IEC/SC 22F - IEC_SC_22F
Standardization of electronic power conversion and/or semiconductor switching equipment and systems including the means for their control, protection, monitoring, cooling and other auxiliary systems and their application to electrical transmission and distribution systems. NOTE: Typical examples are power electronic equipment for flexible a.c. power transmission (controlled series capacitors, unified power flow controllers, etc), converters and associated equipment for high-voltage direct current (HVDC) systems irrespective of d.c. voltage level, reactive power compensation means (static VAR compensators, STATCOM, etc), power electronic equipment for smart grids, connection to electrical transmission and distribution systems of renewable and distributed power generation (wind farms, solar stations, etc) including the standardization of system-related features of d.c. systems with d.c. voltages 100 kV and lower, as well as other applications where power electronics is used, e.g., phase shifters and active filters.
IEC_SC_22F
Standardization of electronic power conversion and/or semiconductor switching equipment and systems including the means for their control, protection, monitoring, cooling and other auxiliary systems and their application to electrical transmission and distribution systems. NOTE: Typical examples are power electronic equipment for flexible a.c. power transmission (controlled series capacitors, unified power flow controllers, etc), converters and associated equipment for high-voltage direct current (HVDC) systems irrespective of d.c. voltage level, reactive power compensation means (static VAR compensators, STATCOM, etc), power electronic equipment for smart grids, connection to electrical transmission and distribution systems of renewable and distributed power generation (wind farms, solar stations, etc) including the standardization of system-related features of d.c. systems with d.c. voltages 100 kV and lower, as well as other applications where power electronics is used, e.g., phase shifters and active filters.
General Information
IEC 62501:2024 applies to self-commutated converter valves, for use in a three-phase bridge voltage sourced converter (VSC) for high voltage DC power transmission or as part of a back-to-back link, and to dynamic braking valves. It is restricted to electrical type and production tests. This document can be used as a guide for testing of high-voltage VSC valves used in energy storage systems (ESS). The tests specified in this document are based on air insulated valves. The test requirements and acceptance criteria can be used for guidance to specify the electrical type and production tests of other types of valves. This edition includes the following significant technical changes with respect to the previous edition: a) Conditions for use of evidence in lieu are inserted as a new Table 1; b) Test parameters for valve support DC voltage test, 7.3.2, and MVU DC voltage test, 8.4.1, updated; c) AC-DC voltage test between valve terminals, Clause 9, is restructured and alternative tests, by individual AC and DC voltage tests, added in 9.4.2; d) Partial discharge test in routine test program is removed; e) More information on valve component fault tolerance, Annex B, is added; f) Valve losses determination is added as Annex C.
- Standard57 pagesEnglish languagesale 10% offe-Library read for1 day
- Amendment11 pagesEnglish languagesale 10% offe-Library read for1 day
- Amendment11 pagesEnglish languagesale 10% offe-Library read for1 day
This part of IEC 60700 specifies the service conditions, the definitions of essential ratings and characteristics of thyristor valves utilized in line commutated converters with three-phase bridge connections to realize the conversion from AC to DC and vice versa for high voltage direct current (HVDC) power transmission applications. It is applicable for air insulated, liquid cooled and indoor thyristor valves.
- Standard37 pagesEnglish languagesale 10% offe-Library read for1 day
DAV on 2020-02-28.
- Amendment10 pagesEnglish languagesale 10% offe-Library read for1 day
- Amendment10 pagesEnglish languagesale 10% offe-Library read for1 day
This part of IEC 62751 gives the detailed method to be adopted for calculating the power
losses in the valves for an HVDC system based on the “modular multi-level converter”, where
each valve in the converter consists of a number of self-contained, two-terminal controllable
voltage sources connected in series. It is applicable both for the cases where each modular
cell uses only a single turn-off semiconductor device in each switch position, and the case
where each switch position consists of a number of turn-off semiconductor devices in series
(topology also referred to as “cascaded two-level converter”). The main formulae are given for
the two-level “half-bridge” configuration but guidance is also given in Annex A as to how to
extend the results to certain other types of MMC building block configuration.
The standard is written mainly for insulated gate bipolar transistors (IGBTs) but may also be
used for guidance in the event that other types of turn-off semiconductor devices are used.
Power losses in other items of equipment in the HVDC station, apart from the converter
valves, are excluded from the scope of this standard.
This standard does not apply to converter valves for line-commutated converter HVDC
systems.
- Amendment14 pagesEnglish languagesale 10% offe-Library read for1 day
IEC 60633:2019 is available as IEC 60633:2019 RLV which contains the International Standard and its Redline version, showing all changes of the technical content compared to the previous edition.IEC 6033:2019 defines terms for high-voltage direct current (HVDC) power transmission systems and for HVDC substations using electronic power converters for the conversion from AC to DC or vice versa. This document is applicable to HVDC substations with line commutated converters, most commonly based on three-phase bridge (double way) connections (see Figure 2) in which unidirectional electronic valves, for example semiconductor valves, are used. For the thyristor valves, only the most important definitions are included in this document. A more comprehensive list of HVDC valve terminology is given in IEC 60700-2. This edition includes the following significant technical changes with respect to the previous edition: - 40 terms and definitions have been amended and 31 new terms and definitions have been added mainly on converter units and valves, converter operating conditions, HVDC systems and substations and HVDC substation equipment; - a new Figure 13 on capacitor commutated converter configurations has been added.
- Standard40 pagesEnglish languagesale 10% offe-Library read for1 day
- Amendment8 pagesEnglish languagesale 10% offe-Library read for1 day
This International Standard defines terms for the subject of self-commutated voltage-sourced converters used for transmission of power by high voltage direct current (HVDC). The standard is written mainly for the case of application of insulated gate bipolar transistors (IGBTs) in voltage sourced converters (VSC) but may also be used for guidance in the event that other types of semiconductor devices which can both be turned on and turned off by control action are used. Line-commutated and current-sourced converters for high-voltage direct current (HVDC) power transmission systems are specifically excluded from this standard.
- Amendment8 pagesEnglish languagesale 10% offe-Library read for1 day
This International Standard defines type, production and optional tests on thyristor valves used in thyristor controlled reactors (TCR), thyristor switched reactors (TSR) and thyristor switched capacitors (TSC) forming part of static VAR compensators (SVC) for power system applications. The requirements of the standard apply both to single valve units (one phase) and to multiple valve units (several phases). Clauses 4 to 7 detail the type tests, i.e. tests which are carried out to verify that the valve design meets the requirements specified. Clause 8 covers the production tests, i.e. tests which are carried out to verify proper manufacturing. Clauses 9 and 10 detail optional tests, i.e. tests additional to the type and production tests.
- Standard47 pagesEnglish languagesale 10% offe-Library read for1 day
No scope available
- Amendment9 pagesEnglish languagesale 10% offe-Library read for1 day
No scope available
- Amendment7 pagesEnglish languagesale 10% offe-Library read for1 day
- Amendment7 pagesEnglish languagesale 10% offe-Library read for1 day
IEC 61803:2020 is available as IEC 61803:2020 RLV which contains the International Standard and its Redline version, showing all changes of the technical content compared to the previous edition.IEC 61803:2020 applies to all line-commutated high-voltage direct current (HVDC) converter stations used for power exchange (power transmission or back-to-back installation) in utility systems. This document presumes the use of 12-pulse thyristor converters but can, with due care, also be used for 6-pulse thyristor converters. In some applications, synchronous compensators or static var compensators (SVC) may be connected to the AC bus of the HVDC converter station. The loss determination procedures for such equipment are not included in this document. This document presents a set of standard procedures for determining the total losses of an HVDC converter station. The procedures cover all parts, except as noted above, and address no-load operation and operating losses together with their methods of calculation which use, wherever possible, measured parameters. Converter station designs employing novel components or circuit configurations compared to the typical design assumed in this document, or designs equipped with unusual auxiliary circuits that could affect the losses, are assessed on their own merits. This edition includes the following significant technical changes with respect to the previous edition: - to facilitate the application of this document and to ensure its quality remains consistent, 5.1.8 and 5.8 have been reviewed, taking into consideration that the present thyristor production technology provides considerably less thyristor parameters dispersion comparing with the situation in 1999 when the first edition of IEC 61803 was developed, and therefore the production records of thyristors can be used for the power losses calculation; - the calculation of the total station load losses (cases D1 and D2 in Annex C) has been corrected.
- Standard40 pagesEnglish languagesale 10% offe-Library read for1 day
- Amendment10 pagesEnglish languagesale 10% offe-Library read for1 day
IEC 62927:2017 applies to self-commutated valves, for use in voltage sourced converter (VSC) for static synchronous compensator (STATCOM). It is restricted to electrical type and production tests. The tests specified in this document are based on air insulated valves. For other types of valves, the test requirements and acceptance criteria are agreed between the purchaser and the supplier.
- Standard43 pagesEnglish languagesale 10% offe-Library read for1 day
IEC 60700-2:2016 defines terms for thyristor valves for high-voltage direct current (HVDC) power transmission with line commutated converters most commonly based on three-phase bridge connections for the conversion from AC to DC and vice versa.
- Standard25 pagesEnglish languagesale 10% offe-Library read for1 day
IEC 62823:2015 defines routine and type tests on thyristor valves used in thyristor controlled series capacitor (TCSC) installations for a.c. power transmission. The tests specified in this standard are based on air insulated valves operating in capacitive boost mode or bypass mode.
- Standard42 pagesEnglish languagesale 10% offe-Library read for1 day
IEC 60700-1:2015 is available as IEC 60700-1:2015 RLV which contains the International Standard and its Redline version, showing all changes of the technical content compared to the previous edition. IEC 60700-1:2015 applies to thyristor valves with metal oxide surge arresters directly connected between the valve terminals, for use in a line commutated converter for high voltage d.c. power transmission or as part of a back-to-back link. It is restricted to electrical type and production tests. The tests specified in this standard are based on air insulated valves. For other types of valves, the test requirements and acceptance criteria can be agreed. This edition includes the following significant technical changes with respect to the previous edition. a) Definitions of terms "redundant thyristor levels", "thyristor level", "valve section" have been changed for clarification. b) The notes were added to test requirements of dielectric d.c. voltage tests for valve support, MVU, valve, specifying that before repeating the test with opposite polarity, the tested object may be short-circuited and earthed for several hours. The same procedure may be followed at the end of the d.c. voltage test. c) Table 1 on thyristor level faults permitted during type tests was supplemented. d) The alternative MVU dielectric test method was added. e) It was specified that production tests may include routine tests as well as sample tests. f) It was added into test requirements for periodic firing and extinction tests that a scaling factor for tests shall be applied when testing with valve sections.
- Standard48 pagesEnglish languagesale 10% offe-Library read for1 day
IEC 62751-1:2014 sets out the general principles for calculating the power losses in the converter valves of a voltage sourced converter (VSC) for high-voltage direct current (HVDC) applications, independent of the converter topology. Several clauses in the standard can also be used for calculating the power losses in the dynamic braking valves (where used) and as guidance for calculating the power losses of the valves for a STATCOM installation.
- Standard33 pagesEnglish languagesale 10% offe-Library read for1 day
IEC 62751-2:2014 gives the detailed method to be adopted for calculating the power losses in the valves for an HVDC system based on the "modular multi-level converter", where each valve in the converter consists of a number of self-contained, two-terminal controllable voltage sources connected in series. It is applicable both for the cases where each modular cell uses only a single turn-off semiconductor device in each switch position, and the case where each switch position consists of a number of turn-off semiconductor devices in series (topology also referred to as "cascaded two-level converter"). The main formulae are given for the two-level "half-bridge" configuration but guidance is also given as to how to extend the results to certain other types of MMC building block configuration.
- Standard58 pagesEnglish languagesale 10% offe-Library read for1 day
- Amendment23 pagesEnglish languagesale 10% offe-Library read for1 day
IEC 62747:2014 defines terms for the subject of self-commutated voltage-sourced converters used for transmission of power by high voltage direct current (HVDC). The standard is written mainly for the case of application of insulated gate bipolar transistors (IGBTs) in voltage sourced converters (VSC) but may also be used for guidance in the event that other types of semiconductor devices which can both be turned on and turned off by control action are used. Line-commutated and current-sourced converters for high-voltage direct current (HVDC) power transmission systems are specifically excluded from this standard.
- Standard33 pagesEnglish languagesale 10% offe-Library read for1 day
IEC 61975:2010(E) applies to system tests for high-voltage direct current (HVDC) installations which consist of a sending terminal and a receiving terminal, each connected to an a.c. system. The tests specified in this standard are based on bidirectional and bipolar high-voltage direct current (HVDC) installations which consist of a sending terminal and a receiving terminal, each connected to an a.c. system. The test requirements and acceptance criteria should be agreed for back-to-back installations, while multi-terminal systems and voltage sourced converters are not included in this standard. For monopolar HVDC installations, the standard applies except for bipolar tests. This standard only serves as a guideline to system tests for high-voltage direct current (HVDC) installations. The standard gives potential users guidance, regarding how to plan commissioning activities. The tests described in the guide may not be applicable to all projects, but represent a range of possible tests which should be considered. This edition cancels and replaces IEC/PAS 61975 published jointly in 2004 by IEC and CIGRÉ. It constitutes a technical revision incorporating engineering experience.
- Amendment21 pagesEnglish languagesale 10% offe-Library read for1 day
IEC 61975:2010(E) applies to system tests for high-voltage direct current (HVDC) installations which consist of a sending terminal and a receiving terminal, each connected to an a.c. system. The tests specified in this standard are based on bidirectional and bipolar high-voltage direct current (HVDC) installations which consist of a sending terminal and a receiving terminal, each connected to an a.c. system. The test requirements and acceptance criteria should be agreed for back-to-back installations, while multi-terminal systems and voltage sourced converters are not included in this standard. For monopolar HVDC installations, the standard applies except for bipolar tests. This standard only serves as a guideline to system tests for high-voltage direct current (HVDC) installations. The standard gives potential users guidance, regarding how to plan commissioning activities. The tests described in the guide may not be applicable to all projects, but represent a range of possible tests which should be considered. This edition cancels and replaces IEC/PAS 61975 published jointly in 2004 by IEC and CIGRÉ. It constitutes a technical revision incorporating engineering experience.
- Standard82 pagesEnglish languagesale 10% offe-Library read for1 day
IEC 62501:2009 applies to self-commutated converter valves, for use in a three-phase bridge voltage sourced converter (VSC) for high voltage d.c. power transmission or as part of a back-to-back link. It is restricted to electrical type and production tests.
- Standard44 pagesEnglish languagesale 10% offe-Library read for1 day
IEC/TR 60919-2:2008 provides guidance on the transient performance and fault protection requirements of high voltage direct current (HVDC) systems. It concerns the transient performance related to faults and switching for two-terminal HVDC systems utilizing 12-pulse converter units comprised of three-phase bridge (double way) connections but it does not cover multi-terminal HVDC transmission systems. However, certain aspects of parallel converters and parallel lines, if part of a two-terminal system, are discussed. The converters are assumed to use thyristor valves as the bridge arms, with gapless metal oxide arresters for insulation co-ordination and to have power flow capability in both directions. Diode valves are not considered in this report. This second edition cancels and replaces the first edition, published in 1991, and constitutes a technical revision. It includes the following main changes with respect to the previous edition: it concerns only line-commutated converters;isignificant changes have been made to the control system technology; some environmental constraints, for example audible noise limits, have been added; the capacitor coupled converters (CCC) and controlled series capacitor converters (CSCC) have been included.
- Technical report64 pagesEnglish languagesale 10% offe-Library read for1 day
Provides general guidance on the steady-state performance requirements of HVDC systems. It concerns the steady-state performance of two-terminal HVDC systems utilizing 12-pulse converter units comprised of three-phase bridge (double- way) connections (see Figure 1), but it does not cover multi-terminal HVDC transmission systems. Both terminals are assumed to use thyristor valves as the main semiconductor valves and to have power flow capability in both directions. Diode valves are not considered in this report.
- Technical report86 pagesEnglish languagesale 10% offe-Library read for1 day
- Amendment7 pagesEnglish languagesale 10% offe-Library read for1 day
Applies to all line-commutated high-voltage direct current (HVDC) converter stations used for power exchange in utility systems. Presumes the use of 12-pulse thyristor converters but can also be used for 6-pulse thyristor converters. Presents procedures for determining the total losses of an HVDC converter station. Cover all parts, except synchronous compensators or static var compensators and address no-load operation and operating losses together with their methods of calculation which use, wherever possible, measured parameters.
- Amendment10 pagesEnglish languagesale 10% offe-Library read for1 day
PWI created for possible future // procedures
- Amendment15 pagesEnglish languagesale 10% offe-Library read for1 day
2013-05-16: Publication allocated to cpalagi@cencenelec.eu
- Amendment5 pagesEnglish languagesale 10% offe-Library read for1 day
IEC 61954:2011 defines type, production and optional tests on thyristor valves used in thyristor controlled reactors (TCR), thyristor switched reactors (TSR) and thyristor switched capacitors (TSC) forming part of static VAR compensators (SVC) for power system applications. The requirements of the standard apply both to single valve units (one phase) and to multiple valve units (several phases). This edition includes the following significant technical changes with respect to the previous edition: a) Definitions of terms 'thyristor level', 'valve section', 'valve base electronics' and 'redundant thyristor levels' have been changed for clarification; b) Conditions of testing thyristor valve sections instead of a complete thyristor valve have been defined; c) The requirement has been added that if, following a type test, one thyristor level has become short-circuited, then the failed level shall be restored and this type test repeated; d) The time period of increasing the initial test voltage from 50 % to 100 % during type a.c. dielectric tests on TSC, TCR or TSR valves has been set equal to approximately 10 s; e) The duration of test voltage Uts2 during type a.c.-d.c. dielectric tests between TSC valve terminals and earth as well as the duration of test voltage Utvv2 during dielectric tests between TSC valves (for MVU only) has been changed from 30 min to 3 h; f) The reference on the number of pulses per minute of the periodic partial discharge recorded during a.c.-d.c. dielectric tests on TSC valves and exceeding the permissible level has been deleted.
- Standard47 pagesEnglish languagesale 10% offe-Library read for1 day
Amandma A1:2011 je dodatek k standardu SIST EN 61803:2001
Applies to all line-commutated high-voltage direct current (HVDC) converter stations used for power exchange in utility systems. This standard presimes the use of 12-puls thyristor converters but can, with due care, also be used for 6-pulse thyristor converters.
- Amendment9 pagesEnglish languagesale 10% offe-Library read for1 day
- Amendment7 pagesEnglish languagesale 10% offe-Library read for1 day
- Amendment12 pagesEnglish languagesale 10% offe-Library read for1 day
Superseded by EN 61954:2011
- Amendment9 pagesEnglish languagesale 10% offe-Library read for1 day
- Amendment13 pagesEnglish languagesale 10% offe-Library read for1 day
Defines type, production and optional test on thyristor valves used in thyristor controlled reactots (TCR), Thyristor switched reactor (TSR) and thyristor switched capacitors (TSC) forming part of static VAR compensators (SVC) for power system applications. the requirements of the standard apply both to single valve units (one phase) and to multiple valve units (several phases). Clauses 4 to 7 detail the type tests, clause 8 covers the production tests, clauses 9 and 7 detail optional tests.
- Standard45 pagesEnglish languagesale 10% offe-Library read for1 day
Applies to all line-commutated high-voltage direct current (HVDC) converter stations used for power exchange in utility systems. Presumes the use of 12-pulse thyristor converters but can also be used for 6-pulse thyristor converters. Presents procedures for determining the total losses of an HVDC converter station. Cover all parts, except synchronous compensators or static var compensators and address no-load operation and operating losses together with their methods of calculation which use, wherever possible, measured parameters.
- Standard36 pagesEnglish languagesale 10% offe-Library read for1 day
Applies to terminology for high-voltage direct current (HVDC) systems and especially to HVDC converter substations where electronic converters are used for the conversion from a.c. to d.c. or vice versa.
- Standard36 pagesEnglish languagesale 10% offe-Library read for1 day
Applies to thyristor valves with metal oxide surge arresters directly connected between the valve terminals, for use in a line commuted commutated converter for high voltage d.c. power transmission or as part of a back-to-back link. Retricted to electrical type and production tests. Tests are based on air insulated valves.
- Standard51 pagesEnglish languagesale 10% offe-Library read for1 day