Cable trunking systems and cable ducting systems for electrical installations -- Part 2-1: Cable trunking systems and cable ducting systems intended for mounting on walls and ceilings

This European Standard specifies requirements and tests for cable trunking systems (CTS) and cable ducting systems (CDS) intended for the accommodation, and where necessary for the electrically protective separation, of insulated conductors, cables and possibly other electrical equipment in electrical and/or communication systems installations. The maximum voltage of these installations is 1 000 V a.c. and 1 500 V d.c. These systems are intended for mounting on walls and/or ceilings. They may be embedded, installed in a flush or semi-flush state, surface mounted or mounted away from the surface using fixing devices. This standard does not apply to conduit systems, cable tray systems, cable ladder systems, power track systems or equipment covered by other standards. This standard shall be used in conjunction with EN 50085-1:2005: Cable trunking systems and cable ducting systems for electrical installations;Part 1 General requirements which is referred to in this document as Part 1.

Elektroinstallationskanalsysteme für elektrische Installationen -- Teil 2-1: Besondere Anforderungen für Elektroinstallationskanalsysteme für Wand und Decke

Ersatz: Diese Europäische Norm legt Anforderungen und Prüfungen für Elektroinstallationskanalsysteme, die für die Aufnahme und, wo erforderlich, für die Auseinanderhaltung oder Separierung von isolierten Leitern, Kabeln, Leitungen und möglichen anderen elektrischen Betriebsmitteln in elektrischen Installationen oder Kommunikationssystemen fest. Die maximale Spannung dieser Installationen ist 1000 V Wechselspannung und 1500 V Gleichspannung. Die Systeme sind für die Montage an Wand und/oder Decke vorgesehen. Sie können versenkt, teilversenkt, oberflächenbündig, auf der Oberfläche  oder im Abstand  von der Oberfläche mit Befestigungsmitteln montiert sein Diese Norm gilt nicht für Elektroinstallationsrohrsysteme, Kabelträgersysteme, Stromschienensysteme oder Einrichtungen, die von anderen Normen abgedeckt sind. Diese Norm muss zusammen mit EN 50085-1:2005 „Elektroinstallationssysteme für elektrische Installationen - Teil 1: Allgemeine Anforderungen“ benutzt werden, auf welche in dieser Norm als Teil 1 Bezug genommen wird.

Systèmes de goulottes et systèmes de conduits-profilés pour installations électriques -- Partie 2-1: Systèmes de goulottes et systèmes de conduits-profilés prévus pour être montés sur les murs et les plafonds

Remplacement: La présente Norme Européenne spécifie les règles et les essais pour les systèmes de goulottes (SG) et les systèmes de conduits-profilés (SCP) destinés au logement de conducteurs isolés, câbles et éventuels autres équipements électriques et si nécessaire à leur séparation de protection électrique, dans des installations électriques et/ou de systèmes de communication. La tension maximale de ces installations est de 1 000 V en courant alternatif et 1 500 V en courant continu. Ces systèmes sont prévus pour être montés sur les murs et/ou les plafonds. Ils peuvent être noyés, encastrés, semi-encastrés, montés en saillie ou montés écartés de la surface d'appui avec des dispositifs de fixation. Cette norme ne s'applique pas aux systèmes de conduit, systèmes de chemin de câble, systèmes d'échelle à câble, systèmes de canalisation préfabriquée ou aux équipements couverts par d’autres normes. La présente norme doit être utilisée conjointement avec la EN 50085-1:2005, Systèmes de goulottes et de conduits-profilés pour installations électriques - Partie 1: Règles générales, à laquelle il est fait référence dans ce document comme Partie 1.

Sistemi kabelskih korit in sistemi kabelskih cevi za električne instalacije - 2-1. del: Sistemi kabelskih korit in sistemi kabelskih cevi za montažo na stene in strope

Ta evropski standard določa zahteve in preskuse za sisteme kabelskih korit (CTS) in sisteme kabelskih cevi (CDS), ki so namenjeni namestitvi in po potrebi električnemu zaščitnemu ločevanju izoliranih prevodnikov, kablov in morda druge električne opreme v inštalacijah električnih in/ali komunikacijskih sistemih. Maksimalna napetost teh inštalacij je 1000 V izmeničnega toka in 1500 V enosmernega toka. Ti sistemi so namenjeni montaži na stene in/ali strope. Lahko so vdelani, pritrjeni v vgreznem ali polvgreznem stanju, pritrjeni na površino ali od nje z uporabo pritrditvenih naprav. Ta standard ne velja za sisteme napeljav, sisteme kabelskih polic, sisteme kabelskih lestev, tirne sisteme za električno napeljavo ali opremo, ki jo zajemajo drugi standardi. Ta standard se uporablja skupaj z EN 50085-1:2005: Sistemi kabelskih korit in sistemi kabelskih cevi za električne inštalacije; 1. del Splošne zahteve, ki je naveden v tem dokumentu kot 1. del.

General Information

Status
Published
Publication Date
17-Oct-2007
Technical Committee
Current Stage
6060 - National Implementation/Publication (Adopted Project)
Start Date
09-Oct-2007
Due Date
14-Dec-2007
Completion Date
18-Oct-2007

Relations

Buy Standard

Standard
EN 50085-2-1:2007
English language
24 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

SLOVENSKI STANDARD
SIST EN 50085-2-1:2007
01-december-2007
6LVWHPLNDEHOVNLKNRULWLQVLVWHPLNDEHOVNLKFHYL]DHOHNWULþQHLQVWDODFLMH±GHO
6LVWHPLNDEHOVNLKNRULWLQVLVWHPLNDEHOVNLKFHYL]DPRQWDåRQDVWHQHLQVWURSH
Cable trunking systems and cable ducting systems for electrical installations -- Part 2-1:
Cable trunking systems and cable ducting systems intended for mounting on walls and
ceilings
Elektroinstallationskanalsysteme für elektrische Installationen -- Teil 2-1: Besondere
Anforderungen für Elektroinstallationskanalsysteme für Wand und Decke
Systemes de goulottes et systemes de conduits-profilés pour installations électriques --
Partie 2-1: Systemes de goulottes et systemes de conduits-profilés prévus pour etre
montés sur les murs et les plafonds
Ta slovenski standard je istoveten z: EN 50085-2-1:2006
ICS:
29.120.10 ,QãWDODFLMVNHFHYL]D Conduits for electrical
HOHNWULþQHQDPHQH purposes
SIST EN 50085-2-1:2007 en,fr,de
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

---------------------- Page: 1 ----------------------

EUROPEAN STANDARD
EN 50085-2-1

NORME EUROPÉENNE
October 2006
EUROPÄISCHE NORM

ICS 29.120.10


English version


Cable trunking systems and cable ducting systems
for electrical installations
Part 2-1: Cable trunking systems and cable ducting systems
intended for mounting on walls and ceilings



Systèmes de goulottes et systèmes  Elektroinstallationskanalsysteme
de conduits-profilés pour installations für elektrische Installationen
électriques Teil 2-1: Besondere Anforderungen
Partie 2-1: Systèmes de goulottes et für Elektroinstallationskanalsysteme
systèmes de conduits-profilés prévus pour für Wand und Decke
être montés sur les murs et les plafonds




This European Standard was approved by CENELEC on 2006-10-01. CENELEC members are bound to comply
with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard
the status of a national standard without any alteration.

Up-to-date lists and bibliographical references concerning such national standards may be obtained on
application to the Central Secretariat or to any CENELEC member.

This European Standard exists in three official versions (English, French, German). A version in any other
language made by translation under the responsibility of a CENELEC member into its own language and notified
to the Central Secretariat has the same status as the official versions.

CENELEC members are the national electrotechnical committees of Austria, Belgium, Cyprus, the Czech
Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia,
Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain,
Sweden, Switzerland and the United Kingdom.

CENELEC
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung

Central Secretariat: rue de Stassart 35, B - 1050 Brussels


© 2006 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members.
Ref. No. EN 50085-2-1:2006 E

---------------------- Page: 2 ----------------------

EN 50085-2-1:2006 – 2 –
Foreword
This European Standard was prepared by the Technical Committee CENELEC TC 213, Cable
management.
The text of the draft was submitted to the formal vote and was approved by CENELEC as EN 50085-2-1
on 2006-10-01.
The following dates were fixed:
– latest date by which the EN has to be implemented
at national level by publication of an identical
national standard or by endorsement (dop) 2007-10-01
– latest date by which the national standards conflicting
with the EN have to be withdrawn (dow) 2009-10-01

This standard is a system standard for cable management products used for electro-technical
purposes. It relates to the Council Directives on the approximation of laws, regulations and
administrative provisions of the Member States relating to Low Voltage Directive (73/23/EEC)
through consideration of the essential requirements of this directive.
This standard is supported by separate standards to which references are made.
This Part 2 is to be used in conjunction with EN 50085-1:2005, Cable trunking and cable ducting
systems for electrical installations – Part 1: General requirements.
This Part 2 supplements or modifies the corresponding clauses of Part 1. Where a particular
clause or subclause of Part 1 is not mentioned in this Part 2, that clause or subclause of Part 1
applies as far as is reasonable. Where this Part 2 states “addition” or “replacement”, the relevant
text of Part 1 is to be adapted accordingly.
Subclauses and figures which are additional to those in Part 1 are numbered starting from 101.

---------------------- Page: 3 ----------------------

– 3 – EN 50085-2-1:2006
Contents
Page
1 Scope.4
2 Normative references.4
3 Definitions .4
4 General requirements .5
5 General conditions for tests .5
6 Classification .5
7 Marking and documentation .7
8 Dimensions.7
9 Construction .7
10 Mechanical properties.9
11 Electrical properties .14
12 Thermal properties .14
13 Fire effects .14
14 External influences .14
15 Electromagnetic compatibility.14

Annex A (informative) Types of cable trunking systems (CTS) and cable ducting systems
(CDS) .24
Annex B (informative).24
Annex C (normative) .24

Figure 101 - Types and application of CTS/CDS for wall or ceiling installation.15
Figure 102 - Arrangement for cable support test according to 10.2.2.16
Figure 103 - Arrangement for cable support test according to 10.2.3.16
Figure 104 - Arrangement for cable support test according to 10.2.4.17
Figure 105 - Arrangement for cable support test according to 10.2.5.17
Figure 106 - Impact test for installation and application – Principles for arrangement .18
Figure 107 - Impact test for installation and application – Examples for arrangement .21
Figure 108 - Arrangement for linear deflection test .22
Figure 109 - Example of arrangement for CDS compression test .23

---------------------- Page: 4 ----------------------

EN 50085-2-1:2006 – 4 –
1 Scope
Replacement:
This European Standard specifies requirements and tests for cable trunking systems (CTS) and
cable ducting systems (CDS) intended for the accommodation, and where necessary for the
electrically protective separation, of insulated conductors, cables and possibly other electrical
equipment in electrical and/or communication systems installations. The maximum voltage of these
installations is 1 000 V a.c. and 1 500 V d.c.
These systems are intended for mounting on walls and/or ceilings. They may be embedded,
installed in a flush or semi-flush state, surface mounted or mounted away from the surface using
fixing devices.
This standard does not apply to conduit systems, cable tray systems, cable ladder systems, power
track systems or equipment covered by other standards.
This standard shall be used in conjunction with EN 50085-1:2005: Cable trunking systems and
cable ducting systems for electrical installations - Part 1 General requirements which is referred to
in this document as Part 1.
2 Normative references
This clause of Part 1 is applicable except as follows:
Addition:
EN 60068-2-75 1997 Environmental testing - Part 2-75: Tests - Test Eh: Hammer tests
(IEC 60068-2-75:1997)
EN 20535 1994 Paper and board - Determination of water absorptiveness - Cobb
method (ISO 535:1991)
EN ISO 536 1996 Paper and board – Determination of grammage (ISO 536:1995)
3 Definitions
This clause of Part 1 is applicable except as follows:
3.1 Replace the note by:
NOTE Different types of CTS are shown in Figure 101 and explained in Annex A.1.
3.2 Replace the note by:
NOTE Different types of CDS are shown in Figure 101 and explained in Annex A.1.
Addition:
3.101
type 2 CTS/CDS (Distribution CTS/CDS)
CTS/CDS which provides at least the following functions:
• in line junction between two trunking lengths or ducting lengths,
• internal and external changes of direction between two trunking lengths or ducting lengths,

---------------------- Page: 5 ----------------------

– 5 – EN 50085-2-1:2006
• flat change of direction between two trunking lengths or ducting lengths with the exception of
certain systems where such a function is not required e.g. skirting CTS/CDS,
• "T" function between three trunking lengths or ducting lengths with the exception of certain
systems where such a function is not required e.g. Bench CTS,
• termination of a trunking length or a ducting length
3.102
type 3 CTS/CDS (Installation CTS/CDS)
distribution CTS/CDS which provides in addition apparatus mounting function
3.103
type 1 CTS/CDS
CTS/CDS that cannot be defined as a type 2 CTS/CDS (Distribution CTS/CDS) or as a type 3 CTS/CDS
(Installation CTS/CDS)
3.104
surface mounting CTS/CDS
CTS/CDS which is intended for mounting on a surface
3.105
flush-mounting CTS/CDS
CTS/CDS which is intended for mounting flush with the surface so that at least 90 % of the product depth
is recessed below the finished surface when installed according to manufacturer’s instructions
3.106
semi-flush mounting CTS/CDS
CTS/CDS which is intended to fit within a mounting surface so that more than 10 % of the product depth
projects from the finished surface
4 General requirements
This clause of Part 1 is applicable.
5 General conditions for tests
This clause of Part 1 is applicable.
6 Classification
This clause of Part 1 is applicable except as follows:
Addition:
6.101 According to the intended installation positions
NOTE More than one classification can be declared.
6.101.1 CDS embedded in the wall or ceiling.
6.101.2 CTS/CDS flush in the wall or ceiling.
6.101.2.1 CTS/CDS flush in the wall.

---------------------- Page: 6 ----------------------

EN 50085-2-1:2006 – 6 –
6.101.2.2 CTS/CDS flush in the ceiling.
6.101.3 CTS/CDS semi flush or surface mounted on the wall or ceiling.
6.101.3.1 CTS/CDS semi flush or surface mounted on the wall.
6.101.3.2 CTS/CDS semi flush or surface mounted on the ceiling.
6.101.3.3 CTS/CDS wall fixed and supported by the floor.
6.101.3.4 CTS/CDS wall fixed and supported by a horizontal surface other than the floor.
6.101.4 CTS/CDS mounted away from the wall or ceiling using fixing devices.
6.102 According to the prevention of contact between liquids and insulated conductors
and live parts in case of CTS/CDS mounted in a skirting position and wet-treatment of floor
6.102.1 Not declared.
6.102.2 Relying completely on manufacturer’s instructions restricting the installation position of
the CTS/CDS.
6.102.3 Relying on manufacturer’s instructions allowing all installation positions of the CTS/CDS
but restricting the position of insulated conductors and live parts in CTS/CDS.
6.102.4 Relying on manufacturer’s instructions allowing all installation positions of the CTS/CDS
and all positions of insulated conductors and live parts in CTS/CDS.
NOTE Installation position refers to the distance between CTS/CDS and the floor.
6.103 According to the Type
6.103.1 Type 1 CTS/CDS.
6.103.2 Type 2 CTS/CDS (Distribution CTS/CDS).
6.103.3 Type 3 CTS/CDS (Installation CTS/CDS).
6.104 According to resistance to compression for CDS
6.104.1 CDS for compression 125 N.
6.104.2 CDS for compression 320 N.
6.104.3 CDS for compression 750 N.
6.104.4 CDS for compression 1 250 N.
6.104.5 CDS for compression 4 000 N.

---------------------- Page: 7 ----------------------

– 7 – EN 50085-2-1:2006
7 Marking and documentation
This clause of Part 1 is applicable except as follows:
7.3 Replacement:
7.3 The manufacturer shall provide in his documentation all information necessary for the proper
and safe installation and use. It shall include
- components of the system,
- function of the system components and their assemblies,
- classification of the system in accordance with Clause 6,
- for type 1 CTS/CDS the list of functions,
- linear impedance, in Ω/m, of trunking length or ducting length of system declared according to
6.5.1,
- rated voltage of CTS/CDS declared according to 6.6.2,
2
- usable cross sectional area, in mm , for cables of the CTS/CDS,
NOTE  Certain system components when mounted can reduce the usable cross sectional area for cables.
- instructions to reach the declared classification and functions of the system.
These instructions shall include the recommended installation positioning for the CTS/CDS to
ensure that the declared IP classification is maintained after installation.
Compliance is checked by inspection.
8 Dimensions
This clause of Part 1 is applicable except as follows:
Addition:
There are no dimensions requirements.
9 Construction
This clause of Part 1 is applicable except as follows:
Addition:
9.101 Assembling
System components shall fit correctly.
Compliance is checked by inspection.
9.102 Contact between liquids and insulated conductors and live parts
CTS/CDS declared according to 6.102.2, 6.102.3 or 6.102.4 shall prevent liquids coming into
contact with insulated conductors and live parts during wet-treatment of floor.

---------------------- Page: 8 ----------------------

EN 50085-2-1:2006 – 8 –
Compliance is checked by inspection and measurement when the area intended to accommodate
insulated conductors is at least 10 mm above the floor due to
• design, or
• manufacturer’s instructions restricting the installation position of the CTS/CDS, or
• manufacturer’s instructions allowing all installation positions of the CTS/CDS but restricting
the position of insulated conductors and live parts in CTS/CDS.
In all other cases compliance is checked by the following test carried out on an assembly or
assemblies.
An assembly is made of one or more trunking lengths or ducting lengths with the relevant system
component, if any, to fulfil the various functions of the system and prepared according to the
manufacturer’s instructions. More than one assembly may be necessary to fulfil the various
functions of the system. In each direction, the length L of trunking length or ducting length coming
out of the functional area associated with the function of the system is as long as the width W of
the trunking length or ducting length, or 250 mm, whichever is the greater. The tolerance of L is
± 25 mm.
NOTE 1  Functional area refers, for example, to a fitting, an apparatus mounting device, a junction as shown in Figure 106
The assembly is fixed according to manufacturer’s instructions to an appropriate support. The
ends of the assembly are closed according to manufacturer’s instructions.
A (5 ± 1) mm wide strip of absorbent paper is placed on the lowest internal surface of CTS/CDS
intended for the accommodation of insulated conductors. If this lowest internal surface is
horizontal, the strip is placed approximately on the centre line of the surface. The absorbent paper
has a water absorptive height longitudinal of 75 mm per 10 min according to EN 20535 and a
basis weight of 250 g per m² according to EN ISO 536. The length of the strip is such that it
covers the whole length of the assembly.
NOTE 2  When the tested function of the system includes a change of direction, the length of paper can be made of more than
one strip.
Provisions are made such that the absorbent paper makes contact with the lowest internal surface
of CTS/CDS intended for the accommodation of insulated conductors along the whole length of
the assembly. These provisions shall not influence absorption by the paper.
The assembly is carefully placed in a tray containing water to simulate a (10 , 0/-1) mm height of
water on the floor.
NOTE 3  For easy measurement of wet area coloured water can be used.
After (15 ± 1) s the assembly is removed from the tray and the exterior of the assembly is
immediately wiped.
After careful removal of the access covers, if any, the abso
...