Electrical installation guide - Part 53: Selection and erection of electrical equipment - Switchgear and controlgear

This technical report is for use as a guide for electrical installations.  It explains the relationship between the time/current characteristic of protective devices and wiring, prospective short-circuit currents and maximum length of wiring and the thermal characteristics of conductors.[
]The contents of the corrigendum of October 1995 have been included in this copy.

Guide pour les installations électriques - Partie 53: Choix et mise en oeuvre des matériels électriques - Appareillage

Ce rapport technique est destiné à servir de guide pour les installations électriques.  Il explique la relation entre les caractéristiques temps/courant des dispositifs de protection et les canalisations, les courants présumés de court-circuit, les longueurs maximales des canalisations et les caractéristiques thermiques des conducteurs.[
]Le contenu du corrigendum d'octobre 1995 a été pris en considération dans cet exemplaire.

Vodilo za električne inštalacije – 53. del: Izbira in namestitev električne opreme – Stikalne in krmilne naprave

General Information

Status
Published
Publication Date
31-Jan-2000
Current Stage
6060 - National Implementation/Publication (Adopted Project)
Start Date
01-Feb-2000
Due Date
01-Feb-2000
Completion Date
01-Feb-2000

Buy Standard

Standard
IEC 60079-10-1:2015 - Explosive atmospheres - Part 10-1: Classification of areas - Explosive gas atmospheres
English and French language
226 pages
sale 15% off
Preview
sale 15% off
Preview
Technical report
SIST IEC/TR2 61200-53:2000
English language
17 pages
sale 10% off
Preview
sale 10% off
Preview

e-Library read for
1 day

Standards Content (sample)

IEC 60079-10-1
Edition 2.0 2015-09
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE
colour
inside
Explosive atmospheres –
Part 10-1: Classification of areas – Explosive gas atmospheres
Atmosphères explosives –
Partie 10-1: Classement des emplacements – Atmosphères explosives gazeuses
IEC 60079-10-1:2015-09(en-fr)
---------------------- Page: 1 ----------------------
THIS PUBLICATION IS COPYRIGHT PROTECTED
Copyright © 2015 IEC, Geneva, Switzerland

All rights reserved. Unless otherwise specified, no part of this publication may be reproduced or utilized in any form

or by any means, electronic or mechanical, including photocopying and microfilm, without permission in writing from

either IEC or IEC's member National Committee in the country of the requester. If you have any questions about IEC

copyright or have an enquiry about obtaining additional rights to this publication, please contact the address below or

your local IEC member National Committee for further information.

Droits de reproduction réservés. Sauf indication contraire, aucune partie de cette publication ne peut être reproduite

ni utilisée sous quelque forme que ce soit et par aucun procédé, électronique ou mécanique, y compris la photocopie

et les microfilms, sans l'accord écrit de l'IEC ou du Comité national de l'IEC du pays du demandeur. Si vous avez des

questions sur le copyright de l'IEC ou si vous désirez obtenir des droits supplémentaires sur cette publication, utilisez

les coordonnées ci-après ou contactez le Comité national de l'IEC de votre pays de résidence.

IEC Central Office Tel.: +41 22 919 02 11
3, rue de Varembé Fax: +41 22 919 03 00
CH-1211 Geneva 20 info@iec.ch
Switzerland www.iec.ch
About the IEC

The International Electrotechnical Commission (IEC) is the leading global organization that prepares and publishes

International Standards for all electrical, electronic and related technologies.
About IEC publications

The technical content of IEC publications is kept under constant review by the IEC. Please make sure that you have the

latest edition, a corrigenda or an amendment might have been published.
IEC Catalogue - webstore.iec.ch/catalogue Electropedia - www.electropedia.org

The stand-alone application for consulting the entire The world's leading online dictionary of electronic and

bibliographical information on IEC International Standards, electrical terms containing 20 000 terms and definitions in

Technical Specifications, Technical Reports and other English and French, with equivalent terms in 15 additional

documents. Available for PC, Mac OS, Android Tablets and languages. Also known as the International Electrotechnical

iPad. Vocabulary (IEV) online.

IEC publications search - www.iec.ch/searchpub IEC Glossary - std.iec.ch/glossary

The advanced search enables to find IEC publications by a 65 000 electrotechnical terminology entries in English and

variety of criteria (reference number, text, technical French extracted from the Terms and Definitions clause of

committee,…). It also gives information on projects, replaced IEC publications issued since 2002. Some entries have been

and withdrawn publications. collected from earlier publications of IEC TC 37, 77, 86 and

CISPR.
IEC Just Published - webstore.iec.ch/justpublished

Stay up to date on all new IEC publications. Just Published IEC Customer Service Centre - webstore.iec.ch/csc

details all new publications released. Available online and If you wish to give us your feedback on this publication or

also once a month by email. need further assistance, please contact the Customer Service

Centre: csc@iec.ch.
A propos de l'IEC

La Commission Electrotechnique Internationale (IEC) est la première organisation mondiale qui élabore et publie des

Normes internationales pour tout ce qui a trait à l'électricité, à l'électronique et aux technologies apparentées.

A propos des publications IEC

Le contenu technique des publications IEC est constamment revu. Veuillez vous assurer que vous possédez l’édition la

plus récente, un corrigendum ou amendement peut avoir été publié.
Catalogue IEC - webstore.iec.ch/catalogue Electropedia - www.electropedia.org
Application autonome pour consulter tous les renseignements
Le premier dictionnaire en ligne de termes électroniques et
bibliographiques sur les Normes internationales,
électriques. Il contient 20 000 termes et définitions en anglais
Spécifications techniques, Rapports techniques et autres
et en français, ainsi que les termes équivalents dans 15
documents de l'IEC. Disponible pour PC, Mac OS, tablettes
langues additionnelles. Egalement appelé Vocabulaire
Android et iPad.
Electrotechnique International (IEV) en ligne.
Recherche de publications IEC - www.iec.ch/searchpub
Glossaire IEC - std.iec.ch/glossary
65 000 entrées terminologiques électrotechniques, en anglais
La recherche avancée permet de trouver des publications IEC

en utilisant différents critères (numéro de référence, texte, et en français, extraites des articles Termes et Définitions des

comité d’études,…). Elle donne aussi des informations sur les publications IEC parues depuis 2002. Plus certaines entrées

projets et les publications remplacées ou retirées. antérieures extraites des publications des CE 37, 77, 86 et

CISPR de l'IEC.
IEC Just Published - webstore.iec.ch/justpublished
Service Clients - webstore.iec.ch/csc
Restez informé sur les nouvelles publications IEC. Just

Published détaille les nouvelles publications parues. Si vous désirez nous donner des commentaires sur cette

Disponible en ligne et aussi une fois par mois par email. publication ou si vous avez des questions contactez-nous:

csc@iec.ch.
---------------------- Page: 2 ----------------------
IEC 60079-10-1
Edition 2.0 2015-09
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE
colour
inside
Explosive atmospheres –
Part 10-1: Classification of areas – Explosive gas atmospheres
Atmosphères explosives –
Partie 10-1: Classement des emplacements – Atmosphères explosives gazeuses
INTERNATIONAL
ELECTROTECHNICAL
COMMISSION
COMMISSION
ELECTROTECHNIQUE
INTERNATIONALE
ICS 29.260.20 ISBN 978-2-8322-3112-8

Warning! Make sure that you obtained this publication from an authorized distributor.

Attention! Veuillez vous assurer que vous avez obtenu cette publication via un distributeur agréé.

® Registered trademark of the International Electrotechnical Commission
Marque déposée de la Commission Electrotechnique Internationale
---------------------- Page: 3 ----------------------
– 2 – IEC 60079-10-1:2015 © IEC 2015
CONTENTS

FOREWORD ........................................................................................................................... 6

INTRODUCTION ..................................................................................................................... 9

1 Scope ............................................................................................................................ 10

2 Normative references .................................................................................................... 10

3 Terms and definitions .................................................................................................... 11

4 General ......................................................................................................................... 15

4.1 Safety principles ................................................................................................... 15

4.2 Area classification objectives ................................................................................ 16

4.3 Explosion risk assessment .................................................................................... 16

4.4 Competence of personnel ..................................................................................... 17

5 Area classification methodology .................................................................................... 17

5.1 General ................................................................................................................. 17

5.2 Classification by sources of release method .......................................................... 18

5.3 Use of industry codes and national standards ....................................................... 18

5.4 Simplified methods ............................................................................................... 18

5.5 Combination of methods ....................................................................................... 19

6 Release of flammable substance ................................................................................... 19

6.1 General ................................................................................................................. 19

6.2 Sources of release ................................................................................................ 19

6.3 Forms of release ................................................................................................... 20

6.3.1 General ......................................................................................................... 20

6.3.2 Gaseous release ........................................................................................... 21

6.3.3 Liquefied under pressure ............................................................................... 21

6.3.4 Liquefied by refrigeration ............................................................................... 22

6.3.5 Aerosols ........................................................................................................ 22

6.3.6 Vapours ......................................................................................................... 22

6.3.7 Liquid releases .............................................................................................. 22

6.4 Ventilation (or air movement) and dilution ............................................................. 23

6.5 Main types of ventilation ....................................................................................... 23

6.5.1 General ......................................................................................................... 23

6.5.2 Natural ventilation.......................................................................................... 23

6.5.3 Artificial ventilation ........................................................................................ 24

6.5.4 Degree of dilution .......................................................................................... 25

7 Type of zone ................................................................................................................. 26

7.1 General ................................................................................................................. 26

7.2 Influence of grade of the source of release ........................................................... 26

7.3 Influence of dilution ............................................................................................... 27

7.4 Influence of availability of ventilation ..................................................................... 27

8 Extent of zone ............................................................................................................... 27

9 Documentation .............................................................................................................. 28

9.1 General ................................................................................................................. 28

9.2 Drawings, data sheets and tables ......................................................................... 28

Annex A (informative) Suggested presentation of hazardous areas ...................................... 30

A.1 Hazardous area zones – Preferred symbols ................................................................. 30

A.2 Hazardous area suggested shapes ....................................................................... 33

---------------------- Page: 4 ----------------------
IEC 60079-10-1:2015 © IEC 2015 – 3 –

Annex B (informative) Estimation of sources of release........................................................ 35

B.1 Symbols ................................................................................................................ 35

B.2 Examples of grade of release ................................................................................ 35

B.2.1 General ......................................................................................................... 35

B.2.2 Sources giving a continuous grade of release ................................................ 35

B.2.3 Sources giving a primary grade of release ..................................................... 36

B.2.4 Sources giving a secondary grade of release ................................................. 36

B.3 Assessment of grades of release .......................................................................... 36

B.4 Summation of releases ......................................................................................... 37

B.5 Hole size and source radius .................................................................................. 38

B.6 Forms of release ................................................................................................... 40

B.7 Release rate ......................................................................................................... 41

B.7.1 General ......................................................................................................... 41

B.7.2 Estimation of Release Rate ........................................................................... 41

B.7.3 Release rate of evaporative pools .................................................................. 44

B.8 Release from openings in buildings ....................................................................... 46

B.8.1 General ......................................................................................................... 46

B.8.2 Openings as possible sources of release ....................................................... 46

B.8.3 Openings classification .................................................................................. 46

Annex C (informative) Ventilation guidance .......................................................................... 48

C.1 Symbols ................................................................................................................ 48

C.2 General ................................................................................................................. 49

C.3 Assessment of ventilation and dilution and its influence on hazardous area .......... 49

C.3.1 General ......................................................................................................... 49

C.3.2 Effectiveness of ventilation ............................................................................ 50

C.3.3 Criteria for dilution ......................................................................................... 50

C.3.4 Assessment of ventilation velocity ................................................................. 51

C.3.5 Assessment of the degree of dilution ............................................................. 52

C.3.6 Dilution in a room .......................................................................................... 53

C.3.7 Criteria for availability of ventilation ............................................................... 55

C.4 Examples of ventilation arrangements and assessments ....................................... 56

C.4.1 Introduction ................................................................................................... 56

C.4.2 Jet release in a large building ........................................................................ 56

C.4.3 Jet release in a small naturally ventilated building ......................................... 57

C.4.4 Jet release in a small artificially ventilated building ........................................ 57

C.4.5 Release with low velocity ............................................................................... 58

C.4.6 Fugitive emissions ......................................................................................... 59

C.4.7 Local ventilation-extraction ............................................................................ 59

C.5 Natural Ventilation in buildings .............................................................................. 60

C.5.1 General ......................................................................................................... 60

C.5.2 Wind induced ventilation ................................................................................ 60

C.5.3 Buoyancy induced ventilation......................................................................... 61

C.5.4 Combination of the natural ventilation induced by wind and buoyancy ........... 63

Annex D (informative) Estimation of hazardous zones.......................................................... 65

D.1 General ................................................................................................................. 65

D.2 Estimating types of the zones ............................................................................... 65

D.3 Estimating the extent of the hazardous zone ......................................................... 65

Annex E (informative) Examples of hazardous area classification ........................................ 68

---------------------- Page: 5 ----------------------
– 4 – IEC 60079-10-1:2015 © IEC 2015

E.1 General ................................................................................................................. 68

E.2 Examples .............................................................................................................. 68

E.3 Example case study for area classification ............................................................ 83

Annex F (informative) Schematic approach to classification of hazardous areas .................. 93

F.1 Schematic approach to classification of hazardous areas ...................................... 93

F.2 Schematic approach to classification of hazardous areas ...................................... 94

F.3 Schematic approach to classification of hazardous areas ...................................... 95

F.4 Schematic approach to classification of hazardous areas ...................................... 96

Annex G (informative) Flammable mists ............................................................................... 97

Annex H (informative) Hydrogen .......................................................................................... 99

Annex I (informative) Hybrid mixtures ................................................................................ 101

I.1 General ............................................................................................................... 101

I.2 Use of ventilation ................................................................................................ 101

I.3 Concentration limits ............................................................................................ 101

I.4 Chemical reactions ............................................................................................. 101

I.5 Energy/Temperature limits .................................................................................. 101

I.6 Zoning requirements ........................................................................................... 101

Annex J (informative) Useful equations in support to hazardous area classification .......... 102

J.1 General ............................................................................................................... 102

J.2 Dilution with air of a flammable substance release .............................................. 102

J.3 Estimate of the time required to dilute a flammable substance release ................ 102

Annex K (informative) Industry codes and national standards ............................................ 104

K.1 General ............................................................................................................... 104

Bibliography ........................................................................................................................ 106

Figure A.1 – Preferred symbols for hazardous area zones .................................................... 30

Figure A.2 – Gas/vapour at low pressure (or at high pressure in case of unpredictable

release direction) .................................................................................................................. 33

Figure A.3 – Gas/vapour at high pressure ............................................................................. 33

Figure A.4 – Liquefied gas .................................................................................................... 34

Figure A.5 – Flammable liquid (non boiling evaporative pool) ................................................ 34

Figure B.1 – Forms of release ............................................................................................... 40

Figure B.2 – Volumetric evaporation rate of liquids ............................................................... 45

Figure C.1 – Chart for assessing the degree of dilution ......................................................... 52

Figure C.2 – Self diffusion of an unimpeded high velocity jet release .................................... 57

Figure C.3 – Supply only ventilation ...................................................................................... 58

Figure C.4 – Supply and extraction ventilation ...................................................................... 58

Figure C.5 – Local extraction ventilation ............................................................................... 60

Figure C.6 – Volumetric flow rate of fresh air per m of equivalent effective opening

area ...................................................................................................................................... 63

Figure C.7 – Example of opposing ventilation driving forces ................................................. 64

Figure D.1 – Chart for estimating hazardous area distances ................................................. 66

Figure E.1 – Degree of dilution (Example No. 1) ................................................................... 69

Figure E.2 – Hazardous distance (Example No. 1) ................................................................ 70

Figure E.3 – Zone classification (Example No. 1) .................................................................. 70

Figure E.4 – Degree of dilution (Example No. 2) ................................................................... 72

---------------------- Page: 6 ----------------------
IEC 60079-10-1:2015 © IEC 2015 – 5 –

Figure E.5 – Hazardous distance (Example No. 2) ................................................................ 73

Figure E.6 – Degree of dilution (Example No. 3) ................................................................... 75

Figure E.7 – Hazardous distance (Example No. 3) ................................................................ 76

Figure E.8 – Zones classification (Example No. 3) ................................................................ 76

Figure E.9 – Degree of dilution (Example No. 4) ................................................................... 78

Figure E.10 – Hazardous distance (Example No. 4) .............................................................. 79

Figure E.11 – Zones classification (Example No. 4) .............................................................. 79

Figure E.12 – Degree of dilution (Example No. 5) ................................................................. 82

Figure E.13 – Hazardous distance (Example No. 5) .............................................................. 83

Figure E.14 – Enclosed compressor handling natural gas ..................................................... 85

Figure E.15 – Example of area classification for a compressor facility handling natural

gas (elevation) ...................................................................................................................... 91

Figure E.16 – Example of area classification for a compressor facility handling natural

gas (plan) ............................................................................................................................. 92

Figure F.1 – Schematic approach to classification ................................................................ 93

Figure F.2 – Schematic approach to classification for continuous grade releases .................. 94

Figure F.3 – Schematic approach to classification for primary grade releases ....................... 95

Figure F.4 – Schematic approach to classification for secondary grade releases .................. 96

Table A.1 − Hazardous area classification data sheet – Part I: Flammable substance

list and characteristics .......................................................................................................... 31

Table A.2 − Hazardous area classification data sheet − Part II: List of sources of

release ................................................................................................................................. 32

Table B.1 – Suggested hole cross sections for secondary grade of releases ......................... 39

Table B.2 – Effect of hazardous zones on openings as possible sources of release ............. 47

Table C.1 – Indicative outdoor ventilation velocities (u ) ...................................................... 52

Table D.1 – Zones for grade of release and effectiveness of ventilation ................................ 65

Table E.1 – Compressor facility handling natural gas ............................................................ 86

Table E.2 – Hazardous area classification data sheet − Part I: Flammable substance

list and characteristics .......................................................................................................... 88

Table E.3 – Hazardous area classification data sheet − Part II: List of sources of

release (1 of 2) ..................................................................................................................... 89

Table K.1 – Examples of codes and standards .................................................................... 105

---------------------- Page: 7 ----------------------
– 6 – IEC 60079-10-1:2015 © IEC 2015
INTERNATIONAL ELECTROTECHNICAL COMMISSION
____________
EXPLOSIVE ATMOSPHERES –
Part 10-1: Classification of areas –
Explosive gas atmospheres
FOREWORD

1) The International Electrotechnical Commission (IEC) is a worldwide organization for standardization comprising

all national electrotechnical committees (IEC National Committees). The object of IEC is to promote

international co-operation on all questions concerning standardization in the electrical and electronic fields. To

this end and in addition to other activities, IEC publishes International Standards, Technical Specifications,

Technical Reports, Publicly Available Specifications (PAS) and Guides (hereafter referred to as “IEC

Publication(s)”). Their preparation is entrusted to technical committees; any IEC National Committee interested

in the subject dealt with may participate in this preparatory work. International, governmental and non-

governmental organizations liaising with the IEC also participate in this preparation. IEC collaborates closely

with the International Organization for Standardization (ISO) in accordance with conditions determined by

agreement between the two organizations.

2) The formal decisions or agreements of IEC on technical matters express, as nearly as possible, an international

consensus of opinion on the relevant subjects since each technical committee has representation from all

interested IEC National Committees.

3) IEC Publications have the form of recommendations for international use and are accepted by IEC National

Committees in that sense. While all reasonable efforts are made to ensure that the technical content of IEC

Publications is accurate, IEC cannot be held responsible for the way in which they are used or for any

misinterpretation by any end user.

4) In order to promote international uniformity, IEC National Committees undertake to apply IEC Publications

transparently to the maximum extent possible in their national and regional publications. Any divergence

between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in

the latter.

5) IEC itself does not provide any attestation of conformity. Independent certification bodies provide conformity

assessment services and, in some areas, access to IEC marks of conformity. IEC is not responsible for any

services carried out by independent certification bodies.

6) All users should ensure that they have the latest edition of this publication.

7) No liability shall attach to IEC or its directors, employees, servants or agents including individual experts and

members of its technical committees and IEC National Committees for any personal injury, property damage or

other damage of any nature whatsoeve
...

SLOVENSKI STANDARD
SIST IEC/TR2 61200-53:2000
01-februar-2000

9RGLOR]DHOHNWULþQHLQãWDODFLMH±GHO,]ELUDLQQDPHVWLWHYHOHNWULþQHRSUHPH±

6WLNDOQHLQNUPLOQHQDSUDYH

Electrical installation guide - Part 53: Selection and erection of electrical equipment -

Switchgear and controlgear

Guide pour les installations électriques - Partie 53: Choix et mise en oeuvre des

matériels électriques - Appareillage
Ta slovenski standard je istoveten z: IEC/TS 61200-53
ICS:
29.130.01 Stikalne in krmilne naprave Switchgear and controlgear
na splošno in general
91.140.50 Sistemi za oskrbo z elektriko Electricity supply systems
SIST IEC/TR2 61200-53:2000 en

2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

---------------------- Page: 1 ----------------------
SIST IEC/TR2 61200-53:2000
---------------------- Page: 2 ----------------------
SIST IEC/TR2 61200-53:2000
RAPPORT CEI
TECHNIQUE IEC
1200-53
TECHNICAL
Première édition
REPORT
First edition
1994-10
Guide pour les installations électriques —
Partie 53:
Choix et mise en oeuvre des matériels électriques -
Appareillage
Electrical installation guide —
Part 53:
Selection and erection of electrical equipment —
Switchgear and controlgear
Numéro de référence
IEC
Reference number
CEI/IEC 1200-53: 1994
---------------------- Page: 3 ----------------------
SIST IEC/TR2 61200-53:2000
Numéros des publications Numbering
CEI As from 1 January 1997 all IEC publications are
Depuis le 1er janvier 1997, les publications de la

sont numérotées à partir de 60000. issued with a designation in the 60000 series.

Consolidated publications
Publications consolidées

Les versions consolidées de certaines publications de Consolidated versions of some IEC publications

including amendments are available. For example,
la CEI incorporant les amendements sont disponibles.

Par exemple, les numéros d'édition 1.0, 1.1 et 1.2 edition numbers 1.0, 1.1 and 1.2 refer, respectively, to

indiquent respectivement la publication de base, la the base publication, the base publication incor-

porating amendment 1 and the base publication
publication de base incorporant l'amendement 1, et
incorporating amendments 1 and 2.
la publication de base incorporant les amendements 1
et 2.
Validité publication Validity of this publication
de la présente

Le contenu technique des publications de la CEI est The technical content of IEC publications is kept under

constamment revu par la CEI afin qu'il reflète l'état constant review by the IEC, thus ensuring that the

content reflects current technology.
actuel de la technique.
Information relating to the date of the reconfirmation of
Des renseignements relatifs à la date de re-

confirmation de la publication sont disponibles dans the publication is available in the IEC catalogue.

le Catalogue de la CEI.
Information on the subjects under consideration and
Les renseignements relatifs à des questions à l'étude et
work in progress undertaken by the technical com-
des travaux en cours entrepris par le comité technique

qui a établi cette publication, ainsi que la liste des mittee which has prepared this publication, as well as

the list of publications issued, is to be found at the
publications établies, se trouvent dans les documents
following IEC sources:
ci-dessous:
• IEC web site*
• «Site web» de la CEI*
• Catalogue of IEC publications
• Catalogue des publications de la CEI
Published yearly with regular updates
Publié annuellement et mis à jour régulièrement
(Catalogue en ligne)* (On-line catalogue)*
• Bulletin de la CEI • IEC Bulletin

Disponible à la fois au «site web» de la CEI* Available both at the IEC web site* and

as a printed periodical
et comme périodique imprimé
Terminologie, symboles graphiques Terminology, graphical and letter
et littéraux symbols
For general terminology, readers are referred to
En ce qui concerne la terminologie générale, le lecteur

se reportera à la CEI 60050: Vocabulaire Electro- IEC 60050: International Electrotechnical Vocabulary

(VEI). (IEV).
technique International
For graphical symbols, and letter symbols and signs
Pour les symboles graphiques, les symboles littéraux
approved by the IEC for general use, readers are
et les signes d'usage général approuvés par la CEI, le
Symboles littéraux à referred to publications IEC 60027: Letter symbols to
lecteur consultera la CEI 60027:
Symboles be used in electrical technology, IEC 60417: Graphical
utiliser en électrotechnique, la CEI 60417:

graphiques utilisables sur le matériel. Index, relevé et symbols for use on equipment. Index, survey and

compilation des feuilles individuelles, et la CEI 60617: compilation of the single sheets and IEC 60617:

Graphical symbols for diagrams.
Symboles graphiques pour schémas.
la page de titre. * See web site address on title page.
* Voir adresse «site web» sur
---------------------- Page: 4 ----------------------
SIST IEC/TR2 61200-53:2000
RAPPORT CEI
TECHNIQUE - TYPE 2 I EC
1200-53
TECHNICAL
Première
édition
REPORT - TYPE 2
First edition
1994-10
électriques —
Guide pour les installations
Partie 53:
Choix et mise en oeuvre des matériels électriques —
Appareillage
Electrical installation guide —
Part 53:
Selection and erection of electrical equipment —
Switchgear and controlgear
réservés — Copyright - all rights reserved
© CEI 1994 Droits de reproduction
No part of this publication may be reproduced or utilized in
Aucune partie de cette publication ne peut être reproduite ni
any form or by any means, electronic or mechanical,
utilisée sous quelque forme que ce soit et par aucun pro-
including photocopying and microfilm, without permission
cédé, électronique ou mécanique, y compris la photocopie et
in writing from the publisher.
les microfilms, sans l'accord écrit de l'éditeur.
Genève, Suisse

Bureau Central de la Commission Electrotechnique Internationale 3, rue de Varembé

CODE PRIX
Commission Electrotechnique Internationale
International Electrotechnical Commission J
PRICE CODE
IEC McNgiyuapoQHae 3nelcrpoTe%HH4ecna i HoMHCCHa
voir catalogue en vigueur
Pour prix, ^
For price, see current catalogue
---------------------- Page: 5 ----------------------
SIST IEC/TR2 61200-53:2000
IEC Publication 1200-53
Publication 1200-53 de la CEI
(First edition - 1994)
(Première édition - 1994)
installations électriques – Electrical installation guide –
Guide pour les
Partie 53:
Part 53:
Choix et mise en oeuvre des matériels électriques –
Selection and erection of electrical equipment –
Appareillage
Switchgear and controlgear
C O R R I G E N D U M 1
Page 5
Page 4
In the second column of the table, indicating
Dans la deuxième colonne du tableau,
the report on voting, add the following:
indiquant le rapport de vote, ajouter ce qui
suit:
64(SEC)677B
64(SEC)677B
Page 7
Page 6
Under the title, before subclause 53. 1, add
Sous le titre, avant le paragraphe 53. 1,
the following introductory lines:
ajouter les lignes d’introduction suivantes:
In the informative annexes A and B,
Dans les annexes informatives A et B, des
information is given, respectively, on the
informations sont données, respectivement
choice of the utilisation categories of low-
sur le choix des catégories d’emploi des
voltage switchgear and controlgear and on
appareillages à basse tension et sur les
the methods of installation of electrical
méthodes d’ins-tallation des accessoires
accessories for household and similar
électriques pour usages domestiques et
analogues. applications.
Page 17
Page 16
After figure 4, add the following annexes A
Après la figure 4, ajouter les annexes A et B
and B:
suivantes:
(see overleaf)
(voir au verso)
---------------------- Page: 6 ----------------------
SIST IEC/TR2 61200-53:2000
− 2 −
Annexe A
(informative)
Exemples de catégories d’emploi pour l’appareillage à
basse tension
(voir annexe B de la CEI 947-1)
Norme CEI
Nature du
Catégorie Applications caractéristiques de matériel
courant
correspondante
(voir article 1)

Alternatif AC-1 Charges non inductives ou faiblement inductives, fours à résistances

AC-2 Moteurs à bagues: démarrage, coupure
Moteurs à cage: démarrage, coupure des moteurs lancés
AC-3
AC-4 Moteurs à cage: démarrage, inversion de marche 1 ), marche par
à-coups
Commande de lampes à décharge
AC-5a
AC-5b Commande de lampes à incandescence 947-1
AC-6a Commande de transformateurs
AC-6b Commande de batteries de condensateurs
AC-7a Charges faiblement inductives pour appareils domestiques et appli-
cations similaires
AC-7b Moteurs pour applications domestiques
AC-8a Commande de moteurs de compresseurs hermétiques de réfrigéra-
tion avec réarmement manuel des déclencheurs de surcharge
AC-8b Commande de moteurs de compresseurs hermétiques de réfrigéra-
tion avec réarmement automatique des déclencheurs de surcharge
AC-12 Commande de charges ohmiques et de charges statiques isolées par
photo-coupleur
AC-13 Commande de charges statiques isolées par transformateur 947-5
AC-14 Commande de faibles charges électromagnétiques d’électro-aimants
Commande de charges électromagnétiques d’électro-aimants
AC-15
AC-20 Fermeture et ouverture à vide
AC-21 Charges ohmiques, y compris surcharges modérées
AC-22
Charges mixtes ohmiques et inductives, y compris surcharges
modérées 947-3
AC-23 Charges constituées par des moteurs ou autres charges fortement
inductives
Alternatif A
Protection des circuits sans courant assigné de courte durée
et admissible
947-2
continu B Protection des circuits avec courant assigné de courte durée
admissible
Charges non inductives ou faiblement inductives, fours à résistances
Continu DC-1
DC-3 Moteurs shunts, démarrage, inversion de marche 1 ), marche par
947-4
à-coups
, coupure dynamique de moteurs
DC-5 Moteurs série, démarrage, inversion de marche 1 ), marche par
à-coups 2), coupure dynamique de moteurs
DC-6 Commande de lampes à incandescence
DC-12 Commande de charges ohmiques et de charges statiques isolées par
photo-coupleurs
DC-13 Commande d’électro-aimants à courant continu 947-5
DC-14 Commande d’électro-aimants à courant continu ayant des résis-
tances d’économie
DC-20 Fermeture et ouverture à vide
DC-21 Charges résistives, y compris surcharges modérées
DC-22 Charges mixtes résistives et inductives, y compris surcharges 947-3
modérées (par exemple: moteurs shunt)
DC-23 Charges fortement inductives (par exemple: moteurs série)

Par inversion de marche, on entend l’arrêt ou l’inversion rapide du sens de rotation du moteur en permutant

des connexions d’alimentation du moteur pendant que celui-ci tourne.

Par marche par à-coups, on entend une commande caractérisée par une ou plusieurs fermetures brèves et

fréquentes du circuit d’un moteur, afin d’obtenir de petits déplacements de l’organe entraîné.

---------------------- Page: 7 ----------------------
SIST IEC/TR2 61200-53:2000
− 3 −
Annex A
(informative)
Examples of utilization categories for low-voltage
switchgear and controlgear
(see annex B of IEC 947-1)
Relevant IEC
Nature of
Category Typical applications product
current
standard
(see clause 1)
Non-inductive or slightly inductive loads, resistance furnaces
AC AC-1
Slip-ring motors: starting, switching off
AC-2
Squirrel-cage motors: starting, switching off motors during running
AC-3
1 2)
AC-4 Squirrel-cage motors: starting, plugging ), inching
AC-5a Switching of electic discharge lamp control
AC-5b Switching of incandescent lamps 947-1
AC-6a Switching of transformers
AC-6b Switching of capacitor banks
AC-7a Slightly inductive loads in household appliances and similar
applications
AC-7b Motor-loads for household applications
AC-8a Hermetic refrigerant compressor motor control with manual resetting
of overload releases
AC-8b Hermetic refrigerant compressor motor control with automatic
resetting of overload releases
AC-12 Control of resistive loads and solid state loads with isolation by
optocouplers
AC-13 Control of solid state loads with transformer isolation 947-5
AC-14 Control of small electromagnetic loads
AC-15 Control of a.c. electromagnetic loads
AC-20 Connecting and disconnecting under no-load conditions
AC-21 Switching of resistive loads, including moderate overloads
AC-22 Switching of mixed resistive and inductive loads, including moderate
overloads 947-3
AC-23 Switching of motor loads or other highly inductive loads
AC A Protection of circuits, with no rated short-time withstand current
947-2
and DC B Protection of circuits, with a rated short-time withstand current
DC DC-1 Non-inductive or slightly inductive loads, resistance furnaces
DC-3 1 ), inching 2), dynamic breaking of
Shunt-motors, starting, plugging
947-4
motors
DC-5 Series-motors, starting, plugging 1 ), inching 2), dynamic breaking of
motors
DC-6 Switching of incandescent lamps
DC-12 Control of resistive loads and solid state loads with isolation by
optocouplers
DC-13 Control of d.c. electromagnets 947-5
DC-14 Control of d.c. electromagnetic loads having economy resistors in
circuit
DC-20 Connecting and disconnecting under non-load conditions
DC-21 Switching of resistive loads, including moderate overloads
DC-22 Switching of mixed resistive and inductive loads, including moderate 947-3
overloads (e.g. shunt motors)
DC-23 Switching of highly inductive loads (e.g. series motors)

By plugging is understood stopping or reversing the motor rapidly by reversing motor primary connections

while the motor is running.

By inching (jogging) is understood energizing a motor once or repeatedly for short periods to obtain small

movements of the driven mechanism.
---------------------- Page: 8 ----------------------
SIST IEC/TR2 61200-53:2000
− 4 −
Annexe B
(informative)
Méthodes d’installation des électriques
appareillages
(voir CEI 669-1 et 884-1)

Selon leur méthode d’installation, les appareillages électriques sont classifiés (voir paragraphe

7.1.7 de la CEI 669-1, sur les interrupteurs et le paragraphe 7.2.3 de la CEI 884-1, sur les

prises de courant pour les installations domestiques et analogues, comme suit:

− appareillages de conception A, si le capot ou une plaque de couverture ou des parties de

ces derniers peuvent être retirés sans déplacement des conducteurs;

− appareillages de conception B, si le capot ou une plaque de couverture ou des parties de

ces derniers ne peuvent être retirés sans déplacement des conducteurs;

NOTE − Si un appareil fixe possède un socle (partie principale) ne pouvant être séparé du couvercle ou de

la plaque de couverture, et qui nécessite une plaque supplémentaire pouvant être retirée pour des travaux

de décoration murale sans déplacement des conducteurs, alors cet appareillage est considéré comme étant

de conception A, à condition que la plaque supplémentaire satisfasse aux prescriptions spécifiées pour les

couvercles et les plaques de couverture.

Les appareillages de type A et B sont considérés comme sûrs s’ils sont correctement installés

et utilisés.
---------------------- Page: 9 ----------------------
SIST IEC/TR2 61200-53:2000
− 5 −
Annex B
(informative)
Methods of installation of electrical accessories
(see IEC 669-1 and 884-1)

According to their method of installation, fixed accessories are classified (see subclause 7.1.7

of IEC 669-1, concerning switches, and subclause 7.2.3 of IEC 884-1, concerning socket-

outlets, for household and similar applications) as follows:

− accessories of design A, where the cover or cover-plate or parts of them can be removed

without displacement of the conductors;

− accessories of design B, where the cover or cover-plate or parts of them cannot be

removed without displacement of the conductors.

NOTE − If a fixed accessory has a base (main part) which cannot be separated from the cover or cover-

plate, and requires a supplementary plate which can be removed for redecorating the wall without

displacement of the conductors, it is considered to be of design A, provided the supplementary plate meets

the requirements specified for covers and cover-plates.

Both accessories of design A and of design B are considered to be adequately safe when

correctly installed and used.
Octobre 1995 October 1995
---------------------- Page: 10 ----------------------
SIST IEC/TR2 61200-53:2000
---------------------- Page: 11 ----------------------
SIST IEC/TR2 61200-53:2000
– 2 – 1200-53 ©CEI:1994
COMMISSION ÉLECTROTECHNIQUE INTERNATIONALE
GUIDE POUR LES INSTALLATIONS ÉLECTRIQUES —
Partie 53: Choix et mise en oeuvre des matériels électriques —
Appareillage
AVANT-PROPOS

1) La CEI (Commission Electrotechnique Internationale) est une organisation mondiale de normalisation

composée de l'ensemble des comités électrotechniques nationaux (Comités nationaux de la CEI). La CEI a

pour objet de favoriser la coopération internationale pour toutes les questions de normalisation dans les

domaines de l'électricité et de l'électronique. A cet effet, la CEI, entre autres activités, publie des Normes

internationales. Leur élaboration est confiée à des comités d'études, aux travaux desquels tout Comité

national intéressé par le sujet traité peut participer. Les organisations internationales, gouvernementales et

non gouvernementales, en liaison avec la CEI, participent également aux travaux. La CEI collabore

étroitement avec l'Organisation Internationale de Normalisation (ISO), selon des conditions fixées par

accord entre les deux organisations.

Les décisions ou accords officiels de la CEI en ce qui concerne les questions techniques, préparés par les

comités d'études où sont représentés tous les Comités nationaux s'intéressant à ces questions, expriment

dans la plus grande mesure possible un accord international sur les sujets examinés.

3) Ces décisions constituent des recommandations internationales publiées sous forme de normes, de

rapports techniques ou de guides et agréées comme telles par les Comités nationaux.

4) Dans le but d'encourager l'unification internationale, les Comités nationaux de la CEI s'engagent

appliquer de façon transparente, dans toute la mesure possible, les Normes internationales de la CEI

dans leurs normes nationales et régionales. Toute divergence entre la norme de la CEI et la norme

nationale ou régionale correspondante doit être indiquée en termes clairs dans cette dernière.

La tâche principale des comités d'études de la CEI est d'élaborer des Normes

internationales. Exceptionnellement, un comité d'études peut proposer la publication d'un

rapport technique de l'un des types suivants:

type 1, lorsque, en dépit de maints efforts, l'accord requis ne peut être réalisé en

faveur de la publication d'une Norme internationale;
type 2, lorsque le sujet en question est encore en cours de développement

technique ou lorsque, pour une raison quelconque, la possibilité d'un accord pour la

publication d'une Norme internationale peut être envisagée pour l'avenir mais pas dans

l'immédiat;
• type 3, lorsqu'un comité d'études a réuni des données de nature différente de
celles qui sont normalement publiées comme Normes internationales, cela pouvant
comprendre, par exemple, des informations sur l'état de la technique.

Les rapports techniques des types 1 et 2 font l'objet d'un nouvel examen trois ans au plus

tard après leur publication afin de décider éventuellement de leur transformation en

Normes internationales. Les rapports techniques de type 3 ne doivent pas nécessairement

être révisés avant que les données qu'ils contiennent ne soient plus jugées valables ou

utiles.
technique de type 2, a par le comité d'études 64 de
La CEI 1200-53, rappo rt été établie
la CEI: Installations électriques des bâtiments.
---------------------- Page: 12 ----------------------
SIST IEC/TR2 61200-53:2000
1200-53 © - 3 -
IEC:1994
INTERNATIONAL ELECTROTECHNICAL COMMISSION
ELECTRICAL INSTALLATION GUIDE —
Part 53: Selection and erection of electrical equipment —
Switchgear and controlgear
FOREWORD

1) The IEC (International Electrotechnical Commission) is a worldwide organization for standardization

comprising all national electrotechnical committees (IEC National Committees). The object of the IEC is to

promote international cooperation on all questions concerning standardization in the electrical and

electronic fields. To this end and in addition to other activities, the IEC publishes International Standards.

Their preparation is entrusted to technical committees; any IEC National Committee interested in the

subject dealt with may participate in this preparatory work. International, governmental and

non-governmental organizations liaising with the IEC also participate in this preparation. The IEC

collaborates closely with the International Organization for Standardization (ISO) in accordance with

conditions determined by agreement between the two organizations.

2) The formal decisions or agreements of the IEC on technical matters, prepared by technical committees on

which all the National Committees having a special interest therein are represented, express, as nearly as

possible, an international consensus of opinion on the subjects dealt with.

3) They have the form of recommendations for international use published in the form of standards, technical

reports or guides and they are accepted by the National Committees in that sense.

In order to promote international unification, IEC National Committees undertake to apply IEC International

Standards transparently to the maximum extent possible in their national and regional standards. Any

divergence between the IEC Standard and the corresponding national or regional standard shall be clearly

indicated in the latter.

The main task of IEC technical committees is to prepare International Standards. In excep-

tional circumstances, a technical committee may propose the publication of a technical

of one of the following types:
repo rt
cannot be obtained for the publication of an Inter-
• type 1, when the required suppo rt
rts;
national Standard, despite repeated effo

type 2, when the subject is still under technical development or where for any other

reason there is the future but not immediate possibility of an agreement on an Inter-

national Standard;

• type 3, when a technical committee has collected data of a different kind from that

which is normally published as an International Standard, for example "state of the a rt".

s of types 1 and 2 are subject to review within three years of publication to
Technical repo rt

decide whether they can be transformed into International Standards. Technical reports of

type 3 do not necessarily have to be reviewed until the data they provide are considered

to be no longer valid or useful.
of type 2, has been prepared by IEC technical
IEC 1200-53, which is a technical repo rt
committee 64: Electrical installations of buildings.
---------------------- Page: 13 ----------------------
SIST IEC/TR2 61200-53:2000
– 4 – 1200-53 ©CEI:1994
complément à la CEI 364-5-53 pour le choix
Le présent guide donne des indications en
courts-circuits
des de protection destinés à protéger les canalisations contre les
dispositifs
de protection.
concernant la sélectivité relative entre dispositifs
et donne des explications
du présent guide correspondent à ceux de la CEI 364-5-53.
Les numéros des paragraphes
rapport technique est issu des documents suivants:
Le texte de ce
de comité Rapport de vote
Projet
64(SEC)677A
64(SEC)630A
donne toute information sur le vote
Le rapport de vote indiqué dans le tableau ci-dessus
ce rapport technique.
ayant abouti à l'approbation de
Le présent document est publié dans la série des rapports techniques de
type 2 (conformément au paragraphe G.4.2.2 de la partie 1 des Directives
CEI/ISO) comme 'norme prospective d'application provisoire' dans le
domaine des systèmes d'isolation car il est urgent d'avoir des indications
sur la meilleure façon d'utiliser les normes dans ce domaine afin de
répondre à un besoin déterminé.
Ce document ne doit pas être considéré comme une 'Norme
internationale». Il est proposé pour une mise en oeuvre provisoire, dans
le but de recueillir des informations et d'acquérir de l'expérience quant à
son application dans la pratique. Il est de règle d'envoyer les observations
éventuelles relatives au contenu de ce document au Bureau Central de
la CEI.
Il sera procédé à un nouvel examen de ce rapport technique de type 2
trois ans au plus tard après sa publication, avec la faculté d'en prolonger
la validité pendant trois autres années, de le transformer en Norme
internationale ou de l'annuler.
---------------------- Page: 14 ----------------------
SIST IEC/TR2 61200-53:2000
1200-53 © IEC:1994 - 5 -

This guide gives additional information to the requirements according to IEC 364-5-53 for

the selection of protective devices to protect wiring systems against short-circuit currents

and explains how protective devices are to be selected in order to achieve discrimination.

The subclause numbers used herein are in line with subclauses in IEC 364-5-53.
The text of this technical report is based on the following documents:
Committee draft Report on voting
64(SEC)630
64(SEC)677A
64(SEC)630A

Full information on the voting for the approval of this technical report can be found in the

repo rt on voting indicated in the above table.
document is issued in the type 2 technical report series of
This
1 of the IEC/ISO Directives) as
publications (according to G.4.2.2 of pa rt
a "prospective standard for provisional application" in the field of insu-
lation systems because there is an urgent requirement for guidance on
how standards in this field should be used to meet an identified need.
document is not to be regarded as an "International Standard". It is
This
proposed for provisional application so that information and experience
of its use in practice may be gathered. Comments on the content of this
document should be sent to the IEC Central Office.
will be carried out not later than
A review of this type 2 technical report
three years after its publication, with the options of either extension for a
further three years or conversion to an International Standard or
withdrawal.
---------------------- Page: 15 ----------------------
SIST IEC/TR2 61200-53:2000
- 6 - 1200-53 ©CEI:1994
GUIDE POUR LES INSTALLATIONS ÉLECTRIQUES —
Partie 53: Choix et mise en oeuvre des matériels électriques —
Appareillage
53.1 Généralités
53.1.1 Domaine d'application

Ce rapport technique est destiné à servir de guide pour les installations électriques. Il

explique la relation entre les caractéristiques temps/courant des dispositifs de protection

et les canalisations, les courants présumés de court-circuit, les longueurs maximales des

canalisations et les caractéristiques thermiques des conducteurs.
53.1.2 Références normatives

Les documents normatifs suivants contiennent des dispositions qui, par suite de la

référence qui y est faite, constituent des dispositions valables pour la présente partie de la

CEI 1200. Au moment de la publication, les éditions indiquées étaient en vigueur. Tout

document normatif est sujet à révision et les parties prenantes aux accords fondés sur la

présente partie de la CEI 1200 sont invitées à rechercher la possibilité d'appliquer les

éditions les plus récentes des documents normatifs indiqués ci-après. Les membres de

la CEI et de l'ISO possèdent le registre des Normes internationales en vigueur.
Installations électriques des bâtiments - Quatrième partie: Protection
CEI 364-4-41: 1992,
pour assurer la sécurité - Chapitre 41: Protection contre les chocs électriques
Installations électriques des bâtiments - Quatrième partie: Protection
CEI 364-4-43: 1977,
pour assurer la sécurité - Chapitre 43: Protection contre les surintensités
Installations électriques des bâtiments - Partie 5: Choix et mise en
CEI 364-5-53: 1994,
oeuvre des matériels électriques - Chapitre 53: Appareillage
Guide d'application pour le calcul des courants de court-circuit dans les
CEI 781: 1989,
réseaux à basse tension radiaux
Calcul des courants de court-circuit dans les réseaux triphasés à courant
CEI 909: 1988,
alternatif
Appareillage à basse tension - Deuxième partie: Disjoncteurs
CEI 947-2: 1989,
Amendement n° 1 (1992)
Interrupteurs automatiques à courant différentiel-résiduel pour usages
CEI 1008-1: 1990,

domestiques et analogues sans dispositif de protection contre les surintensités incor-

poré (ID) - Partie 1: Règles générales
533.3 Choix des dispositifs de protection contre les courts-circuits

Pour appliquer les règles selon 533.3 de la CEI 364-5-53, il convient de se conformer aux

conditions suivantes:
---------------------- Page: 16 ----------------------
SIST IEC/TR2 61200-53:2000
1200-53 © I EC:1994 - 7 -
ELECTRICAL INSTALLATION GUIDE —
Part 53: Selection and erection of electrical equipment —
Switchgear and controlgear
53.1 General
53.1.1 Scope

This technical report is for use as a guide for electrical installations. It explains the relation-

ship between the time/current characteristic of protective devices and wiring, prospective

short-circuit currents and maximum length of wiring and the thermal characteristics of

conductors.
53.1.2 Normative references

The following normative documents contain provisions which, through reference in this

text, constitute provisions of this part of IEC 1200. At the time of publication, the editions

indicated were valid. All normative documents are subject to revision, and parties to agree-

ments based on this part of IEC 1200 are encouraged to investigate the possibility of

applying the most recent editions of the normative documents indicated below. Members

of IEC and ISO maintain registers of currently valid International Standards.

IEC 364-4-41: 1992, Electrical installations of buildings - Part 4: Protection for safety -

Chapter 41: Protection against electric shock