Amendment 1 - Residual current operated circuit-breakers without integral overcurrent protection for household and similar uses (RCCBs) - Part 1: General rules

The contents of the corrigendum of May 2016 have been included in this copy.

Amendement 1 - Interrupteurs automatiques à courant différentiel résiduel sans dispositif de protection contre les surintensités incorporé pour usages domestiques et analogues (ID) - Partie 1: Règles générales

Le contenu du corrigendum de mai 2016 a été pris en considération dans cet exemplaire.

General Information

Status
Published
Publication Date
29-Apr-2012
Current Stage
PPUB - Publication issued
Start Date
30-Apr-2012
Completion Date
30-Apr-2012
Ref Project

Relations

Buy Standard

Standard
IEC 61008-1:2010/AMD1:2012 - Amendment 1 - Residual current operated circuit-breakers without integral overcurrent protection for household and similar uses (RCCBs) - Part 1: General rules
English and French language
107 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)


IEC 61008-1 ®
Edition 3.0 2012-04
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE
AMENDMENT 1
AMENDEMENT 1
Residual current operated circuit-breakers without integral overcurrent
protection for household and similar uses (RCCBs) –
Part 1: General rules
Interrupteurs automatiques à courant différentiel résiduel sans dispositif de
protection contre les surintensités incorporé pour usages domestiques et
analogues (ID) –
Partie 1: Règles générales
IEC 61008-1:2010/A1:2012
All rights reserved. Unless otherwise specified, no part of this publication may be reproduced or utilized in any form
or by any means, electronic or mechanical, including photocopying and microfilm, without permission in writing from
either IEC or IEC's member National Committee in the country of the requester.
If you have any questions about IEC copyright or have an enquiry about obtaining additional rights to this publication,
please contact the address below or your local IEC member National Committee for further information.

Droits de reproduction réservés. Sauf indication contraire, aucune partie de cette publication ne peut être reproduite ni
utilisée sous quelque forme que ce soit et par aucun procédé, électronique ou mécanique, y compris la photocopie et les
microfilms, sans l'accord écrit de la CEI ou du Comité national de la CEI du pays du demandeur.
Si vous avez des questions sur le copyright de la CEI ou si vous désirez obtenir des droits supplémentaires sur cette
publication, utilisez les coordonnées ci-après ou contactez le Comité national de la CEI de votre pays de résidence.

IEC Central Office Tel.: +41 22 919 02 11
3, rue de Varembé Fax: +41 22 919 03 00
CH-1211 Geneva 20 info@iec.ch
Switzerland www.iec.ch
About the IEC
The International Electrotechnical Commission (IEC) is the leading global organization that prepares and publishes
International Standards for all electrical, electronic and related technologies.

About IEC publications
The technical content of IEC publications is kept under constant review by the IEC. Please make sure that you have the
latest edition, a corrigenda or an amendment might have been published.

Useful links:
IEC publications search - www.iec.ch/searchpub Electropedia - www.electropedia.org
The advanced search enables you to find IEC publications The world's leading online dictionary of electronic and
by a variety of criteria (reference number, text, technical electrical terms containing more than 30 000 terms and
committee,…). definitions in English and French, with equivalent terms in
It also gives information on projects, replaced and additional languages. Also known as the International
withdrawn publications. Electrotechnical Vocabulary (IEV) on-line.

IEC Just Published - webstore.iec.ch/justpublished Customer Service Centre - webstore.iec.ch/csc
Stay up to date on all new IEC publications. Just Published If you wish to give us your feedback on this publication
details all new publications released. Available on-line and or need further assistance, please contact the
also once a month by email. Customer Service Centre: csc@iec.ch.

A propos de la CEI
La Commission Electrotechnique Internationale (CEI) est la première organisation mondiale qui élabore et publie des
Normes internationales pour tout ce qui a trait à l'électricité, à l'électronique et aux technologies apparentées.

A propos des publications CEI
Le contenu technique des publications de la CEI est constamment revu. Veuillez vous assurer que vous possédez
l’édition la plus récente, un corrigendum ou amendement peut avoir été publié.

Liens utiles:
Recherche de publications CEI - www.iec.ch/searchpub Electropedia - www.electropedia.org
La recherche avancée vous permet de trouver des Le premier dictionnaire en ligne au monde de termes
publications CEI en utilisant différents critères (numéro de électroniques et électriques. Il contient plus de 30 000
référence, texte, comité d’études,…). termes et définitions en anglais et en français, ainsi que
Elle donne aussi des informations sur les projets et les les termes équivalents dans les langues additionnelles.
publications remplacées ou retirées. Egalement appelé Vocabulaire Electrotechnique
International (VEI) en ligne.
Just Published CEI - webstore.iec.ch/justpublished
Service Clients - webstore.iec.ch/csc
Restez informé sur les nouvelles publications de la CEI.
Just Published détaille les nouvelles publications parues. Si vous désirez nous donner des commentaires sur
Disponible en ligne et aussi une fois par mois par email. cette publication ou si vous avez des questions
contactez-nous: csc@iec.ch.
IEC 61008-1 ®
Edition 3.0 2012-04
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE
AMENDMENT 1
AMENDEMENT 1
Residual current operated circuit-breakers without integral overcurrent

protection for household and similar uses (RCCBs) –

Part 1: General rules
Interrupteurs automatiques à courant différentiel résiduel sans dispositif de

protection contre les surintensités incorporé pour usages domestiques et

analogues (ID) –
Partie 1: Règles générales
INTERNATIONAL
ELECTROTECHNICAL
COMMISSION
COMMISSION
ELECTROTECHNIQUE
PRICE CODE
INTERNATIONALE
XA
CODE PRIX
ICS 29.120.50 ISBN 978-2-83220-018-6

– 2 – 61008-1 Amend.1 © IEC:2012
FOREWORD
This amendment has been prepared by subcommittee 23E: Circuit-breakers and similar
equipment for household use, of IEC technical committee 23: Electrical accessories.
The text of this amendment is based on the following documents:
FDIS Report on voting
23E/740/FDIS 23E/744/RVD
Full information on the voting for the approval of this amendment can be found in the report
on voting indicated in the above table.
The committee has decided that the contents of this amendment and the base publication will
remain unchanged until the stability date indicated on the IEC web site under
"http://webstore.iec.ch" in the data related to the specific publication. At this date, the
publication will be
• reconfirmed,
• withdrawn,
• replaced by a revised edition, or
• amended.
The contents of the corrigendum of May 2016 have been included in this copy.
_____________
1 Scope
Delete Note 5 and replace it by the following paragraph and new Note 5:
For RCCBs incorporated in, or intended only for association with socket-outlets, the
requirements of this standard may be used, as far as applicable, in conjunction with the
requirements of IEC 60884-1 or the national requirements of the country where the product is
placed on the market.
NOTE 5 RCCBs incorporated in, or intended only for association with socket-outlets, can either meet IEC 62640
or this standard.
2 Normative references
Delete the reference to IEC 60051.
Add to the existing list, the following new references:
IEC 60228:2004, Conductors of insulated cables
IEC 60664-3, Insulation coordination for equipment within low-voltage systems - Part 3: Use
of coating, potting or moulding for protection against pollution
Replace the reference to IEC 61543:1995 by the following new reference:
IEC 61543:1995, Residual current-operated protective devices (RCDs) for household and
similar use – Electromagnetic compatibility

61008-1 Amend.1 © IEC:2012 – 3 –
Amendment 1(2004)
Amendment 2 (2005)
4.10 According to the method of connection
In this subclause, replace the existing text and note by the following:
– RCCBs, the electrical connections of which are not associated with the mechanical
mounting;
– RCCBs, the electrical connections of which are associated with the mechanical mounting.
NOTE Examples of this type are:
– plug-in type;
– bolt-on type;
– screw-in type.
Some RCCBs may be of the plug-in type or bolt-on type on the line side only, the load terminals being usually
suitable for wiring connection.
Add the following new subclause:
4.11 According to the type of terminals:
– RCCBs with screw-type terminals for external copper conductors;
– RCCBs with screwless type terminals for external copper conductors;
NOTE 1 The requirements for RCCBs equipped with this type of terminals are given in Annex J.
– RCCBs with flat quick-connect terminals for external copper conductors;
NOTE 2 The requirements for RCCBs equipped with these types of terminals are given in Annex K.
– RCCBs with screw-type terminals for external aluminium conductors;
NOTE 3 The requirements for RCCBs equipped with these types of terminals are under consideration.
Table 1 – Limit values of break time and non-actuating time for alternating residual
currents (r.m.s values) for type AC and A RCCB
Replace, in this Table, the word “non-operating” by “non-actuating”.
Table 3 – Rated impulse withstand voltage as a function of the nominal voltage of the
installation
Replace, in Note 2, "see Table 15" by "see Table 22".
Replace, in table footnote a), "(see Tables 5 and 15)" by "(see Tables 5 and 22)".
6 Marking and other product information
Replace the contents of item k) by the following:
k) the position of use, if necessary;
Replace in the twelfth paragraph after Note 1, the word “circuit” by “conductor”
Add the following text at the end of Clause 6:
For universal terminals (for rigid-solid, rigid-stranded and flexible conductors):
– no marking.
– 4 – 61008-1 Amend.1 © IEC:2012
For non-universal terminals:
– terminals declared for rigid-solid conductors only shall be marked by the letters “s” or
"sol";
– terminals declared for rigid (solid and stranded) conductors only shall be marked by the
letter "r".
The markings should appear on the RCCB or, if the space available is not sufficient, on the
smallest package unit or in technical information.
8.1.3 Clearances and creepage distances (see Annex B)
Replace the existing text of this subclause by the following:
The minimum required clearances and creepage distances are given in Table 5 which is
based on the RCCB being designed for operating in an environment with pollution degree 2.
Compliance for item 1 in Table 5 is checked by measurement and by the test of 9.7.7.4.1 and
9.7.7.4.2. The test is carried out with samples not submitted to the humidity treatment
described in 9.7.1.
The clearances of items 2, 4 and 5 may be reduced provided that the measured clearances
are not shorter than the minimum allowed in IEC 60664-1 for homogenous field conditions.
In this case, after the humidity treatment described in 9.7.1, compliance for items 2, 4 and 5
and arrangements of 9.7.2 items b), c), d) and e) is checked in the following order:
– Tests according to 9.7.2 to 9.7.6 as applicable,
– Test according to 9.7.7.2 is applied with test voltages given in Table 16 with test
arrangements of 9.7.2 items b), c), d), e).
If measurement does not show any reduced clearance, test in 9.7.7.2 is not applied.
Compliance for item 3 in Table 5 is checked by measurement.
NOTE 1 All measurements required in 8.1.3 are carried out in Test sequence A on one sample and the tests of
9.7.7.2 are carried out before 9.7.1 on three samples of Test sequence B.
Parts of PCBs connected to the live parts protected against pollution by the use of a type 2
protection according to IEC 60664-3 are exempt from this verification.
The insulating materials are classified into material groups on the basis of their comparative
tracking index (CTI) according to 4.8.1 of IEC 60664-1:2007.
NOTE 2 Information on the requirements for design of solid insulation and appropriate testing is provided in
IEC 60664-1:2007, 5.3 and 6.1.3.
NOTE 3 For clearances on printed wiring material, the following Note 3 Table F.2 in 60664-1:2007 can be used:
“For printed wiring material, the values for pollution degree 1 apply except that the value shall not be less than
0,04 mm, as specified in Table F.4.” For creepage distances on printed wiring material, distances in Table F.4 in
60664-1:2007 can be used if protected with a coating meeting IEC 60664-3 requirements and tests.
NOTE 4 The dimensioning of clearances and creepage distances for spacings equal to or less than 2 mm for
printed wiring board may be optimised under certain conditions in case of use of IEC 60664-5. Only humidity levels
HL2 and HL3 are considered.
Table 5 – Minimum clearances and creepage distances
Delete, in this table, point 5 in the first column and the existing Note 3.
e
by the following text:
Replace, in this table, the last sentence of the existing footnote

61008-1 Amend.1 © IEC:2012 – 5 –
When interpolating, linear interpolation shall be used and values shall be rounded to the same number of digits as
the values picked up from the tables. For determination of creepage distances, see Annex B.
8.1.4.4
In the subclause, replace the existing text by the following:
Current-carrying parts including parts intended for protective conductors, if any, shall be
made of a metal having, under the conditions occurring in the equipment, mechanical
strength, electrical conductivity and resistance to corrosion adequate for their intended use.
Examples of suitable materials are given below:
– copper;
– an alloy containing at least 58 % copper for parts worked cold, or at least 50 % copper for
other parts;
– other metal or suitably coated metal, no less resistant to corrosion than copper and having
mechanical properties no less suitable.
Replace the existing note of this subclause by the following text:
In case of using ferrous alloys or suitably coated ferrous alloys, compliance to resistance to
corrosion is checked by a test of resistance to rusting (9.25).
This correction applies to the French text only.

8.1.5.1
Delete the second paragraph and the note in this subclause.
Replace the contents of the last paragraph by the following:
Compliance is checked by inspection, by the tests of 9.5 for screw-type terminals, by specific
tests for plug-in or bolt-on RCCBs included in the standard, or by the tests of Annex J, K or L,
as relevant for the type of connection.
8.1.5.2
Replace the existing text and Table 6 by the foll
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.