Air conditioners, liquid chilling packages and heat pumps with electrically driven compressors for space heating and cooling - Part 4: Requirements

This part of EN 14511 specifies minimum requirements which ensure that air conditioners, heat pumps and liquid chilling packages with electrical driven compressors are fit for the use designated by the manufacturer when used for space heating and/or cooling.
This European Standard applies to factory made units that can be ducted.
This standard applies to factory made liquid chilling packages with integral condensers or for use with remote condensers.
This standard applies to factory-made units of either fixed capacity or variable capacity by any means.
Packaged units, single split and multisplit systems are covered by this standard. Single duct and double duct units are covered by the standard.
In the case of units consisting of several parts, the standard applies only to those designed and supplied as a complete package, except for liquid chilling packages with remote condenser.
This standard is primarily intended for water and brine chilling packages but can be used for cooling any other liquid subject to agreement.
This standard applies to air-to-air air conditioners which evaporate the condensate on the condenser side.
The units having their condenser cooled by air and by the evaporation of external additional water are not covered by this standard.
This standard does not apply to units using transcritical cycles, e.g. with CO2 as refrigerant.
Installations used for heating and/or cooling of industrial processes are not within the scope of this standard.
NOTE   Part load testing of units is dealt with in CEN/TS 14825.

Luftkonditionierer, Flüssigkeitskühlsätze und Wärmepumpen mit elektrisch angetriebenen Verdichtern für die Raumbeheizung und Kühlung - Teil 4: Anforderungen

Dieser Teil der EN 14511 legt Mindestanforderungen fest, durch die sichergestellt ist, dass Luftkonditionierer, Wärmepumpen und Flüssigkeitskühlsätze mit elektrisch angetriebenem Verdichter für den vom Hersteller vor-gesehenen Einsatzbereich geeignet sind, wenn sie für die Raumheizung und/oder -kühlung eingesetzt werden. Diese Europäische Norm gilt für fabrikmäßig zusammengebaute Geräte, die mit Luftkanalanschlüssen ver-sehen sein können. Diese Norm gilt für fabrikmäßig zusammengebaute Flüssigkeitskühlsätze, die mit eingebauten Verflüssigern oder mit getrennt angeordneten Verflüssigern betrieben werden. Diese Norm gilt für fabrikmäßig zusammengebaute Geräte mit fest eingestellter oder durch beliebige Vorrich-tungen zu verändernder Leistung (variable Leistung). Kompaktgeräte, Einzelgeräte in Split-Bauweise und Multi-Split-Systeme fallen unter den Anwendungsbereich dieser Norm. Geräte mit Ein- und Zweikanalsystemen werden ebenfalls in dieser Norm behandelt. Wenn die Geräte aus mehreren Teilen bestehen, gilt diese Norm mit der Ausnahme von Flüssigkeitskühl-sätzen mit getrennt angeordnetem Verflüssiger nur für die Teile, die als vollständige Baueinheit konstruiert und geliefert werden. Diese Norm gilt hauptsächlich für Wasser- und Solekühlsätze, kann jedoch bei Vereinbarung auf weitere Flüssigkeitskühlsätze angewendet werden. Diese Norm gilt für Luft/Luft-Luftkonditionierer, die das Kondensat auf der Verflüssigerseite verdampfen. Geräte, deren Verflüssiger durch Belüftung und durch Verdampfung von zusätzlichem, von außen zuge-führtem Wasser abgekühlt wird, werden in dieser Norm nicht behandelt. Diese Norm gilt nicht für Geräte, bei denen, z. B. mit CO2 als Kältemittel, der Kreisprozess transzyklisch be-trieben wird. Anlagen für die Beheizung und/oder Kühlung industrieller Prozesse fallen nicht in den Anwendungsbereich dieser Norm. ANMERKUNG Die Prüfung der Geräte unter Teillastbedingungen ist in CEN/TS 14825 festgelegt.

Climatiseurs, groupes refroidisseurs de liquide et pompes à chaleur avec compresseur entraîné par moteur électrique pour le chauffage et la réfrigération des locaux - Partie 4: Exigences

La présente partie de l’EN 14511 spécifie les exigences minimales permettant d’assurer que des climatiseurs, des pompes à chaleur et des groupes refroidisseurs de liquide avec compresseur entraîné par moteur électrique sont aptes à l’emploi prévu par le fabricant lorsqu’ils sont utilisés pour le chauffage et/ou la réfrigération des locaux. La présente Norme européenne s’applique aux appareils fabriqués en usine qui peuvent être raccordés. La présente norme s’applique aux groupes refroidisseurs de liquide autonomes fabriqués en usine ou conçus pour être utilisés avec des condenseurs fournis séparément. La présente norme s’applique aux appareils fabriqués en usine de capacité fixe ou variable par tous moyens. La présente norme couvre les systèmes monoblocs, à deux éléments séparés et multi-split. La présente norme couvre les appareils à simple et à double raccordement. Dans le cas d’appareils à éléments séparés, la présente norme ne s’applique qu’aux appareils conçus et fournis comme un ensemble, sauf pour ce qui concerne les groupes refroidisseurs de liquide avec condenseur séparé. La présente norme est principalement destinée aux groupes refroidisseurs d’eau et d’eau glycolée mais peut être utilisée, après accord, pour d’autres liquides. La présente norme s’applique aux climatiseurs air/air qui évaporent les condensats du côté condenseur. La présente norme ne couvre pas les appareils ayant leur condenseur refroidi par air et par évaporation d’eau d’un circuit supplémentaire externe. La présente norme ne couvre pas les appareils utilisant des cycles transcritiques, par exemple avec CO2 comme fluide frigorigène. La présente norme ne s’applique pas aux installations utilisées pour le chauffage et/ou le refroidissement des procédés industriels. NOTE Les essais à charge partielle des appareils sont traités dans la CEN/TS 14825.

Klimatske naprave, enote za tekočinsko hlajenje in toplotne črpalke z električnimi kompresorji za segrevanje in hlajenje prostora - 4. del: Zahteve

General Information

Status
Withdrawn
Publication Date
03-Apr-2008
Withdrawal Date
17-Nov-2011
Technical Committee
Current Stage
9900 - Withdrawal (Adopted Project)
Start Date
17-Nov-2011
Due Date
10-Dec-2011
Completion Date
18-Nov-2011

Relations

Buy Standard

Standard
EN 14511-4:2008
English language
13 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.Luftkonditionierer, Flüssigkeitskühlsätze und Wärmepumpen mit elektrisch angetriebenen Verdichtern für die Raumbeheizung und Kühlung - Teil 4: AnforderungenClimatiseurs, groupes refroidisseurs de liquide et pompes à chaleur avec compresseur entraîné par moteur électrique pour le chauffage et la réfrigération des locaux - Partie 4: ExigencesAir conditioners, liquid chilling packages and heat pumps with electrically driven compressors for space heating and cooling - Part 4: Requirements91.140.30VLVWHPLVentilation and air-conditioning27.080Heat pumps23.120QDSUDYHVentilators. Fans. Air-conditionersICS:Ta slovenski standard je istoveten z:EN 14511-4:2007SIST EN 14511-4:2008en,fr,de01-maj-2008SIST EN 14511-4:2008SLOVENSKI
STANDARDSIST EN 14511-4:20041DGRPHãþD



SIST EN 14511-4:2008



EUROPEAN STANDARDNORME EUROPÉENNEEUROPÄISCHE NORMEN 14511-4November 2007ICS 23.120Supersedes EN 14511-4:2004
English VersionAir conditioners, liquid chilling packages and heat pumps withelectrically driven compressors for space heating and cooling -Part 4: RequirementsClimatiseurs, groupes refroidisseurs de liquide et pompes àchaleur avec compresseur entraîné par moteur électriquepour le chauffage et la réfrigération des locaux - Partie 4 :ExigencesLuftkonditionierer, Flüssigkeitskühlsätze undWärmepumpen mit elektrisch angetriebenen Verdichternfür die Raumbeheizung und Kühlung - Teil 4:AnforderungenThis European Standard was approved by CEN on 13 October 2007.CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this EuropeanStandard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such nationalstandards may be obtained on application to the CEN Management Centre or to any CEN member.This European Standard exists in three official versions (English, French, German). A version in any other language made by translationunder the responsibility of a CEN member into its own language and notified to the CEN Management Centre has the same status as theofficial versions.CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Cyprus, Czech Republic, Denmark, Estonia, Finland,France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal,Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom.EUROPEAN COMMITTEE FOR STANDARDIZATIONCOMITÉ EUROPÉEN DE NORMALISATIONEUROPÄISCHES KOMITEE FÜR NORMUNGManagement Centre: rue de Stassart, 36
B-1050 Brussels© 2007 CENAll rights of exploitation in any form and by any means reservedworldwide for CEN national Members.Ref. No. EN 14511-4:2007: ESIST EN 14511-4:2008



EN 14511-4:2007 (E) 2 Contents Page Foreword.3 1 Scope.4 2 Normative references.4 3 Terms and definitions.5 4 Requirements.5 4.1 General.5 4.2 Temperature operating range.5 4.3 Outside the operating range.7 4.4 Shutting off the heat transfer medium flows.7 4.5 Complete power supply failure.8 4.6 Condensate draining and enclosure sweat test.8 4.7 Defrosting.9 4.8 Other requirements.9 5 Marking.9 6 Technical data sheet.10 6.1 General description.10 6.2 Performance characteristics.10 6.3 Electrical characteristics.11 6.4 Operating range.11 7 Instructions.11 7.1 General.11 7.2 Physical description.11 7.3 Instructions for installation.12 7.4 Instruction for maintenance.12 Bibliography.13
SIST EN 14511-4:2008



EN 14511-4:2007 (E) 3 Foreword This document (EN 14511-4:2007) has been prepared by Technical Committee CEN/TC 113 “Heat pumps and air conditioning units”, the secretariat of which is held by AENOR. This European Standard shall be given the status of a national standard, either by publication of an identical text or by endorsement, at the latest by May 2008, and conflicting national standards shall be withdrawn at the latest by May 2008. Attention is drawn to the possibility that some of the elements of this document may be the subject of patent rights. CEN shall not be held responsible for identifying any or all such patent rights. This document supersedes EN 14511-4:2004. EN 14511 comprises the following parts under the general title "Air conditioners, liquid chilling packages and heat pumps with electrically driven compressors for space heating and cooling“: - Part 1: Terms and definitions - Part 2: Test conditions - Part 3: Test methods - Part 4: Requirements According to the CEN/CENELEC Internal Regulations, the national standards organizations of the following countries are bound to implement this European Standard: Austria, Belgium, Bulgaria, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and the United Kingdom. SIST EN 14511-4:2008



EN 14511-4:2007 (E) 4 1 Scope This part of EN 14511 specifies minimum requirements which ensure that air conditioners, heat pumps and liquid chilling packages with electrical driven compressors are fit for the use designated by the manufacturer when used for space heating and/or cooling. This European Standard applies to factory-made units that can be ducted. This standard applies to factory-made liquid chilling packages with integral condensers or for use with remote condensers. This standard applies to factory-made units of either fixed capacity or variable capacity by any means. Packaged units, single split and multisplit systems are covered by this standard. Single duct and double duct units are covered by the standard. In the case of units consisting of several parts, the standard applies only to those designed and supplied as a complete package, except for liquid chilling packages with remote condenser. This standard is primarily intended for water and brine chilling packages but can be used for cooling any other liquid subject to agreement. This standard applies to air-to-air air conditioners which evaporate the condensate on the condenser side. The units having their condenser cooled by air and by the evaporation of external additional water are not covered by this standard. This standard does not apply to units using transcritical cycles, e.g. with CO2 as refrigerant. Installations used for heating and/or cooling of industrial processes are not within the scope of this standard. NOTE Part load testing of units is dealt with in CEN/TS 14825. 2 Normative references The following referenced documents are indispensable for the application of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. ENV 12102, Air conditioners, heat pumps and dehumidifiers with electrically driven compressors – Measurement of airborne noise – Determination of the sound power level EN 14511-1:2007, Air conditioners, liquid chilling packages and heat pumps with electrically driven compressors for space heating and cooling – Part 1: Terms and definitions EN 14511-2:2007, Air conditioners, liquid chilling packages and heat pumps with electrically driven compressors for space heating and cooling – Part 2: Test conditions EN 14511-3:2007, Air conditioners, liquid chilling packages and heat pumps with electrically driven compressors for space heating and cooling – Part 3: Test methods EN 60204-1, Safety of machinery - Electrical equipment of machines - Part 1: General requirements (IEC 60204-1:2005, modified) EN 60335-2-40, Household and similar electrical appliances - Safety - Part 2-40: Particular requirements for electrical heat pumps, air-conditioners and dehumidifiers (IEC 60335-2-40:2002, modified) SIST EN 14511-4:2008



EN 14511-4:2007 (E) 5 EN 61000-3-11, Electromagnetic compatibility (EMC) – Part 3-11: Limits; Limitation of voltage changes, voltage fluctuations and flicker in public low-voltage supply system; Equipment with rated current ≤ 75 A and subject to conditional connection (IEC 61000-3-11:2000) 3 Terms and definitions For the purposes of this document, the terms and definitions given in EN 14511-1:2007 apply. 4 Requirements 4.1 General Except where otherwise stated, tests shall be conducted as described in EN 14511-2 and EN 14511-3. 4.2 Temperature operating range 4.2.1 Starting test The unit shall be capable of operating within the limit of use indicated by the manufacturer. For every condition stated in Table 1, and for both cooling and heating mode where applicable, the unit shall start up and operate for at least 20 min, without being stopped by the safety devices. Table 1 — Operational requirements conditions Type Temperature at outdoor heat exchanger
ºC Temperature at indoor heat exchanger
°C Voltage V All types Upper limit of use Upper limit of use Rated voltage All types Lower limit of use Lower limit of use Rated voltage
The temperatures are set at the beginning of the test and maintained constant during the test. Test voltage shall be as specified in Table 1. It is set at the beginning of the test and maintained constant during the test. The environmental conditions during the test shall be as specified in Tables 1 and 2 of EN 14511-2:2007. The flow rates shall be the same as that used for rating capacity test, as specified in EN 14511-2. Deviation between individual values and set values shall be between:  zero and minus twice the permissible deviation according to Table 2 of EN 14511-3:2007, for the upper limit of use;  zero and plus twice the permissible deviation according to Table 2 of EN 14511-3:2007, for the lower limit of use. Uncertainty of measurement shall be as specified in Table 1 of EN 14511-3:2007. SIST EN 14511-4:2008



EN 14511-4:2007 (E) 6 4.2.2 Test at maximum operating conditions (cooling mode) When operated at conditions stated in Table 2 during 1 h, then switch off for 3 min, and then switched on again for 1 h, the unit shall meet the following requirements:  the unit shall suffer no damage;  the unit motor shall operate continuously for the first hour without tripping of the motor overload protective devices;  after the shut-down period of 3 min, the unit shall restart automatically no more than 5 min after restarting of the compressor;  the unit motor shall operate again continuously for the rest of the second hour without tripping of the motor overload protective devic
...