Automatic electrical controls for household and similar use - Part 1: General requirements

IEC 60703-1:2010 applies to automatic electrical controls for use in, on, or in association with equipment for household and similar use, including controls for heating, air conditioning and similar applications. The equipment may use electricity, gas, oil, solid fuel, solar thermal energy, etc., or a combination thereof. This standard also applies to the inherent safety; to the operating values, operating times, and operating sequences where such are associated with equipment safety, and to the testing of automatic electrical control devices used in, or in association with, household or similar equipment. This standard is also applicable to controls for appliances within the scope of IEC 60335-1 as well as controls for building automation systems within the scope of ISO 16484-2. The principal changes in this edition as compared to the previous edition are as follows: - changes to the low temperature test requirements for in-line cords; - revision to the pollution degree for the environment surronding contacts; - addition of the use of screwless terminals on printed circuit boards and revisions to creepage distances; - additions of CISPR 11 EMC requirements; - incorporation of EMC test levels from IEC 60335 series; - additional testing for flexible cords; - revisions to the requirements for resistance to heat, fire and tracking including replacement of clause 21 and Annexes F and G; - new Annex T for additional requirements for non-SELV supplied sensor cable or cord; - new requirements in H.27.1 for first and second fault approach to ensure functional safety; - incorporation of software techniques from IEC 61508-3 in H.11.12; - replacement of Annex D (Canada and USA) with reference to UL 746C; - updates to the references and bibliography; - the keyword index was deleted.

Automatische elektrische Regel- und Steuergeräte für den Hausgebrauch und ähnliche Anwendungen - Teil 1: Allgemeine Anforderungen

Dispositifs de commande électrique automatiques à usage domestique et analogue - Partie 1: Exigences générales

La CEI 60703-1:2010 s'applique aux dispositifs de commande électrique automatiques destinés à être utilisés dans, sur, ou avec des équipements à usage domestique et analogue, y compris des dispositifs de commande pour chauffage, air conditionné et usages analogues. Les matériels peuvent utiliser l'électricité, le gaz, le pétrole, des combustibles solides, l'énergie thermique solaire, etc., ou une combinaison de ces sources d'énergie. La présente Norme internationale s'applique également à la sécurité intrinsèque; aux valeurs de fonctionnement, aux temps de fonctionnement et aux séquences de fonctionnement dans la mesure où ils interviennent dans la sécurité du matériel, ainsi qu'aux essais des dispositifs de commande électriques automatiques utilisés dans ou avec du matériel électrodomestique et analogue. La présente norme s'applique également aux dispositifs de commande d'appareils relevant du domaine d'application de la CEI 60335-1. La présente norme s'applique également aux dispositifs de commande pour les systèmes d'automatisation et de gestion technique du bâtiment relevant du domaine d'application de l'ISO 16484-2. Les principales modifications techniques s'appliquant à cette norme, depuis sa précédente publication, sont comme suit: - modifications des exigences d'essais à basse température pour les câbles souples; - révision du degré de pollution pour l'environnement proche des contacts; - addition de l'utilisation de bornes sans vis sur les circuits imprimés et révision des distances de ligne de fuite; - addition des exigences en CEM de la CISPR 11; - incorporation des niveaux d'essai en CEM de la série CEI 60335; - essais additionnels pour les cordons flexibles; - révision des exigences pour la résistance à la chaleur, au feu et au cheminement, y compris le remplacement de l'Article 21 et des Annexes F et G; - nouvelle Annexe T pour des exigences additionnelles concernant un câble à capteur non TBTS ou un cordon; - nouvelle exigence en H.27.1 pour une première ou une seconde approche de défaut pour assurer la sécurité fonctionnelle; - ajout d'une technique logicielle issue de la CEI 61508-3 en H.11.12; - remplacement de l'Annexe D (Canada et Etats-Unis) par une référence à la UL 746C; - mise à jour des références et de la bibliographie; - l'index des mots clé a été supprimé.",EC

Avtomatske električne krmilne naprave za uporabo v gospodinjstvu in za podobno uporabo - 1. del: Splošne zahteve

Ta mednarodni standard se na splošno uporablja za avtomatske električne krmilne naprave, ki se uporabljajo v opremi za gospodinjstvo in podobno uporabo, na njej ali v povezavi z njo, vključno s krmilnimi napravami za ogrevanje, klimatizacijo in podobno. Za opremo se lahko samostojno ali v kombinaciji uporabljajo elektrika, plin, nafta, trdno gorivo, sončna toplotna energija itd. Ta mednarodni standard se uporablja za varnost, vrednosti delovanja, čas delovanja in zaporedja delovanja, ki so povezana varnostjo opreme, ter za preskušanje avtomatskih električnih krmilnih naprav, ki se uporabljajo v opremi za gospodinjstvo ali podobni opremi oziroma v povezavi z njo. Ta standard se uporablja tudi za krmiljenje naprav iz standarda IEC 60335-1. Ta standard se uporablja tudi za krmiljenje sistemov za avtomatizacijo stavb iz standarda ISO 16484-2.

General Information

Status
Published
Publication Date
22-Dec-2011
Current Stage
6060 - Document made available - Publishing
Start Date
23-Dec-2011
Completion Date
23-Dec-2011

Relations

Buy Standard

Standard
EN 60730-1:2012 - BARVE
English language
294 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)


SLOVENSKI STANDARD
01-marec-2012
1DGRPHãþD
SIST EN 60730-1:2001
SIST EN 60730-1:2001/A1:2005
SIST EN 60730-1:2001/A11:2002
SIST EN 60730-1:2001/A12:2004
SIST EN 60730-1:2001/A13:2005
SIST EN 60730-1:2001/A14:2005
SIST EN 60730-1:2001/A15:2007
SIST EN 60730-1:2001/A16:2007
SIST EN 60730-1:2001/A2:2009
$YWRPDWVNHHOHNWULþQHNUPLOQHQDSUDYH]DXSRUDERYJRVSRGLQMVWYXLQ]DSRGREQR
XSRUDERGHO6SORãQH]DKWHYH
Automatic electrical controls for household and similar use - Part 1: General
requirements
Automatische elektrische Regel- und Steuergeräte für den Hausgebrauch und ähnliche
Anwendungen - Teil 1: Allgemeine Anforderungen
Dispositifs de commande électrique automatiques à usage domestique et analogue -
Partie 1: Exigences générales
Ta slovenski standard je istoveten z: EN 60730-1:2011
ICS:
97.120 Avtomatske krmilne naprave Automatic controls for
za dom household use
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

EUROPEAN STANDARD
EN 60730-1
NORME EUROPÉENNE
December 2011
EUROPÄISCHE NORM
ICS 97.120 Supersedes EN 60730-1:2000 + corr. Aug.2007 + A1:2004 + A2:2008 + A12:2003 + A13:2004
+ A14:2005 + A16:2007 + corr. Mar.2010
English version
Automatic electrical controls for household and similar use -
Part 1: General requirements
(IEC 60730-1:2010, modified)
Dispositifs de commande électrique Automatische elektrische Regel- und
automatiques à usage domestique et Steuergeräte für den Hausgebrauch und
analogue - ähnliche Anwendungen -
Partie 1: Exigences générales Teil 1: Allgemeine Anforderungen
(CEI 60730-1:2010, modifiée) (IEC 60730-1:2010, modifiziert)
This European Standard was approved by CENELEC on 2011-10-24. CENELEC members are bound to
comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European
Standard the status of a national standard without any alteration.
Up-to-date lists and bibliographical references concerning such national standards may be obtained on
application to the CEN-CENELEC Management Centre or to any CENELEC member.
This European Standard exists in three official versions (English, French, German). A version in any other
language made by translation under the responsibility of a CENELEC member into its own language and
notified to the CEN-CENELEC Management Centre has the same status as the official versions.
CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia,
Cyprus, the Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland,
Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania,
Slovakia, Slovenia, Spain, Sweden, Switzerland and the United Kingdom.

CENELEC
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung

Management Centre: Avenue Marnix 17, B - 1000 Brussels

© 2011 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members.
Ref. No. EN 60730-1:2011 E
Foreword
The text of the International Standard IEC 60730-1:2010, prepared by IEC/TC 72, Automatic controls for
household use, together with the common modifications prepared by the Technical Committee CENELEC
TC 72, Automatic controls for household use, was submitted to the CENELEC Unique Acceptance
Procedure and approved by CENELEC as EN 60730-1:2011.
This document supersedes EN 60730-1:2000 + corr. Aug.2007 + A12:2003 + A1:2004 + A13:2004 +
A14:2005 + A16:2007 + corr. Mar.2010 + A2:2008.
The main technical modifications of this European Standard since the above previous edition are listed
below:
– changes to the low temperature test requirements for in-line cords;
– revision to the pollution degree for the environment surrounding contacts;
– addition to the use of screwless terminals on printed circuit boards and revisions to creepage
distances;
– additions of EN 55011 EMC requirements;
– incorporation of EMC test levels from EN 60335 series;
– additional testing for flexible cords;
– revisions to the requirements for resistance to heat, fire and tracking including replacement of
Clause 21 and Annexes F and G;
– new requirements in H.27.1 for first and second fault approach to ensure functional safety;
– incorporation of software techniques from EN 61508-3 in H.11.12;
– updates to the references and bibliography;
– the keyword index was deleted as unnecessary due to the availability of search functions for
electronic editions of the standard.
Additionally, this European Standard is the editorial result of the combined texts of EN 60730-1:2000 and
its amendments, except where CENELEC common modifications have already been incorporated in
IEC 60730-1:2010, together with the deletion of additional ‘in some countries’ paragraphs and ‘under
consideration’ paragraphs which have been introduced in IEC 60730-1:2010.
The following dates are fixed:
– latest date by which the EN has to be implemented
at national level by publication of an identical
national standard or by endorsement (dop) 2012-10-24
– latest date by which the national standards conflicting
with the EN have to be withdrawn (dow) – *
Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. CENELEC [and/or CEN] shall not be held responsible for identifying any or all such patent
rights.
– 3 – EN 60730-1:2011
* Justification for no dow:
This European Standard replaces EN 60730-1:2000 and its amendments. However, EN 60730-1:2000
remains valid until all the Part 2’s which are used in conjunction with it have been withdrawn. No date of
withdrawal (dow) has been given pending the updating of all the Part 2's to align with this
Part 1 will be fixed once all the Part 2's have been updated.
This Part 1 is to be used in conjunction with the appropriate Part 2 for a particular type of control, or for
controls for particular applications. This Part 1 may also be applied, so far as reasonable, to controls not
mentioned in a Part 2, and to controls designed on new principles, in which case additional requirements
may be necessary.
Subclauses which are additional to those in IEC 60730-1:2010 are numbered 601, 602 etc. Annexes
which are additional to those in IEC 60730-1:2010 are prefixed “Z”.
Where reference is made to other international or harmonized standards, the edition of that standard
quoted in Annex ZA (normative) is applicable.
Special national conditions causing a deviation from this European Standard are listed in Annex ZB
(normative) which forms part of this standard.
National deviations from this European Standard are listed in Annex ZC (informative).
This European Standard has been prepared under a mandate given to CENELEC by the European
Commission and the European Free Trade Association and covers essential requirements of
EU Directive 2004/108/EC. See Annex ZZ.
NOTE In this standard the following print types are used:
– Requirements proper: in roman type.
– Test specifications: in italic type.
– Explanatory matter: in smaller roman type.

Endorsement notice
The text of the International Standard IEC 60730-1:2010 was approved by CENELEC as a European
Standard with the following common modifications.
COMMON MODIFICATIONS
General common modification valid for the entire document
If an explanatory statement does not start with NOTE, add in front of this explanatory statement "NOTE"
and number it if more than one note is given in the same subclause.
Contents
Annexes Add the following after Annex U:
Annex ZA (normative) Normative references to international publications with their
corresponding European publications
Annex ZB (normative) Special national conditions
Annex ZC (informative) A-deviations
Annex ZD (normative) EMC immunity for controls
Annex ZZ (informative) Coverage of Essential Requirements of EC Directives
Figures Delete Figures 25 to 30 and Figures H.3 and H.4.
After Figure R.3, add "Figure ZD.1 EMC test framework for controls".
Tables Delete Table 2.
In the title of Table 14, delete “(this table applies in all countries except Canada, and the USA).”
After Table 14, add "Table Z1'.
Delete Tables 15 to 18, Table 25 and Table H.16.
After Table P.1, add the following:
Table ZD.1 – Classification and test overview
Table ZD.2 – Compliance criteria
Table ZD.3 – Test levels for voltage surges
Table ZD.4 – Test levels for burst
Table ZD.5 – Test application for electrical fast transient burst test
Table ZD.6 – Test levels for conducted disturbances on mains, I/O lines and DC power lines
Table ZD.7 – Test levels for electrostatic discharge
Table ZD.8 – Test levels for radiated electromagnetic field on enclosure
Table ZD.9 – Test levels for radiated electromagnetic field on enclosure
Table ZD.10 – Voltage dips (50 Hz / 60 Hz)
Table ZD.11 – Voltage interruption (50 Hz/60 Hz)

– 5 – EN 60730-1:2011
1 Scope
1.1.1 Replace the fourth paragraph by the following:
NOTE 1 Throughout this standard the word "equipment" means "appliance and equipment”.
Replace Note 1 and Note 2 by the following:
NOTE 2 These requirements are referred to by IEC 61810-1:2008, Clause 1.
NOTE 3 This standard is intended to be used for the testing of any stand-alone relay which is
intended to be used as a control of an appliance according to IEC 60335-1. It is not intended to be
used for any other stand-alone relay, or to replace the IEC 61810 series of standards.
1.1.3 Add the following note:
NOTE Starting relays are tested as voltage sensing or current sensing controls.
1.5 Add the following normative reference after IEC 60695-10-2:
EN 60730 series, Automatic electrical controls for household and similar use
(IEC 60730 series)
Add the following normative reference before CISPR 22:2008:
EN 55016-1:2010 + A1:2010, Specification for radio disturbance and immunity measuring
apparatus and methods – Part 1-1: Radio disturbance and immunity measuring
apparatus – Measuring apparatus (CISPR 16-1-1:2010 + A1:2010)
Add the following normative references after IEC 62326
HD 21.5 S3:1994 + A1:1999 + A2:2001, Polyvinyl chloride insulated cables of rated
voltages up to and including 450/750 V – Part 5: Flexible cables (cords)
(IEC 60227-5:1979, mod.)
HD 22.4 S4:2004, Cables of rated voltages up to and including 450/750 V and having
cross-linked insulation – Part 4: Cords and flexible cables
2 Definitions
2.1.5 Delete Note 2.
2.1.15 Delete “(conductive) shield (US)”.
2.1.16 Delete “(electrically) protective shield (US)”.
2.1.17 Delete “(electrically) protective shielding (US)”.
2.2.8 Replace the two last paragraphs by:
NOTE 1 A thermal cut-out may be of the automatic, manual reset or non-resettable type.
NOTE 2 Normally a thermal cut-out will provide a type 2 action.
2.7.2 Replace the two last paragraphs by:
NOTE 1 See Annex ZB.
NOTE 2 An earthing terminal is only allowed if it is for continuity or functional (as distinct from
protective) purposes.
2.7.3 Replace the two last paragraphs by:
NOTE 1 See Annex ZB.
NOTE 2 An earthing terminal is only allowed if it is for continuity (as distinct from protective)
purposes.
2.7.5.3 Replace the paragraph by:
NOTE 1 The enclosure of an all-insulated class II control may form a part or the whole of the
supplementary insulation or of the reinforced insulation. If a control with double insulation and/or
reinforced insulation throughout has an earthing terminal or earthing contact, it is deemed to be of
class 0I or class I construction.
NOTE 2 See Annex ZB.
2.13.9 Delete “Explanatory” in front of the four notes.
2.14.2 Delete the explanatory paragraph.
4 General notes on tests
4.2.1 Replace the first sentence by:
One sample is used for the tests in Clauses 5 to 11 and 18 to 27 including the relevant
annexes.
Delete the third explanatory paragraph.
4.3.3.1 Add “See Annex ZB.” at the end of the paragraph.
4.3.3.3 Add “See Annex ZB.” at the end of the paragraph.
5 Rating
st
5.1 Add a new requirement paragraph after the 1 paragraph:
The rated voltage of controls, having terminals intended to be directly connected to the
supply mains single phase, shall cover usage at 230 V and to the supply mains multi-
phase, 400 V.
6 Classification
6.6.1 Delete the explanatory paragraph.
6.8.2.1 Add “(see Annex ZB)” before the semi column.
6.8.2.2 Add “(see Annex ZB)” before the semi column.
6.8.3.1 Add “(see Annex ZB)” before the semi column.
6.8.3.2 Add “(see Annex ZB)” before the semi column.

– 7 – EN 60730-1:2011
7 Information
7)
Table 1 In Requirement 7, replace the wording by "The type of load and rated current ".
9)
In Requirement 19, delete “ ”.
In Requirement 23, add to the wording "if more than 20 K above T ”.
max
In Requirement 78, replace the second column by:
"Table 20 (19.1 of the previous edition), Note 1"
After requirements 91 and 92, add the following new requirements:
601 EMC standard/test method 23.1 X
602 Declared voltage and declared current for the purposes of 23.1.1 D
601)
EMC emission tests
4)
In Note , replace the text before the table by:
4) α = minimum rising rate
β = minimum falling rate
The rate of change (α and β ) of the activating quantity are those applicable to normal use.
1 1
α = maximum rising rate (for Type 2 actions only)
β = maximum falling rate (for Type 2 actions only)
For test purposes, α and β shall be as declared but not lower than the limit(s) indicated in the appropriate
1 1
Part 2s for Type 1 actions and/or Type 2 actions. The values α and β are for test purposes only, and may
2 2
alternatively be declared as a maximum cycling rate. The rates of change for the purpose of this standard shall be
expressed in the units as shown in the following table*:
7)
Replace Note by:
7)
For each circuit of the control, the type of load and rated current. For controls with more than one circuit it
shall
...

Questions, Comments and Discussion