part 2-5 applies to systems using NTC or PTC thermistors, additional requirements for
which are contained in annex J.
---------------------- Page: 13 ----------------------
SIST EN 60730-2-5:2002
60730-2-5 IEC:2000 – 11 –
This part 2-5 does not apply to systems designed exclusively for industrial applications.
1.1.2 This part 2-5 applies to manual controls when such are electrically and/or mechanically
integral with automatic controls.
Requirements for manual switches not forming part of an automatic control are contained in IEC 61058-1.
Throughout this part 2-5, the word "equipment" means "appliance and equipment".
1.2 Replacement:
This part 2-5 applies to systems with a rated voltage not exceeding 660 V and with a rated
current not exceeding 63 A.
1.3 Replacement:
This part 2-5 does not take into account the response value of an automatic action of a control,
if such a response value is dependent upon the method of mounting the control in the
equipment. Where a response value is of significant purpose for the protection of the user, or
surroundings, the value defined in the appropriate household equipment standard or as
determined by the manufacturer applies.
This part 2-5 includes systems responsive to flame properties.
1.4 Replacement:
This part 2-5 applies also to systems incorporating electronic devices, requirements for which
are contained in annex H.
1.5 Normative references:
This clause of part 1 is applicable except as follows:
Addition:
IEC 60068-2-6:1995, Environmental testing – Part 2: Tests – Test Fc: Vibration (sinusoidal)
IEC 60384-16:1982, Fixed capacitors for use in electronic equipment – Part 16: Sectional
specification: Fixed metallized polypropylene film dielectric d.c. capacitors
IEC 60989:1991, Separating transformers, autotransformers, variable transformers and
reactors
---------------------- Page: 14 ----------------------
SIST EN 60730-2-5:2002
60730-2-5 IEC:2000 – 13 –
2 Definitions
This clause of part 1 is applicable except as follows:
2.2 Definitions of types of control according to purpose
Additional definitions:
2.2.101
burner control system
system which monitors the operation of fuel burners. It includes a programming unit, a flame
detector and may include an ignition source and/or ignition device
The various functions of the system may be in one or more housings.
2.2.102
flame detector
device which provides the programming unit with a signal indicating the presence or absence of
flame
It includes the flame sensor and may include an amplifier and a relay for signal transmission. The amplifier and
relay may be in its own housing or combined with the programming unit.
2.2.103
flame sensor
device which senses the flame and provides the input signal to the flame detector amplifier
Examples are optical sensors and flame electrodes (flame rods).
2.2.104
ignition source
electrical or electronic system component which provides energy to an ignition device
It may be separated from or incorporated in the programming unit. Examples are ignition transformers and
electronic high-voltage generators.
2.2.105
ignition device
device mounted on or adjacent to a burner for igniting fuel at the burner
Examples are pilot burners, spark electrodes and hot surface igniters.
2.2.106
programming unit
device which controls the burner operation in a declared sequence from start-up to shutdown
within declared timings and in response to signals from regulating, limiting and monitoring
devices
2.2.107
multitry system
system that allows more than one valve open period during its declared operating sequence
---------------------- Page: 15 ----------------------
SIST EN 60730-2-5:2002
60730-2-5 IEC:2000 – 15 –
2.3 Definitions relating to the function of controls
2.3.30
T
max
Replace "switch head" by "burner control system."
Additional definitions:
2.3.101
automatic recycle
automatic repetition of the start-up procedure, without manual intervention, following loss of the
supervised flame and subsequent fuel supply shutoff
2.3.102
controlled shutdown
de-energization of the fuel flow means as a result of the opening of a control loop by a control
device such as a thermostat. The system returns to the start position
Controlled shutdown may include additional actions by the system.
2.3.103
flame detector response time
period of time between the loss of the sensed flame and the signal indicating the absence of
flame
2.3.104
flame detector operating characteristics
that function of the flame detector which indicates absence or presence of flame as the output
signal of the flame detector relating to the input signal
Normally the input signal is provided by a flame sensor.
2.3.104.1
signal for presence of flame (S )
1
minimum signal which indicates the presence of flame when there was previously no flame
2.3.104.2
signal for absence of flame (S )
2
maximum signal which indicates the loss of flame
S is less than S .
2 1
2.3.104. 3
maximum flame signal (S )
max
maximum signal which does not affect the timings or the sequence
2.3.104.4
signal for visible light flame simulation (S )
3
minimum signal which indicates the presence of flame during the visible light flame simulation
test
S is less than S .
3 2
---------------------- Page: 16 ----------------------
SIST EN 60730-2-5:2002
60730-2-5 IEC:2000 – 17 –
2.3.105
self-checking flame detector
flame detector which checks for correct operation of the flame detector and its associated
electronic circuitry while the burner is in the running position
2.3.106
flame detector self-checking rate
frequency of the self-checking function of the flame detector (in number of operations per unit
of time)
2.3.107
flame failure lock-out time
period of time between the signal indicating absence of flame and lock-out
2.3.108
flame failure reignition time (relight time)
period of time between the signal indicating absence of flame and the signal to energize the
ignition device. During this time period the fuel supply is not shut off
2.3.109
flame signal
output signal of the flame detector
2.3.110
flame simulation
condition which occurs when the flame detector indicates the presence of flame when in reality
no flame is present
2.3.111
ignition time
period of time during which the ignition device is energized
2.3.112
lock-out
process in which the system goes into one of two lock-out conditions following safety shutdown
2.3.112.1
non-volatile lock-out
condition of a system following safety shutdown such that a restart can only be accomplished
by a manual reset of the system and by no other cause
2.3.112.2
volatile lock-out
condition of a system following safety shutdown such that a restart can be accomplished by
either a manual reset of the system or by an interruption of the power supply and its
subsequent restoration
2.3.113
main flame establishing period
period of time between the signal to energize the main fuel flow means and the signal
indicating presence of the main burner flame
---------------------- Page: 17 ----------------------
SIST EN 60730-2-5:2002
60730-2-5 IEC:2000 – 19 –
2.3.114
pilot flame establishing period
period of time between the signal to energize the pilot fuel flow means and the signal indicating
presence of the pilot flame
2.3.115
post-ignition time
period of the ignition time between the signal indicating presence of flame and the signal to
de-energize t
...
Questions, Comments and Discussion