EN 60598-2-22:2014
(Main)Luminaires - Part 2-22: Particular requirements - Luminaires for emergency lighting
Luminaires - Part 2-22: Particular requirements - Luminaires for emergency lighting
IEC 60598-2-22:2014 specifies requirements for emergency luminaires for use with electrical lamps on emergency power supplies not exceeding 1 000 V. This fourth edition cancels and replaces the third edition published in 1997, AMD1:2002 and AMD2:2008. This edition constitutes a technical revision. This edition includes the following significant technical changes with respect to the previous edition: a) Clause 22.3, addition of definitions for PELF and Self-contained portable emergency luminaire; b) Clause 22.5, updated with the introduction of requirements for non-replaceable lamp and batteries; c) Clause 22.6, improved requirements to confirm that the charge indication is correctly connected to the circuit together with other clarifications regarding the controlgear and the remote box with its connecting cabe to the emergency luminaire; d) Clause 22.12, improved requirements to ensure that the luminaire shall not become unsafe; e) Clause 22.16, full revision of the photometric testing to align with ISO and CIE; f) Clause 22.17, now only references the requirements which are now covered in IEC 61347 2-7; g) Clause 22.19, now only references the requirements which are now covered in IEC 61347 2-7; h) Annex A, now includes nickel metal hydride batteries and reference to cell types in IEC 61951-1; i) Annex B, minor changes to the classifications; j) Annex C, Figure C.1 deleted in favour of a revised text; k) Annex E, the additional requirements covering self-contained portable emergency luminaires. This publication is to be read in conjunction with IEC 60598-1:2014.
Leuchten - Teil 2-22: Besondere Anforderungen - Leuchten für Notbeleuchtung
Luminaires - Partie 2-22: Exigences particulières - Luminaires pour éclairage de secours
L'IEC 60598-2-22:2014 spécifie les exigences applicables aux luminaires d'éclairage de secours à utiliser avec des lampes électriques sur des tensions d'alimentation de secours ne dépassant pas 1 000 V. Cette quatrième édition annule et remplace la troisième édition parue en 1997, AMD1:2002 et AMD2:2008. Cette édition constitue une révision technique. Cette édition inclut les modifications techniques majeures suivantes par rapport à l'édition précédente: a) Article 22.3, ajout des définitions pour PELF et bloc autonome d'éclairage de secours; b) Article 22.5, mise à jour avec présentation des exigences relatives aux lampes et batteries non remplaçables; c) Article 22.6, exigences améliorées pour confirmer que le voyant de charge est correctement raccordé au circuit avec d'autres clarifications concernant l'appareillage d'alimentation et la boîte de commande à distance avec son câble de raccordement au bloc d'éclairage de secours; d) Article 22.12, exigences améliorées pour garantir que le luminaire ne doit pas devenir dangereux; e) Article 22.16, révision complète des essais photométriques pour un alignement entre ISO et CIE; f) Article 22.17, fait maintenant uniquement référence aux exigences qui sont maintenant couvertes dans l'IEC 61347-2-7; g) Article 22.19, fait maintenant uniquement référence aux exigences qui sont maintenant couvertes dans l'IEC 61347-2-7; h) Annexe A, inclut maintenant les batteries à l'hydrure métallique de nickel et fait référence types d'éléments dans l'IEC 61951-1; i) Annexe B, modifications mineures apportées aux classifications; j) Annexe C, Figure C.1 supprimée en faveur d'un texte révisé; k) Annexe E, exigences supplémentaires couvrant les blocs autonomes d'éclairage de secours portatif. Cette publication doit être lue conjointement avec l'IEC 60598-1:2014.
Svetilke - 2-22. del: Posebne zahteve - Svetilke za zasilno razsvetljavo (IEC 60598-2-22:2014)
Ta del standarda IEC 60598 določa zahteve za svetilke za zasilno razsvetljavo za uporabo z zasilnimi napajalnimi sistemi, ki ne presegajo napetosti 1000 V. Ta del ne zajema učinkov zmanjšanja napetosti v primerih, ki niso nujni, na visokotlačne razelektrilne svetilke. Ta del določa splošne zahteve za opremo za zasilno razsvetljavo. V tem delu se še vedno uporablja izraz »svetilka«, ki zajema tudi »vir(e) svetlobe«, kjer je to ustrezno.
General Information
Relations
Standards Content (Sample)
SLOVENSKI STANDARD
01-april-2015
1DGRPHãþD
SIST EN 60598-2-22:2000
SIST EN 60598-2-22:2000/A1:2004
Svetilke - 2-22. del: Posebne zahteve - Svetilke za zasilno razsvetljavo (IEC 60598-2
-22:2014)
Luminaires - Part 2-22: Particular requirements - Luminaires for emergency lighting (IEC
60598-2-22:2014)
Leuchten - Teil 2-22: Besondere Anforderungen - Leuchten für Notbeleuchtung (IEC
60598-2-22:2014)
Luminaires - Partie 2-22: Exigences particulières - Luminaires pour éclairage de secours
(IEC 60598-2-22:2014)
Ta slovenski standard je istoveten z: EN 60598-2-22:2014
ICS:
29.140.40 Svetila Luminaires
91.160.10 Notranja razsvetljava Interior lighting
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
EUROPEAN STANDARD EN 60598-2-22
NORME EUROPÉENNE
EUROPÄISCHE NORM
October 2014
ICS 29.140.40 Supersedes EN 60598-2-22:1998
English Version
Luminaires - Part 2-22: Particular requirements - Luminaires for
emergency lighting
(IEC 60598-2-22:2014)
Luminaires - Partie 2-22: Exigences particulières - Leuchten - Teil 2-22: Besondere Anforderungen - Leuchten
Luminaires pour éclairage de secours für Notbeleuchtung
(CEI 60598-2-22:2014) (IEC 60598-2-22:2014)
This European Standard was approved by CENELEC on 2014-07-24. CENELEC members are bound to comply with the CEN/CENELEC
Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration.
Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN-CENELEC
Management Centre or to any CENELEC member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by translation
under the responsibility of a CENELEC member into its own language and notified to the CEN-CENELEC Management Centre has the
same status as the official versions.
CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus, the Czech Republic,
Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia,
Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland,
Turkey and the United Kingdom.
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung
CEN-CENELEC Management Centre: Avenue Marnix 17, B-1000 Brussels
© 2014 CENELEC All rights of exploitation in any form and by any means reserved worldwide for CENELEC Members.
Ref. No. EN 60598-2-22:2014 E
Foreword
The text of document 34D/1119/FDIS, future edition 4 of IEC 60598-2-22, prepared by SC 34D,
"Luminaires", of IEC TC 34, "Lamps and related equipment", was submitted to the IEC-CENELEC parallel
vote and approved by CENELEC as EN 60598-2-22:2014.
The following dates are fixed:
(dop) 2015-04-24
• latest date by which the document has
to be implemented at national level by
publication of an identical national
standard or by endorsement
• latest date by which the national (dow) 2017-07-24
standards conflicting with the
document have to be withdrawn
This document supersedes EN 60598-2-22:1998
Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. CENELEC [and/or CEN] shall not be held responsible for identifying any or all such patent
rights.
This standard covers the Principle Elements of the Safety Objectives for Electrical Equipment Designed
for Use within Certain Voltage Limits (LVD - 2006/95/EC).
Endorsement notice
The text of the International Standard IEC 60598-2-22:2014 was approved by CENELEC as a European
Standard without any modification.
- 3 - EN 60598-2-22:2014
Annex ZA
(normative)
Normative references to international publications
with their corresponding European publications
The following documents, in whole or in part, are normatively referenced in this document and are
indispensable for its application. For dated references, only the edition cited applies. For undated
references, the latest edition of the referenced document (including any amendments) applies.
NOTE 1 When an International Publication has been modified by common modifications, indicated by (mod), the relevant EN/HD
applies.
NOTE 2 Up-to-date information on the latest versions of the European Standards listed in this annex is available here:
www.cenelec.eu.
Publication Year Title EN/HD Year
IEC 60073 - Basic and safety principles for man-machine EN 60073 -
interface, marking and identification - Coding
principles for indicators and actuators
IEC 60155 - Glow-starters for fluorescent lamps EN 60155 -
IEC 60364-5-56 - Low-voltage electrical installations -- Part 5- HD 60364-5-56 -
(mod) 56: Selection and erection of electrical
equipment - Safety services
+A11 2013
+A1 2011
+AA
IEC 60598-1 - Luminaires -- Part 1: General requirements EN 60598-1 -
and tests
IEC 60896-21 - Stationary lead-acid batteries -- Part 21: EN 60896-21 -
Valve regulated types - Methods of test
IEC 61056-1 - General purpose lead-acid batteries (valve- EN 61056-1 -
regulated types) -- Part 1: General
requirements, functional characteristics -
Methods of test
IEC 61347-2-2 - Lamp controlgear -- Part 2-2: Particular EN 61347-2-2 -
requirements for d.c. or a.c. supplied
electronic step-down convertors for filament
lamps
IEC 61347-2-3 - Lamp controlgear -- Part 2-3: Particular EN 61347-2-3 -
requirements for a.c. and/or d.c. supplied
electronic control gear for fluorescent lamps
+AC 2011
IEC 61347-2-7 - Lamp controlgear -- Part 2-7: Particular EN 61347-2-7 -
requirements for battery supplied electronic
controlgear for emergency lighting (self-
contained)
IEC 61347-2-12 - Lamp controlgear - Part 2-12: Particular - -
requirements for d.c. or a.c. supplied
electronic ballasts for discharge lamps
(excluding fluorescent lamps)
IEC 61347-2-13 - Lamp controlgear -- Part 2-13: Particular FprEN 61347-2-13 -
requirements for d.c. or a.c. supplied
electronic controlgear for LED modules
IEC 61951-1 - Secondary cells and batteries containing EN 61951-1 -
alkaline or other non-acid electrolytes -
Portable sealed rechargeable single cells --
Part 1: Nickel-cadmium
IEC 61951-2 - Secondary cells and batteries containing EN 61951-2 -
alkaline or other non-acid electrolytes -
Portable sealed rechargeable single cells --
Part 2: Nickel-metal hydride
IEC 62034 - Automatic test systems for battery powered EN 62034 -
emergency escape lighting
ISO 3864-1 2011 Graphical symbols_- Safety colours and - -
safety signs_- Part_1: Design principles for
safety signs and safety markings
ISO 3864-4 - Graphical symbols_- Safety colours and - -
safety signs_- Part_4: Colorimetric and
photometric properties of safety sign
materials
ISO 30061 - Emergency lighting - -
CIE 121 SPI - The Photometry and Goniophotometry of - -
Luminaires - Supplement 1: Luminaires for
Emergency Lighting
- 5 - EN 60598-2-22:2014
Annex ZB
(informative)
A-deviations
A-deviation: National deviation due to regulations, the alteration of which is for the time being outside
the competence of the CEN-CENELEC national member.
This European Standard falls under Directive 2006/95/EC.
NOTE (from CEN-CENELEC IR Part 2:2011, 2.17) Where standards fall under EU Directives, it is the view of
the Commission of the European Communities (OJ No C 59; 1982-03-09) that the effect of the decision of
the Court of Justice in case 815/79 Cremonini/Vrankovich (European Court Reports 1980, p. 3583) is
that compliance with A- deviations is no longer mandatory and that the free movement of products
be restricted except under the safeguard procedure provided for
complying with such a standard should not
in the relevant Directive.
A-deviations in an EFTA-country are valid instead of the relevant provisions of the European
Standard in that country until they have been removed.
Clause Deviation
22.6.18 France Ministry of the Interior, Overseas and Local Authorities - Order of 11
December 2009 approving various provisions supplementing and amending
Regulation for fire hazard safety for buildings open to the public -
Clause EL 10 paragraph 1.
In premises open to the public, electrical installations shall have only permanent
fittings.
22.11.1 France Ministry of the Interior, Overseas and Local Authorities - Order of 11
December 2009 approving various provisions supplementing and amending
Regulation for fire hazard safety for buildings open to the public -
Clause EL 10 paragraph 1.
In premises open to the public, electrical installations shall have only permanent
fittings.
France Ministry of the Interior - Order of 19 November 2001 approving various
22.6.15
provisions supplementing and amending regulation for fire hazard safety
for buildings open to the public - Clauses EC 9 and EC 10.
The required photometric characteristics of products are only based on the
“rated lumen output” as defined in 22.3.14, which shall be measured. Therefore
the photometric data distribution of the luminaire may not to be provided or
checked.
22.17.1 France Ministry of the Interior - Order of 19 November 2001 approving various
provisions supplementing and amending regulation for fire hazard safety
for buildings open to the public - Clauses EC 9 and EC 10.
The required photometric characteristics of products are only based on the
“rated lumen output” as defined in 22.3.14, which shall be measured. Therefore
the photometric data distribution of the luminaire may not to be provided or
checked.
IEC 60598-2-22 ®
Edition 4.0 2014-06
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE
Luminaires –
Part 2-22: Particular requirements – Luminaires for emergency lighting
Luminaires –
Partie 2-22: Règles particulières – Luminaires pour éclairage de secours
INTERNATIONAL
ELECTROTECHNICAL
COMMISSION
COMMISSION
ELECTROTECHNIQUE
PRICE CODE
INTERNATIONALE
CODE PRIX V
ICS 29.140.40 ISBN 978-2-8322-1659-0
– 2 – IEC 60598-2-22:2014 © IEC 2014
CONTENTS
FOREWORD . 3
22.1 Scope . 5
22.2 Normative references . 5
22.3 Terms and definitions . 6
22.4 General test requirements . 9
22.5 Classification of luminaires . 9
22.6 Marking . 9
22.7 Construction . 11
22.8 Creepage distances and clearances . 14
22.9 Provision of earthing . 14
22.10 Terminals . 14
22.11 External and internal wiring . 14
22.12 Protection against electric shock . 14
22.13 Endurance test and thermal test. 14
22.14 Resistance to dust and moisture . 16
22.15 Insulation resistance and electric strength . 16
22.16 Resistance to heat, fire and tracking . 16
22.17 Photometric data . 17
22.18 Changeover operation . 18
22.19 High temperature operation . 18
22.20 Battery chargers for self-contained emergency luminaires . 19
22.21 Test devices for emergency operation . 19
Annex A (normative) Batteries for self-contained emergency luminaires . 20
Annex B (normative) Luminaire classification . 22
Annex C (normative) Luminance measurements . 24
Annex D (informative) Rest mode and inhibition mode facilities.
...
Questions, Comments and Discussion
Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.