Ventilation for buildings - Duct mounted fire dampers

This European Standard applies to fire dampers that are to be used in conjunction with fire separating elements to maintain fire compartments. This standard specifies requirements and gives reference to the test methods defined for fire dampers, which are intended to be installed in Heating, Ventilating and Air Conditioning (HVAC) installations in buildings. All fire dampers close automatically in response to raised temperatures indicating fire. Details are given for the provision of evaluation of conformity and marking of fire dampers. To avoid duplication reference is made to a variety of other standards. To this end it is advised to read this standard in conjunction with EN 1366-2 and EN 1363-1 for details of the fire resistance testing and EN 13501-3 for classification. Fire dampers meeting requirements of this standard may be considered suitable for both ducted and unducted applications. This standard has not considered in detail the detrimental and/or corrosive effects that may be caused by chemical processes present in the atmosphere, which are drawn through the system intentionally or inadvertently and therefore does not apply to fire dampers used in such applications. An indication of salt spray corrosion may be determined using the method described in Annex B.

Lüftung von Gebäuden - Brandschutzklappen in Luftleitungen

Diese Europäische Norm gilt für Brandschutzklappen, die zur Aufrechterhaltung von Brandabschnitten in Verbindung mit Trennwänden zu verwenden sind. Dazu gehören Klappen, die in Systemen mit wie auch ohne Luftführung enthalten sind.
Diese Norm legt Anforderungen fest und verweist auf die Prüfverfahren für Brandschutzklappen, die zum Einbau in allgemeinen Heizungs  und Lüftungsleitungen (HLK Leitungen) in Gebäuden vorgesehen sind.
Um Doppelnennungen zu vermeiden, wird auf eine Anzahl weiterer Normen verwiesen. Für Einzelheiten zu den Ofenprüfungen ist die vorliegende Norm daher in Verbindung mit EN 1366 2 und EN 1363 zu lesen.
Die vorliegende Norm geht nicht im Einzelnen auf die schädigenden und korrosionsverursachenden Wirkungen von in der Atmosphäre vorhandenen Prozess Chemikalien ein, die absichtlich oder unbeabsichtigt im System mitgeführt werden.

Lüftung von Gebäuden - Brandschutzklappen

La présente Norme européenne s'applique aux clapets coupe-feu devant être utilisés conjointement avec des
éléments de compartimentage de façon à maintenir les compartiments coupe feu. La présente norme spécifie les
prescriptions et fait référence aux méthodes d'essai définies pour les clapets coupe-feu destinés à être installés
dans les installations de Chauffage, Ventilation et Conditionnement d’Air (CVCA) des bâtiments. Tous les clapets
coupe-feu se ferment automatiquement en réponse à des températures élevées indiquant un incendie. Des détails
sont donnés concernant les dispositions à prendre pour l’évaluation de la conformité et le marquage des clapets
coupe-feu.
Pour éviter toute duplication, il est fait référence à un large éventail d'autres normes. A cette fin, il est conseillé de
lire la présente norme conjointement à l'EN 1366-2 et à l’EN 1363-1 de façon à obtenir des détails sur les essais à
la résistance au feu et à l’EN 13501-3 pour la classification.
Les clapets coupe-feu satisfaisant aux prescriptions de la présente norme peuvent être considérés comme
appropriés pour les applications raccordées et non raccordées.
La présente norme n’a pas tenu compte dans le détail des éventuels effets néfastes et/ou corrosifs des produits
chimiques présents dans l’atmosphère et véhiculés par le système, volontairement ou par accident et qui donc ne
s’appliquent pas aux clapets coupe-feu utilisés dans de telles applications. Une indication de la corrosion au
brouillard salin peut être déterminée en utilisant la méthode décrite en Annexe B.

Prezračevanje stavb - Požarne lopute v zračni napeljavi

Ta evropski standard velja za požarne lopute, ki naj se uporabljajo skupaj z elementi za ločevanje ognja za vzdrževanje požarnih sektorjev. Ta standard določa zahteve in podaja referenco za metode preskušanja, opredeljene za požarne lopute, ki so namenjene vgradnji v grelne, prezračevalne in klimatske (HVAC) postavitve v stavbah. Vse požarne lopute se zaprejo avtomatsko kot odziv na povišane temperature, ki nakazujejo požar. Podane so podrobnosti za zagotavljanje ocenjevanja skladnosti in označevanje požarnih loput. V izogib podvajanju je referenca podana v več različnih standardih. V ta namen se svetuje, da se ta standard bere skupaj z EN 1366-2 in EN 1363-1 za podrobnosti o preskušanju ognjevarnosti in EN 13501-3 za klasifikacijo. Požarne lopute, ki ustrezajo zahtevam tega standarda, se lahko štejejo kot primerne tako za uporabo v ceveh kot tudi zunaj njih. Ta standard ni podrobno obravnaval škodljivih in/ali korozijskih učinkov, ki so lahko posledica kemičnih procesov, prisotnih v atmosferi, ki  potekajo skozi sistem namenoma ali nenamerno, in zato ne velja za požarne lopute pri takšnih uporabah. Navedba korozije razpršila soli je lahko določena z uporabo metode, opisane v dodatku B.

General Information

Status
Published
Public Enquiry End Date
30-Jul-2007
Publication Date
09-Jun-2010
Technical Committee
Current Stage
6060 - National Implementation/Publication (Adopted Project)
Start Date
17-May-2010
Due Date
22-Jul-2010
Completion Date
10-Jun-2010

Relations

Buy Standard

Standard
EN 15650:2010
English language
33 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.Lüftung von Gebäuden - Brandschutzklappen in LuftleitungenLüftung von Gebäuden - BrandschutzklappenVentilation for buildings - Duct mounted fire dampers91.140.30VLVWHPLVentilation and air-conditioning13.220.01Varstvo pred požarom na splošnoProtection against fire in generalICS:Ta slovenski standard je istoveten z:EN 15650:2010SIST EN 15650:2010en,fr,de01-september-2010SIST EN 15650:2010SLOVENSKI
STANDARD



SIST EN 15650:2010



EUROPEAN STANDARD NORME EUROPÉENNE EUROPÄISCHE NORM
EN 15650
April 2010 ICS 91.140.30 English Version
Ventilation for buildings - Fire dampers
Ventilation dans les bâtiments - Clapets coupe-feu
Lüftung von Gebäuden - Brandschutzklappen This European Standard was approved by CEN on 27 February 2010.
CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN Management Centre or to any CEN member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by translation under the responsibility of a CEN member into its own language and notified to the CEN Management Centre has the same status as the official versions.
CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION EUROPÄISCHES KOMITEE FÜR NORMUNG
Management Centre:
Avenue Marnix 17,
B-1000 Brussels © 2010 CEN All rights of exploitation in any form and by any means reserved worldwide for CEN national Members. Ref. No. EN 15650:2010: ESIST EN 15650:2010



EN 15650:2010 (E) 2 Contents Page Foreword .4Introduction .51Scope .62Normative references .63Terms and definitions .64Fire damper requirements .84.1General .84.1.1Fire resistance .84.1.2General application.84.2Construction and components: characteristics .84.2.1Construction and operation .84.2.2Protection against corrosion .94.2.3Actuators .94.3Fire resistance performance criteria .94.3.1Fire dampers: integrity, insulation, leakage, operational reliability .94.3.2Fire resistance classification and designation . 104.3.3Durability . 104.3.4Other performance criteria . 115Test methods . 115.1Ambient Leakage Tests . 115.2Fire resistance test . 115.2.1General . 115.2.2Fire damper: integrity and insulation . 115.2.3Leakage rated fire damper . 125.2.4Response delay of a fire damper . 125.2.5Sensing element: response temperature and load bearing capacity . 125.3Salt Spray Exposure Test . 125.4Cycling Tests . 125.4.1Pre-fire test cycling. 125.4.2Damper durability cycling . 125.5Damper Aerodynamic Performance. 126Evaluation of conformity . 136.1General . 136.2Initial type testing . 136.2.1General . 136.2.2Modifications . 146.2.3Previous tests and product families . 146.2.4Test samples . 156.2.5Test report . 156.3Factory Product Control (FPC) . 156.3.1General . 156.3.2General requirements . 156.3.3FPC specific requirements . 166.3.4Initial inspection of factory and FPC . 186.3.5Continuous surveillance of FPC . 186.3.6Procedure for modifications . 186.4One-off fire dampers, pre-production fire dampers (e.g. prototypes) and fire dampers produced in very low quantities . 18SIST EN 15650:2010



EN 15650:2010 (E) 3 7Marking and documentation. 198Product, installation and maintenance information (documentation) . 208.1Product specification . 208.2Installation information . 208.3Maintenance information . 20Annex A (informative)
Typical fire damper descriptions . 21Annex B (normative)
Salt spray exposure test . 22Annex C (normative)
Cycling Tests . 23Annex D (informative)
Example of inspection and maintenance procedure . 25Annex E (normative)
Factory Production Control – TEST PLAN . 26Annex ZA (informative)
Relationship between this European Standard and the Essential Requirements of EU Directive (Construction products Directive 89/106/EEC). 27Bibliography . 33 SIST EN 15650:2010



EN 15650:2010 (E) 4 Foreword This document (EN 15650:2010) has been prepared by Technical Committee CEN/TC 156 “Ventilation for buildings”, the secretariat of which is held by BSI. This European Standard shall be given the status of a national standard, either by publication of an identical text or by endorsement, at the latest by October 2010, and conflicting national standards shall be withdrawn at the latest by October 2010. Attention is drawn to the possibility that some of the elements of this document may be the subject of patent rights. CEN [and/or CENELEC] shall not be held responsible for identifying any or all such patent rights. This document has been prepared under a mandate given to CEN by the European Commission and the European Free Trade Association, and supports essential requirements of EU Directive(s). For relationship with EU Directive(s), see informative Annex ZA, which is an integral part of this document. According to the CEN/CENELEC Internal Regulations, the national standards organizations of the following countries are bound to implement this European Standard: Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and the United Kingdom. SIST EN 15650:2010



EN 15650:2010 (E) 5 Introduction This standard contains the basic performance and requirements for fire dampers. A fire damper is used to prevent fire and reduce smoke spreading from one fire compartment to another through the air ductwork system which may penetrate fire separating walls and floors. Annex A gives descriptions of typical fire dampers. Where the words separating element are used in this standard, they should be taken to mean e.g. a wall, a floor, a ceiling or any other barrier that is designed to maintain compartmentation. This covers any type of construction (e.g. block and mortar, concrete, board or mineral wool). In the case of fire or elevated temperatures, the dampers should close automatically by means contained within their own construction (a thermal activation element). As an addition, fire dampers may be closed by an external input.
Particular reference should be made to EN 1366-2, which defines the furnace testing associated with these products and EN 13501-3, which provides details on their fire resistance classification. Consideration of any caution notices within any fire testing standards (e.g. health and safety) should be considered before undertaking any fire testing. In addition, the aerodynamic performance of fire dampers should be tested to EN 1751, if such information is to be presented by a manufacturer. The areas for which products supplied to this standard are considered applicable include, but are not limited to: a) commercial premises; b) shopping and retail centres; c) hospitals; d) multi-residential buildings.
SIST EN 15650:2010



EN 15650:2010 (E) 6 1 Scope This European Standard applies to fire dampers that are to be used in conjunction with fire separating elements to maintain fire compartments. This standard specifies requirements and gives reference to the test methods defined for fire dampers, which are intended to be installed in Heating, Ventilating and Air Conditioning (HVAC) installations in buildings. All fire dampers close automatically in response to raised temperatures indicating fire. Details are given for the provision of evaluation of conformity and marking of fire dampers.
To avoid duplication reference is made to a variety of other standards. To this end it is advised to read this standard in conjunction with EN 1366-2 and EN 1363-1 for details of the fire resistance testing and
EN 13501-3 for classification. Fire dampers meeting requirements of this standard may be considered suitable for both ducted and unducted applications. This standard has not considered in detail the detrimental and/or corrosive effects that may be caused by chemical processes present in the atmosphere, which are drawn through the system intentionally or inadvertently and therefore does not apply to fire dampers used in such applications. An indication of salt spray corrosion may be determined using the method described in Annex B. 2 Normative references The following referenced documents are indispensable for the application of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. EN 1366-2:1999, Fire resistance tests for service installations — Part 2: Fire dampers EN 1751, Ventilation for buildings — Air terminal devices — Aerodynamic testing of dampers and valves EN 13501-3:2005, Fire classification of construction products and building elements — Part 3: Classification using data from fire resistance tests on products and elements used in building service installations: fire resisting ducts and fire dampers EN 60068-2-52:1996, Environmental testing — Part 2: Tests — Test Kb: Salt mist, cyclic (sodium chloride solution) (IEC 60068-2-52:1996) EN 60529:1991, Degrees of protection provided by enclosures (IP code) (IEC 60529:1989) EN ISO 5135, Acoustics — Determination of sound power levels of noise from air-terminal devices, air-terminal units, dampers and valves by measurement in a reverberation room (ISO 5135:1997) EN ISO 13943:2000, Fire safety — Vocabulary (ISO 13943:2000) ISO 10294-4:2001, Fire resistance tests — Fire dampers for air distribution systems — Part 4: Test of thermal release mechanism 3 Terms and definitions For the purpose of this document, the terms and definitions given in EN ISO 13943:2000 and the following apply. SIST EN 15650:2010



EN 15650:2010 (E) 7 3.1 fire damper device for use in heating, ventilation and air conditioning (HVAC) systems at fire boundaries to maintain compartmentation and protect means of escape in case of fire
3.2 insulated fire damper fire damper of any type that shows classifiable insulation characteristics when tested 3.3 leakage rated fire damper fire damper of any type that shows classifiable reduced leakage characteristics when tested 3.4 multi-section fire dampers fire damper of any type constructed from smaller units 3.5
fire compartment enclosed space, comprising one or more separate spaces, bounded by elements of construction having a specified fire resistance and intended to prevent the spread of fire (in either direction) for a given period of time NOTE Fire compartment often has regulatory definitions and requirements. The term should not be confused with "room of origin" or "fire cell". 3.6 triggering device device such as a fire detector system, smoke detector or pushbutton, which sends an activating signal to the initiation device 3.7 horizontal mounting position of the damper mounted horizontally when installed in a floor or a ceiling 3.8 vertical mounting position of the damper mounted vertically when installed in a wall 3.9 actuating mechanism mechanism, integral or directly associated with the fire damper which, when initiated by the fire damper release device, which causes the movable component of the damper to change from the "open" to the "closed" position 3.10 thermal release mechanism mechanism, containing/linked to the sensing element, that causes the open damper to release and close in response to elevated temperature 3.11 sensing element device that senses temperature, that causes the thermal release mechanism to activate at a defined elevated temperature SIST EN 15650:2010



EN 15650:2010 (E) 8 4 Fire damper requirements 4.1 General 4.1.1 Fire resistance The fire damper shall be fire resisting and demonstrate the following and shall be classified in accordance with EN 13501-3: a) integrity: this shall be tested in accordance with test method in 5.2.2 and the integrity classification (E) declared; b) insulation: this shall be tested in accordance with test method in 5.2.2 and the insulation classification (I) declared; c) leakage: this shall be tested in accordance with test method in 5.2.3 and the leakage classification (S) declared. 4.1.2 General application Where the manufacturer intends to provide information regarding aerodynamic characteristics, this shall be done according to EN 1751. 4.2 Construction and components: characteristics 4.2.1 Construction and operation 4.2.1.1 General Fire dampers shall have one safety position, fully closed. This is required to maintain compartmentation.
4.2.1.2 Nominal activation conditions / Sensitivity 4.2.1.2.1 General The units may be open as part of a heating and ventilating system and shall close only on the receipt of:  an elevated temperature; or  an external input. Consequently, fire dampers shall: a) move to and maintain their closed position; b) have known leakage characteristics; c) include a thermal release mechanism that causes the damper to close (this may be function of their design), where the thermal release mechanism uses a sensing element which shall be tested in accordance with 5.2.5; d) be fire resisting to maintain compartmentation in closed position. NOTE A facility for manual override to open and close the damper for inspection purposes may be useful and may be included in the product design. This would be of use during commissioning should no power be available. SIST EN 15650:2010



EN 15650:2010 (E) 9 4.2.1.2.2 Sensing element response temperature The thermal release mechanism shall be equipped with a sensing element with response temperature to an increase of temperature in accordance with test method in 5.2.5. 4.2.1.2.3 Sensing element load bearing capacity The thermal release mechanism shall be equipped with a sensing element which load bearing capacity is in accordance with test method in 5.2.5. 4.2.1.3 Response delay: closure time Any temperature may be used, provided that the fire dampers' response delay (closure time) is within the time period of 2 min in accordance with test method in 5.2.4. 4.2.1.4 Position indication When fire dampers incorporate blade positioning signalling devices, such devices shall be demonstrated to provide information (at ambient temperature) which is indicative of the actual blade position (open and closed) in accordance with Annex C (C.1).
4.2.2 Protection against corrosion Where a manufacturer intends to demonstrate an enhanced salt spray corrosion resistant performance of a fire damper to give a guide on its durability, the test detailed in Annex B shall be performed and the result of these tests declared (i.e. pass/fail). Alternatively, this performance may be made by using of known-corrosion-resistance products, components and treatments and this shall be declared. NOTE Except for products used in a corrosive/contaminated environment, there are no corrosion resistance requirements on products for other uses. 4.2.3 Actuators Actuators shall be constructed and assembled to have the strength and rigidity necessary to perform the design operations to which it may be subjected, without the loosening or displacement of parts, or other serious defects when subjected to the tests referred to in Annex C. Actuators shall be assessed by an IP42 test as a minimum according to EN 60529:1991. Actuator construction shall be such that it does not cause a fire damper to fail the test by flaming outside of the furnace and outside the duct. Where modulating actuators allowing fire dampers to give variable volume control are to be supplied, these shall be subjected to more extensive cycle testing according to Annex C. As smoke is seen as being as, if not more, dangerous than fire, closing actuators may be used that close the unit early as the result of, for instance, a fire alarm. These shall form a part of the tested construction if the actuator is seen as being the prime mover of the unit. If an actuator is associated with a fire damper for everyday use, it should be tested at the same time as the fire damper to ensure that it does not cause the fire damper to fail in any way that may have not been foreseen. 4.3 Fire resistance performance criteria 4.3.1 Fire dampers: integrity, insulation, leakage, operational reliability The assessment of integrity (E) of fire dampers, as one of the fire resistance performance characteristics, shall be made on the basis of: SIST EN 15650:2010



EN 15650:2010 (E) 10 a) Largest size − 50 cycles prior to the fire test (unless it is impossible to re-open the damper in any way once it has been closed). Except for fire dampers which have "single use" (no mechanical closing element), but giving closure by change of state, such as a fully intumescent style product, may be exempted from the 50 cycle test and the cold leakage test and consequently cannot be considered for extra restriction on leakage.
The operational reliability shall be satisfied by the 0 or 50 cycle test at ambient temperature; b) Largest size − leakage (measured continuously) through the damper when closed after 5 min from the start of the fire test; c) Cracks or openings in excess of given dimensions and ignition of a cotton pad and sustained flaming on the non-exposed side at the perimeter of the damper junction with the wall or floor or duct (the penetration). When insulation characteristics (I) are proven for fire dampers, this shall be classified and declared, together with integrity. A smoke leakage performance requirement is described in EN 1366-2 to allow the (S) classification, and this shall be applied, if the damper is intended for the end uses where this performance is required (largest and smallest sizes at ambient and largest size (measured continuously) after 5 min from the start of the fire test). 4.3.2 Fire resistance classification and designation Having achieved the performance criteria in 4.3.1, the fire damper shall be classified and designated in accordance with EN 13501-3. The following shall be declared for each fire damper: a) integrity class "E", integrity and insulation class "EI" (in accordance with EN 13501-3:2005); b) indication(s) of suitability for vertical and/or horizontal use, together with mounting in, or on to, a wall or in a duct passing through a wall or in, or on to, a floor, or in a duct passing through a floor, or both, respectively: as ve and/or ho. The classification is completed by "(i Æ o)", "(o Æ i)", or (i ÅÆ o)" to indicate whether the element has been tested and fulfils the requirements from the inside of outside only or both. In addition, the symbols "ve" and/or "ho" indicate the suitability for vertical and/or horizontal use. The addition of the symbol "S" indicates the satisfaction of an extra restriction on leakage. NOTE
ve or ho should not be taken to imply the direction of operation, nor the orientation of the axis of the damper blade.
EXAMPLE EI 60 (ve) S. 4.3.3 Durability
4.3.3.1 Durability of response delay Following the test described in 5.2.5 demonstrates the durability of response delay by testing the sensing element for response temperature and load bearing capacity. 4.3.3.2 Durability of operational reliability To ensure requirements on this durability aspect, the following proxy characteristics shall be taken in account: The ability of the fire damper to demonstrate its operational reliability over the life of the system shall be determined by the open and closing cycle tests shown in Annex C. SIST EN 15650:2010



EN 15650:2010 (E) 11 The intended application of the product within the system determines the number of complete cycles to be achieved during this test. A cycle is defined as the damper moving from the open position to the closed and back to the open position or between the upper position to the lower position and back to the upper position for modulating dampers. The fire damper passes the open and closing cycle test when:  the cycles required are fully completed with the average time of each travel less than 120 s;  the average time of the last travel is less than 120 s. 4.3.4 Other performance criteria Where the manufacturer intends to provide information regarding aerodynamic performance, it shall do so in accordance with EN 1751.
5 Test methods 5.1 Ambient Leakage Tests The test method shall be in accordance with EN 1366-2 and/or EN 1751. 5.2 Fire resistance test 5.2.1 General In addition to other requirements in this standard, the fire damper shall be subjected to a furnace mounted fire resistance test. The purpose of the test is to evaluate the ability of a fire damper to prevent fire and smoke spreading from one fire compartment to another through the air ductwork system which may penetrate fire separating walls and floors. The fire damper is attached (directly or remotely via a section of ducting), in/to a supporting construction using a method described in the test standard (EN 1366-2) in a manner generally representative of practice. Fire dampers may be situated within the construction of the wall/floor, attached to the face of the wall/floor, or mounted remotely from it via a section of fire resistant ducting. NOTE Test results are only valid for the tested method of mounting, together with any direct or extended field of application that may be applicable. Tests shall be performed starting with the fire damper in the open position to expose the thermal release mechanism of the fire damper to furnace conditions. Temperature and integrity measurements shall be carried out in various parts of the test construction during the test. The impermeability of the fire damper system shall be measured by direct flow measurements whilst maintaining a constant pressure differential across the closed fire damper of 300 Pa. The leakage rate of dampers requiring an S classification shall be measured at ambient temperature.
It may be necessary to test fire dampers not mounted directly within the centre of the supporting construction, both inside and outside the supporting construction for it to be universally acceptable for that method of installation. 5.2.2 Fire damper: integrity and insulation Equipment and method as fully described in EN 1366-2, the largest size to be manufactured shall be subjected to the closure test, followed by the fire resistance test (EN 1366-2). Units shall be fire tested in the SIST EN 15650:2010



EN 15650:2010 (E) 12 plane of proposed installation (i.e. for classification the damper shall be tested horizontally mounted or vertically mounted, depending on the proposed installation). NOTE For information purposes only, the unit may be ambient leakage tested prior to the fire test. 5.2.3 Leakage rated fire damper Equipment and method as fully described in EN 1366-2, the largest size to be manufactured shall be subjected to the closure test, followed by the ambient leakage test, followed by the fire resistance test (see EN 1366-2). Units need to be fire tested in t
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.