Secure storage units - Classification and methods of test for resistance to fire - Part 2: Data rooms and data container

Data rooms and data containers are fire protection security products whose purpose is to protect temperature and humidity sensitive data media and hardware systems from the effects of fire. These fire resistance products do not provide any defined protection against burglary.
Based on these objectives, the CEN/TC 263 Working Group WG2 Fire Resistance unanimously noted at its meeting on 8 March 2012 that the requirement for a certified high security lock according to EN 1300 for data rooms and data containers suggests protection that is not provided and does not reflect the requirements of the market.
For the reasons explained above, WG2 unanimously recommended deletion of the requirements for a certified high security lock according to EN 1300 without replacement from EN 1047-2:2009. In the interest of the market, this change in this European Standard shall be implemented very soon via an Amendment to EN 1047-2:2009. The necessary decision shall be taken in a 3 months shortened UAP. The necessary application shall be filed with the CEN/TC 263 via DIN.
The draft for Amendment A1 to EN 1047-2:2009 shall be presented to the CEN/TC 263 together with the application for changes in this European Standard.

Wertbehältnisse - Klassifizierung und Methoden zur Prüfung des Widerstandes gegen Brand - Teil 2: Datensicherungsräume und Datensicherungscontainer

Unités de stockage en lieu sûr - Classification et méthodes d'essai de résistance au feu - Partie 2: Conteneurs et chambres réfractaires

Varnostne shranjevalne enote - Klasifikacija in metode preskušanja odpornosti proti ognju - 2. del: Prostori in vsebniki za shranjevanje podatkov

General Information

Status
Not Published
Public Enquiry End Date
30-Oct-2012
Current Stage
98 - Abandoned project (Adopted Project)
Start Date
11-Apr-2024
Due Date
16-Apr-2024
Completion Date
11-Apr-2024

Relations

Overview

EN 1047-2:2009/FprA1 (CEN amendment A1, 2012) is the European standard for fire-resistant data rooms and data containers - secure storage units designed to protect temperature- and humidity‑sensitive data media and hardware from the effects of fire. The amendment clarifies classification, test methods and requirements for fire endurance, thermal and humidity performance, and removes a previous requirement for certified high‑security locks (EN 1300), because these products are intended for fire protection only and do not claim burglary resistance.

Key topics and requirements

  • Scope: Protection of data media and hardware from fire; not intended to provide burglary resistance.
  • Classification: Designations such as R60D (data rooms) and C60D (data containers) indicate 60 minutes fire exposure capability and the “D” category of protected media.
  • Performance limits:
    • Maximum permitted temperature increase during fire tests: 50 K (above ambient) for the measured location.
    • Maximum relative humidity allowed during/after testing: 85% for the protected environment.
    • The “D” class excludes media that lose data below 75 °C or at relative humidity above 85%.
  • Test methods:
    • Fire endurance test (referenced clause 6.6.1) to confirm temperature and humidity performance over the rated period.
    • Impact tests and comparison tests (clause 6.6.2) for construction variants (floors, walls, ceilings). A formula for assessing temperature-rise differences between type-tested and variant constructions is included.
    • References to EN 1363‑1 methods for integrity assessments where applicable.
  • Amendment change: Removal of the normative reference to EN 1300 (high‑security lock classification) and replacement of the definition of “door” to mean any access equipped with at least one lock.

Applications and users

  • Manufacturers of fire‑resistant data rooms and data containers who need to design, test and certify products to European fire‑protection criteria.
  • Independent testing laboratories and certification bodies performing fire endurance, impact and comparison tests.
  • IT facilities managers, data center planners, archival and records managers specifying secure fire‑protected storage for magnetic, optical, tape and other data media.
  • Insurance underwriters, specifiers and procurement teams requiring objective proof of fire‑resistance for data storage solutions.

Related standards

  • EN 1363‑1 - fire resistance tests (referenced for integrity assessments).
  • EN 1300 - previously referenced for high‑security locks (deleted by FprA1 because lock level implies burglary protection that these products do not provide).
  • CEN/TC 263 (WG2) - technical committee responsible for this amendment.

Keywords: EN 1047-2, fire resistance, data rooms, data containers, secure storage units, fire protection for data media, EN 1300, EN 1363-1.

Draft
SIST EN 1047-2:2009/kFprA1:2012
English language
5 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)


SLOVENSKI STANDARD
01-oktober-2012
Varnostne shranjevalne enote - Klasifikacija in metode preskušanja odpornosti
proti ognju - 2. del: Prostori in vsebniki za shranjevanje podatkov
Secure storage units - Classification and methods of test for resistance to fire - Part 2:
Data rooms and data container
Wertbehältnisse - Klassifizierung und Methoden zur Prüfung des Widerstandes gegen
Brand - Teil 2: Datensicherungsräume und Datensicherungscontainer
Unités de stockage en lieu sûr - Classification et méthodes d'essai de résistance au feu -
Partie 2: Conteneurs et chambres réfractaires
Ta slovenski standard je istoveten z: EN 1047-2:2009/FprA1
ICS:
13.220.40 Sposobnost vžiga in Ignitability and burning
obnašanje materialov in behaviour of materials and
proizvodov pri gorenju products
13.310 Varstvo pred kriminalom Protection against crime
35.220.99 Druge naprave za Other data storage devices
shranjevanje podatkov
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

EUROPEAN STANDARD
FINAL DRAFT
EN 1047-2:2009
NORME EUROPÉENNE
EUROPÄISCHE NORM
FprA1
August 2012
ICS 13.220.40; 13.310; 35.020
English Version
Secure storage units - Classification and methods of test for
resistance to fire - Part 2: Data rooms and data container
Unités de stockage en lieu sûr - Classification et méthodes Wertbehältnisse - Klassifizierung und Methoden zur
d'essai de résistance au feu - Partie 2: Conteneurs et Prüfung des Widerstandes gegen Brand - Teil 2:
chambres réfractaires Datensicherungsräume und Datensicherungscontainer
This draft amendment is submitted to CEN members for unique acceptance procedure. It has been drawn up by the Technical Committee
CEN/TC 263.
This draft amendment A1, if approved, will modify the European Standard EN 1047-2:2009. If this draft becomes an amendment, CEN
members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for inclusion of this amendment
into the relevant national standard without any alteration.

This draft amendment was established by CEN in three official versions (English, French, German). A version in any other language made
by translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC Management Centre has
the same status as the official versions.

CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,
Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania,
Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and United
Kingdom.
Recipients of this draft are invited to submit, with their comments, notification of any relevant patent rights of which they are aware and to
provide supporting documentation.

Warning : This document is not a European Standard. It is distributed for review and comments. It is subject to change without notice and
shall not be referred to as a European Standard.

EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION

EUROPÄISCHES KOMITEE FÜR NORMUNG

Management Centre: Avenue Marnix 17, B-1000 Brussels
© 2012 CEN All rights of exploitation in any form and by any means reserved Ref. No. EN 1047-2:2009/FprA1:2012: E
worldwide for CEN national Members.

Contents Pa
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.

Loading comments...

Frequently Asked Questions

SIST EN 1047-2:2009/kFprA1:2012 is a draft published by the Slovenian Institute for Standardization (SIST). Its full title is "Secure storage units - Classification and methods of test for resistance to fire - Part 2: Data rooms and data container". This standard covers: Data rooms and data containers are fire protection security products whose purpose is to protect temperature and humidity sensitive data media and hardware systems from the effects of fire. These fire resistance products do not provide any defined protection against burglary. Based on these objectives, the CEN/TC 263 Working Group WG2 Fire Resistance unanimously noted at its meeting on 8 March 2012 that the requirement for a certified high security lock according to EN 1300 for data rooms and data containers suggests protection that is not provided and does not reflect the requirements of the market. For the reasons explained above, WG2 unanimously recommended deletion of the requirements for a certified high security lock according to EN 1300 without replacement from EN 1047-2:2009. In the interest of the market, this change in this European Standard shall be implemented very soon via an Amendment to EN 1047-2:2009. The necessary decision shall be taken in a 3 months shortened UAP. The necessary application shall be filed with the CEN/TC 263 via DIN. The draft for Amendment A1 to EN 1047-2:2009 shall be presented to the CEN/TC 263 together with the application for changes in this European Standard.

Data rooms and data containers are fire protection security products whose purpose is to protect temperature and humidity sensitive data media and hardware systems from the effects of fire. These fire resistance products do not provide any defined protection against burglary. Based on these objectives, the CEN/TC 263 Working Group WG2 Fire Resistance unanimously noted at its meeting on 8 March 2012 that the requirement for a certified high security lock according to EN 1300 for data rooms and data containers suggests protection that is not provided and does not reflect the requirements of the market. For the reasons explained above, WG2 unanimously recommended deletion of the requirements for a certified high security lock according to EN 1300 without replacement from EN 1047-2:2009. In the interest of the market, this change in this European Standard shall be implemented very soon via an Amendment to EN 1047-2:2009. The necessary decision shall be taken in a 3 months shortened UAP. The necessary application shall be filed with the CEN/TC 263 via DIN. The draft for Amendment A1 to EN 1047-2:2009 shall be presented to the CEN/TC 263 together with the application for changes in this European Standard.

SIST EN 1047-2:2009/kFprA1:2012 is classified under the following ICS (International Classification for Standards) categories: 13.220.40 - Ignitability and burning behaviour of materials and products; 13.310 - Protection against crime; 35.220.99 - Other data storage devices. The ICS classification helps identify the subject area and facilitates finding related standards.

SIST EN 1047-2:2009/kFprA1:2012 has the following relationships with other standards: It is inter standard links to SIST EN 1047-2:2009+A1:2013. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.

You can purchase SIST EN 1047-2:2009/kFprA1:2012 directly from iTeh Standards. The document is available in PDF format and is delivered instantly after payment. Add the standard to your cart and complete the secure checkout process. iTeh Standards is an authorized distributor of SIST standards.