SIST CEN/TR 14819-1:2004
(Main)Safety recommendations for cableway installations designed to carry persons - Prevention and fight against fire - Part 1: Funicular railways in tunnels
Safety recommendations for cableway installations designed to carry persons - Prevention and fight against fire - Part 1: Funicular railways in tunnels
This part of CEN/TR 14819 specifies safety recommendations applicable to the prevention and fighting of fires in funicular railways in tunnels that may endanger the health and safety of persons.
This part of CEN/TR 14819 covers the design, manufacture, construction, maintenance and operation of all funicular railways running in tunnels of length greater than 300 m or where the evacuation zones are more than 300 m apart, an evacuation zone being comparable to a station from the point of view of protecting passengers against fire risks. Tunnels with these characteristics are called "long tunnels" in the following.
For shorter tunnels, some of the same measures could be applied depending on the results of the installation safety study and taking account particularly of the number of passengers and the width of the evacuation passage.
With regard to these fire problems, it is essential to take organizational measures relating to operation, but these are not covered in this document
Sicherheitsempfehlungen für Seilbahnen für den Personenverkehr - Brandverhütung und -bekämpfung - Teil 1: Tunnelstandseilbahnen
Recommandations de sécurité pour les installations a câbles transportant des personnes - Prévention et lutte contre les incendies - Partie 1 : Funiculaires en tunnel
Varnostna priporočila za žičniške naprave za prevoz oseb – Preprečevanje in gašenje požara – 1. del: Vzpenjače v predorih
General Information
Relations
Standards Content (Sample)
SLOVENSKI STANDARD
SIST CEN/TR 14819-1:2004
01-november-2004
9DUQRVWQDSULSRURþLOD]DåLþQLãNHQDSUDYH]DSUHYR]RVHE±3UHSUHþHYDQMHLQ
JDãHQMHSRåDUD±GHO9]SHQMDþHYSUHGRULK
Safety recommendations for cableway installations designed to carry persons -
Prevention and fight against fire - Part 1: Funicular railways in tunnels
Sicherheitsempfehlungen für Seilbahnen für den Personenverkehr - Brandverhütung und
-bekämpfung - Teil 1: Tunnelstandseilbahnen
Recommandations de sécurité pour les installations a câbles transportant des personnes
- Prévention et lutte contre les incendies - Partie 1 : Funiculaires en tunnel
Ta slovenski standard je istoveten z: CEN/TR 14819-1:2004
ICS:
13.220.20 3RåDUQD]DãþLWD Fire protection
45.100 2SUHPD]DåLþQLFH Cableway equipment
SIST CEN/TR 14819-1:2004 en
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
---------------------- Page: 1 ----------------------
SIST CEN/TR 14819-1:2004
---------------------- Page: 2 ----------------------
SIST CEN/TR 14819-1:2004
TECHNICAL REPORT
CEN/TR 14819-1
RAPPORT TECHNIQUE
TECHNISCHER BERICHT
September 2004
ICS 45.100; 13.220.20
English version
Safety recommendations for cableway installations designed to
carry persons - Prevention and fight against fire - Part 1:
Funicular railways in tunnels
Recommandations de sécurité pour les installations à Sicherheitsempfehlungen für Seilbahnen für den
câbles transportant des personnes - Prévention et lutte Personenverkehr - Brandverhütung und -bekämpfung - Teil
contre les incendies - Partie 1 : Funiculaires en tunnel 1: Tunnelstandseilbahnen
This Technical Report was approved by CEN on 24 February 2004. It has been drawn up by the Technical Committee CEN/TC 242.
CEN members are the national standards bodies of Austria, Belgium, Cyprus, Czech Republic, Denmark, Estonia, Finland, France,
Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Slovakia,
Slovenia, Spain, Sweden, Switzerland and United Kingdom.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION
EUROPÄISCHES KOMITEE FÜR NORMUNG
Management Centre: rue de Stassart, 36 B-1050 Brussels
© 2004 CEN All rights of exploitation in any form and by any means reserved Ref. No. CEN/TR 14819-1:2004: E
worldwide for CEN national Members.
---------------------- Page: 3 ----------------------
SIST CEN/TR 14819-1:2004
CEN/TR 14819-1:2004 (E)
Contents Page
Foreword .4
Introduction.5
1 Scope.6
2 Normative references.6
3 Terms and definitions .7
4 General recommendations.8
4.1 Application of the technical report .8
4.2 Safety principles.8
4.2.1 Hazard scenarios.8
4.2.2 Safety measures.8
5 Basic recommendations .9
6 Recommendations concerning fire prevention and firefighting in the carriers .10
6.1 Materials .10
6.2 Electrical cabinets.10
6.3 Cabling outside the electrical cabinets and lighting.10
6.4 Batteries.10
6.5 Battery chargers.11
6.6 Video equipment (camera, monitor) .11
6.7 Heating, air conditioning.11
6.8 Electrical components outside cabinets which are energized during travel (dynamos,
alternators, motors).11
6.9 Pantographs .11
6.10 Rail brake – Retarder.11
6.11 Hydraulic power plants and circuits – Pressure vessels – Refrigerants .11
6.12 Rotating parts (wheels, axles, bearings).12
6.13 Prohibition of smoking, open fires and the transportation of flammable materials.12
6.14 Extinguishers and other means of firefighting .12
6.15 Dimensioning of the carriers .12
6.16 Recovery measures in the event of a fire on board the carrier .12
6.17 Emergency exits from the carriers .13
7 Recommendations concerning fire prevention and firefighting in the tunnel.13
7.1 Tunnel materials.13
7.2 Fire – Smoke from a station.13
7.3 Rails and overhead catenaries supplying auxiliary electrical energy to the carriers.13
7.4 Lighting equipment .13
7.5 Transmission of electrical energy in the tunnel.13
7.6 Remote communication cable between carrier and control point .14
7.7 Transportation of flammable liquid inside the tunnel.14
7.8 Spaces adjacent to the tunnel (outside stations).14
7.9 Communication device .14
8 Recommendations concerning fire prevention and firefighting in stations.14
8.1 General.14
8.2 Platform materials .15
8.3 Maintenance pit beneath carriers at the platform .15
8.4 Spaces adjacent to the platforms.15
8.5 Transmission of electrical energy .15
8.6 Contacts for recharging of the carrier batteries .16
2
---------------------- Page: 4 ----------------------
SIST CEN/TR 14819-1:2004
CEN/TR 14819-1:2004 (E)
8.7 Video equipment (camera, monitor) . 16
8.8 Dispensing machines for users and other platform furniture . 16
8.9 Prohibition of smoking, open fires and the transportation of flammable materials. 16
8.10 Extinguishers. 16
8.11 Smoke detection and clearing. 16
9 Recommendations concerning fire prevention and firefighting in the machine room and
the space for the electrical power system. 16
9.1 Prevention. 16
9.2 Limitation of spread of fire. 17
10 Recommendations concerning fire prevention and firefighting in the electrical supply
spaces. 17
11 Recommendations concerning fire prevention and firefighting in the control room. 17
11.1 Civil engineering. 17
11.2 Spaces adjacent to the control point. 17
11.3 Electrical equipment. 17
11.4 Video monitors . 18
11.5 Space heating .18
11.6 Domestic utensils. 18
11.7 Furniture . 18
11.8 Putting safety devices out of service. 18
11.9 Personnel. 18
12 Lightning. 18
13 Training of personnel . 19
14 Maintenance. 19
Bibliography. 20
3
---------------------- Page: 5 ----------------------
SIST CEN/TR 14819-1:2004
CEN/TR 14819-1:2004 (E)
Foreword
This document (CEN/TR 14819-1:2004) has been prepared by Technical Committee CEN/TC 242 “Safety
requirements for passenger transportation by rope”, the secretariat of which is held by AFNOR.
CEN/TR 14819 comprises the following parts presented under the general title of Prevention and fight against
fire:
Part 1: Funicular railways in tunnels
Part 2: Other funicular railways and other installations
This document forms part of the standards programme approved by the CEN Technical Board (CEN/BT) on
safety requirements for cableway installations designed to carry persons:
1 Safety requirements for cableway installations designed to carry persons - Terminology
2 Safety requirements for cableway installations designed to carry persons - General requirements
3 Safety requirements for cableway installations designed to carry persons - Calculations
4 Safety requirements for cableway installations designed to carry persons - Ropes
5 Safety requirements for cableway installations designed to carry persons - Tensioning devices
6 Safety requirements for cableway installations designed to carry persons - Drive systems and other
mechanical equipment
7 Safety requirements for cableway installations designed to carry persons - Carriers
8 Safety requirements for cableway installations designed to carry persons - Electrical equipment other
than for drive systems
9 Safety requirements for cableway installations designed to carry persons - Civil engineering works
10 Safety requirements for cableway installations designed to carry persons – Pre-commissioning inspection,
maintenance and operational inspection and checks
11 Safety requirements for cableway installations designed to carry persons – Recovery and evacuation
12 Safety requirements for cableway installations designed to carry persons - Operation
13 Safety requirements for cableway installations designed to carry persons - Quality assurance
Together these form a series of standards regarding design, manufacture, construction, maintenance and
operation of all cableway installations designed to carry persons.
4
---------------------- Page: 6 ----------------------
SIST CEN/TR 14819-1:2004
CEN/TR 14819-1:2004 (E)
Introduction
This report has been prepared by a working group set up by TC 242 "Safety requirements for passenger
transportation by rope". It responds to a request by the European Commission and CEN and will be of use to
operators and designers of funicular railways in tunnels.
5
---------------------- Page: 7 ----------------------
SIST CEN/TR 14819-1:2004
CEN/TR 14819-1:2004 (E)
1 Scope
This part of CEN/TR 14819 specifies safety recommendations applicable to the prevention and fighting of fires
in funicular railways in tunnels that may endanger the health and safety of persons.
This part of CEN/TR 14819 covers the design, manufacture, construction, maintenance and operation of all
funicular railways running in tunnels of length greater than 300 m or where the evacuation zones are more
than 300 m apart, an evacuation zone being comparable to a station from the point of view of protecting
passengers against fire risks. Tunnels with these characteristics are called "long tunnels" in the following.
For shorter tunnels, some of the same measures could be applied depending on the results of the installation
safety study and taking account particularly of the number of passengers and the width of the evacuation
passage.
With regard to these fire problems, it is essential to take organizational measures relating to operation, but
these are not covered in this document
2 Normative references
The following referenced documents are indispensable for the application of this document. For dated
references, only the edition cited applies. For undated references, the latest edition of the referenced
document (including any amendments) applies
.ENV 1907:1999, Safety requirements for cableway installations designed to carry persons – Terminology.
EN 50119, Railway applications – Fixed installations – Electric traction overhead contact lines.
EN 50122-1, Railway applications – Fixed installations – Part 1: Protective provisions relating to electrical
safety and earthing
EN 50122-1, Railway applications – Fixed installations – Part 2: Protective provisions against the effects of
stray currents caused by d.c. traction systems.
EN 50206-2, Railway applications – Rolling stock – Pantographs: Characteristics and tests – Part 2:
Pantographs for metros and light rail carriers.
EN 50264-1, Railway applications – Railway rolling stock cables having special fire performance – Standard
wall - Part 1: General requirements.
EN 50290-2-27, Communication cables – Part 2-27: Common design rules and construction – Halogen free
flame retardant thermoplastic sheathing compound
prEN 13796-1, Safety requirements for cableway installations designed to carry persons – Carriers – Part 1:
Grips, carrier trucks, on-board brakes, cabins, chairs, carriages, maintenance carriers, tow-hangers.
prEN 45545-1, Railway applications – Fire protection of railway vehicles – Part 1: General.
prEN 45545-2, Railway applications – Fire protection of railway vehicles – Part 2: Fire resistance
requirements for materials and components.
prEN 45545-3, Railway applications – Fire protection of railway vehicles – Part 3: Fire resistance requirements
for fire barriers and partitions.
prEN 45545-4, Railway applications – Fire protection of railway vehicles – Part 4: Fire safety requirements for
railway rolling stock design.
6
---------------------- Page: 8 ----------------------
SIST CEN/TR 14819-1:2004
CEN/TR 14819-1:2004 (E)
prEN 45545-5, Railway applications – Fire protection of railway vehicles –- Part 5: Fire safety requirements
for electrical equipment including that of trolley buses, track guided buses and magnetic levitation carriers.
prEN 45545-6, Railway applications – Fire protection of railway vehicles –- Part 6: Fire control and
management systems.
prEN 45545-7, Railway applications – Fire protection of railway vehicles –- Part 7: Fire safety requirements for
flammable liquid and flammable gas installations.
prEN 50163, Railway applications – Supply voltages of traction systems.
EN ISO 13943:2000, Fire safety – Vocabulary (ISO 13943:2000).
IEC 60331-11, Tests for electric cables under fire conditions – Circuit integrity – Part 11: Apparatus – Fire
alone at a flame temperature of at least 750 °C.
IEC 60331-21, Tests for electric cables under fire conditions – Circuit integrity – Part 21: Procedures and
requirements – Cables of rated voltage up to and including 0, 6/1, 0 kV.
3 Terms and definitions
For the purposes of this document, the terms and definitions given in ENV 1907:1999, EN ISO 13943:2000
and the following apply:
3.1
control point
operator's position in the control room of the drive station where all the types of travel may be monitored
3.2
fire resistance
ability of an object to maintain for a specified period the required fire stability, fire integrity, thermal insulation
and/or any other required function specified in a standardized fire resistance test
NOTE The qualifier "fire resistant" only applies to this ability.
3.3
reaction to fire
behaviour of a material that, as a result of its own decomposition, feeds a fire to which it is exposed under
specified conditions
3.4
fire stability criterion "R"
criterion determining the ability of an element or a structure to withstand specified loads and/or actions during
the appropriate fire resistance test
3.5
fire barrier, fire integrity criterion "E"
criterion determining the ability of a separating element to prevent the passage of flames and hot gases
3.6
thermal insulation, fire break criterion "I"
criterion determining the ability of a separating element to prevent the passage of heat during a fire resistance
test
3.7
REI time, EI time
minimum time for which the criteria are met (examples REI 60, EI 30)
7
---------------------- Page: 9 ----------------------
SIST CEN/TR 14819-1:2004
CEN/TR 14819-1:2004 (E)
4 General recommendations
4.1 Application of the technical report
The recommendations in this part of the document apply to all funicular railways In tunnels intended for
persons.
4.2 Safety principles
The safety principles formulated in prEN 12929-1 apply.
In addition, the hazard scenarios and safety measures relating to the scope of this document are to be taken
into account.
4.2.1 Hazard scenarios
The following events may bring about hazardous situations that may be avoided or limited by the
recommendations in this document:
fire in a carrier;
fire in the tunnel;
fire in a station, particularly in a machinery space, an electrical power supply space or a control point;
fire outside the installation;
lack or inadequacy of evacuation routes in the station;
inappropriate behaviour by persons.
NOTE If there is a fire in a funicular railway tunnel, the existence of the following aggravating elements should be
taken into account:
chimney effect of the tunnel. Also, because of the pressure differences, smoke does not always travel in the
same direction.
depending on the situation of the installation, the external emergency services may require time to arrive on site.
In the majority of cases, they may only be able to operate at the ends of the tunnel;
passengers who have left a carrier that has stopped can only evacuate the tunnel by a pathway of limited width
alongside the track;
the logic of the safety functions generally leads to an immediate stoppage of the installation or carrier if a fault is
detected.
4.2.2 Safety measures
Safety measures should be taken to eliminate the hazard scenarios listed in 4.2.1 and to ensure that the
funicular railway passengers or persons on the platforms avoid being injured by fire or choked by smoke. The
measures listed in this document are design and operational measures intended to:
avoid a fire resulting in damage to the installation;
minimize the thermal loads in the installation;
8
---------------------- Page: 10 ----------------------
SIST CEN/TR 14819-1:2004
CEN/TR 14819-1:2004 (E)
limit the damaging effects of a fire on the major safety components by timely detection, alarm and
firefighting;
define adequate characteristics (in particular, reaction to fire and fire resistance) of the major safety
components taking into account thermal stressing in the event of a fire in the installation;
provide a fire resistant separation between adjoining areas for an adequate period of time;
install adequate escape routes in stations;
provide personnel and passengers with suitable instructions;
ensure personnel are competent in matters relating to fire prevention and firefighting.
5 Basic recommendations
5.1 Measures should be taken:
to prevent or hinder the initiation of a fire and its spread;
to prevent a carrier in which a fire has been started from leaving the station.
If a fire starts in a carrier,
the priority is to allow the carrier to reach the next station or evacuation zone whilst avoiding a
concentration of smoke on board;
in certain cases, evacuation on foot remains possible as long as technical and organizational measures
have been taken.
It should also be possible to protect and evacuate persons in the station.
5.2 It is necessary for the installation safety analysis to take into account the risk of fire and to indicate in what
way the safety recommendations of this document shall be met.
5.3 In order to allow the recovery of the carriers in the event of a fire, care should be taken in particular to
keep the following units able to function:
carriers;
ropes and end fixings;
tensioning devices;
drive wheel, particularly the lining of the drive wheel;
drive systems and brakes;
electrotechnical devices (power supply, control, communication, monitoring devices);
civil engineering of the tunnel and stations;
evacuation routes from the stations;
communication devices between the passengers, conductor, control point.
9
---------------------- Page: 11 ----------------------
SIST CEN/TR 14819-1:2004
CEN/TR 14819-1:2004 (E)
5.4 Whatever the technical measures taken, and in particular, those contained in this part of the document,
the haul ropes will be the subject of permanent attention in the event of a fire. Care should also be taken to
ensure that any construction elements falling under the effect of a fire cannot damage the ropes during the
time required for recovery.
6 Recommendations concerning fire prevention and firefighting in the carriers
6.1 Materials
It is recommended that the materials meet the requirements of the relevant parts of prEN 45545 or, whilst
awaiting their publication, of national standards covering the same subject.
6.2 Electrical cabinets
It is recommended that:
either the electrical conductors and components should meet the requirements of prEN 45545-5 and be
fitted with electrical overload protection devices;
or automatic detection and extinguishing devices should be installed in the cabinets. These devices
should be capable of being triggered manually.
In principle, the electrical cabinets should not contain any hydraulic devices. However, if this is necessary, it
is mandatory to have an automatic detection and extinguishing device in the cabinet.
It is recommended that only metallic electrical cabinets with devices that can only be opened by the personnel
should be used. With regard to protecting the cabinets against heat or fire from an external source, it is
recommended that they should meet the requirements of prEN 45545-3 and prEN 45545-5.
6.3 Cabling outside the electrical cabinets and lighting
It is recommended that the cabling should meet the requirements of prEN 45545-4 and EN 50264-1 and be
protected by electrical overload protection devices.
It is recommended that the cables should be run in metallic ducts.
Crossings between the routes of electric cables and hydraulic piping should be avoided as far as possible.
It is recommended that lighting devices should meet the requirements of the specific standards applicable to
guided transport systems for carrying persons.
6.4 Batteries
If batteries with electrolyte are used, it is recommended that the latter be in the form of a gel in order to limit
the risk of explosion.
To avoid the carrier stopping as a result of a supply fault in a safety cabinet, it is recommended that each
block of batteries should have its own electrical protection (for example, fuse) and that, if there are several
blocks, they should be physically separated. The blocks of batteries should also either be separated in a
leaktight manner from the passenger compartments or be placed in trays that are adequately ventilated to
avoid a discharge of gas into the passenger compartment of the carriers. The integrity should be classified as
REI 15.
10
---------------------- Page: 12 ----------------------
SIST CEN/TR 14819-1:2004
CEN/TR 14819-1:2004 (E)
6.5 Battery chargers
It is recommended that the chargers should be separated in a leaktight manner from the passenger
compartments, or in an adequately ventilated space avoiding any discharge of fumes into the passenger
compartment. The integrity should then be classified as REI 15.
The installation of a temperature rise detector is recommended.
6.6 Video equipment (camera, monitor)
It is recommended that the voltage of the equipment should be less than 50 V and that the standards relating
to this equipment should be applied.
It is recommended that cathode ray tubes should not be allowed.
6.7 Heating, air conditioning
It is recommended that this should conform to prEN 45545-5 and that the impossibility of placing any object on
the heating/air conditioning device should be demonstrated.
6.8 Electrical components outside cabinets which are energized during travel (dynamos,
alternators, motors)
It is recommended that these components should be protected (principally by thermal relays).
It is recommended that these components should be separated physically from flammable elements and from
safety electrical cabinets whilst avoiding any discharge of smoke into the passenger compartment.
In the absence of a safety analysis proving that there is no fire risk to the carrier, it is recommended that a
temperature rise detector should be installed near these components.
6.9 Pantographs
It is recommended that prEN 45545-5 and the relevant requirements on metros and light rail carriers in
EN 50206-2 should be applied.
6.10 Rail brake – Retarder
It is recommended that the engaged position of a brake jaw or of the retarder should automatically result in the
stopping of the installation via a safety circuit.
6.11 Hydraulic power plants and circuits – Pressure vessels – Refrigerants
It is recommended:
that the quantity of oil on board should be as small as possible. It is recommended that oils with the
highest flash point compatible with their use should be used and that their capacity to hold an electrostatic