Lightning Protection Components (LPC) - Part 1: Requirements for connection components

This functional standard specifies the graphic character repertoires and their coding, which are available for use for information interchange between information processing systems and for use within such systems, in the languages that are commonly used by the members of CEN/CENELEC and the Institutions of the European Community and the European Free Trade Association.

Blitzschutzbauteile - Teil 1: Anforderungen an Verbindungsbauteile

Composants de protection contre la foudre (CPF) - Partie 1: Prescriptions pour les composants de connexion

Elementi za zaščito pred strelo (LPC) - 1. del: Zahteve za povezovalne elemente

General Information

Status
Withdrawn
Publication Date
24-Aug-2006
Withdrawal Date
28-Feb-2009
Drafting Committee
Parallel Committee
Current Stage
9960 - Withdrawal effective - Withdrawal
Start Date
01-Apr-2011
Completion Date
01-Apr-2011

Relations

Buy Standard

Amendment
EN 50164-1:2000/A1:2006
English language
10 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

6/29(16., 6,67(1$

67$1'$5'
GHFHPEHU
(OHPHQWL]D]DãþLWRSUHGVWUHOR /3& GHO=DKWHYH]DSRYH]RYDOQH
HOHPHQWH
/LJKWQLQJSURWHFWLRQFRPSRQHQWV /3& 3DUW5HTXLUHPHQWVIRUFRQQHFWLRQ
FRPSRQHQWV
,&6 5HIHUHQþQDãWHYLOND

6,67(1$ HQ
!"#$%&’( )&!*+,%- .

---------------------- Page: 1 ----------------------

EUROPEAN STANDARD
EN 50164-1/A1

NORME EUROPÉENNE
August 2006
EUROPÄISCHE NORM

ICS 91.120.40


English version


Lightning Protection Components (LPC)
Part 1: Requirements for connection components



Composants de protection contre la Blitzschutzbauteile
foudre (CPF) Teil 1: Anforderungen
Partie 1: Prescriptions an Verbindungsbauteile
pour les composants de connexion





This amendment A1 modifies the European Standard EN 50164-1:1999; it was approved by CENELEC on
2006-03-01. CENELEC members are bound to comply with the CEN/CENELEC Internal Regulations which
stipulate the conditions for giving this amendment the status of a national standard without any alteration.

Up-to-date lists and bibliographical references concerning such national standards may be obtained on
application to the Central Secretariat or to any CENELEC member.

This amendment exists in three official versions (English, French, German). A version in any other language
made by translation under the responsibility of a CENELEC member into its own language and notified to the
Central Secretariat has the same status as the official versions.

CENELEC members are the national electrotechnical committees of Austria, Belgium, Cyprus, the Czech
Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia,
Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain,
Sweden, Switzerland and the United Kingdom.

CENELEC
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung

Central Secretariat: rue de Stassart 35, B - 1050 Brussels


© 2006 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members.
Ref. No. EN 50164-1:1999/A1:2006 E

---------------------- Page: 2 ----------------------

EN 50164-1:1999/A1:2006 - 2 -
Foreword

This amendment was prepared by the Technical Committee CENELEC TC 81X, Lightning
protection.
The text of the draft was submitted to the formal vote and was approved by CENELEC as
amendment A1 to EN 50164-1:1999 on 2006-03-01.
The following dates were fixed:
– latest date by which the amendment has to be
implemented at national level by publication of
an identical national standard or by endorsement (dop) 2007-03-01
– latest date by which the national standards conflicting
with the amendment have to be withdrawn (dow) 2009-03-01
__________

---------------------- Page: 3 ----------------------

- 3 - EN 50164-1:1999/A1:2006
Contents

Add:

7 Electromagnetic compatibility (EMC)

Replace “Annex A (informative) Summary of the requirements and corresponding tests” by
“Annex A Void”


2 Normative references

Add after EN ISO 6988 the following new reference:

IEC 61312-1 1995 Protection against lightning electromagnetic impulse - Part 1: General
principles


3 Definitions

Add:

3.10
bonding bar
metal bar on which metal installations, external conductive parts, electric power and
telecommunication lines, and other cables can be connected to an LPS


5 Requirements

5.1 General

Delete the note.

5.8 Marking

nd
Replace in the 2 paragraph “b)” by “b) and c)”.

Delete in the last paragraph "by inspection and".

Add:

5.9 Terminals of bonding bars

Terminals of bonding bars used for lightning protection installations, shall have connection sizes
equal to or greater than 16 mm².

---------------------- Page: 4 ----------------------

EN 50164-1:1999/A1:2006 - 4 -
6 Tests

6.1 General

Replace the subclause by:

6.1 General condition on tests

6.1.1 The tests in accordance with this standard are type tests.

6.1.2 Unless otherwise specified, tests are carried out with the specimens assembled and
installed as in normal use according to the manufacturer's or supplier's installation instructions with
the recommended conductor materials, sizes and the tightening torques. If the connection
component is suitable for various conductors materials, then it shall be tested on each material
combination.

6.1.3 All tests are carried out on new specimens.

6.1.4 Unless otherwise specified, three specimens are subjected to the tests and the
requirements are satisfied if all the tests are met.

If only one of the specimens does not satisfy a test due to an assembly or a manufacturing fault,
that test and any preceding one which may have influenced the results of the tes
...