Air conditioners, liquid chilling packages and heat pumps for space heating and cooling and process chillers, with electrically driven compressors - Part 2: Test conditions

1.1   The scope of prEN 14511 1 is applicable.
1.2   This European Standard specifies the test conditions for the rating of air conditioners, liquid chilling packages and heat pumps, using either, air, water or brine as heat transfer media, with electrically driven compressors when used for space heating and/or cooling. The standard also specifies the test conditions for the rating of air-cooled and water-cooled process chillers.
1.3   This European Standard specifies the conditions for which performance data shall be declared for single duct and double duct units for compliance to the ecodesign Regulation 206/2012 and Energy Labelling Regulation 626/2011.

Luftkonditionierer, Flüssigkeitskühlsätze und Wärmepumpen für die Raumbeheizung und -kühlung und Prozess-Kühler mit elektrisch angetriebenen Verdichtern - Teil 2: Prüfbedingungen

1.1   Es gilt der Anwendungsbereich von EN 14511-1.
1.2   Diese Europäische Norm legt die Bedingungen für die Leistungsprüfung von Luftkonditionierern, Flüssigkeitskühlsätzen und Wärmepumpen, die entweder Luft, Wasser oder Sole als Wärmeträger nutzen, mit elektrisch angetriebenen Verdichtern für die Raumbeheizung und/oder -kühlung fest. Die Norm legt auch die Bedingungen für die Leistungsprüfung von luftgekühlten und von wassergekühlten Prozess-Kühlern fest.
1.3   Die vorliegende Europäische Norm legt die Bedingungen fest, für die die leistungsbezogenen Daten zu Einkanal- und Zweikanal-Geräten zum Zwecke der Übereinstimmung mit der Ökodesign-Verordnung 206/2012 und der Energiekennzeichnungs-Verordnung 626/2011 anzugeben sind.

Climatiseurs, groupes refroidisseurs de liquide et pompes à chaleur pour le chauffage et le refroidissement des locaux et refroidisseurs industriels avec compresseur entraîné par moteur électrique - Partie 2: Conditions d'essai

1.1   Le domaine d'application du prEN 14511-1 est applicable.
1.2   La présente Norme européenne spécifie les conditions d'essai pour la détermination des caractéristiques de performance des climatiseurs, groupe refroidisseurs de liquide et pompes à chaleur utilisant l’air, l’eau ou l’eau glycolée comme fluide caloporteur avec compresseur entraîné par moteur électrique, lorsqu'ils sont utilisés pour le chauffage et/ou le refroidissement des locaux. La norme spécifie également les conditions d’essai pour la détermination des refroidisseurs industriels à condensation par eau ou par air.
1.3   La présente Norme européenne spécifie les conditions pour lesquelles les données de performance doivent être déclarées pour les appareils à simple ou double raccordement pour la conformité au règlement d’écoconception 206/2012 et du Règlement Etiquetage énergétique 626/2011.

Klimatske naprave, enote za hlajenje kapljevine, toplotne črpalke za ogrevanje in hlajenje prostora ter procesne hladilne naprave z električnimi kompresorji - 2. del: Preskusni pogoji

1.1 Velja področje uporabe standarda prEN 14511 1.
1.2 Ta evropski standard določa preskusne pogoje za ocenjevanje klimatskih naprav, enot za tekočinsko hlajenje in toplotnih črpalk, ki uporabljajo zrak, vodo ali slanico kot medij za prenos toplote, z električnimi kompresorji, kadar se uporabljajo za segrevanje in/ali hlajenje prostora. Standard določa tudi preskusne pogoje za ocenjevanje zračno in vodno hlajenih procesnih ohlajevalnikov.
1.3 Ta evropski standard določa pogoje, za katere se navedejo podatki o delovanju za enote z enojnim in dvojnim jaškom v zvezi s skladnostjo z uredbo o okoljsko primerni zasnovi št. 206/2012 in uredbo o energijskem označevanju št. 626/2011.

General Information

Status
Withdrawn
Public Enquiry End Date
30-Dec-2015
Publication Date
12-Apr-2018
Withdrawal Date
13-Sep-2022
Technical Committee
Current Stage
9900 - Withdrawal (Adopted Project)
Start Date
14-Sep-2022
Due Date
07-Oct-2022
Completion Date
14-Sep-2022

Relations

Buy Standard

Standard
EN 14511-2:2018
English language
21 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day
Draft
prEN 14511-2:2015
English language
20 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.Luftkonditionierer, Flüssigkeitskühlsätze und Wärmepumpen für die Raumbeheizung und -kühlung und Prozess-Kühler mit elektrisch angetriebenen Verdichtern - Teil 2: PrüfbedingungenClimatiseurs, groupes refroidisseurs de liquide et pompes à chaleur pour le chauffage et le refroidissement des locaux et refroidisseurs industriels avec compresseur entraîné par moteur électrique - Partie 2: Conditions d'essaiAir conditioners, liquid chilling packages and heat pumps for space heating and cooling and process chillers, with electrically driven compressors - Part 2: Test conditions91.140.30VLVWHPLVentilation and air-conditioning systems27.080Heat pumps23.120QDSUDYHVentilators. Fans. Air-conditionersICS:Ta slovenski standard je istoveten z:EN 14511-2:2018SIST EN 14511-2:2018en,fr,de01-maj-2018SIST EN 14511-2:2018SLOVENSKI
STANDARDSIST EN 14511-2:20131DGRPHãþD



SIST EN 14511-2:2018



EUROPEAN STANDARD NORME EUROPÉENNE EUROPÄISCHE NORM
EN 14511-2
March
t r s z ICS
t yä r z râ
{ sä s v rä u r Supersedes EN
s v w s sæ tã t r s uEnglish Version
Air conditionersá liquid chilling packages and heat pumps for space heating and cooling and process chillersá with electrically driven compressors æ Part
tã Test conditions Climatiseursá groupes refroidisseurs de liquide et pompes à chaleur pour le chauffage et le refroidissement des locaux et refroidisseurs industriels avec compresseur entraîné par moteur électrique æ Partie
tã Conditions d 5essai
Luftkonditioniererá Flüssigkeitskühlsätze und Wärmepumpen für die Raumbeheizung und ækühlung und ProzessæKühler mit elektrisch angetriebenen Verdichtern æ Teil
tã Prüfbedingungen This European Standard was approved by CEN on
u s December
t r s yä
egulations which stipulate the conditions for giving this European Standard the status of a national standard without any alterationä Upætoædate lists and bibliographical references concerning such national standards may be obtained on application to the CENæCENELEC Management Centre or to any CEN memberä
translation under the responsibility of a CEN member into its own language and notified to the CENæCENELEC Management Centre has the same status as the official versionsä
CEN members are the national standards bodies of Austriaá Belgiumá Bulgariaá Croatiaá Cyprusá Czech Republicá Denmarká Estoniaá Finlandá Former Yugoslav Republic of Macedoniaá Franceá Germanyá Greeceá Hungaryá Icelandá Irelandá Italyá Latviaá Lithuaniaá Luxembourgá Maltaá Netherlandsá Norwayá Polandá Portugalá Romaniaá Serbiaá Slovakiaá Sloveniaá Spainá Swedená Switzerlandá Turkey and United Kingdomä
EUROPEAN COMMITTEE FOR STANDARDIZATION COMITÉ EUROPÉEN DE NORMALISATION EUROPÄISCHES KOMITEE FÜR NORMUNG
CEN-CENELEC Management Centre:
Rue de la Science 23,
B-1040 Brussels
9
t r s z CEN All rights of exploitation in any form and by any means reserved worldwide for CEN national Membersä Refä Noä EN
s v w s sæ tã t r s z ESIST EN 14511-2:2018



EN 14511-2:2018 (E) 2 Contents Page European foreword . 3 1 Scope . 4 2 Normative references . 4 3 Terms and definitions . 4 4 Test conditions . 4 4.1 Environmental conditions and electrical power supply requirements . 4 4.2 Rating conditions . 5 Annex ZA (informative)
Relationship between this European Standard and the ecodesign requirements of Commission Regulation (EU) No 206/2012 aimed to be covered . 19 Annex ZB (informative)
Relationship between this European Standard and the ecodesign requirements of Commission Regulation (EU) No 2015/1095 aimed to be covered . 20 Bibliography . 21
SIST EN 14511-2:2018



EN 14511-2:2018 (E) 3 European foreword This document (EN 14511-2:2018) has been prepared by Technical Committee CEN/TC 113 “Heat pumps and air conditioning units”, the secretariat of which is held by UNE. This European Standard shall be given the status of a national standard, either by publication of an identical text or by endorsement, at the latest by September 2018, and conflicting national standards shall be withdrawn at the latest by March 2021. Attention is drawn to the possibility that some of the elements of this document may be the subject of patent rights. CEN not be held responsible for identifying any or all such patent rights. This document supersedes EN 14511-2:2013. This document has been prepared under a mandate given to CEN by the European Commission and the European Free Trade Association, and supports essential requirements of EU Regulation(s). For relationship with EU Regulation(s), see informative Annexes ZA and ZB, which are an integral part of this document. The main change with respect to the previous edition is the inclusion of process chillers in the scope of the standard with a table of relevant test conditions. EN 14511, Air conditioners, liquid chilling packages and heat pumps for space heating and cooling and process chillers, with electrically driven compressors currently comprises the following parts: — Part 1: Terms and definitions — Part 2: Test conditions — Part 3: Test methods — Part 4: Requirements According to the CEN/CENELEC Internal Regulations, the national standards organizations of the following countries are bound to implement this European Standard: Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and the United Kingdom. SIST EN 14511-2:2018



EN 14511-2:2018 (E) 4 1 Scope 1.1 The scope of EN 14511-1 is applicable. 1.2 This European Standard specifies the test conditions for the rating of air conditioners, liquid chilling packages and heat pumps, using either, air, water or brine as heat transfer media, with electrically driven compressors when used for space heating and/or cooling. The standard also specifies the test conditions for the rating of air-cooled and water(brine)-cooled process chillers. 1.3 This European Standard specifies the conditions for which performance data is to be declared for single duct and double duct units for compliance to the Ecodesign Regulation 206/2012 and Energy Labelling Regulation 626/2011. 2 Normative references The following documents are referred to in the text in such a way that some or all of their content constitutes requirements of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. EN 14511-1:2018, Air conditioners, liquid chilling packages and heat pumps for space heating and cooling and process chillers with electrically driven compressors — Part 1: Terms and definitions EN 14511-4:2018, Air conditioners, liquid chilling packages and heat pumps for space heating and cooling and process chillers, with electrically driven compressors — Part 4: Requirements EN 15218, Air conditioners and liquid chilling packages with evaporatively cooled condenser and with electrically driven compressors for space cooling — Terms, definitions, test conditions, test methods and requirements 3 Terms and definitions For the purposes of this document, the terms and definitions given in EN 14511-1:2018 apply. ISO and IEC maintain terminological databases for use in standardization at the following addresses:
IEC Electropedia: available at http://www.electropedia.org/
ISO Online browsing platform: available at http://www.iso.org/obp 4 Test conditions 4.1 Environmental conditions and electrical power supply requirements The tests shall be carried out under the environmental conditions specified in Table 1 or Table 2 depending on the location of the unit. For all units, electrical power voltage and frequency shall be given by the manufacturer. SIST EN 14511-2:2018



EN 14511-2:2018 (E) 5 Table 1 — Environmental conditions for units designed for installation indoors Type Measured quantities Rating test Water(brine)-to-water(brine) units Dry bulb temperature 15 °C to 30 °C Air-to-water(brine) units with duct connection on the air inlet and outlet side Dry bulb temperature 15 °C to 30 °C Air-to-water(brine) units without duct connection on the air inlet side Dry bulb temperature Wet bulb temperature 15 °C to 30 °C Water(brine)-to-air units with duct connection on the air inlet and outlet side Dry bulb temperature 15 °C to 30 °C Water(brine)-to-air units without duct connection on the air inlet and outlet side Dry bulb temperature Wet bulb temperature Inlet temperature (see Table 5 or Table 6) Air-to-air units with duct connection
on the outdoor air inlet and outlet side Dry bulb temperature 15 °C to 30 °C Air-to-air units without duct connection
on the outdoor air inlet and outlet side Dry bulb temperature Wet bulb temperature As inlet temperature (see Table 3 or Table 4) Air-cooled process chillers ducted on the air side Dry bulb temperature 15 °C to 30 °C Water(brine)-cooled process chillers Dry bulb temperature 15 °C to 30 °C Table 2 — Environmental conditions for units designed for installation outdoors Type Measured quantities Rating test Air-to-water(brine) units Dry bulb temperature Wet bulb temperature Inlet temperature (see Tables 12 to 16) Water(brine)-to-air units without duct connection on the air inlet side Dry bulb temperature Wet bulb temperature Inlet temperature (see Table 5 and Table 6) Water(brine)-to-water(brine) units operating in cooling mode Dry bulb temperature 15 °C to 30 °C Water(brine)-to-water(brine) units operating in heating mode Dry bulb temperature 0 °C to 7 °C Air-to-air units with duct connection on the indoor air inlet and outlet side Dry bulb temperature Wet bulb temperature Inlet temperature (see Table 3 and Table 4) Air-cooled process chillers (non-ducted on the air side) Dry bulb temperature Wet bulb temperature Inlet temperature (see Table 25) Water(brine)-cooled process chillers Dry bulb temperature 15 °C to 30 °C 4.2 Rating conditions For the rating tests, the appropriate test conditions shall be applied in accordance with: — Table 3 for air-to-air units in heating mode; SIST EN 14511-2:2018



EN 14511-2:2018 (E) 6 — Table 4 for air-to-air units in cooling mode; — Table 5 for water(brine)-to-air units in heating mode; — Table 6 for water(brine)-to-air units in cooling mode; — Tables 7 to 10 for water(brine)-to-water(brine) units in heating mode, depending on the temperature applications; — Table 11 for water(brine)-to-water(brine) units in cooling mode; — Tables 12 to 15 for air-to-water(brine) in heating mode, depending on the temperature applications; — Table 16 for air-to-water(brine) units in cooling mode; — Table 17 for liquid chilling packages with remote condenser; — Table 18 for liquid chilling packages for heat recovery condenser; — Table 19 for air-cooled multisplit systems and modular air-cooled multisplit systems in the heating mode; — Table 20 for air-cooled multisplit systems and modular air-cooled multisplit systems in the cooling mode; — Table 21 for modular heat recovery air-cooled multisplit systems; — Table 22 for water-cooled multisplit systems and modular water-cooled multisplit systems in the heating mode; — Table 23 for water-cooled multisplit systems and modular water-cooled multisplit systems in the cooling mode; — Table 24 for modular heat recovery water-cooled multisplit systems. — Table 25 for process chillers For units with brine, the test shall be carried out with the brine specified by the manufacturer, see EN 14511-4:2018, 7.2.1. For air-to-water(brine),and water(brine)-to-water(brine) heat pumps, the manufacturer may declare the water(brine) temperatures levels (low, intermediate, medium, and high) applicable to the heating mode. NOTE For comparison purposes between reverse cycle and non-reverse cycle units, the conditions on the water(brine) side are given by the inlet and outlet water(brine) temperatures, possibly leading to different water(brine) flow rates in heating and cooling modes. The rating tests in heating mode also apply for units having evaporatively cooled condenser, which performance in cooling mode is determined in accordance with EN 15218, and which can operate in heating mode. The standard rating conditions, extracted from Table 3 for heating mode and specified in Table ZA.1, shall be used to determine the rated capacity (Prated), the rated power input (PCOP), the rated coefficient of performance (COPrated) and the electricity consumption (QDD, QSD) in heating mode. SIST EN 14511-2:2018



EN 14511-2:2018 (E) 7 Table 3 — Air-to-air units - Heating mode
Outdoor heat exchanger Indoor heat exchanger Inlet dry bulb temperature °C Inlet wet bulb temperature °C Inlet dry bulb temperature °C Inlet wet bulb temperature °C Standard rating
conditions Outdoor air / recycled air (e.g. window, double duct, split units) 7 6 20 15 max Exhaust air / recycled air (e.g. single duct heat pump) 20 12 20 12 Exhaust air / outdoor air 20 12 7 6 Application rating
conditions Outdoor air / recycled air (e.g. window, double duct, split units) 2 1 20 15 max. Outdoor air / recycled air (e.g. window, double duct, split units) - 7 - 8 20 15 max. Outdoor air / recycled air (e.g. window, double duct, split units) - 15 — 20 15 max. Outdoor air / recycled air (e.g. window, double duct, split units) 12 11 20 15 max. Exhaust air / outdoor air 20 12 2 1 Exhaust air / outdoor air 20 12 - 7 - 8 SIST EN 14511-2:2018



EN 14511-2:2018 (E) 8 Table 4 — Air-to-air units - Cooling mode
Outdoor heat exchanger Indoor heat exchanger Inlet dry bulb temperature °C Inlet wet bulb temperature °C Inlet dry bulb temperature °C Inlet wet bulb temperature °C Standard rating
conditions Comfort (outdoor air / recycled air) (e.g. window, double duct, split units) 35 24 a 27 19 Comfort (exhaust air / recycled air) 27 19 27 19 Comfort (exhaust air / outdoor air) 27 19 35 24 Single duct b, c 35 24 35 24 Control cabinet 35 24 35 24 Close control 35 24 24 17 Application rating
conditions Comfort (outdoor air / recycled air) (e.g. window, double duct, split units) 27 19 a 21 15 Single duct b, c 27 19 27 19 Comfort (outdoor air / recycled air) (e.g. window, double duct, split units) 46 24 a 29 19 Control cabinet 50 30 35 24 Close control 27 19 21 15 a The wet bulb temperature condition is not required when testing units which do not evaporate condensate. b When using the calorimeter room method, pressure equilibrium between indoor and outdoor compartments shall be obtained by introducing into indoor compartment, air at the same rating temperature conditions. c The pressure difference between the two compartments of the calorimeter room shall not be greater than 1,25 Pa. This pressure equilibrium can be achieved by using an equalizing device or by creating an open space area in the separation partition wall, which dimensions shall be calculated for the maximum airflow of the unit to be tested. If an open space is created in the partition wall, an air sampling device or several temperature sensors shall be used to measure the temperature of the air from the outdoor compartment to the indoor compartment. SIST EN 14511-2:2018



EN 14511-2:2018 (E) 9 Table 5 — Water(brine)-to-air units - Heating mode
Outdoor heat exchanger Inlet heat exchanger Inlet temperature Outlet temperature Inlet dry bulb temperature Inlet wet bulb temperature °C °C °C °C Standard rating conditions Water a 10 7 20 15 max. Brine 0
«3 20 15 max. Water loop 20 17 20 15 max. Application rating conditions Water 15 b 20 15 max. Brine 5 b 20 15 max. a The term “water” includes indifferently water from a river or a lake, ground water. b test at the corresponding standard rating conditions for units with variable flow rate. If the resulting flow rate is below the minimum flow rate then this minimum is used with the inlet temperature. Table 6 — Water(brine)-to-air units - Cooling mode
Outdoor heat exchanger Indoor heat exchanger Inlet temperature Outlet temperature Inlet dry bulb temperature Inlet wet bulb temperature °C °C °C °C Standard rating conditions Cooling tower 30 35 27 19 Ground coupled (water or brine) 10 15 27 19 Control cabinet 15 20 35 24 Close control 30 35 24 17 Application rating
conditions Cooling tower 40 a 27 19 Ground coupled (water or brine) 15 a 27 19 C
...

SLOVENSKI STANDARD
oSIST prEN 14511-2:2015
01-december-2015
.OLPDWVNHQDSUDYHHQRWH]DWHNRþLQVNRKODMHQMHLQWRSORWQHþUSDONH]HOHNWULþQLPL
NRPSUHVRUML]DVHJUHYDQMHLQKODMHQMHSURVWRUDGHO3UHVNXVQLSRJRML
Air conditioners, liquid chilling packages and heat pumps with electrically driven
compressors for space heating and cooling and process chillers, using electrically driven
compressors - Part 2: Test conditions
Luftkonditionierer, Flüssigkeitskühlsätze und Wärmepumpen für die Raumbeheizung und
-kühlung und Prozess-Kühler mit elektrisch angetriebenen Verdichtern - Teil 2:
Prüfbedingungen
Climatiseurs, groupes refroidisseurs de liquide et pompes à chaleur pour le chauffage et
le refroidissement des locaux et refroidisseurs industriels avec compresseur entraîné par
moteur électrique - Partie 2 : Conditions d'essai
Ta slovenski standard je istoveten z: prEN 14511-2
ICS:
23.120 =UDþQLNL9HWUQLNL.OLPDWVNH Ventilators. Fans. Air-
QDSUDYH conditioners
27.080 7RSORWQHþUSDONH Heat pumps
91.140.30 3UH]UDþHYDOQLLQNOLPDWVNL Ventilation and air-
VLVWHPL conditioning
oSIST prEN 14511-2:2015 en,fr,de
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

---------------------- Page: 1 ----------------------
oSIST prEN 14511-2:2015

---------------------- Page: 2 ----------------------
oSIST prEN 14511-2:2015


DRAFT
EUROPEAN STANDARD
prEN 14511-2
NORME EUROPÉENNE

EUROPÄISCHE NORM

October 2015
ICS 27.080; 91.140.30 Will supersede EN 14511-2:2013
English Version

Air conditioners, liquid chilling packages and heat pumps
with electrically driven compressors for space heating and
cooling and process chillers, using electrically driven
compressors - Part 2: Test conditions

This draft European Standard is submitted to CEN members for enquiry. It has been drawn up by the Technical Committee
CEN/TC 113.

If this draft becomes a European Standard, CEN members are bound to comply with the CEN/CENELEC Internal Regulations
which stipulate the conditions for giving this European Standard the status of a national standard without any alteration.

This draft European Standard was established by CEN in three official versions (English, French, German). A version in any other
language made by translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC
Management Centre has the same status as the official versions.

CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,
Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania,
Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and
United Kingdom.

Recipients of this draft are invited to submit, with their comments, notification of any relevant patent rights of which they are
aware and to provide supporting documentation.

Warning : This document is not a European Standard. It is distributed for review and comments. It is subject to change without
notice and shall not be referred to as a European Standard.


EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION

EUROPÄISCHES KOMITEE FÜR NORMUNG

CEN-CENELEC Management Centre: Avenue Marnix 17, B-1000 Brussels
© 2015 CEN All rights of exploitation in any form and by any means reserved Ref. No. prEN 14511-2:2015 E
worldwide for CEN national Members.

---------------------- Page: 3 ----------------------
oSIST prEN 14511-2:2015
prEN 14511-2:2015 (E)
Contents Page
European foreword . 3
1 Scope . 4
2 Normative references . 4
3 Terms and definitions . 4
4 Test conditions . 4
4.1 Environmental conditions and electrical power supply requirements . 4
4.2 Rating conditions . 6
Annex ZA (informative) Relationship between this European Standard and the
requirements of Commission Regulation (EU) No 206/2012 . 19
Bibliography . 20

2

---------------------- Page: 4 ----------------------
oSIST prEN 14511-2:2015
prEN 14511-2:2015 (E)
European foreword
This document (prEN 14511-2:2015) has been prepared by Technical Committee CEN/TC 113 “Heat
pumps and air conditioning units”, the secretariat of which is held by AENOR.
This document is currently submitted to the CEN Enquiry.
This document will supersede EN 14511-2:2013.
This document has been prepared under a mandate given to CEN by the European Commission and the
European Free Trade Association, and supports essential requirements of EU Regulation No 206/2012.
For relationship with EU Regulation No 206/2012, see informative Annex ZA, which is an integral part
of this document.
The main changes with respect to the previous edition are listed below:
— the inclusion of process chillers in the scope of the standard with a table of relevant test conditions.
Although this document has been prepared in the frame of the Commission Regulation (EU)
No 206/2012 implementing Directive 2009/125/EC with regard to ecodesign requirements for air
conditioners and comfort fans, it is also intended to support the Essential Requirements of the
European Directive 2010/30/EU.
prEN 14511 currently comprises the following parts:
— Air conditioners, liquid chilling packages and heat pumps for space heating and cooling and process
chillers using electrically driven compressors — Part 1: Terms and definitions,
— Air conditioners, liquid chilling packages and heat pumps with electrically driven compressors for
space heating and cooling and process chillers, using electrically driven compressors — Part 2: Test
conditions,
— Air conditioners, liquid chilling packages and heat pumps for space heating and cooling and process
chillers, with electrically driven compressors — Part 3: Test methods,
— Air conditioners, liquid chilling packages and heat pumps for space heating and cooling and process
chillers, with electrically driven compressors — Part 4: Requirements.
3

---------------------- Page: 5 ----------------------
oSIST prEN 14511-2:2015
prEN 14511-2:2015 (E)
1 Scope
1.1 The scope of prEN 14511-1 is applicable.
1.2 This European Standard specifies the test conditions for the rating of air conditioners, liquid
chilling packages and heat pumps, using either, air, water or brine as heat transfer media, with
electrically driven compressors when used for space heating and/or cooling. The standard also specifies
the test conditions for the rating of air-cooled and water-cooled process chillers.
1.3 This European Standard specifies the conditions for which performance data shall be declared for
single duct and double duct units for compliance to the ecodesign Regulation 206/2012 and
Energy Labelling Regulation 626/2011.
2 Normative references
The following documents, in whole or in part, are normatively referenced in this document and are
indispensable for its application. For dated references, only the edition cited applies. For undated
references, the latest edition of the referenced document (including any amendments) applies.
prEN 14511-1:2015, Air conditioners, liquid chilling packages and heat pumps for space heating and
cooling and process chillers using electrically driven compressors — Part 1: Terms and definitions
prEN 14511-4:2015, Air conditioners, liquid chilling packages and heat pumps for space heating and
cooling and process chillers, with electrically driven compressors — Part 4: Requirements
EN 15218, Air conditioners and liquid chilling packages with evaporatively cooled condenser and with
electrically driven compressors for space cooling — Terms, definitions, test conditions, test methods and
requirements
3 Terms and definitions
For the purposes of this document, the terms and definitions given in prEN 14511-1:2015 apply.
4 Test conditions
4.1 Environmental conditions and electrical power supply requirements
The tests shall be carried out under the environmental conditions specified in Table 1 or Table 2
depending on the location of the unit.
For all units, electrical power voltage and frequency shall be given by the manufacturer.
4

---------------------- Page: 6 ----------------------
oSIST prEN 14511-2:2015
prEN 14511-2:2015 (E)
Table 1 —Environmental conditions for units designed for installation indoors
Type Measured quantities Rating test
Water-to-water and brine-to-water
Dry bulb temperature 15 °C to 30 °C
units
Air-to-water units with duct connection
Dry bulb temperature 15 °C to 30 °C
on the air inlet and outlet side
Dry bulb temperature
Air-to-water units without duct
15 °C to 30 °C
connection on the air inlet side
Wet bulb temperature
Water-to-air and brine-to-air units with
duct connection on the air inlet and Dry bulb temperature 15 °C to 30 °C
outlet side
Water-to-air and brine-to-air units
Dry bulb temperature
Inlet temperature
without duct connection on the air inlet
(see Table 5 or Table 6).
Wet bulb temperature
and outlet side
Air-to-air units with duct connection
Dry bulb temperature 15 °C to 30 °C
on the outdoor air inlet and outlet side
Dry bulb temperature
Air-to-air units without duct connection As inlet temperature
on the outdoor air inlet and outlet side see Table 3 or Table 4.
Wet bulb temperature
Air-cooled process chillers ducted on
Dry bulb temperature 15 °C to 30 °C
the air side
Water-cooled process chillers Dry bulb temperature 15 °C to 30 °C
Table 2 — Environmental conditions for units designed for installation outdoors
Type Measured quantities Rating test
Inlet temperature
Dry bulb temperature
Air-to-water units (see Tables 12 to 15 and
Wet bulb temperature
Table 16)
Water-to-air and brine-to-air units
Dry bulb temperature
Inlet temperature
without duct connection on the air inlet
(see Table 5 and Table 6)
Wet bulb temperature
side
Water-to-water and brine-to-water
Dry bulb temperature 15 °C to 30 °C
operating in cooling mode
Water-to-water and brine-to-water
Dry bulb temperature 0 °C to 7 °C
operating in heating mode
Dry bulb temperature
Air-to-air units with duct connection on Inlet temperature
the indoor air inlet and outlet side (see Table 3 and Table 4)
Wet bulb temperature
Dry bulb temperature
Air-cooled process chillers (non-ducted Inlet temperature
on the air side) (see Table 25)
Wet bulb temperature
Water-cooled process chillers Dry bulb temperature 15 °C to 30 °C

5

---------------------- Page: 7 ----------------------
oSIST prEN 14511-2:2015
prEN 14511-2:2015 (E)
4.2 Rating conditions
For the rating tests, the appropriate test conditions shall be applied in accordance with:
— Table 3 for air-to-air units in heating mode;
— Table 4 for air-to-air units in cooling mode;
— Table 5 for water-to-air and brine-to-air units in heating mode;
— Table 6 for water-to-air and brine-to-air units in cooling mode;
— Tables 7 to 10 for water-to-water and brine-to-water units in heating mode, depending on the
temperature applications;
— Table 11 for water-to-water, brine-to-water, water-to-brine and brine-to-brine units in cooling
mode;
— Tables 12 to 15 for air-to-water in heating mode, depending on the temperature applications;
— Table 16 for air-to-water and air-to-brine units in cooling mode;
— Table 17 for liquid chilling packages with remote condenser;
— Table 18 for liquid chilling packages for heat recovery condenser;
— Table 19 for air-cooled multisplit systems and modular air-cooled multisplit systems in the heating
mode;
— Table 20 for air-cooled multisplit systems and modular air-cooled multisplit systems in the cooling
mode;
— Table 21 for modular heat recovery air-cooled multisplit systems;
— Table 22 for water-cooled multisplit systems and modular water-cooled multisplit systems in the
heating mode;
— Table 23 for water-cooled multisplit systems and modular water-cooled multisplit systems in the
cooling mode;
— Table 24 for modular heat recovery water-cooled multisplit systems.
— Table 25 for process chillers
For units with brine, the test shall be carried out with the brine specified by the manufacturer,
see prEN 14511-4:2015, 7.2.1.
For air-to-water, brine-to-water and water-to-water heat pumps, the manufacturer may declare the
water temperatures levels (low, intermediate, medium, and high) applicable to the heating mode.
NOTE For comparison purposes between reverse cycle and non-reverse cycle units, the conditions on the
water side are given by the inlet and outlet water temperatures, possibly leading to different water flow rates in
heating and cooling modes.
The rating tests in heating mode also apply for units having evaporatively cooled condenser, which
performance in cooling mode is determined in accordance with EN 15218, and which can operate in
heating mode.
6

---------------------- Page: 8 ----------------------
oSIST prEN 14511-2:2015
prEN 14511-2:2015 (E)
The standard rating conditions, extracted from Table 3 for heating mode and specified in Table ZA.1,
shall be used to determine the rated capacity (P ), the rated power input (P ), the rated coefficient
rated COP
of performance (COP ) and the electricity consumption (Q , Q ) in heating mode.
rated DD SD
Table 3 — Air-to-air units - Heating mode
 Outdoor heat exchanger Indoor heat exchanger
Inlet dry Inlet wet Inlet dry Inlet wet
bulb bulb bulb bulb
temperature temperature temperature temperature
°C °C °C °C
Outdoor air / recycled 7 6 20 15 max
air (e.g. window, double
duct, split units)
Standard rating
Exhaust air / recycled 20 12 20 12
conditions
air (e.g. single duct heat
pump)
Exhaust air / outdoor air 20 12 7 6
Outdoor air / recycled
air (e.g. window, double 2 1 20 15 max.
duct, split units)
Outdoor air / recycled
air (e.g. window, double - 7 - 8 20 15 max.
duct, split units)
Application
Outdoor air / recycled
rating
air (e.g. window, double - 15 - 20 15 max.
conditions
duct, split units)
Outdoor air / recycled
air (e.g. window, double 12 11 20 15 max.
duct, split units)
Exhaust air / outdoor air 20 12 2 1
Exhaust air / outdoor air 20 12 - 7 - 8
7

---------------------- Page: 9 ----------------------
oSIST prEN 14511-2:2015
prEN 14511-2:2015 (E)
Table 4 — Air-to-air units - Cooling mode
 Outdoor heat exchanger Indoor heat exchanger
Inlet dry Inlet wet Inlet dry Inlet wet
bulb bulb bulb bulb
temperature temperature temperature temperature
°C °C °C °C
Comfort (outdoor air / 35 a 27 19
24
recycled air) (e.g.
window, double duct,
split units)
Comfort (exhaust air / 27 19 27 19
recycled air)
Standard rating
conditions
Comfort (exhaust air / 27 19 35 24
outdoor air)
b, c 35 24 35 24
Single duct
Control cabinet 35 24 35 24
Close control 35 24 24 17
Comfort (outdoor air /
recycled air) (e.g.
a
27 21 15
19
window, double duct,
split units)
b, c
27 19 27 19
Single duct
Application
rating
Comfort (outdoor air /
conditions
recycled air) (e.g.
a
46 29 19
24
window, double duct,
split units)
Control cabinet 50 3
...