SIST EN 14511-2:2013
(Main)Air conditioners, liquid chilling packages and heat pumps with electrically driven compressors for space heating and cooling - Part 2: Test conditions
Air conditioners, liquid chilling packages and heat pumps with electrically driven compressors for space heating and cooling - Part 2: Test conditions
This European Standard specifies the test conditions for the rating of air conditioners, liquid chilling packages and heat pumps, using either, air, water or brine as heat transfer media, with electrically driven compressors when used for space heating and/or cooling. This European Standard specifies the conditions for which performance data shall be declared for single duct and double duct units for compliance to the Ecodesign regulation 206/2012 and Energy labelling regulation 626/2011.
Luftkonditionierer, Flüssigkeitskühlsätze und Wärmepumpen mit elektrisch angetriebenen Verdichtern für die Raumbeheizung und -kühlung - Teil 2: Prüfbedingungen
1.1 Es gilt der Anwendungsbereich von EN 14511 1.
1.2 Diese Europäische Norm legt die Bedingungen für die Leistungsprüfung von Luftkonditionierern, Flüssigkeitskühlsätzen und Wärmepumpen, die Luft, Wasser oder Sole als Wärmeträger nutzen, mit elektrisch angetriebenen Verdichtern für die Raumbeheizung und/oder -kühlung fest.
1.3 Die vorliegende Europäische Norm legt die Bedingungen fest, für die die leistungsbezogenen Daten zu Einkanal- und Zweikanal-Geräten zum Zwecke der Übereinstimmung mit der Ökodesign-Verordnung 206/2012 und der Energiekennzeichnungs-Verordnung 626/2011 anzugeben sind.
Climatiseurs, groupes refroidisseurs de liquide et pompes à chaleur avec compresseur entraîné par moteur électrique pour le chauffage et la réfrigération des locaux - Partie 2: Conditions d'essai
1.1 Le domaine d'application de l’EN 14511-1 est applicable.
1.2 La présente Norme européenne spécifie les conditions d'essai pour la détermination des caractéristiques de performance des climatiseurs, groupe refroidisseurs de liquide et pompes à chaleur utilisant l’air, l’eau ou l’eau glycolée comme fluide caloporteur avec compresseur entraîné par moteur électrique, lorsqu'ils sont utilisés pour le chauffage et/ou le refroidissement des locaux.
1.3 La présente Norme européenne spécifie les conditions pour lesquelles les données de performance doivent être déclarées pour les appareils à simple ou double raccordement pour la conformité au règlement d’écoconception 206/2012 et du Règlement Etiquetage énergétique 626/2011
Klimatske naprave, enote za tekočinsko hlajenje in toplotne črpalke z električnimi kompresorji za segrevanje in hlajenje prostora - 2. del: Preskusni pogoji
Ta evropski standard določa preskusne pogoje za ocenjevanje klimatskih naprav, enot za tekočinsko hlajenje in toplotnih črpalk, ki uporabljajo zrak, vodo ali slanico kot medij za prenos toplote, z električnimi kompresorji, kadar se uporabljajo za segrevanje in/ali hlajenje prostora. Ta evropski standard določa pogoje, za katere se navedejo podatki o delovanju za enote z enojnim in dvojnim jaškom v zvezi s skladnostjo z uredbo o okoljski primerni zasnovi št. 206/2012 in uredbo o energijskem označevanju št. 626/2011.
General Information
Relations
Standards Content (Sample)
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.Luftkonditionierer, Flüssigkeitskühlsätze und Wärmepumpen mit elektrisch angetriebenen Verdichtern für die Raumbeheizung und -kühlung - Teil 2: PrüfbedingungenClimatiseurs, groupes refroidisseurs de liquide et pompes à chaleur avec compresseur entraîné par moteur électrique pour le chauffage et la réfrigération des locaux - Partie 2: Conditions d'essaiAir conditioners, liquid chilling packages and heat pumps with electrically driven compressors for space heating and cooling - Part 2: Test conditions91.140.30VLVWHPLVentilation and air-conditioning27.080Heat pumps23.120QDSUDYHVentilators. Fans. Air-conditionersICS:Ta slovenski standard je istoveten z:EN 14511-2:2013SIST EN 14511-2:2013en,fr,de01-december-2013SIST EN 14511-2:2013SLOVENSKI
STANDARDSIST EN 14511-2:20121DGRPHãþD
SIST EN 14511-2:2013
EUROPEAN STANDARD NORME EUROPÉENNE EUROPÄISCHE NORM
EN 14511-2
August 2013 ICS 27.080; 91.140.30 Supersedes EN 14511-2:2011English Version
Air conditioners, liquid chilling packages and heat pumps with electrically driven compressors for space heating and cooling - Part 2: Test conditions
Climatiseurs, groupes refroidisseurs de liquide et pompes à chaleur avec compresseur entraîné par moteur électrique pour le chauffage et la réfrigération des locaux - Partie 2: Conditions d'essai
Luftkonditionierer, Flüssigkeitskühlsätze und Wärmepumpen mit elektrisch angetriebenen Verdichtern für die Raumbeheizung und -kühlung - Teil 2: Prüfbedingungen This European Standard was approved by CEN on 30 May 2013.
CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN-CENELEC Management Centre or to any CEN member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC Management Centre has the same status as the official versions.
CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and United Kingdom.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION EUROPÄISCHES KOMITEE FÜR NORMUNG
Management Centre:
Avenue Marnix 17,
B-1000 Brussels © 2013 CEN All rights of exploitation in any form and by any means reserved worldwide for CEN national Members. Ref. No. EN 14511-2:2013: ESIST EN 14511-2:2013
EN 14511-2:2013 (E) 2 Contents Page Foreword .3 1 Scope .4 2 Normative references .4 3 Terms and definitions .4 4 Test conditions .4 4.1 Environmental conditions and electrical power supply requirements .4 4.2 Rating conditions.5 Annex ZA (informative)
Relationship between this European Standard and the requirements of Commission Regulation (EC) No 206/2012 . 18 Bibliography . 19
SIST EN 14511-2:2013
EN 14511-2:2013 (E) 3 Foreword This document (EN 14511-2:2013) has been prepared by Technical Committee CEN/TC 113 “Heat pumps and air conditioning units”, the secretariat of which is held by AENOR. This European Standard shall be given the status of a national standard, either by publication of an identical text or by endorsement, at the latest by February 2014 and conflicting national standards shall be withdrawn at the latest by February 2014. Attention is drawn to the possibility that some of the elements of this document may be the subject of patent rights. CEN [and/or CENELEC] shall not be held responsible for identifying any or all such patent rights. This document supersedes EN 14511-2:2011. The main changes with respect to the previous edition are listed below: a) the addition of an Annex ZA related to the Commission Regulation (EC) n°206/2012. This document has been prepared under a mandate given to CEN by the European Commission and the European Free Trade Association, and supports essential requirements of EU Directive(s). For relationship with EU Directive(s), see informative Annex ZA, which is an integral part of this document. Although this document has been prepared in the frame of the commission regulation (EU) No 206/2012 implementing Directive 2009/125/EC with regard to ecodesign requirements for air conditioners and comfort fans, it is also intended to support the essential requirements of the European Directive 2010/30/CE. EN 14511 comprises the following parts under the general title Air conditioners, liquid chilling packages and heat pumps with electrically driven compressors for space heating and cooling: Part 1: Terms, definitions and classification, Part 2: Test conditions, Part 3: Test methods, Part 4: Operating requirements, marking and instructions. According to the CEN/CENELEC Internal Regulations, the national standards organisations of the following countries are bound to implement this European Standard: Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and the United Kingdom. SIST EN 14511-2:2013
EN 14511-2:2013 (E) 4 1 Scope 1.1 The scope of EN 14511-1 is applicable. 1.2 This European Standard specifies the test conditions for the rating of air conditioners, liquid chilling packages and heat pumps, using either, air, water or brine as heat transfer media, with electrically driven compressors when used for space heating and/or cooling.
1.3 This European Standard specifies the conditions for which performance data shall be declared for single duct and double duct units for compliance to the Ecodesign regulation 206/2012 and Energy labelling regulation 626/2011. 2 Normative references The following documents, in whole or in part, are normatively referenced in this document and are indispensable for its application. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. EN 14511-1:2013, Air conditioners, liquid chilling packages and heat pumps with electrically driven compressors for space heating and cooling Part 1: Terms, definitions and classification EN 14511-4:2013, Air conditioners, liquid chilling packages and heat pumps with electrically driven compressors for space heating and cooling Part 4: Operating requirements, marking and instructions 3 Terms and definitions For the purposes of this document, the terms and definitions given in EN 14511-1:2013 apply. 4 Test conditions 4.1 Environmental conditions and electrical power supply requirements The tests shall be carried out under the environmental conditions specified in Table 1 or Table 2 depending on the location of the unit. For all units, electrical power voltage and frequency shall be given by the manufacturer. SIST EN 14511-2:2013
EN 14511-2:2013 (E) 5 Table 1 —Environmental conditions for units designed for installation indoors Type Measured quantities Rating test Water-to-water and brine-to-water units Dry bulb temperature 15 °C to 30 °C Air-to-water units with duct connection on the air inlet and outlet side Dry bulb temperature 15 °C to 30 °C Air-to-water units without duct connection on the air inlet side Dry bulb temperature Wet bulb temperature
15 °C to 30 °C Water-to-air and brine-to-air units with duct connection on the air inlet and outlet side Dry bulb temperature 15 °C to 30 °C Water-to-air and brine-to-air units without duct connection on the air inlet and outlet side Dry bulb temperature Wet bulb temperature
Inlet temperature (see Table 5 or Table 6) Air-to-air units with duct connection
on the outdoor air inlet and outlet side Dry bulb temperature 15 °C to 30 °C Air-to-air units without duct connection
on the outdoor air inlet and outlet side Dry bulb temperature Wet bulb temperature
As inlet temperature see Table 3 or Table 4
Table 2 — Environmental conditions for units designed for installation outdoors Type Measured quantities Rating test Air-to-water units
Dry bulb temperature Wet bulb temperature Inlet temperature (see Tables 12 to 15 and Table 16) Water-to-air and brine-to-air units without duct connection on the air inlet side Dry bulb temperature Wet bulb temperature
Inlet temperature (see Table 5 and Table 6) Water-to-water and brine-to-water operating in cooling mode Dry bulb temperature 15 °C to 30 °C Water-to-water and brine-to-water operating in heating mode Dry bulb temperature 0 °C to 7 °C Air-to-air units with duct connection on the indoor air inlet and outlet side Dry bulb temperature Wet bulb temperature
Inlet temperature (see Table 3 and Table 4)
4.2 Rating conditions For the rating tests, the appropriate test conditions shall be applied in accordance with: Table 3 for air-to-air units in heating mode; Table 4 for air-to-air units in cooling mode; Table 5 for water-to-air and brine-to-air units in heating mode; Table 6 for water-to-air and brine-to-air units in cooling mode; Tables 7 to 10 for water-to-water and brine-to-water units in heating mode, depending on the temperature applications; SIST EN 14511-2:2013
EN 14511-2:2013 (E) 6 Table 11 for water-to-water, brine-to-water, water-to-brine and brine-to-brine units in cooling mode; Tables 12 to 15 for air-to-water in heating mode, depending on the temperature applications; Table 16 for air-to-water and air-to-brine units in cooling mode; Table 17 for liquid chilling packages with remote condenser; Table 18 for liquid chilling packages for heat recovery condenser; Table 19 for air-cooled multisplit systems and modular air-cooled multisplit systems in the heating mode; Table 20 for air-cooled multisplit systems and modular air-cooled multisplit systems in the cooling mode; Table 21 for modular heat recovery air-cooled multisplit systems; Table 22 for water-cooled multisplit systems and modular water-cooled multisplit systems in the heating mode; Table 23 for water-cooled multisplit systems and modular water-cooled multisplit systems in the cooling mode. For units with brine, the test shall be carried out with the brine specified by the manufacturer, see EN 14511-4:2013, 7.2.1. NOTE 1 For air-to-water, brine-to-water and water-to-water units, the manufacturer may declare the water temperatures levels (lower, medium, high and very high) applicable to the heating mode. NOTE 2 For comparison purposes between reverse cycle and non reverse cycle units, the conditions on the water side are given by the inlet and outlet water temperatures, possibly leading to different water flow rates in heating and cooling modes. The rating tests in heating mode also apply for units having evaporatively cooled condenser, which performance in cooling mode is determined in accordance with EN 15218, and which can operate in heating mode. The standard rating conditions, extracted from EN 14511-2:2013, Table 3 for heating mode and specified in Table ZA.1 shall be used to determine the rated capacity (Prated), the rated power input (PCOP), the rated coefficient of performance (COPrated) and the electricity consumption (QDD, QSD) in heating mode. SIST EN 14511-2:2013
EN 14511-2:2013 (E) 7 Table 3 — Air-to-air units - Heating mode
Outdoor heat exchanger Indoor heat exchanger Inlet dry bulb temperature °C Inlet wet bulb temperature °C Inlet dry bulb temperature °C Inlet wet bulb temperature °C Standard rating
conditions Outdoor air / recycled air (e.g. window, double duct, split units) 7 6 20 15 max Exhaust air / recycled air (e.g. single duct heat pump) 20 12 20 12 Exhaust air / outdoor air 20 12 7 6 Application rating
conditions Outdoor air / recycled air (e.g. window, double duct, split units) 2 1 20 15 max. Outdoor air / recycled air (e.g. window, double duct, split units) - 7 - 8 20 15 max. Outdoor air / recycled air (e.g. window, double duct, split units) - 15 - 20 15 max. Outdoor air / recycled air (e.g. window, double duct, split units) 12 11 20 15 max. Exhaust air / outdoor air 20 12 2 1 Exhaust air / outdoor air 20 12 - 7 - 8
SIST EN 14511-2:2013
EN 14511-2:2013 (E) 8 Table 4 — Air-to-air units - Cooling mode
Outdoor heat exchanger Indoor heat exchanger Inlet dry bulb temperature °C Inlet wet bulb temperature °C Inlet dry bulb temperature °C Inlet wet bulb temperature °C Standard rating
conditions Comfort (outdoor air / recycled air) (e.g. window, double duct, split units)
35 24 a 27 19 Comfort (exhaust air / recycled ai
...