(Main)Eurocode 10 - Design of glass structures - Part 3: In-plane loaded glass components
- Abstract
1.1 Scope of EN 19100-3
(1) This document gives design rules for glass components and assemblies primarily subjected to in-plane loading. It also covers effects of loads acting both in-plane and parallel to the plane produced by the neutral axes of the component, including construction rules for joints connecting in-plane loaded glass components.
1.2 Assumptions
(1) The assumptions of EN 1990-1, EN 19100-1 and EN 19100-2 apply.
(2) This document is intended to be used in conjunction with, EN 1990-1, EN 1991 (all parts), EN 1993-1-1, EN 1995-1-1, EN 1998 (all parts), EN 1999-1-1, EN 19100-1, EN 19100-2 and EN 12488.
- Status
- Published
- Publication Date
- 18-Dec-2025
- Technical Committee
- CEN/TC 250 - Structural Eurocodes
- Drafting Committee
- CEN/TC 250/SC 11/WG 1 - Design of Glass Structures
- Current Stage
- 6060 - Definitive text made available (DAV) - Publishing
- Start Date
- 19-Aug-2026
- Due Date
- 19-Dec-2025
- Completion Date
- 19-Dec-2025
EN 19100-3 is the CEN part of Eurocode 10 for the design of glass structures. It gives design rules for glass components and assemblies primarily subjected to in-plane loading, including effects of combined in-plane and parallel-to-plane actions and the joints that connect these components. Engineers, manufacturers, buyers and checking authorities use it with EN 1990, EN 19100-1 and EN 19100-2 when they need to verify safety, serviceability, fracture behaviour and connections.
What does EN 19100-3 specify?
EN 19100-3 specifies design rules for glass components and assemblies mainly loaded in-plane. It also addresses loads acting in-plane and parallel to the plane through the neutral axes of the component, and it includes construction rules for joints for in-plane loaded glass components.
The document is organized into clauses on scope, normative references, terms and symbols, basis of design, materials, durability, structural analysis and detailing, limit states, serviceability, and joints and connections. It finishes with three informative annexes that support buckling, laminated glass stiffness, and simplified bolted-splice calculations.
| Annex | What it covers |
|---|---|
| Annex A | Calculation of the critical buckling load and critical bending moment |
| Annex B | Calculation of effective inertia values for laminated glass |
| Annex C | Calculation of K-values for simplified bolted-splice design |
What are the key requirements of EN 19100-3?
EN 19100-3 focuses on how to verify in-plane loaded glass for safety in normal use, during fracture events, and after fracture. In practice, that means the designer must check resistance, stability, residual load carrying capacity, and the details of supports and joints.
Design basis and robustness
Clause 4 requires the Limit State Scenario (LSS) to follow EN 19100-1. It requires fracture of any glass plies not to compromise adjacent components or cause progressive collapse, and it expects the design to address robustness, redundancy and repair or replacement planning. For laminated glass, shear interaction rules from EN 19100-1 should be used.
This matters because in-plane glass often carries load through the whole assembly, so a single broken ply can affect both local and global behaviour. The standard asks the designer to think beyond intact strength and to show that the structure can still behave safely after damage.
Fracture Limit State (FLS)
Clause 4.2 requires a verification of sufficient safety during sudden fracture. The FLS may be checked by experimental testing or by theoretical assessment, and the assessment has to include dynamic amplification, eccentricity shifts after ply fracture, forced constraint deformations, and stiffness and resistance reduction.
This matters when the structure can experience impact, breakage or other sudden events. The designer must decide whether test evidence, calculations, or both are needed, and whether a lateral impact check is relevant for the project.
Post Fracture Limit State (PFLS)
Clause 4.3 requires verification of residual safety after fracture for a limited time period, either by residual resistance or by an alternative load path. The PFLS may also be verified by testing or by theoretical assessment, but the standard expects the residual resistance of in-plane loaded glass components to be verified by testing only unless an alternative load path is ensured.
This matters for assemblies where people or other structural parts could still be exposed after a breakage event. The designer must define how long the component needs to remain safe, and what fractured condition is assumed in the global system.
Structural analysis, imperfections and buckling
Clause 7 requires structural analysis to follow EN 19100-1, and it expects nominal glass thicknesses to be used. It also requires imperfections to be included, with basic imperfection values and modified imperfection effects for laminated glass after fracture. Clause 7.2 says second-order effects should be considered when they are significant, and third-order analysis should be used when membrane effects are safety relevant.
This matters because in-plane glass can fail by instability as well as by stress. The standard gives a framework for deciding when simplified first-order analysis is acceptable and when nonlinear analysis is needed.
Limit states and serviceability
Clause 8 requires Ultimate Limit State (ULS) verification by structural calculation, with all glass components taken as intact in ULS. Clause 9 requires Serviceability Limit State (SLS) verification by calculation, although SLS may also be checked by testing. In SLS, all plies are generally taken as intact.
This matters because the design has to work both before any damage and under everyday conditions such as deflection or stress limits. The standard separates intact behaviour from fractured behaviour so the designer can use the right model for each case.
Joints and connections
Clause 10 covers sleeve bearings, lapped splices with bolts in shear, and friction connections. It requires joint behaviour, stress concentrations and force redistribution to be considered, and it gives detailed rules for geometry, bolt arrangement, sleeves, grouts, pre-stress, friction resistance and contact conditions.
This matters because many glass failures start at the connection. The document tells the designer how to model and detail joints so the glass, bolts and clamps behave together without creating unwanted stress peaks.
What terms does EN 19100-3 define?
EN 19100-3 defines the terms it uses for in-plane design, fracture verification and buckling analysis.
- Shear element made of glass - a glass element intended to sustain in-plane loads or stresses.
- Buckling length - the equivalent pinned-end length that gives the same critical buckling load as the member or segment.
- Second order analysis - geometrically nonlinear analysis that includes out-of-plane deflections in equilibrium.
- Third order analysis - geometrically nonlinear analysis that includes both out-of-plane and in-plane deflections.
- Membrane effect - the influence of in-plane deflections on stresses and sectional forces in static equilibrium.
- Structural redundancy - the ability of the structure to redistribute load after damage in some members or connections.
- Protection measure - a measure intended to prevent or reduce accidental damage that could affect structural function.
- Polymeric-modified mortar - mortar used to fill gaps between glass and other parts for force and stress transfer.
Who uses EN 19100-3?
EN 19100-3 is intended for designers, clients, manufacturers, constructors, relevant authorities, educators, software developers and committees drafting related product, testing and execution standards. In practice, it is used by structural engineers, facade and glass specialists, manufacturers of glass assemblies, and checking bodies that need to assess in-plane loaded glass components and their joints.
It is relevant in building and other structural applications where glass carries in-plane actions, including laminated glass assemblies and bolted or friction-type connections. It is also used when a project needs decisions on robustness, fracture behaviour, residual resistance, detailing and verification method.
What changed in EN 19100-3 from the previous edition?
EN 19100-3 supersedes CEN/TS 19100-3:2021. The foreword states two changes compared with the previous edition: the title and scope were modified, and the references were updated.
Which standards are used with EN 19100-3?
EN 19100-3 is intended to be used with these standards named in its scope and references:
- EN 1990 - provides the basis of structural and geotechnical design, including load combinations and reliability concepts.
- EN 1991 (all parts) - provides actions on structures.
- EN 1993-1-1 and EN 1993 (all parts) - support steel design checks for bolts and related components.
- EN 1995-1-1 - supports timber-related structural design where relevant.
- EN 1998 (all parts) - supports earthquake design where relevant.
- EN 1999-1-1 and EN 1999 (all parts) - support aluminium design for metal parts in joints and supports.
- EN 19100-1 - provides general rules, basis of design, materials, analysis rules and laminated-glass interaction provisions.
- EN 19100-2 - provides rules for out-of-plane loaded glass components and is used for assumptions, fracture verification and point-fixing-related guidance.
- EN 12488 - is named for use alongside the standard in the intended set of design documents.
- EN 1090-2 - is used for application of bolt pre-stress in friction connections.
- EN 12150, EN 14179, EN 1863, EN ISO 12543 - support glass product, spacing and laminated-glass detailing rules referenced in joint design.
- EN 16612 - provides calculation guidance for lateral load resistance of glass panes.
What does the EN 19100-3 document contain?
EN 19100-3 contains a full Eurocode-style structure with clauses on scope, references, terminology, basis of design, materials, durability, structural analysis, limit states, serviceability, and joints and connections. It gives explicit treatment of ULS, FLS and PFLS, including dynamic effects in fracture cases and residual resistance after fracture.
The document also contains figures that illustrate axes, eccentricity shifts, fracture-related deformation, support effects and bolt/joint geometry. Tables support imperfection values, joint coefficients and friction-connection calculations.
Three informative annexes provide calculation procedures for critical buckling load and critical bending moment, effective inertia for laminated glass, and K-values for simplified bolted-splice design. These annexes support design calculations, while the main clauses state when analysis, testing or a transparent and reproducible assessment is needed for verification.
Relations
- Effective Date
- 19-Jan-2023
- Effective Date
- 09-Sep-2026
- Effective Date
- 09-Sep-2026
- Effective Date
- 25-Aug-2026
Get Certified
Connect with accredited certification bodies for this standard

DIBt (Deutsches Institut für Bautechnik)
German Institute for Building Technology.
DIN CERTCO
DIN Group product certification.

Aboma Certification B.V.
Specialized in construction, metal, and transport sectors.
Sponsored listings
Frequently Asked Questions
EN 19100-3:2026 is a draft published by the European Committee for Standardization (CEN). Its full title is "Eurocode 10 - Design of glass structures - Part 3: In-plane loaded glass components". This standard covers: 1.1 Scope of EN 19100-3 (1) This document gives design rules for glass components and assemblies primarily subjected to in-plane loading. It also covers effects of loads acting both in-plane and parallel to the plane produced by the neutral axes of the component, including construction rules for joints connecting in-plane loaded glass components. 1.2 Assumptions (1) The assumptions of EN 1990-1, EN 19100-1 and EN 19100-2 apply. (2) This document is intended to be used in conjunction with, EN 1990-1, EN 1991 (all parts), EN 1993-1-1, EN 1995-1-1, EN 1998 (all parts), EN 1999-1-1, EN 19100-1, EN 19100-2 and EN 12488.
1.1 Scope of EN 19100-3 (1) This document gives design rules for glass components and assemblies primarily subjected to in-plane loading. It also covers effects of loads acting both in-plane and parallel to the plane produced by the neutral axes of the component, including construction rules for joints connecting in-plane loaded glass components. 1.2 Assumptions (1) The assumptions of EN 1990-1, EN 19100-1 and EN 19100-2 apply. (2) This document is intended to be used in conjunction with, EN 1990-1, EN 1991 (all parts), EN 1993-1-1, EN 1995-1-1, EN 1998 (all parts), EN 1999-1-1, EN 19100-1, EN 19100-2 and EN 12488.
EN 19100-3:2026 is classified under the following ICS (International Classification for Standards) categories: 81.040.20 - Glass in building; 91.080.99 - Other structures. The ICS classification helps identify the subject area and facilitates finding related standards.
EN 19100-3:2026 has the following relationships with other standards: It is inter standard links to CEN/TS 19100-3:2021, EN 19100-2:2026, EN 19100-1:2026, CEN/TS 19100-4:2024. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.
EN 19100-3:2026 is associated with the following European legislation: Standardization Mandates: M/515. When a standard is cited in the Official Journal of the European Union, products manufactured in conformity with it benefit from a presumption of conformity with the essential requirements of the corresponding EU directive or regulation.
EN 19100-3:2026 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.
Standards Content (Sample)
Contents
- 0 Introduction
- 0.1 Introduction to the Eurocodes
- 0.2 Introduction to EN 19100 (all parts)
- 0.4 Verbal forms used in the Eurocodes
- Annex A Annex B Annex C
- 1 Scope
- 1.2 Assumptions
- 2 Normative references
- 3 Terms, definitions and symbols
- 3.1 Terms and definitions
- 3.1.1 shear element made of glass
- 3.1.2 buckling length
- 3.1.3 second order analysis
- 3.1.4 third order analysis
- 3.1.5 membrane effect
- 3.1.6 axes of a glass pane, component or member and their direction
- 3.1.7 structural redundancy
- 3.1.8 sudden fracture
- 3.1.9 protection measure
- 3.1.10 polymeric-modified mortar
- 3.2 Symbols and abbreviations
- 4 Basis of design
- 4.1 Requirements
- 4.2 Fracture limit state (FLS) verification
- 4.3 Post fracture limit state (PFLS) verification
- 5 Materials
- 6 Durability
- 7 Structural analysis and detailing
- 7.1 Structural modelling for analysis
- 7.2 Effects of deformed geometry of the structure
- 7.3 Consideration of imperfections
- 7.4 Interlayers of laminated glass
- 7.5 Temperature effect and long-term effect
- 7.6 Detailing
- 8 Limit states including ULS, FLS and PFLS
- 8.1 General
- 8.2 Dynamic effects in FLS
- 9 Serviceability limit states
- 10 Joints and Connections
- 10.1 General
- 10.2 Sleeve bearings
- 10.3 Lapped splices with bolts in shear
- 10.4 Friction connections
- Annex A
- Annex B
- Annex C
- Bibliography
0 Introduction
0.1 Introduction to the Eurocodes
The Structural Eurocodes comprise the following standards generally consisting of a number of parts:
EN 1990 Eurocode — Basis of structural and geotechnical design EN 1991 Eurocode 1 — Actions on structures EN 1992 Eurocode 2 — Design of concrete structures EN 1993 Eurocode 3 — Design of steel structures EN 1994 Eurocode 4 — Design of composite steel and concrete structures EN 1995 Eurocode 5 — Design of timber structures EN 1996 Eurocode 6 — Design of masonry structures EN 1997 Eurocode 7 — Geotechnical design EN 1998 Eurocode 8 — Design of structures for earthquake resistance EN 1999 Eurocode 9 — Design of aluminium structures EN 19100 Eurocode 10 — Design of glass structures The Eurocodes are intended for use by designers, clients, manufacturers, constructors, relevant authorities (in exercising their duties in accordance with national or international regulations), educators, software developers, and committees drafting standards for related product, testing and execution standards. NOTE Some aspects of design are most appropriately specified by relevant authorities or, where not specified, can be agreed on a project-specific basis between relevant parties such as designers and clients. The Eurocodes identify such aspects making explicit reference to relevant authorities and relevant parties.
0.2 Introduction to EN 19100 (all parts)
EN 19100 (all parts) applies to the structural design of mechanically supported glass components and assemblies of glass components. It complies with the principles and requirements for the safety and serviceability of structures, the basis of their design and verification that are given in EN 1990, Basis of structural and geotechnical design.
EN 19100 is subdivided into three parts:
EN 19100-1, Eurocode 10 — Design of glass structures — Part 1: General rules EN 19100-2, Eurocode 10 — Design of glass structures — Part 2: Out-of-plane loaded glass components EN 19100-3, Eurocode 10 — Design of glass structures — Part 3: In-plane loaded glass components 0.3 Introduction to EN 19100-3 EN 19100-3 applies to the structural design of in-plane loaded glass components in conjunction with EN 19100-1 and EN 19100-2.
oSIST prEN 19100-3:2024 prEN 19100-3:2024 (E)
0.4 Verbal forms used in the Eurocodes
The verb “shall" expresses a requirement strictly to be followed and from which no deviation is permitted in order to comply with the Eurocodes.
The verb “should” expresses a highly recommended choice or course of action. Subject to national regulation and/or any relevant contractual provisions, alternative approaches could be used/adopted where technically justified.
The verb “may" expresses a course of action permissible within the limits of the Eurocodes. The verb “can" expresses possibility and capability; it is used for statements of fact and clarification of concepts. 0.5 National annex for EN 19100-3 National choice is allowed in this document where explicitly stated within notes. National choice includes the selection of values for Nationally Determined Parameters (NDPs). The national standard implementing EN 19100-1 can have a National Annex containing all national choices to be used for the design of buildings and civil engineering works to be constructed in the relevant country. When no national choice is given, the default choice given in this document is to be used. When no national choice is made and no default is given in this document, the choice can be specified by a relevant authority or, where not specified, agreed for a specific project by appropriate parties. National choice is allowed in EN 19100-1 through notes to the following clauses:
4.2.1(2) 4.2.1(5) – 2 choices 4.3.1(2) 4.3.1(3) 4.3.1(7) 7.3.2(1) 8.2(3) 10.3.1(4) – 2 choices 10.3.3(1) 10.3.4.3(2) 10.4.1(1) National choice is allowed in EN 19100-3 on the application of the following informative annexes:
Annex A Annex B Annex C
The National Annex can contain, directly or by reference, non-contradictory complementary information for ease of implementation, provided it does not alter any provisions of the Eurocodes.
oSIST prEN 19100-3:2024 prEN 19100-3:2024 (E)
1 Scope
1.1 Scope of prEN 19100-3 (1) This document gives design rules for glass components and assemblies primarily subjected to in-plane loading. It also covers effects of loads acting both in-plane and parallel to the plane produced by the neutral axes of the component, including construction rules for joints connecting in-plane loaded glass components.
1.2 Assumptions
(1) The assumptions of EN 1990, prEN 19100-1 and prEN 19100-2 apply. (2) This document is intended to be used in conjunction with, EN 1990, EN 1991 (all parts), EN 1993-1-1, EN 1995-1-1, EN 1998 (all parts), EN 1999-1-1, prEN 19100-1, prEN 19100-2 and EN 12488.
2 Normative references
The following documents are referred to in the text in such a way that some or all of their content constitutes requirements of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. NOTE See the Bibliography for a list of other documents cited that are not normative references, including those referenced as recommendations (i.e. through ‘should’ clauses) and permissions (i.e. through ‘may’ clauses). EN 1990, Eurocode — Basis of structural and geotechnical design prEN 19100-1:2024, Eurocode 10 — Design of glass structures — Part 1: Basis of design and materials prEN 19100-2:2024, Eurocode 10 — Design of glass structures — Part 2: Design of out-of-plane loaded glass components
3 Terms, definitions and symbols
3.1 Terms and definitions
For the purposes of this document, the terms and definitions given in prEN 19100-1 and prEN 19100-2 and the following apply.
3.1.1 shear element made of glass
glass element sustaining on purpose loads or stresses in-plane (F , F ,p , p ,) x z x z Note 1 to entry: The element may be loaded also by loading transversal to the plane (qy).
3.1.2 buckling length
system length of an otherwise similar member with pinned ends, which has the same critical buckling load as a given member or segment of member [SOURCE: EN 1993-1-1:2022, 3.1.7]
3.1.3 second order analysis
geometrically non-linear analysis taking account of the out-of-plane deflections whilst calculating equilibrium of stresses or sectional forces of a glass pane
oSIST prEN 19100-3:2024 prEN 19100-3:2024 (E)
3.1.4 third order analysis
geometrically non-linear analysis taking account of both the out-of-plane and in-plane deflections whilst calculating equilibrium of stresses or sectional forces of a glass pane
3.1.5 membrane effect
influence on stresses and sectional forces due to consideration of in-plane deflections in static equilibrium
3.1.6 axes of a glass pane, component or member and their direction
x-x in the glass pane, component or member, preferably one of the gravity lines y-y perpendicular to the glass pane, defined by the x- and the z-axes z-z in the glass pane, component or member, perpendicular to x-x Note 1 to entry: The directions of x-, y- and z-axes should accord to those of thumb (x), index finger (y) and middle finger (z) of the right hand in the defined planes, see Figure 3.1.
Note 2 to entry: When bending about the y-axis occurs this axis is also called strong axis, and accordingly, when bending about the x-axis or the z-axis these axes are called weak axes.
Figure 3.1 — Definition of axes of a glass pane, component or member and their direction
3.1.7 structural redundancy
ability of a structure to redistribute among its members/connections the loads which can no longer be carried by some other damaged portions
3.1.8 sudden fracture
fracture event of unpredictable origin
3.1.9 protection measure
measure that is intended to prevent or reduce the risk of accidental damage of a glass member that may affect its structural function
3.1.10 polymeric-modified mortar
mortar, used for filling gaps between glass and other parts for force and stress transmission Note 1 to entry: For reasons of strength and ductility, to avoid stress peaks, polymeric materials are added to the mortar.
oSIST prEN 19100-3:2024 prEN 19100-3:2024 (E)
3.2 Symbols and abbreviations
3.2.1 Latin upper-case letters
A Glass cross section area of ply i
C , C Factors taking into account different bending moments 1 2 E Modulus of elasticity for glass F Design loading on the structure Ed F Elastic critical buckling load for global instability mode based on initial elastic stiffnesses cr G Shear modulus of glass G Shear modulus of interlayer int I Moment of inertia of ply i
I Effective torsional moment of inertia T,eff I Effective moment of inertia about the minor axis (z-axis) z,eff Km Equilibrium parameter L Buckling length B L Buckling length (lateral torsional buckling) LT M The design value of the moment Ed M Critical buckling moment (lateral torsional buckling) cr,LT N Design value of normal forces in the relevant direction of the considered cross section or joint Ed N Elastic critical force for the relevant buckling mode cr P Arbitrary in-plane load P Actions having been present in the plies whose fracture is investigated fractured P Actions having been and still being present in the unfractured part of the cross section unfractured Pu Ultimate arbitrary in-plane load P Applied bolt pre-stress P,b P P Forces according to Table C.1 x,I ( x,m) S Design bolt forces b,Ed S Friction shear resistance Fr,b,Rd V Design value of the shear force Ed
oSIST prEN 19100-3:2024 prEN 19100-3:2024 (E)
3.2.2 Latin lower-case letters
b Width b Effective width m d Hole diameter
e Basic imperfection
e Considering all imperfections of the component being length related 0,length e Considering deviations coming from unplanned eccentric load introduction 0,installation e Distance of the mid-plane of two conjunct glass panels z fg,d Design bending strength according to prEN 19100-1:2024, Annex A h Glass ply thickness h Component thickness for calculation of installation eccentricity e h Thickness of ply i
h Thickness of the interlayer int h Total thickness of the laminate tot k Factors considering constructive influences for the design of bolted shear connections, {j=1, … j 10} NOTE The factors k1 to k10 are not the same as the ki factor given in prEN 19100-1:2024, Annex A. l Length of the shorter edge of the glass pane l Component length
n Number of plies p Hole distance
t Sleeve thickness sleeve v Initial lateral deflection of midplane 0,m w Deflection in z-direction w Width of the polymer or polymeric-modified mortar mortar z Distance of the i-th ply's center to center of adjacent interlayer
zp Distance between the member axis and the point where the load is applied
3.2.3 Greek upper-case letters
Δe Eccentricity shift due to fracture of a ply shift Δe Forced constraint deformation exp Θ Torsional deflection 0,m
oSIST prEN 19100-3:2024 prEN 19100-3:2024 (E)
3.2.4 Greek lower-case letters
α Factor by which the design loading would have to be increased to cause the critical elastic cr instability in terms of indifferent equilibrium λ Slenderness for torsional buckling T µ Coefficient of friction Fr μ Design value of friction coefficient Fr,d σ Maximal principal stress p,Ed σ Maximum stress for lapped splices φ,max,E Φ Dynamic load amplification factor for those actions which originate from mass inertia Φ Dynamic amplification factor mg
4 Basis of design
4.1 Requirements
(1) For an in-plane loaded glass component, the Limit State Scenario (LSS) should be chosen according to prEN 19100-1:2024, 4.2.4.
(2) The fracture of any glass plies shall neither compromise the stability or resistance of adjacent components nor result into a progressive collapse.
(3) Verification in ULS, FLS and PFLS is deemed to verify that fracture of a glass ply prevents progressive collapse.
(4) Special attention shall be paid to robustness of the structure, see prEN 19100-1 and EN 1990. (5) When ensuring sufficient robustness, depending on the function, importance and installation position (e.g. height over ground or floor resp., vertical or non-vertical), care shall be taken on the aspects as given in prEN 19100-2:2024, 4.1(3). In addition to that, sufficient redundancy by providing a second load path (background safety) on assembly level and/or structure´s level shall be ensured. (6) In case of laminated glass, the shear interaction provisions as given in prEN 19100-1:2024, 7.2.2 should be used. Guidance can be taken from prEN 19100-2:2024, Annex A or from EN 16612. (7) In case of fracture of a ply or of a component the consequences for the safety and integrity of adjoining structure, components and people shall be analysed and verified. (8) To achieve robustness a sufficient number of glass plies should be provided. NOTE Redundancy and robustness can be enhanced by a coarse crack pattern and/or further restricting boundary conditions of the glass component.
(9) A concept for the repair or replacement of in-plane loaded glass components should be provided.
4.2 Fracture limit state (FLS) verification
4.2.1 General
(1) In the FLS sufficient safety during sudden fracture shall be verified (failsafe verification). NOTE 1 For events of impact in the FLS, see 4.2.1(5).
NOTE 2 The sudden fracture can be of one or several glass plies or of one or several glass components.
oSIST prEN 19100-3:2024 prEN 19100-3:2024 (E) NOTE 3 If fracture of glass components is taken into account, then normally the number of suddenly fractured glass components is 1.
(2) In the FLS, an appropriate load combination should be used for the static loading that arises during the sudden fracture and if necessary during the event of impact, see 4.2.1(5). NOTE The load combination in the FLS is the accidental load combination according to EN 1990, unless the National Annex gives a different specification. For load combination in case of dynamic effects in the FLS, see 8.2. (3) Depending on the project specific situation also elevated temperatures e.g. due to solar absorption should be taken into account for laminated glass components, see prEN 19100-1:2024, 4.3.1. (4) In the FLS the glass component can be verified by experimental testing or alternatively, by a theoretical assessment.
NOTE Verification can include reference to previously executed tests or calculations. (5) Depending on the project, an additional energy intensive lateral impact verification perpendicular to the surface at the most unfavourable location may be conducted. The type of impactor and energy should be as specified by the relevant authority or, where not specified, agreed for a specific project by the relevant parties. NOTE 1 The National Annex can also specify type of impactor and energy. NOTE 2 Generally, further provisions for the verification in the FLS can be given in the National Annex.
4.2.2 Verification of the Fracture Limit State by testing
(1) For the verification of the FLS by experimental testing, prEN 19100-2:2024, 4.2.2 should be applied.
4.2.3 Verification of the Fracture Limit State by theoretical assessment
(1) Alternatively to 4.2.2, a theoretical assessment in the FLS may be performed. All static and dynamic effects originating from impact and/or damage/fracture of parts of the glass component or of the whole shall reasonably be taken into account for the short time of impact including:
- dynamic amplification;
- eccentricity shift due to fracture of a ply if laminated glass is used, see Figure 7.1;
- forced constraint deformation on the remaining cross-section after breakage of a ply if laminated glass is used, see Figure 7.2;
- stiffness and resistance reduction of the cross-section.
NOTE Generally, a theoretical assessment in the FLS is performed by a transient numerical simulation. (2) The applicability of the theoretical model shall be validated. NOTE Normally, the applicability of a theoretical model is validated by experimental benchmark tests. (3) To that end, the dynamic amplification effects by fracture - of one or more plies of the laminate glass component (i.e. sudden fracture out of the static rest position due to hard impact with low energy or spontaneous breakage), and - if necessary, of one or more plies of the laminate with hard lateral impact with energy, and - if necessary, of one or more glass components should be taken into account.
oSIST prEN 19100-3:2024 prEN 19100-3:2024 (E) NOTE For the amount of the dynamic amplification out of the static rest position, see 8.2. (4) If a lateral mass impact has additionally to be taken into account (lateral impact with energy), a further investigation should be carried out to determine the amount of impact energy and the resulting effective dynamic amplification factor Φ due to mass inertia.
(5) Whether a lateral mass impact needs to be taken into account should be specified by the relevant authority or, where not specified, agreed for a specific project by the relevant parties.
4.3 Post fracture limit state (PFLS) verification
4.3.1 General
(1) In the PFLS sufficient safety after fracture for a limited period of time shall be verified (verification of residual resistance of the glass component or verification of an alternative load path). The fracture may be of one or several glass plies or of one or several components.
NOTE 1 The mechanical behaviour, including the residual resistance, of the glass component in the post fracture limit state (PFLS) is influenced by the type of glass component (e.g. mode of breakage, type of interlayer, number of plies), the size of the glass component and its supporting system.
NOTE 2 If fracture of a component is taken into account then normally the number of fractured glass components is 1. (2) In the PFLS an appropriate load combination should be used. NOTE The load combination in the PFLS is the accidental load combination according to EN 1990 and prEN 19100-1 unless the National Annex gives different specification.
(3) Aspects that should be considered for the determination of the time period can originate from the following:
time to secure the environment, temporary support, time to replace, time to remove the load etc. The time limited variable actions may be reduced according to EN 1991-1-6. NOTE Post fracture time periods in the PFLS can be set by the National Annex. (4) Depending on the project specific situation compared to the ambient temperature level, elevated temperatures e.g. due to solar absorption should be taken into account for laminated glass components for assessment in PFLS.
(5) In the PFLS the glass component can be verified by experimental testing or alternatively by a theoretical assessment.
(6) The verification of the residual resistance of in plane loaded glass components for PFLS should be verified by testing only. If an alternative load path is ensured, then the verification of the residual resistance for PFLS may be neglected.
NOTE Verification can include reference to previously executed tests. (7) In PFLS, the load carrying capacity of the global system shall be verified taking into account the fracture of glass components. The number of fractured glass components in the global structure should be assessed based on the specific design situation, see 4.3.1(1), unless it is as agreed for a specific project by the relevant parties. NOTE Generally, further provisions for the verification in the PFLS can be given in the National Annex.
...