Petrol filling stations - Part 1: Safety requirements for construction and performance of metering pumps, dispensers and remote pumping units

This European Standard applies to metering pumps, dispensers and remote pumping units to be installed at petrol filling stations, designed to dispense liquid fuels into the tanks of motor vehicles, boats and light aircraft and into portable containers at flow rates up to 200 l min-1, and intended for use and storage at ambient temperatures between -20 °C and +40 °C. Measures in addition to those required by this standard may be required for use and storage at temperature outside this range. The need for and nature of additional requirements should be determined by the manufacturer, if necessary after consulting the client.
This European Standard deals with all significant hazards, hazardous situations and events relevant to metering pumps, dispensers and remote pumping units, when they are used as intended and under the conditions foreseeable by the manufacturer (see clause 4).
This European Standard gives health and safety related requirements for the selection, construction and performance of the equipment.
This European Standard does not deal with noise and with hazards related to transportation and installation.
This European Standard does not include any requirements for metering performance.
Vapour recovery efficiency rates are not considered within this European Standard.
This European Standard is not applicable to metering pumps, dispensers and remote pumping units which are manufactured before the date of publication of this document by CEN.
NOTE   Liquefied petroleum gas (LPG) is not a liquid fuel in the sense of this European Standard.

Tankstellen - Teil 1: Sicherheitstechnische Anforderungen an Bau- und Arbeitsweise von Zapfsäulen, druckversorgten Zapfsäulen und Fernpumpen

Diese Europäische Norm gilt für Zapfsäulen, druckversorgte Zapfsäulen und Fernpumpen, die an Tankstellen
für die Abgabe von flüssigen Kraftstoffen in Tanks von Automobilen, Booten und Leichtflugzeugen und in
tragbare Behälter bei Durchflussraten bis zu 200 l ⋅min−1, installiert werden und die für den Gebrauch und die
Lagerung bei Umgebungstemperaturen zwischen −20 °C und +40 °C vorgesehen sind. ! Zusätzlich zu den
in dieser Norm geforderten Maßnahmen dürfen weitere Maßnahmen für den Gebrauch und die Lagerung bei
Umgebungstemperaturen außerhalb dieses Bereichs verlangt werden. Der Bedarf an und die Art der
zusätzlichen Maßnahmen sollten vom Hersteller, falls erforderlich nach Beratung mit dem Kunden, bestimmt
werden."
Diese Europäische Norm behandelt alle kennzeichnenden Gefährdungen, Gefährdungssituationen und
Ereignisse, die Zapfsäulen, druckversorgte Zapfsäulen und Fernpumpen betreffen, wenn sie wie vorgesehen
und nach den absehbaren Bedingungen des Herstellers verwendet werden (siehe Abschnitt 4).
Diese Europäische Norm beinhaltet gesundheits- und sicherheitstechnische Anforderungen an die
Auswahl, den Bau und die Arbeitsweise der Einrichtungen."
Diese Europäische Norm befasst sich nicht mit Lärm und mit Gefährdungen in Bezug auf Transport und
Installation.
Diese Europäische Norm beinhaltet keine Anforderungen für Messausführungen.
Effizienzraten für Gasrückführung fallen nicht in den Anwendungsbereich dieser Europäischen Norm.
Diese Europäische Norm gilt nicht für Zapfsäulen, druckversorgte Zapfsäulen und Fernpumpen, die vor der
Publikation dieser Norm durch CEN hergestellt wurden.
ANMERKUNG Flüssiggas (LPG) ist keine Flüssigkeit im Sinne dieser Europäischen Norm.

Stations-service - Partie 1: Exigences relatives à la construction et aux performances de sécurité des distributeurs à pompe immergée, distributeurs de carburants et unités de pompage à distance

Bencinski servisi - 1. del: Varnostne zahteve za izdelavo in lastnosti avtomatov za točenje bencina, razdeljevalnikov in oddaljenih črpalnih enot

General Information

Status
Withdrawn
Publication Date
17-Nov-2009
Withdrawal Date
08-Aug-2012
Technical Committee
Current Stage
9900 - Withdrawal (Adopted Project)
Start Date
08-Aug-2012
Due Date
31-Aug-2012
Completion Date
09-Aug-2012

Relations

Buy Standard

Standard
EN 13617-1:2004+A1:2009
English language
54 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.Tankstellen - Teil 1: Sicherheitstechnische Anforderungen an Bau- und Arbeitsweise von Zapfsäulen, druckversorgten Zapfsäulen und FernpumpenStations-service - Partie 1: Exigences relatives à la construction et aux performances de sécurité des distributeurs à pompe immergée, distributeurs de carburants et unités de pompage à distancePetrol filling stations - Part 1: Safety requirements for construction and performance of metering pumps, dispensers and remote pumping units75.200Petroleum products and natural gas handling equipmentICS:Ta slovenski standard je istoveten z:EN 13617-1:2004+A1:2009SIST EN 13617-1:2004+A1:2009en,fr,de01-december-2009SIST EN 13617-1:2004+A1:2009SLOVENSKI
STANDARD



SIST EN 13617-1:2004+A1:2009



EUROPEAN STANDARD NORME EUROPÉENNE EUROPÄISCHE NORM
EN 13617-1:2004+A1
June 2009 ICS 75.200 Supersedes EN 13617-1:2004English Version
Petrol filling stations - Part 1: Safety requirements for construction and performance of metering pumps, dispensers and remote pumping units
Stations-service - Partie 1: Exigences relatives à la construction et aux performances de sécurité des distributeurs de carburants et unités de pompage à distance
Tankstellen - Teil 1: Sicherheitstechnische Anforderungen an Bau- und Arbeitsweise von Zapfsäulen, druckversorgten Zapfsäulen und Fernpumpen This European Standard was approved by CEN on 5 May 2004 and includes Corrigendum 1 issued by CEN on 25 Janvier 2006 and Amendment 1 approved by CEN on 21 May 2009.
CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN Management Centre or to any CEN member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by translation under the responsibility of a CEN member into its own language and notified to the CEN Management Centre has the same status as the official versions.
CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION EUROPÄISCHES KOMITEE FÜR NORMUNG
Management Centre:
Avenue Marnix 17,
B-1000 Brussels © 2009 CEN All rights of exploitation in any form and by any means reserved worldwide for CEN national Members. Ref. No. EN 13617-1:2004+A1:2009: ESIST EN 13617-1:2004+A1:2009



EN 13617-1:2004+A1:2009 (E) 2 Contents pageForeword . 41Scope . 62Normative references . 63Terms and definitions . 74List of significant hazards . 115Safety requirements and/or protective measures . 135.1Explosion protection measures . 135.2Selection of equipment . 145.3Safety requirements, protective measures, construction and performance . 215.4Safety requirements related to electromagnetic phenomena . 296Tests . 306.1Type tests . 306.2Routine tests . 377Information for use . 387.1General . 387.2Signals and warnings . 397.3Accompanying documents . 397.4Marking . 40Annex A (normative)
Classification of vapour barriers . 41A.1General . 41A.2Vapour barrier Type 1 . 41A.3Vapour barrier Type 2 . 41A.4Typical vapour barrier arrangements . 42Annex B (informative)
Information on explosion protected equipment . 48Annex ZA (informative)
˜Relationship between this European Standard and the Essential Requirements of EU Directive 94/9/EC™ . 50Annex ZB (informative)
!Relationship between this European Standard and the Essential Requirements of EU Directive 98/37/EC" . 52Annex ZC (informative)
!Relationship between this European Standard and the Essential Requirements of EU Directive 2006/42/EC" . 53Bibliography . 54Figures Figure 1 — Nozzle outside a housing at distance > 50 mm and ≤≤≤≤ 200 mm . 16Figure 2 — Nozzle outside a housing at distance > 50 mm and ≤≤≤≤ 200 mm . 17Figure 3 — Nozzle outside a housing at distance ≤≤≤≤ 50 mm. 18Figure 4 — Nozzle boot area, front view. 19Figure 5 — Nozzle boot area, side view. 20Figure 6 — Nozzle boot area, top view . 21Figure 7 — Test set-up for the impact test . 32Figure 8 — Test set-up for flame transmission test . 35Figure A.1 — Horizontal vapour barrier Type 1 . 42Figure A.2 — Vertical vapour barrier Type 1 . 43Figure A.3 — Horizontal vapour barrier Type 2 . 44SIST EN 13617-1:2004+A1:2009



EN 13617-1:2004+A1:2009 (E) 3 Figure A.4 — Vertical vapour barrier Type 2. 45Figure A.5 — Vertical vapour barrier Type 2. 46Figure A.6 — Vertical vapour barrier Type 2. 47 Tables Table 1 — List of significant hazards . 12Table 2 — Test voltages . 33Table 3 — Routine electrical tests . 38Table B.1 — Standard protection concepts allowed . 49Table ZA.1 — Essential requirements of Directive 94/9/EC Equipment and protective systems intended for use in potentially explosive atmospheres — Annex II . 50 SIST EN 13617-1:2004+A1:2009



EN 13617-1:2004+A1:2009 (E) 4 Foreword This document (EN 13617-1:2004+A1:2009) has been prepared by Technical Committee CEN/TC 393 “Equipment for storage tanks and for service stations”, the secretariat of which is held by DIN. This European Standard shall be given the status of a national standard, either by publication of an identical text or by endorsement, at the latest by December 2009, and conflicting national standards shall be withdrawn at the latest by December 2009. This document includes Amendment 1, approved by CEN on 2009-05-21 and Corrigendum 1, issued by CEN on
25 January 2006. This document supersedes EN 13617-1:2004. The start and finish of text introduced or altered by amendment is indicated in the text by tags ! ". The modifications of the related CEN Corrigendum have been implemented at the appropriate places in the text and are indicated by the tags ˜ ™. This document has been prepared under a mandate given to CEN by the European Commission and the European Free Trade Association, and supports essential requirements of EU Directive(s). !For relationship with EU Directives, see informative Annexes ZA, ZB and ZC, which are integral parts of this document." This European Standard “Petrol filling stations” consists of 4 parts: Part 1: Safety requirements for construction and performance of metering pumps, dispensers and remote pumping units Part 2 !deleted text" : Safety requirements for construction and performance of safe breaks for use on metering pumps and dispensers Part 3 !deleted text" : Safety requirements for construction and performance of shear valves Part 4 !deleted text" : Safety requirements for construction and performance of swivels for use on metering pumps and dispensers Annex A is normative. Annex B is informative. According to the CEN/CENELEC Internal Regulations, the national standards organizations of the following countries are bound to implement this European Standard: Austria, Belgium, Bulgaria, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom.
SIST EN 13617-1:2004+A1:2009



EN 13617-1:2004+A1:2009 (E) 5 Introduction This document is a type C standard as stated in !EN ISO 12100-1 and EN 12100-2". The machinery concerned and the extent to which hazards, hazardous situations and events are covered are indicated in the scope of this document. When provisions of this type C standard are different from those which are stated in type A or B standards, the provisions of this type C standard take precedence over the provisions of the other standards, for machines that have been designed and built according to the provisions of the type C standard. It has been assumed that the use of the equipment for dispensing of fuels will be by untrained persons (user / dispenser), while other aspects of the operation, maintenance, etc, will be by designated and trained personnel (station personnel or operator). SIST EN 13617-1:2004+A1:2009



EN 13617-1:2004+A1:2009 (E) 6
1 Scope This European Standard applies to metering pumps, dispensers and remote pumping units to be installed at petrol filling stations, designed to dispense liquid fuels into the tanks of motor vehicles, boats and light aircraft and into portable containers at flow rates up to 200 l·min-1, and intended for use and storage at ambient temperatures between -20 °C and +40 °C. !Measures in addition to those required by this standard may be required for use and storage at temperature outside this range. The need for and nature of additional requirements should be determined by the manufacturer, if necessary after consulting the client." This European Standard deals with all significant hazards, hazardous situations and events relevant to metering pumps, dispensers and remote pumping units, when they are used as intended and under the conditions !foreseeable" by the manufacturer (see clause 4). !This European Standard gives health and safety related requirements for the selection, construction and performance of the equipment." This European Standard does not deal with noise and with hazards related to transportation and installation. This European Standard does not include any requirements for metering performance. Vapour recovery efficiency rates are not considered within this European Standard. This European Standard is not applicable to metering pumps, dispensers and remote pumping units which are manufactured before the date of publication of this document by CEN. NOTE Liquefied petroleum gas (LPG) is not a liquid fuel in the sense of this European Standard. 2 Normative references !The following referenced documents are indispensable for the application of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies." EN 228, Automotive fuels — Unleaded petrol — Requirements and test methods !deleted text" EN 1360, Rubber hoses and hose assemblies for measured fuel dispensing — Specification EN 12874, Flame arresters — Performance requirements, test methods and limits for use EN 13012, Petrol filling stations — Construction and performance of automatic nozzles for use on fuel dispensers EN 13463-1:2001, Non-electrical equipment for potentially explosive atmospheres — Part 1: Basic method and requirements !EN 13483", !Rubber and plastic hoses" and hose assemblies with internal vapour recovery for measured fuel dispensing systems — Specification !deleted text" !EN 60079-0:2006, Electrical apparatus for explosive gas atmospheres — Part 0: General requirements
(IEC 60079-0:2004, modified) EN 60079-1:2007, Explosive atmospheres — Part 1: Equipment protection by flameproof enclosures "d" (IEC 60079-1:2007) SIST EN 13617-1:2004+A1:2009



EN 13617-1:2004+A1:2009 (E) 7 EN 60079-7:2007, Explosive atmospheres — Part 7: Equipment protection by increased safety "e"
(IEC 60079-7:2006)" EN 60079-10, Electrical apparatus for explosive gas atmospheres — Part 10: Classification of hazardous areas !(IEC 60079-10:2002)" EN 60079-14, Electrical apparatus for explosive gas atmospheres — Part 14: Electrical installations in hazardous areas (other than mines) !(IEC 60079-14:2002)" !EN 60079-15, Electrical apparatus for explosive gas atmospheres — Part 15: Construction, test and marking of type of protection "n" electrical apparatus (IEC 60079-15:2005)" !EN 60204-1:2006, Safety of machinery — Electrical equipment of machines — Part 1: General requirements (IEC 60204-1:2005, modified)" EN 60529, Degrees for protection provided by enclosures (IP code) (IEC 60529:1989) EN 60730-2-10, Automatic electrical controls for household and similar use — Part 2: Particular requirements for motor starting relays !(IEC 60730-2-10:2006)" EN 60947-3, Low-voltage switchgear and controlgear — Part 3: Switches, disconnectors, switch-disconnectors and fuse-combination units (IEC 60947-3:1999) EN 60950-1, Information technology equipment — Safety — Part 1: General requirements !(IEC 60950-1:2005, modified)" EN ISO 1182, Reaction to fire tests for building products — Non-combustibility test (ISO 1182:2002) EN ISO 12100-1:2003, Safety of machinery — Basic concepts, general principles for design — Part 1: Basic terminology, methodology (ISO 12100-1:2003) EN ISO 12100-2:2003, Safety of machinery — Basic concepts, general principles for design — Part 2: Technical principles (ISO 12100-2:2003) !EN ISO 13849-1, Safety of machinery — Safety-related parts of control systems — Part 1: General principles for design (ISO 13849-1:2006) EN ISO 14121-1, Safety of machinery — Risk assessment — Part 1: Principles (ISO 14121-1:2007)" ISO 11925-3, Reaction to fire tests — Ignitability of building products subjected to direct impingement of flame — Part 3: Multi-source test HD21.13 S1, Polyvinyl chloride insulated cables of rated voltages up to and including 450/750 V — Part 13: Oil resistant PVC sheathed cables with two or more conductors HD22.4 S3, Rubber insulated cables of rated voltages up to and including 450/750 V — Part 4: Cords and flexible cables 3 Terms and definitions For the purposes of this European Standard, the terms and definitions given in !EN ISO 12100-1" and the following apply. 3.1 air and/or vapour separator device used for continuously separating and removing air or gases contained in the liquid 3.2 delivery hose assembly flexible delivery system to which the nozzle is connected SIST EN 13617-1:2004+A1:2009



EN 13617-1:2004+A1:2009 (E) 8 3.3 column extension fabrication extending upwards from a metering pump/dispenser hydraulic housing 3.4 metering pump measuring system containing its own pumping system to draw and deliver liquid fuel from a supply tank or tanks into the tanks of motor vehicles, boats and light aircraft and into portable containers 3.5 dispenser measuring and delivery system similar to that of a metering pump but without an integral pumping system 3.6 multi product metering pump/dispenser unit designed to deliver liquid fuels where the customer can choose from more than one product, this may include systems where the fuel delivered is a mix of more than one base fuel 3.7 remote pumping unit suction pump assembly mounted remotely from a dispenser 3.8 filling station establishment providing for the delivery of liquid fuels into the tanks of motor vehicles, boats and light aircraft and into portable containers 3.9 hazardous area area in which an explosive gas atmosphere is present, or may be expected to be present, in quantities such as to require special precautions for the construction, installation and use of apparatus 3.10 non-hazardous area according to EN 60079-10 3.11 metering unit device for continuously measuring the amount of liquid fuels delivered 3.12 safe-break according to !EN 13617-2" 3.13 type of protection the specific measures applied to electrical apparatus to avoid ignition of a surrounding explosive atmosphere [!EN 60079-0:2006"] 3.14 metering pump/dispensers hydraulic housing housing which provides physical protection to the liquid and/or vapour equipment 3.15 automatic delivery nozzle (nozzle) according to EN 13012 3.16 vapour recovery nozzle according to EN 13012 SIST EN 13617-1:2004+A1:2009



EN 13617-1:2004+A1:2009 (E) 9 3.17 nozzle boot location, normally a partially enclosed housing, where the nozzle or vapour recovery nozzle is stored when not in use 3.18 nozzle sensor device detecting the nozzle position in the nozzle boot 3.19 vapour barrier sealing system to limit hazardous areas 3.20 shear valve (impact check valve) normally open valve(s), activated by impact and heat, which closes to prevent flow from a pressure source and remains closed after activation 3.21 sight glass device to allow
checking that all, or part, of the measuring system is completely filled with liquid 3.22 vapour recovery system system in and attached to the metering pump/dispenser to feed back the vapours displaced from the fuel tank and led back into the vapour return lines to the storage tank 3.23 vapour pump pump positioned in the vapour recovery system to supply vacuum for vapour suctioning 3.24 screen perforated cladding fabrication which may be provided to enhance the visual appearance of a pump or dispenser or to provide another related function 3.25 vapour pipe tubing of the vapour recovery system, excluding the vapour recovery delivery hose assembly and vapour recovery nozzle 3.26 retraction system system to assist the stowage of delivery hose assembly or vapour recovery delivery hose assembly 3.27 hose cassette separate assembly primarily for the storage of delivery hose assembly(s) or vapour recovery delivery hose assembly(s) 3.28 normal operation situation when the equipment, protective systems, and components perform their intended function within their design parameters (see also 5.2.2 a) of EN ISO 12100-1:2003) NOTE Minor release of flammable material may be part of normal operation. For example, releases of substances from seals which rely on wetting by the fluid which is being pumped are considered to be minor releases. NOTE Failures (such as a breakdown of pump seals, flange gaskets or releases of substances caused by accidents) which involve repair or shut-down are not considered to be part of normal operation. [see EN 1127-1:1997] SIST EN 13617-1:2004+A1:2009



EN 13617-1:2004+A1:2009 (E) 10 3.29 cladding external panels that serve no structural, load bearing, purpose but which contribute to the physical protection of the contents of the housing 3.30 vapour trap unventilated part of a structure where vapours can accumulate creating an area of greater hazard than its immediate surroundings 3.31 preset delivery (preset) delivery where the maximum volume (cost) for that delivery is fixed, either directly at the metering pump/dispenser or remote from the metering pump/dispenser, before the delivery commences 3.32 preset slowdown last part of a preset delivery where the flow rate is limited by the metering pump/dispenser to allow accurate completion of the delivery 3.33 flow rate volume flow delivered, in l⋅min-1or m3⋅h-1under normal working conditions 3.34 potential ignition source any part of a process that is able to cause an ignition of an explosive atmosphere 3.35 high hose inlet joint delivery hose assembly connection at a location on equipment that will be at a height greater than 2 m above ground level when the equipment is installed 3.36 de-mountable joint joint which is designed to be assembled and disassembled 3.37 satellite delivery system remote delivery system connected to a metering pump/dispenser 3.38 check valve normally closed, opened by flow of liquid in normal working conditions 3.39 catastrophic failure irreversible damage resulting in an unsafe condition
3.40 routine test test performed on each unit on completion of manufacture 3.41 powering up sequence internal sequence of events that follows the application of electrical power to the equipment SIST EN 13617-1:2004+A1:2009



EN 13617-1:2004+A1:2009 (E) 11 4 List of significant hazards This clause contains the significant hazards and hazardous situations, as far as they are dealt with in this European Standard, identified by a risk assessment significant for metering pumps, dispensers and remote pumping units used for the dispensing of liquid fuels, and which require action to eliminate or reduce risks. Before using this standard it is important to carry out a risk assessment of equipment to check that it has the hazards identified in this clause. SIST EN 13617-1:2004+A1:2009



EN 13617-1:2004+A1:2009 (E) 12 Table 1 — List of significant hazards Significant hazards according to !EN ISO 14121-1" Significant hazards, danger zones, hazardous situations or events, associated with the covered machinery Safety requirement No. Type of hazard — Clauses of this standard
1 Mechanical hazards due to: — machine parts or work pieces, e.g. a) shape; b) relative location; c) mass and stability (potential energy of elements
which may move under the effect of gravity); d) mass and velocity (kinetic energy of elements in
controlled or uncontrolled motion); e) inadequacy of mechanical strength. f) moving parts
Drive belts and/or shafts
5.3.6.2,
7.3 1.9 High pressure fluid injection or ejection hazard Fluid in the hose, pipes etc. 5.3.1.5,
5.3.1.6, 5.3.3.2,
5.3.4 2 Electrical hazards due to — — 2.1 Contact of persons with live parts (direct contact) Electrical components e.g. motors, solenoid valves, control systems, lighting
5.3.2 2.2 Contact of persons with parts which have become live under faulty conditions (indirect contact) Electrical components e.g. motors, solenoid valves, control systems, lighting
5.3.2 2.4 Electrostatic phenomena Charging of
belts, hoses and cladding 5.3.4.1,
5.3.3.4 5.3.4.3 3 Thermal hazards, resulting in: — — 3.1 Burns and other injuries by
possible explosions
Ignition of possible explosive atmosphere by electrical or non-electrical parts or electrical charge 5.1,
5.2,
5.3
7 Hazards generated by materials and substances
(and their constituent elements) processed or used by the machinery — — 7.1 Hazards from contact with or inhalation of harmful fluids, gases, mists, fumes, and dusts Tightness of components, pipes, hoses 5.3.3,
5.3.4,
SIST EN 13617-1:2004+A1:2009



EN 13617-1:2004+A1:2009 (E) 13
Table 1 (concluded) Hazards according to !EN ISO 14121-1" Significant hazards, danger zones, hazardous situations or events, associated with the covered machinery Safety requirement 7.2 Fire or explosion hazard Sparks or high temperatures from electrical and non-electrical parts in combination with explosive atmospheres 5.1,
5.2,
5.3
10 Unexpected start-up, unexpected overrun/ overspeed (or any similar malfunction) from: — — 10.1 Failure/disorder of the control system Explosive atmospheres due to unexpected liquid flow 5.3.1.2,
5.3.4.2,
10.2 Restoration of energy supply after an interruption Explosive atmospheres due to unexpected liquid flow 5.3.1.2 10.3 External influences on electrical equipment Explosive atmospheres due to unexpected liquid flow 5.3.1.2,
5.3.2.1 10.5 Errors in the software Explosive atmospheres due to unexpected liquid flow 5.3.1.2 10.6 Errors made by the operator (due to mismatch of machinery with human characteristics and abilities)
Explosive atmospheres due to unexpected liquid flow 5.3.1.2,
5.3.1.3, 7.2 11 Impossibility of stopping the machine in the best possible conditions Explosive atmospheres due to unexpected liquid flow 5.3.1.2,
5.3.1.3 5.3.4.2 13 Failure of the power supply Explosive atmospheres due to unexpected liquid flow 5.3.1.2 14 Failure of the control circuit
Explosive atmospheres due to unexpected liquid flow 5.3.1.1,
5.3.1.2,
5.3.1.3 5.3.2 15 Errors of fitting Leakage 7.3 16 Break-up during operation Leakage 5.3.1.1, 5.3.1.4, 5.3.1.6,
5.3.4.7
17 Falling or ejected objects or fluids Moving parts and ejected fuel 5.3.4
5.3.6 18 Loss of stability / overturning of machinery Stability of the dispenser in normal use Vehicle movement 5.3.1.6
6.1.5 5.3.4.7
7.3 5 Safety requirements and/or protective measures 5.1 Explosion protection measures 5.1.1 Explosion protection measures should be taken in accordance with annex B. 5.1.2 Equipment, components and protective systems used within hazardous areas, shall be suitable as a minimum requirement for Explosion Group IIA with temperature class T3 as defined in !EN 60079-0" and EN 13463-1. SIST EN 13617-1:2004+A1:2009



EN 13617-1:2004+A1:2009 (E) 14 5.2 Selection of equipment 5.2.1 General 5.2.1.1 Hazardous areas considered in this standard are only those created by an individual metering pump/dispenser in open air. 5.2.1.2 The use of the expression 'hazardous areas' and ‘zones’ within this standard is restricted to the selection of equipment, protective systems and protective measures. 5.2.1.3 All references to the degree of protection IP54 shall be taken as IP54 Category 2 according to EN 60529. 5.2.1.4 Hazardous areas are created in and around metering pumps/dispensers as shown in 5.2. The extent of hazardous areas may be limited by the use of Type 1 or Type 2 vapour barriers. 5.2.1.5 Enclosures for use in zone 2 areas shall either: a) be as defined in !EN 60079-15" for an enclosure totally immersed in a zone 2; or b) have
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.