Uninterruptible power systems (UPS) - Part 1-1: General and safety requirements for UPS used in operator access areas

applies to electronic uninterruptible power systems (UPS) with an electrical energy storage device in the d.c. link. It is to be used with EN 60950-1 which is referred to in this standard as RD.

Unterbrechungsfreie Stromversorgungssysteme (USV) - Teil 1-1: Allgemeine Anforderungen und Sicherheitsanforderungen an USV außerhalb abgeschlossener Betriebsräume

Alimentations sans interruption (ASI) - Partie 1-1: Prescriptions générales et règles de sécurité pour les ASI utilisées dans des locaux accessibles aux opérateurs

s'applique aux alimentations sans interruption électroniques (ASI) possédant un dispositif d'accumulation de l'énergie sur la liaison à courant continu. Elle est utilisée conjointement avec la EN 60950-1, qui est référencée RD dans la présente norme.

Uninterruptible power systems (UPS) - Part 1-1: General and safety requirements for UPS used in operator access areas (IEC 62040-1-1:2002 + Corrigendum 2002)

General Information

Status
Withdrawn
Publication Date
15-Jan-2003
Withdrawal Date
31-Oct-2005
Technical Committee
Drafting Committee
Parallel Committee
Current Stage
9960 - Withdrawal effective - Withdrawal
Start Date
01-Sep-2011
Completion Date
01-Sep-2011

Relations

Buy Standard

Standard
EN 62040-1-1:2003
English language
49 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)


SLOVENSKI SIST EN 62040-1-1:2003

STANDARD
junij 2003
Uninterruptible power systems (UPS) - Part 1-1: General and safety requirements
for UPS used in operator access areas (IEC 62040-1-1:2002 + Corrigendum 2002)
ICS 29.200 Referenčna številka
©  Standard je založil in izdal Slovenski inštitut za standardizacijo. Razmnoževanje ali kopiranje celote ali delov tega dokumenta ni dovoljeno

EUROPEAN STANDARD EN 62040-1-1
NORME EUROPÉENNE
EUROPÄISCHE NORM January 2003

ICS 29.200 Supersedes EN 50091-1-1:1996

English version
Uninterruptible power systems (UPS)
Part 1-1: General and safety requirements for UPS
used in operator access areas
(IEC 62040-1-1:2002 + corrigendum 2002)

Alimentations sans interruption (ASI) Unterbrechungsfreie
Partie 1-1: Prescriptions générales Stromversorgungssysteme (USV)
et règles de sécurité pour les ASI Teil 1-1: Allgemeine Anforderungen
utilisées dans des locaux und Sicherheitsanforderungen
accessibles aux opérateurs an USV außerhalb abgeschlossener
(CEI 62040-1-1:2002 + corrigendum 2002) Betriebsräume
(IEC 62040-1-1:2002 + Corrigendum 2002)

This European Standard was approved by CENELEC on 2002-11-01. CENELEC members are bound to
comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European
Standard the status of a national standard without any alteration.

Up-to-date lists and bibliographical references concerning such national standards may be obtained on
application to the Central Secretariat or to any CENELEC member.

This European Standard exists in three official versions (English, French, German). A version in any other
language made by translation under the responsibility of a CENELEC member into its own language and
notified to the Central Secretariat has the same status as the official versions.

CENELEC members are the national electrotechnical committees of Austria, Belgium, Czech Republic,
Denmark, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Luxembourg, Malta,
Netherlands, Norway, Portugal, Slovakia, Spain, Sweden, Switzerland and United Kingdom.

CENELEC
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung

Central Secretariat: rue de Stassart 35, B - 1050 Brussels

© 2003 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members.

Ref. No. EN 62040-1-1:2003 E
Foreword
The text of document 22H/22/FDIS, future edition 1 of IEC 62040-1-1, prepared by SC 22H,
Uninterruptible power systems (UPS), of IEC TC 22, Power electronic systems and equipment, was
submitted to the IEC-CENELEC parallel vote and was approved by CENELEC as EN 62040-1-1 on
2002-11-01.
This European Standard supersedes EN 50091-1-1:1996.

The following dates were fixed:

– latest date by which the EN has to be implemented
at national level by publication of an identical
national standard or by endorsement (dop) 2003-08-01

– latest date by which the national standards conflicting
with the EN have to be withdrawn (dow) 2005-11-01

Annexes designated "normative" are part of the body of the standard.
Annexes designated "informative" are given for information only.
In this standard, annexes L, M, N and ZA are normative and annexes H and X are informative.
Annex ZA has been added by CENELEC.

In this standard, the following print types are used:
- Requirements proper and normative annexes: in roman type;
- Compliance statements and test specifications: in italic type;
- Notes and other informative matter: in smaller roman type;
- Normative conditions within tables: in smaller roman type;
- Terms that are defined in clause 3: bold.
__________
Endorsement notice
The text of the International Standard IEC 62040-1-1:2002 and its corrigendum December 2002 was
approved by CENELEC as a European Standard without any modification.
__________
- 3 - EN 62040-1-1:2003
Annex ZA
(normative)
Normative references to international publications
with their corresponding European publications
This European Standard incorporates by dated or undated reference, provisions from other
publications. These normative references are cited at the appropriate places in the text and the
publications are listed hereafter. For dated references, subsequent amendments to or revisions of any
of these publications apply to this European Standard only when incorporated in it by amendment or
revision. For undated references the latest edition of the publication referred to applies (including
amendments).
NOTE When an international publication has been modified by common modifications, indicated by (mod), the relevant
EN/HD applies.
Publication Year Title EN/HD Year
IEC 60417 Series Graphical symbols for use on EN 60417 Series
equipment
IEC 60529 1989 Degrees of protection provided by EN 60529 1991
enclosures (IP Code) + corr. May 1993

IEC/TR 60755 1983 General requirements for residual - -
A1 1988 current operated protective devices
A2 1992
IEC 60950-1 (mod) 2001 Information technology equipment - EN 60950-1 2001
Safety
Part 1: General requirements
IEC 61000-2-2 2002 Electromagnetic compatibility (EMC) EN 61000-2-2 2002
Part 2-2: Environment - Compatibility
levels for low-frequency conducted
disturbances and signalling in public
low-voltage power supply systems

1)
IEC 61008-1 1996 Residual current operated circuit-- -
breakers without integral overcurrent
protection for household and similar
uses (RCCBs)
Part 1: General rules
2)
IEC 61009-1 1996 Residual current operated circuit-- -
breakers with integral overcurrent
protection for household and similar
uses (RCBO's)
Part 1: General rules
1)
The European Standard EN 61008-1:1994 (IEC 61008-1:1990 + A1:1992, mod.) + corrigendum December 1997 + A2:1995
(IEC/A2:1995) + A11:1995 + A12:1998 + corrigendum April 1998 + A13:1998 + A14:1998 applies.
2)
The European Standard EN 61009-1:1994 (IEC 61009-1:1991, mod.) + corrigendum December 1997 + A1:1995 (IEC/A1:1995)
+ A11:1995 + A2:1998 + A13:1998 + corrigendum April 1998 + A14:1998 + A15:1998 + A17:1998 applies.

Publication Year Title EN/HD Year
IEC 62040-1-2 2002 Uninterruptible power systems (UPS)
+ corr. December 2002 Part 1-2: General and safety EN 62040-1-2 2003
requirements for UPS used in
restricted access locations
IEC 62040-2 1999 Part 2: Electromagnetic compatibility - -
(EMC) requirements
IEC 62040-3 (mod) 1999 Part 3: Method of specifying the EN 62040-3 2001
performance and test requirements

NORME CEI
INTERNATIONALE
IEC
62040-1-1
INTERNATIONAL
Première édition
STANDARD
First edition
2002-08
Alimentations sans interruption (ASI) –
Partie 1-1:
Exigences générales et règles de sécurité
pour les ASI utilisées dans des locaux
accessibles aux opérateurs
Uninterruptible power systems (UPS) –
Part 1-1:
General and safety requirements
for UPS used in operator access areas
 IEC 2004 Droits de reproduction réservés  Copyright - all rights reserved
Aucune partie de cette publication ne peut être reproduite ni No part of this publication may be reproduced or utilized in any
utilisée sous quelque forme que ce soit et par aucun procédé, form or by any means, electronic or mechanical, including
électronique ou mécanique, y compris la photocopie et les photocopying and microfilm, without permission in writing from
microfilms, sans l'accord écrit de l'éditeur. the publisher.
International Electrotechnical Commission, 3, rue de Varembé, PO Box 131, CH-1211 Geneva 20, Switzerland
Telephone: +41 22 919 02 11 Telefax: +41 22 919 03 00 E-mail: inmail@iec.ch Web: www.iec.ch
CODE PRIX
X
PRICE CODE
Commission Electrotechnique Internationale
International Electrotechnical Commission
МеждународнаяЭлектротехническаяКомиссия
Pour prix, voir catalogue en vigueur
For price, see current catalogue

62040-1-1  IEC:2004 – 3 –
CONTENTS
FOREWORD.7

1 Scope and specific applications .11
1.1 Scope.11
1.2 Specific applications.11
2 Normative references.13
3 Definitions.15
4 General conditions for tests .21
4.1 Operating parameters for tests .21
4.2 Loads for tests .21
4.3 Components.23
4.4 Power interfaces.23
4.5 Marking and instructions.23
5 Fundamental design requirements .33
5.1 Protection against electric shock and energy hazards .33
5.2 Insulation.37
5.3 Limited current circuits .37
5.4 Provisions for protective earthing .37
5.5 AC and d.c. power isolation.37
5.6 Overcurrent and earth fault protection .39
5.7 Protection of personnel – Safety interlocks.43
5.8 Clearances, creepage distances and distances through insulation.45
5.9 External signalling circuits.45
5.10 Limited power source.45
6 Wiring, connections and supply.47
6.1 General.47
6.2 Connection to power .47
6.3 Wiring terminals for external power conductors .47
7 Physical requirements.47
7.1 Enclosure.47
7.2 Stability.49
7.3 Mechanical strength.49
7.4 Construction details.49
7.5 Resistance to fire.51
7.6 Battery location.51
7.7 Temperature rise.55
8 Electrical requirements and simulated abnormal conditions.57
8.1 General.57
8.2 Electric strength.57
8.3 Abnormal operating and fault conditions.57
9 Connection to telecommunication networks.59

62040-1-1  IEC:2004 – 5 –
Annex H (informative) Guidance on protection against ingress of water and foreign objects . 63
Annex L (normative) Backfeed protection test .67
Annex M (normative) Examples of reference load conditions .71
Annex N (normative) Ventilation of battery compartments .79
Annex X (informative) Guidance for disconnection of batteries during shipment .85

Bibliography.89

Figure L.1 – Potential load faults .69
Figure X.1 – Precautionary label for products shipped with the battery disconnected .85
Figure X.2 – Precautionary label for products shipped with the battery connected .87

Table 1 – Location of battery protective device(s) .41
Table 2 – Temperature-rise limits.55
Table 3 – Permitted temperature limits for magnetic windings at the end of stored
energy mode operation .55
Table H.
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.