oSIST prEN 14037-1:2012
(Main)Free hanging heating and cooling surfaces for water with a temperature below 120°C - Part 1: Technical specifications and requirements
Free hanging heating and cooling surfaces for water with a temperature below 120°C - Part 1: Technical specifications and requirements
This European Standard defines the technical specifications and requirements of ceiling mounted hot water radiant panels, heating and cooling surfaces fed with water at temperatures below 120 °C connected with a centralized heating and/or cooling supply source.
An der Decke frei abgehängte Heiz- und Kühlflächen für Wasser mit einer Temperatur unter 120 °C - Teil 1: Technische Spezifikationen und Anforderungen
Panneaux rayonnants de chauffage et de rafraîchissement alimentés avec une eau à une température inférieure à 120 °C - Partie 1: Spécifications techniques et exigences
Stropne sevalne plošče za ogrevanje in hlajenje površin za vodo s temperaturo pod 120 °C - 1. del: Tehnične specifikacije in zahteve
General Information
Relations
Standards Content (Sample)
SLOVENSKI STANDARD
oSIST prEN 14037-1:2012
01-januar-2012
6WURSQHVHYDOQHSORãþH]DRJUHYDQMHLQKODMHQMHSRYUãLQ]DYRGRVWHPSHUDWXUR
SRGƒ&GHO7HKQLþQHVSHFLILNDFLMHLQ]DKWHYH
Free hanging heating and cooling surfaces for water with a temperature below 120°C -
Part 1: Technical specifications and requirements
An der Decke frei abgehängte Heiz- und Kühlflächen für Wasser mit einer Temperatur
unter 120 °C - Teil 1: Technische Spezifikationen und Anforderungen
Panneaux rayonnants de chauffage et de rafraîchissement alimentés avec une eau à
une température inférieure à 120 °C - Partie 1: Spécifications techniques et exigences
Ta slovenski standard je istoveten z: prEN 14037-1
ICS:
01.040.91 Gradbeni materiali in gradnja Construction materials and
(Slovarji) building (Vocabularies)
91.140.10 Sistemi centralnega Central heating systems
ogrevanja
91.140.65 Oprema za ogrevanje vode Water heating equipment
oSIST prEN 14037-1:2012 en,fr,de
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
---------------------- Page: 1 ----------------------
oSIST prEN 14037-1:2012
---------------------- Page: 2 ----------------------
oSIST prEN 14037-1:2012
EUROPEAN STANDARD
DRAFT
prEN 14037-1
NORME EUROPÉENNE
EUROPÄISCHE NORM
November 2011
ICS 91.140.10 Will supersede EN 14037-1:2003
English Version
Free hanging heating and cooling surfaces for water with a
temperature below 120°C - Part 1: Technical specifications and
requirements
Panneaux rayonnants de chauffage et de rafraîchissement An der Decke frei abgehängte Heiz- und Kühlflächen für
alimentés avec une eau à une température inférieure à 120 Wasser mit einer Temperatur unter 120 °C - Teil 1:
°C - Partie 1: Spécifications techniques et exigences Technische Spezifikationen und Anforderungen
This draft European Standard is submitted to CEN members for enquiry. It has been drawn up by the Technical Committee CEN/TC 130.
If this draft becomes a European Standard, CEN members are bound to comply with the CEN/CENELEC Internal Regulations which
stipulate the conditions for giving this European Standard the status of a national standard without any alteration.
This draft European Standard was established by CEN in three official versions (English, French, German). A version in any other language
made by translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC Management
Centre has the same status as the official versions.
CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,
Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland,
Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom.
Recipients of this draft are invited to submit, with their comments, notification of any relevant patent rights of which they are aware and to
provide supporting documentation.
Warning : This document is not a European Standard. It is distributed for review and comments. It is subject to change without notice and
shall not be referred to as a European Standard.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION
EUROPÄISCHES KOMITEE FÜR NORMUNG
Management Centre: Avenue Marnix 17, B-1000 Brussels
© 2011 CEN All rights of exploitation in any form and by any means reserved Ref. No. prEN 14037-1:2011: E
worldwide for CEN national Members.
---------------------- Page: 3 ----------------------
oSIST prEN 14037-1:2012
prEN 14037-1:2011 (E)
Contents
Foreword . 3
Introduction . 4
1 Scope . 4
2 Normative references . 4
3 Terms and definitions . 5
4 Symbols and units . 10
5 Construction specifications . 12
5.1 General construction specifications. 12
5.2 Surface protection . 13
5.3 Surface emissivity . 13
5.4 Fixing points . 14
5.5 Pressure Test (factory test) . 14
5.6 Resistance to pressure (initial type testing) . 14
5.7 Dimensional tolerances . 14
5.8 Materials . 14
5.9 Upper Insulation . 14
5.10 Water flow resistance . 15
5.11 Release of dangerous substances . 15
5.12 Reaction to fire . 15
5.13 Rated thermal output and characteristic curve . 15
6 Maintenance of conformity . 15
7 Catalogue data, marking and labelling . 15
7.1 General . 15
7.2 Designation of the ceiling mounted radiant panels . 16
7.3 Maximum operating pressure . 16
7.4 Maximum operating temperature . 16
7.5 Thermal output respectively cooling capacity . 16
7.6 Dimensions and technical data . 16
7.7 Reference data . 17
7.8 Marking and labelling . 17
Annex ZA (informative) Clauses of this European Standard addressing the provisions of the EU
Construction Products Directive . 18
ZA.1 Scope and relevant characteristics . 18
ZA.2 Procedures for attestation of conformity of ceiling mounted radiant panels for water with a
temperature below 120 °C . 20
ZA.2.1 Systems of attestation of conformity . 20
ZA.2.2 EC Certificate and Declaration of conformity . 22
ZA.3 CE marking and labelling . 23
Bibliography . 25
2
---------------------- Page: 4 ----------------------
oSIST prEN 14037-1:2012
prEN 14037-1:2011 (E)
Foreword
This document (prEN 14037-1:2011) has been prepared by Technical Committee CEN/TC 130 “Space heating
appliances without integral heat sources”, the secretariat of which is held by UNI.
This document is currently submitted to the CEN Enquiry.
This document will supersede EN 14037-1:2003.
This document has been prepared under a mandate given to CEN by the European Commission and the European
Free Trade Association, and supports essential requirements of EU Directive.
For relationship with EU Directive, see informative Annex ZA, which is an integral part of this document.
The main changes are:
- the title has been changed,
- new definitions according to the new parts 4 and 5 of this European Standard have been added,
- the Annex ZA has been adapted.
3
---------------------- Page: 5 ----------------------
oSIST prEN 14037-1:2012
prEN 14037-1:2011 (E)
Introduction
This European Standard results from the recognition that the ceiling mounted heating and cooling surfaces falling
into the field of application hereinafter stated are traded of the basis of their thermal and cooling output. For evalu-
ating and comparing different ceiling mounted radiant panels it is therefore necessary to refer to a single stipulated
value.
The European Standard EN 14037, Free hanging heating and cooling surfaces for water with a temperature below
120°C consists of the following parts:
- Part 1: Technical specifications and requirements
- Part 2: Test method for thermal output of ceiling mounted radiant panels
- Part 3: Rating method and evaluation of radiant thermal output of ceiling mounted radiant panels
- Part 4: Test method for cooling capacity of ceiling mounted radiant panels
- Part 5: Test method for thermal output of open or closed heated ceiling surfaces
1 Scope
This European Standard defines the technical specifications and requirements of ceiling mounted radiant panels,
heating and cooling surfaces fed with water at temperatures below 120 °C connected with a centralized heating
and/or cooling supply source.
The European Standard does not apply to independent heating and/or cooling devices.
The European Standard also defines the additional common data that the manufacturer shall provide to the trade in
order to ensure the correct application of the products.
2 Normative references
The following referenced documents are indispensable for the application of this document. For dated references,
only the edition cited applies. For undated references, the latest edition of the referenced document (including any
amendments) applies.
EN 13501-1, Fire classification of construction products and building elements - Part 1: Classification using data
from reaction to fire tests
prEN 14037-2, Free hanging heating and cooling surfaces for water with a temperature below 120°C - Part 2: Test
method for thermal output of ceiling mounted radiant panels
prEN 14037-3, Free hanging heating and cooling surfaces for water with a temperature below 120°C - Part 3: Rat-
ing method and evaluation of radiant thermal output of ceiling mounted radiant panels
prEN 14037-4, Free hanging heating and cooling surfaces for water with a temperature below 120°C - Part 4: Test
method for cooling capacity of ceiling mounted radiant panels
prEN 14037-5, Free hanging heating and cooling surfaces for water with a temperature below 120°C - Part 5: Test
method for thermal output of open or closed heated ceiling surfaces
4
---------------------- Page: 6 ----------------------
oSIST prEN 14037-1:2012
prEN 14037-1:2011 (E)
3 Terms and definitions
For the purposes of this European Standard, the terms and definitions given below apply.
3.1
heating appliance
device having the purpose of transferring heat in order to provide specific temperature conditions inside buildings
3.2
independent heating appliance
self-contained heating appliance which does not need to be connected to a remote heat source (e. g. a boiler) as it
contains its own heat source (e. g. gas fired appliances, electric appliances, heat pump appliances)
3.3
heated and chilled ceiling surfaces
3.3.1
pre-fabricated ceiling mounted radiant panel
pre-fabricated heat-transmitting device in the form of a heating or cooling element with width of 0,3 m up to 1,5 m fit-
ted with connection components and designed to operate on water flow heating facilities and/or in cooling systems
3.3.2
open or closed ceiling surface
open or closed active and non active elements of chilled ceilings, which are additionally used for heating, which are
part of suspended ceilings and generally constructed modular from industrially prefabricated elements.
3.3.3
Free hanging sails
sails of cooling installations which are additionally used for heating
NOTE Depending on the use of the sails they can be covered with thermal insulation or noise absorption material.
3.3.4
Suspended ceiling with integrated heating elements
single closed elements integrated in closed hanging ceilings and combined with non active elements which are used
for heating and are thermally insulated on the upper side
3.4
model
ceiling mounted radiant panel respectively heated ceiling surface of defined construction, width and height
3.5
type
group of models with identical modular cross section
3.6
sample
ceiling mounted radiant panel respectively heated ceiling surface, whose thermal output and cooling capacity shall be
determined or has been determined
3.7
inlet water temperature
bulk temperature of the water entering the ceiling mounted radiant panel
3.8
outlet water temperature
bulk temperature of the water leaving the ceiling mounted radiant panel
5
---------------------- Page: 7 ----------------------
oSIST prEN 14037-1:2012
prEN 14037-1:2011 (E)
3.9
mean water temperature
arithmetical mean of inlet and outlet water temperature
3.10
Water temperature drop
Temperature difference between the inlet and outlet water temperature of the heating appliance
3.11
Water temperature rise
Temperature difference between the outlet and inlet water temperature of the cooling appliance
3.12
mean radiant temperature
temperature in a defined point of the room resulting from the radiation of all surrounding surfaces and of the ceiling
mounted radiant panel respectively heated ceiling surface
3.13
reference room temperature
temperature measured with a globe thermometer
3.14
Temperature difference
temperature difference between mean water temperature and reference room temperature
3.15
Standard temperature difference
3.15.1
Standard temperature difference of ceiling mounted radiant panels (EN 14037-2)
mean water temperature 75°C and reference room temperature 20°C, determined temperature difference 55 K
3.15.2
Standard temperature difference of heated ceiling surfaces (EN 14037-5)
mean water temperature 35°C and reference room temperature 20°C, determined temperature difference 15 K
3.15.3
Standard temperature difference for the cooling capacity of ceiling mounted radiant panels (EN
14037-4)
reference room temperature 32°C and mean water temperature 17 °C, determined temperature difference 15 K
3.16
Nominal temperature difference (EN 14037-4)
determined temperature difference 8 K between room temperature and mean water temperature
3.17
surface temperatures of the inside surfaces of the test room
mean temperatures of the inside surfaces of the test room
3.18
mean surface temperature of the ceiling mounted radiant panel
mean temperature on the heating or cooling surfaces of the ceiling mounted radiant panel facing the room below
3.19
surface temperature
maximum inlet water temperature
NOTE This definition is given for safety requirements only.
6
---------------------- Page: 8 ----------------------
oSIST prEN 14037-1:2012
prEN 14037-1:2011 (E)
3.20
air temperature
indoor air temperature measured by using radiation shields
3.21
active length of the ceiling mounted radiant panel
length of the usable heating respectively cooling panel with identical cross section and without connection compo-
nents and covers, which are bonded together with the water flow components
3.22
active heated ceiling surface
relating to thermal output of heated ceiling surfaces (prEN 14037-5, chapter 8)
3.23
connection components
all other components attached to the active length of the ceiling mounted radiant panel which are used for connecting
to the distribution system or for venting and draining (see figure 1)
3.24
indirect heating respectively cooling surface (dry surface)
portion of the heating respectively cooling surface of the panel which is in contact with air only (e.g. radiant sheet
between the tubes)
3.25
direct heating respectively cooling surface (wet surface)
portion of the heating respectively cooling surface of the panel which is in contact with the water
3.26
active surface of the ceiling mounted radiant panel
lower panel surface, the lateral edges are not included
3.27
air pressure
pressure of air measured by a barometer at the testing place
3.28
standard air pressure
pressure of air which is defined as 101,325 kPa (1,01325 bar)
3.29
water flow rate
amount of water flowing through the ceiling mounted radiant panel resp. heating and cooling surface, per unit of
time
3.30
total thermal output, total cooling capacity
thermal output respectively cooling capacity of the active length and of the connection components
3.31
radiant output
thermal output emitted downwards by radiation of the active length
3.32
standard thermal output, standard cooling capacity, nominal cooling capacity
3.32.1
standard thermal output
thermal output at standard temperature difference and standard air pressure
7
---------------------- Page: 9 ----------------------
oSIST prEN 14037-1:2012
prEN 14037-1:2011 (E)
3.32.2
standard cooling capacity
cooling capacity at standard temperature difference and standard air pressure
3.32.3
nominal cooling capacity
cooling capacity at nominal temperature difference 8 K
3.33
characteristic equation
equation that gives the thermal output and cooling capacity as a function of the temperature difference at constant
water flow rate
3.34
construction dimensions
NOTE The most important dimensions are defined by following terms.
3.34.1
construction length
length of the ceiling mounted radiant panel including the collectors/ headers but excluding the connecting pieces to
the heating pipe work
3.34.2
outside diameter of circular tubes
nominal diameter according to standard tube dimensions
3.34.3
dimensions of non circular tubes
shape and all dimensions necessary to describe exactly the cross section of the tube
3.34.4
distance between tubes
distance between the centre lines of two tubes in parallel
3.34.5
length of tube
length of tubes between collectors / headers
3.34.6
length of radiant sheet
length of the heat or cold transferring sheets
NOTE Generally identical with the active length according to 3.18.
3.34.7
width of ceiling mounted radiant panel
width of ceiling mounted radiant panels measured over the outsides of lateral edges
3.34.8
thickness of sheet
thickness of the radiant sheet
3.34.9
Height of lateral edges
height of lateral edges of the radiant sheet to hold the upper insulation
3.35
module
1 m of the active length of a ceiling mounted radiant panel, resp. 1m² active surface of a heated ceiling surface
8
---------------------- Page: 10 ----------------------
oSIST prEN 14037-1:2012
prEN 14037-1:2011 (E)
3.36
modular thermal output, modular cooling capacity
3.36.1
modular thermal output
thermal output of one module calculated from the thermal output of the active length of a ceiling mounted radiant
panel, resp. the active surface of a heated ceiling surface
3.36.2
modular cooling capacity
cooling capacity of one module calculated from the cooling capacity of the active length of a ceiling mounted radi-
ant panel.
3.37
standard modular thermal output, standard modular cooling capacity, nominal modular cooling
capacity
3.37.1
standard modular thermal output
thermal output of one module at standard conditions
3.37.2
standard modular cooling capacity
cooling capacity of one module at standard conditions
3.37.3
nominal modular cooling capacity
cooling capacity of one module at nominal temperature difference
3.38
rated thermal output of a ceiling mounted radiant panel
thermal output evaluated in accordance to prEN 14037-3, clause 5 and referred to the value of the standard modu-
lar output of a ceiling mounted radiant panel
3.39
maximum operating pressure
maximum system pressure, to which the panel may be submitted as stated by the manufacturer
3.40
factory test pressure (leak test)
pressure to which the panel is submitted during the manufacturing process
3.41
emissivity
ratio of emissive power of a surface at a given temperature to that of the black body at the same temperature and
with the same surroundings
9
---------------------- Page: 11 ----------------------
oSIST prEN 14037-1:2012
prEN 14037-1:2011 (E)
4 Symbols and units
For quantities defined in a different part of this standard reference to this part of the standard is made.
Table 1 — Symbols and units
No. Quantity Symbol Unit
1 Surface area of the non insulated walls (EN 14037-4) A m²
2 Active surface of a heated ceiling surface modul A m²
a
3 Installation surface (EN 14037-5) A m²
i
b b
4 Active surface of the ceiling mounted radiant panel A m²
rp
5 Specific heat capacity c J/kg K
p
6 Diameter for connection of inlet/outlet D mm
I/O
7 Outside diameter of tubes D mm
O
8 Distance between tubes d mm
tub
9 Specific enthalpy h J/kg
10 Inlet water enthalpy h J/kg
1
11 Outlet water enthalpy h J/kg
2
12 Height of the void including the height of the test sample h mm
v
n
act
K
13 Constant of the characteristic equation of the active act W/ K
length/surface (EN 14037-2 resp. EN 14037-5)
14 Constant of the characteristic equation of the module
n
act
K
(EN 14037-2) actM W/(m K )
n
act
(EN 14037-5) W/(m² K )
15 Constant of the characteristic equation of the active length K -
Cact
(EN 14037-4)
n
comp
16 Constant of the characteristic equation of the connection K W/K
comp
components (EN 14037-2)
n
act
17 Constant of the characteristic equation of the module based K W/(m K )
rto
on the rated thermal output (EN 14037-2)
n
tot
18 Constant of the characteristic equation of the construction Ktot W/K
length/surface (EN 14037-2 resp. EN 14037-5)
19 Active length of the ceiling mounted radiant panel L Mm
act
20 Height of lateral edges L mm
le
21 Length of radiant sheet L mm
sh
22 Construction length L mm
tot
23 Length of tubes L mm
tub
24 Dry mass M kg
3
25 Water content m dm
v
26 Exponent of the characteristic equation of the active n -
act
length/surface (EN 14037-2 resp. EN 14037-5)
n
27 Exponent of the characteristic equation of the active surface Cact -
(EN 14037-4)
28 Exponent of the characteristic equation of the connection n -
comp
components
29 Exponent of the characteristic equation of the construction ntot -
length/surface (EN 14037-2 resp. EN 14037-5)
30 Air pressure p kPa
31 Factory test pressure p kPa
fact
32 Maximum operating pressure p kPa
max
10
---------------------- Page: 12 ----------------------
oSIST prEN 14037-1:2012
prEN 14037-1:2011 (E)
Table 1 (continued)
a
33 Standard air pressure ps kPa
34 Water flow rate q kg/s
m
35 Percentage of radiant output R %
36 Active area ratio (EN 14037-5) R -
a
37 Thickness of upper insulation s mm
i
38 Reproducibility tolerance s W
m
39 Repeatability tolerance s W
o
40 Thickness of sheet s mm
sh
41 Thermodynamic temperature T K
42 Temperature t °C
43 Inlet water temperature t °C
1
44 Outlet water temperature t °C
2
45 Air temperature t °C
a
46 Mean water temperature t °C
m
47 Mean radiant temperature t °C
mrad
48 Reference room temperature t °C
ref
b
49 Mean surface temperature of the ceiling mounted radiant t °C
rp
panel
50 Surface temperature of the inside surfaces of the test booth t °C
w
51 Heat transfer coefficient (air–insulation–wall) (EN 14037-4) u W/(m² K)
b
52 Width of ceiling mounted radiant panel W mm
rp
-8 4
53 Stephan Boltzmann constant (5,67 x 10 ) W/(m² K )
σ
54 Emissivity of the test sample -
ε
55 Time interval s
τ
56 Output of the active length W
Φ
act
57 Total heat flow in all enclosure walls (EN 14037-4) W
ΦB
58 Standard modular cooling capacity (EN 14037-4) Φ W/m
CLs
59 Measured cooling capacity of a ceiling mounted radiant W
Φ
Cme
panel
60 Nominal cooling capacity of a ceiling mounted radiant panel Φ W
CN
61 Output of connection components Φ W
comp
62 Standard cooling capacity of a ceiling mounted radiant panel W
Φ
CS
63 Rated thermal output W/m
Φ
D
64 Modular thermal output (EN 14037-2) W/m
Φ
L
(EN 14037-5) W/m²
a
65 Standard modular thermal output (EN 14037-2) W/m
Φ
Ls
(EN 14037-5) W/m²
66 Measured output W
Φme
67 Standard output of a master panel of the primary set for Φ W
M,s
interlaboratory comparisons
68 Standard output of a master panel W
Φ
O,s
69 Radiant output W
Φ
rad
70 Total thermal output of simulators (EN 14037-4) Φ W
S
71 Total output W
Φ
tot
11
---------------------- Page: 13 ----------------------
oSIST prEN 14037-1:2012
prEN 14037-1:2011 (E)
Table 1 (continued)
72 Temperature difference ∆T K
73 Nominal temperature difference (8 K) of a ceiling mounted K
∆T
cn
radiant panel when cooling
74 Standard temperature difference (15 K) of a ceiling mounted ∆T K
cs
radiant panel when cooling (EN 14037-4)
75 Measured temperature difference ∆T K
me
76 Standard temperature difference of a ceiling mounted radi- K
∆T
s
ant panel when heating (55 K, EN 14037-2)
Standard temperature difference of a heated cooling surface
a
when heating (15 K; EN 14037-5)
a
"s" indicates that the value is in standard conditions.
b
"rp" indicates that the symbol is referred to the ceiling mounted radiant panel.
5 Construction specifications
5.1 General construction specifications
The thermal output of a ceiling mounted radiant panel is mainly transferred downwards to the space by radiation.
The thermal output upwards shall be minimized by insulation.
The maximum surface temperature of the lateral edges shall not exceed the minimum surface temperature of the
radiant sheet between the last two wet surfaces. For ceiling panels with a construction according to Figure 1 with a
tube pitch of X (mm), the distance between the axis of the outside tubes and the edges has to have a minimum
distance of 0,5X (mm).
The panel is freely suspended above the useful space and designed to be a permanent part of the building al-
though not a part incorporated in the building structure
Air flow across the panel is to be prevented.
12
---------------------- Page: 14 ----------------------
oSIST prEN 14037-1:2012
prEN 14037-1:2011 (E)
longitudinal section
Key
1 Connection components 4 Vent
2 Inlet / outlet 5 Upper insulation
3 Drain 6 Radiant sheet
L = L (only for this example)
act sh
Figure 1 — Example for a typical ceiling mounted radiant panel
5.2 Surface protection
If the material in use requires protection, measures for protection against corrosion should be provided.
The paint used for protection shall not contain any chemical substances the use of which is not allowed in building
1)
products .
The compliance with the relevant Directive shall be stated by the manufacturer of the ceiling mounted radiant
panel.
5.3 Surface emissivity
The radiating surface of the active heating surface shall have an emissivity not lower than 0,8.
1) Also in relation to Directive 76/769/EEC, as amended.
13
---------------------- Page: 15 ----------------------
oSIST prEN 14037-1:2012
prEN 14037-1:2011 (E)
5.4 Fixing points
The fixing points
...