Air conditioners, liquid chilling packages and heat pumps with electrically driven compressors for space heating and cooling - Part 2: Test conditions

1.1 The scope of prEN 14511-2:2009 is applicable.
1.2 This part of prEN 14511 specifies the test conditions for the rating of air and water cooled air
conditioners, liquid chilling packages, air-to-air, water-to-air, air-to-water and water-to-water heat pumps with
electrically driven compressors when used for space heating and/or cooling. It also specifies test conditions
for heat recovery operation of multisplit systems.

Luftkonditionerer, Flüssigkeitskühlsätze und Wärmepumpen mit elektrisch angetriebenen Verdichtern für die Raumbehezung und Kühlung - Teil 2: Prüfbedingungen

1.1 Es gilt der Anwendungsbereich von EN 14511-1:2011.
1.2 Diese Europäische Norm legt die Bedingungen für die Prüfung der Leistung von Luftkonditionierern, Flüssigkeitskühlsätzen und Wärmepumpen, die Luft, Wasser oder Sole als Wärmeübertrager nutzen, mit elektrisch angetriebenen Verdichtern für die Raumheizung und/oder -kühlung fest. Sie legt ferner die Bedin-gungen für die Prüfung von Multi-Split-Systemen für die Wärmerückgewinnung fest.

Climatiseurs, groupes refroidisseurs de liquide et pompes à chaleur avec compresseur entraîné par moteur électrique pour le chauffage et la réfrigération des locaux - Partie 2: Conditions d'essai

1.1   Le domaine d'application du prEN 14511-2:2009 est applicable.
1.2   La présente partie du prEN 14511 spécifie les conditions d'essai pour la détermination des caractéristiques de performance des climatiseurs à condensation par air et à condensation par eau, des groupes refroidisseurs de liquide et des pompes à chaleur air/air, eau/air, air/eau et eau/eau, avec compresseur entraîné par moteur électrique, lorsqu'ils sont utilisés pour le chauffage et/ou la réfrigération des locaux. Il spécifie aussi les conditions d'essais pour le fonctionnement de la récupération de chaleur des systèmes multi-split.

Klimatske naprave, enote za tekočinsko hlajenje in toplotne črpalke z električnimi kompresorji za segrevanje in hlajenje prostora - 2. del: Preskusni pogoji

1.1 Velja obseg uporabe prEN 14511-2:2009.
1.2 Ta del prEN 14511 določa preskusne pogoje za ocenjevanje zračno in vodno hlajenih klimatskih naprav, enot za tekočinsko hlajenje, toplotnih črpalk zrak-zrak, voda-zrak, zrak-voda in voda-voda z električnimi kompresorji, kadar se uporabljajo za segrevanje in/ali hlajenje prostora. Prav tako določa preskusne pogoje za vračanje toplote sistemov z več razcepi.

General Information

Status
Withdrawn
Public Enquiry End Date
30-Nov-2009
Publication Date
22-Nov-2011
Withdrawal Date
23-Oct-2013
Technical Committee
Current Stage
9900 - Withdrawal (Adopted Project)
Start Date
24-Oct-2013
Due Date
16-Nov-2013
Completion Date
24-Oct-2013

Relations

Buy Standard

Standard
EN 14511-2:2012
English language
20 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day
Draft
prEN 14511-2:2009
English language
20 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.Luftkonditionerer, Flüssigkeitskühlsätze und Wärmepumpen mit elektrisch angetriebenen Verdichtern für die Raumbehezung und Kühlung - Teil 2: PrüfbedingungenClimatiseurs, groupes refroidisseurs de liquide et pompes à chaleur avec compresseur entraîné par moteur électrique pour le chauffage et la réfrigération des locaux - Partie 2: Conditions d'essaiAir conditioners, liquid chilling packages and heat pumps with electrically driven compressors for space heating and cooling - Part 2: Test conditions91.140.30VLVWHPLVentilation and air-conditioning27.080Heat pumps23.120QDSUDYHVentilators. Fans. Air-conditionersICS:Ta slovenski standard je istoveten z:EN 14511-2:2011SIST EN 14511-2:2012en,fr,de01-januar-2012SIST EN 14511-2:2012SLOVENSKI
STANDARDSIST EN 14511-2:20081DGRPHãþD



SIST EN 14511-2:2012



EUROPEAN STANDARD NORME EUROPÉENNE EUROPÄISCHE NORM
EN 14511-2
October 2011 ICS 91.140.30 Supersedes EN 14511-2:2007English Version
Air conditioners, liquid chilling packages and heat pumps with electrically driven compressors for space heating and cooling - Part 2: Test conditions
Climatiseurs, groupes refroidisseurs de liquide et pompes à chaleur avec compresseur entraîné par moteur électrique pour le chauffage et la réfrigération des locaux - Partie 2: Conditions d'essai
Luftkonditionierer, Flüssigkeitskühlsätze und Wärmepumpen mit elektrisch angetriebenen Verdichtern für die Raumbeheizung und Kühlung - Teil 2: Prüfbedingungen This European Standard was approved by CEN on 20 August 2011.
CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN-CENELEC Management Centre or to any CEN member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC Management Centre has the same status as the official versions.
CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION EUROPÄISCHES KOMITEE FÜR NORMUNG
Management Centre:
Avenue Marnix 17,
B-1000 Brussels © 2011 CEN All rights of exploitation in any form and by any means reserved worldwide for CEN national Members. Ref. No. EN 14511-2:2011: ESIST EN 14511-2:2012



EN 14511-2:2011 (E) 2 Contents Page Foreword .31Scope .42Normative references .43Terms and definitions .44Test conditions .44.1Environmental conditions and electrical power supply requirements .44.2Rating conditions.5Annex A (normative)
Energy labelling application . 17A.1General . 17A.2Rating conditions. 17A.2.1General . 17A.2.2Air-cooled air conditioners (air-to-air conditioners) . 17A.2.3Single-duct (reversible) air conditioners . 17A.2.4Water-cooled air conditioners (water-to-air conditioners) . 17A.2.5Double duct air conditioners . 18A.3Test procedure . 18A.4Tolerances on declared values . 18A.4.1General . 18A.4.2First testing . 18A.4.3Second testing . 19Bibliography . 20 SIST EN 14511-2:2012



EN 14511-2:2011 (E) 3 Foreword This document (EN 14511-2:2011) has been prepared by Technical Committee CEN/TC 113 “Heat pumps and air conditioning units”, the secretariat of which is held by AENOR. This European Standard shall be given the status of a national standard, either by publication of an identical text or by endorsement, at the latest by April 2012, and conflicting national standards shall be withdrawn at the latest by April 2012. Attention is drawn to the possibility that some of the elements of this document may be the subject of patent rights. CEN [and/or CENELEC] shall not be held responsible for identifying any or all such patent rights. This document supersedes EN 14511-2:2007. This document has been prepared under a mandate given to CEN by the European Commission and the European Free Trade Association. EN 14511 comprises the following parts under the general title Air conditioners, liquid chilling packages and heat pumps with electrically driven compressors for space heating and cooling:  Part 1: Terms and definitions,  Part 2: Test conditions,  Part 3: Test methods,  Part 4: Requirements. According to the CEN/CENELEC Internal Regulations, the national standards organizations of the following countries are bound to implement this European Standard: Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and the United Kingdom. SIST EN 14511-2:2012



EN 14511-2:2011 (E) 4 1 Scope 1.1 The scope of EN 14511-1:2011 is applicable. 1.2 This European Standard specifies the test conditions for the rating of air conditioners, liquid chilling packages and heat pumps, using either, air, water or brine as heat transfer media, with electrically driven compressors when used for space heating and/or cooling. It also specifies test conditions for heat recovery operation of multisplit systems. 2 Normative references The following referenced documents are indispensable for the application of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. EN 14511-1:2011, Air conditioners, liquid chilling packages and heat pumps with electrically driven compressors for space heating and cooling  Part 1: Terms and definitions EN 14511-3:2011, Air conditioners, liquid chilling packages and heat pumps with electrically driven compressors for space heating and cooling  Part 3: Test methods EN 14511-4:2011, Air conditioners, liquid chilling packages and heat pumps with electrically driven compressors for space heating and cooling  Part 4: Requirements 3 Terms and definitions For the purposes of this document, the terms and definitions given in EN 14511-1:2011 apply. 4 Test conditions 4.1 Environmental conditions and electrical power supply requirements The tests shall be carried out under the environmental conditions specified in Table 1 or Table 2 depending on the location of the unit. For all units, electrical power voltage and frequency shall be given by the manufacturer. SIST EN 14511-2:2012



EN 14511-2:2011 (E) 5 Table 1 —Environmental conditions for units designed for installation indoors Type Measured quantities Rating test Water-to-water and brine-to-water units Dry bulb temperature 15 °C to 30 °C Air-to-water units with duct connection on the air inlet and outlet side Dry bulb temperature 15 °C to 30 °C Air-to-water units without duct connection on the air inlet side Dry bulb temperature Wet bulb temperature
15 °C to 30 °C Water-to-air and brine-to-air units with duct connection on the air inlet and outlet side Dry bulb temperature 15 °C to 30 °C Water-to-air and brine-to-air units without duct connection on the air inlet and outlet side Dry bulb temperature Wet bulb temperature
Inlet temperature (see Table 5 or Table 6) Air-to-air units with duct connection
on the outdoor air inlet and outlet side Dry bulb temperature 15 °C to 30 °C Air-to-air units without duct connection
on the outdoor air inlet and outlet side Dry bulb temperature Wet bulb temperature
As inlet temperature see Table 3 or Table 4
Table 2 — Environmental conditions for units designed for installation outdoors Type Measured quantities Rating test Air-to-water units
Dry bulb temperature Wet bulb temperature Inlet temperature (see Tables 12 to 15 and Table 16) Water-to-air and brine-to-air units without duct connection on the air inlet side Dry bulb temperature Wet bulb temperature
Inlet temperature (see Table 5 and Table 6) Water-to-water and brine-to-water operating in cooling mode Dry bulb temperature 15 °C to 30 °C Water-to-water and brine-to-water operating in heating mode Dry bulb temperature 0 °C to 7 °C Air-to-air units with duct connection on the indoor air inlet and outlet side Dry bulb temperature Wet bulb temperature
Inlet temperature (see Table 3 and Table 4)
4.2 Rating conditions For the rating tests, the appropriate test conditions shall be applied in accordance with:  Table 3 for air-to-air units in heating mode;  Table 4 for air-to-air units in cooling mode;  Table 5 for water-to-air and brine-to-air units in heating mode;  Table 6 for water-to-air and brine-to-air units in cooling mode;  Tables 7 to 10 for water-to-water and brine-to-water units in heating mode, depending on the temperature applications; SIST EN 14511-2:2012



EN 14511-2:2011 (E) 6  Table 11 for water-to-water, brine-to-water, water-to-brine and brine-to-brine units in cooling mode;  Tables 12 to 15 for air-to-water in heating mode, depending on the temperature applications;  Table 16 for air-to-water and air-to-brine units in cooling mode;  Table 17 for liquid chilling packages with remote condenser;  Table 18 for liquid chilling packages for heat recovery condenser;  Table 19 for air-cooled multisplit systems and modular air-cooled multisplit systems in the heating mode;  Table 20 for air-cooled multisplit systems and modular air-cooled multisplit systems in the cooling mode;  Table 21 for modular heat recovery air-cooled multisplit systems;  Table 22 for water-cooled multisplit systems and modular water-cooled multisplit systems in the heating mode;  Table 23 for water-cooled multisplit systems and modular water-cooled multisplit systems in the cooling mode. For units with brine, the test shall be carried out with the brine specified by the manufacturer, see 7.2.1 of EN 14511-4:2011. NOTE 1 For air-to-water, brine-to-water and water-to-water units, the manufacturer may declare the water temperatures levels (lower, medium, high and very high) applicable to the heating mode. NOTE 2 For comparison purposes between reverse cycle and non reverse cycle units, the conditions on the water side are given by the inlet and outlet water temperatures, possibly leading to different water flow rates in heating and cooling modes. SIST EN 14511-2:2012



EN 14511-2:2011 (E) 7 Table 3 — Air-to-air units - Heating mode
Outdoor heat exchanger Indoor heat exchanger Inlet dry bulb temperature°C Inlet wet bulb temperature°C Inlet dry bulb temperature °C Inlet wet bulb temperature°C Standard rating
conditions Outdoor air / recycled air (e.g. window, double duct, split units) 7 6 20 15 max Exhaust air / recycled air (e.g. single duct heat pump) 20 12 20 12 Exhaust air / outdoor air 20 12 7 6 Application rating
conditions Outdoor air / recycled air (e.g. window, double duct, split units) 2 1 20 15 max. Outdoor air / recycled air (e.g. window, double duct, split units) - 7 - 8 20 15 max. Outdoor air / recycled air (e.g. window, double duct, split units) - 15 - 20 15 max. Outdoor air / recycled air (e.g. window, double duct, split units) 12 11 20 15 max. Exhaust air / outdoor air 20 12 2 1 Exhaust air / outdoor air 20 12 - 7 - 8
SIST EN 14511-2:2012



EN 14511-2:2011 (E) 8 Table 4 — Air-to-air units - Cooling mode
Outdoor heat exchanger Indoor heat exchanger Inlet dry bulb temperature°C Inlet wet bulb temperature°C Inlet dry bulb temperature °C Inlet wet bulb temperature°C Standard rating
conditions Comfort (outdoor air / recycled air) (e.g. window, double duct, split units)
35 24 a 27 19 Comfort (exhaust air / recycled air) 27 19 27 19 Comfort (exhaust air / outdoor air) 27 19 35 24 Single duct b, c 35 24 35 24 Control cabinet 35 24 35 24 Close control 35 24 24 17 Application rating
conditions Comfort (outdoor air / recycled air) (e.g. window, double duct, split units)
27 19 a 21 15 Single duct b, c
27 19 27 19 Comfort (outdoor air / recycled air) (e.g. window, double duct, split units)
46 24 a
29 19 Control cabinet 50 30 35 24 Close control 27 19 21 15 a The wet bulb temperature condition is not required when testing units which do not evaporate condensate. b When using the calorimeter room method, pressure equilibrium between indoor and outdoor compartments shall be obtained by introducing into indoor compartment, air at the same rating temperature conditions. c The pressure difference between the two compartments of the calorimeter room shall not be greater than 1,25 Pa. This pressure equilibrium can be achieved by using an equalising device or by creating an open space area in the separation partition wall, which dimensions shall be calculated for the maximum airflow of the unit to be tested. If an open space is created in the partition wall, an air sampling device or several temperature sensors shall be used to measure the temperature of the air from the outdoor compartment to the indoor compartment.
Table 5 — Water-to-air and brine-to-air units - Heating mode
Outdoor heat exchanger Inlet heat exchanger Inlet temperature °C Outlet temperature °C Inlet dry bulb temperature °C Inlet wet bulb temperature°C Standard rating conditions Water 10 7
20 15 max. Brine 0 -3 20 15 max. Water loop 20 17
20 15 max. Application rating conditions Water 15 a 20 15 max. Brine 5 a 20 15 max. a The test is performed at the flow rate obtained during the test at the corresponding standard rating conditions. SIST EN 14511-2:2012



EN 14511-2:
...

SLOVENSKI STANDARD
oSIST prEN 14511-2:2009
01-november-2009
.OLPDWVNHQDSUDYHHQRWH]DWHNRþLQVNRKODMHQMHLQWRSORWQHþUSDONH]HOHNWULþQLPL
NRPSUHVRUML]DVHJUHYDQMHLQKODMHQMHSURVWRUDGHO3UHVNXVQLSRJRML
Air conditioners, liquid chilling packages and heat pumps with electrically driven
compressors for space heating and cooling - Part 2: Test conditions
Luftkonditionerer, Flüssigkeitskühlsätze und Wärmepumpen mit elektrisch angetriebenen
Verdichtern für die Raumbehezung und Kühlung - Teil 2: Prüfbedingungen
Climatiseurs, groupes refroidisseurs de liquide et pompes à chaleur avec compresseur
entraîné par moteur électrique pour le chauffage et la réfrigération des locaux - Partie 2:
Conditions d'essai
Ta slovenski standard je istoveten z: prEN 14511-2
ICS:
23.120 =UDþQLNL9HWUQLNL.OLPDWVNH Ventilators. Fans. Air-
QDSUDYH conditioners
27.080 7RSORWQHþUSDONH Heat pumps
91.140.30 3UH]UDþHYDOQLLQNOLPDWVNL Ventilation and air-
VLVWHPL conditioning
oSIST prEN 14511-2:2009 en,fr
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

---------------------- Page: 1 ----------------------
oSIST prEN 14511-2:2009

---------------------- Page: 2 ----------------------
oSIST prEN 14511-2:2009


EUROPEAN STANDARD
DRAFT
prEN 14511-2
NORME EUROPÉENNE

EUROPÄISCHE NORM

September 2009
ICS 91.140.30 Will supersede EN 14511-2:2007
English Version
Air conditioners, liquid chilling packages and heat pumps with
electrically driven compressors for space heating and cooling -
Part 2: Test conditions
Climatiseurs, groupes refroidisseurs de liquide et pompes à Luftkonditionerer, Flüssigkeitskühlsätze und
chaleur avec compresseur entraîné par moteur électrique Wärmepumpen mit elektrisch angetriebenen Verdichtern
pour le chauffage et la réfrigération des locaux - Partie 2: für die Raumbehezung und Kühlung - Teil 2:
Conditions d'essai Prüfbedingungen
This draft European Standard is submitted to CEN members for enquiry. It has been drawn up by the Technical Committee CEN/TC 113.

If this draft becomes a European Standard, CEN members are bound to comply with the CEN/CENELEC Internal Regulations which
stipulate the conditions for giving this European Standard the status of a national standard without any alteration.

This draft European Standard was established by CEN in three official versions (English, French, German). A version in any other language
made by translation under the responsibility of a CEN member into its own language and notified to the CEN Management Centre has the
same status as the official versions.

CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Cyprus, Czech Republic, Denmark, Estonia, Finland,
France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal,
Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom.

Recipients of this draft are invited to submit, with their comments, notification of any relevant patent rights of which they are aware and to
provide supporting documentation.

Warning : This document is not a European Standard. It is distributed for review and comments. It is subject to change without notice and
shall not be referred to as a European Standard.


EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION

EUROPÄISCHES KOMITEE FÜR NORMUNG

Management Centre: Avenue Marnix 17, B-1000 Brussels
© 2009 CEN All rights of exploitation in any form and by any means reserved Ref. No. prEN 14511-2:2009: E
worldwide for CEN national Members.

---------------------- Page: 3 ----------------------
oSIST prEN 14511-2:2009
prEN 14511-2:2009 (E)
Contents Page
Foreword .3
1 Scope .4
2 Normative references .4
3 Terms and definitions .4
4 Test conditions .4
4.1 Environmental conditions and electrical power supply requirements .4
4.2 Rating conditions.5
Annex A (normative)  Energy labelling application . 16
A.1 General . 16
A.2 Rating conditions. 16
A.2.1 General . 16
A.2.2 Air-cooled air conditioners (air-to-air conditioners) . 16
A.2.3 Single-duct air conditioners and heat pumps . 16
A.2.4 Water-cooled air conditioners (water-to-air conditioners) . 16
A.2.5 Double duct air conditioners . 17
A.3 Test procedure . 17
A.4 Tolerances on declared values . 17
A.4.1 General . 17
A.4.2 First testing . 17
A.4.3 Second testing . 18
Annex ZA (informative) Relationship between this European Standard and the Essential
Requirements of EC Directive 2002/31/CE . 19
Bibliography . 20

2

---------------------- Page: 4 ----------------------
oSIST prEN 14511-2:2009
prEN 14511-2:2009 (E)
Foreword
This document (prEN 14511-2:2009) has been prepared by Technical Committee CEN/TC 113 “Heat pumps
and air conditioning units”, the secretariat of which is held by AENOR.
This document is currently submitted to the CEN Enquiry.
This document will supersede EN 14511-2:2007.
This document has been prepared under a mandate given to CEN by the European Commission and the
European Free Trade Association, and supports essential requirements of EU Directive 2002/31/EC.

For relationship with EU Directive 2002/31/EC, see informative Annex ZA, which is an integral part of this
document.
prEN 14511 comprises the following parts under the general title "Air conditioners, liquid chilling packages and
heat pumps with electrically driven compressors for space heating and cooling“:
 Part 1: Terms and definitions
 Part 2: Test conditions
 Part 3: Test methods
 Part 4: Requirements

3

---------------------- Page: 5 ----------------------
oSIST prEN 14511-2:2009
prEN 14511-2:2009 (E)
1 Scope
1.1 The scope of prEN 14511-2:2009 is applicable.
1.2 This part of prEN 14511 specifies the test conditions for the rating of air and water cooled air
conditioners, liquid chilling packages, air-to-air, water-to-air, air-to-water and water-to-water heat pumps with
electrically driven compressors when used for space heating and/or cooling. It also specifies test conditions
for heat recovery operation of multisplit systems.
2 Normative references
The following referenced documents are indispensable for the application of this document. For dated
references, only the edition cited applies. For undated references, the latest edition of the referenced
document (including any amendments) applies.
prEN 14511-1:2009, Air conditioners, liquid chilling packages and heat pumps with electrically driven
compressors for space heating and cooling - Part 1: Terms and definitions
prEN 14511-3:2009, Air conditioners, liquid chilling packages and heat pumps with electrically driven
compressors for space heating and cooling - Part 3: Test methods
prEN 14511-4:2009, Air conditioners, liquid chilling packages and heat pumps with electrically driven
compressors for space heating and cooling - Part 4: Requirements
3 Terms and definitions
For the purposes of this document, the terms and definitions given in prEN 14511-1:2009 apply.
4 Test conditions
4.1 Environmental conditions and electrical power supply requirements
The tests shall be carried out under the environmental conditions specified in Table 1 or Table 2 depending on the
location of the unit.
For all units, electrical power voltage and frequency shall be given by the manufacturer.
4

---------------------- Page: 6 ----------------------
oSIST prEN 14511-2:2009
prEN 14511-2:2009 (E)
Table 1 — Environmental conditions for units designed for installation indoors
Type Measured quantities Rating test
Water-to-water and brine-to-water units Dry bulb temperature 15 °C to 30 °C
Air-to-water units with duct connection on
Dry bulb temperature
15 °C to 30 °C
the air inlet and outlet side
Dry bulb temperature
Air-to-water units without duct connection Inlet temperatures (see
on the air inlet side Tables 12 to 15 or Table 16)
Wet bulb temperature
Water-to-air and brine-to-air units with duct
Dry bulb temperature 15 °C to 30 °C
connection on the air inlet and outlet side
Water-to-air and brine-to-air units without
Dry bulb temperature
Inlet temperatures (see Table
duct connection on the air inlet and outlet
5 or Table 6)
Wet bulb temperature
side
Air-to-air units with duct connection
Dry bulb temperature 15 °C to 30 °C
on the indoor air inlet and outlet side
Dry bulb temperature
Air-to-air units without duct connection As inlet temperatures see
on the indoor air inlet and outlet side Table 3 or Table 4
Wet bulb temperature

Table 2 — Environmental conditions for units designed for installation outdoors
Type Measured quantities Rating test
Dry bulb temperature
Inlet temperatures (see
Air-to-water units
Tables 12 to 15 and Table 15)
Wet bulb temperature
Dry bulb temperature
Water-to-air and brine-to-air units without Inlet temperatures (see Table
duct connection on the air inlet side 5 and Table 6)
Wet bulb temperature
Water-to-water and brine-to-water operating
Dry bulb temperature 25 °C to 35 °C
in cooling mode
Water-to-water and brine-to-water operating
Dry bulb temperature 0 °C to 7 °C
in heating mode
Dry bulb temperature
Air-to-air units with duct connection on the Inlet temperatures (see Table
indoor air inlet and outlet side 3 and Table 4)
Wet bulb temperature

4.2 Rating conditions
For the rating tests, the appropriate test conditions shall be applied in accordance with:
 Table 3 for air-to-air units in heating mode;
 Table 4 for air-to-air units in cooling mode;
 Table 5 for water-to-air and brine-to-air units in heating mode;
 Table 6 for water-to-air and brine-to-air units in cooling mode;
5

---------------------- Page: 7 ----------------------
oSIST prEN 14511-2:2009
prEN 14511-2:2009 (E)
 Tables 7 to 10 for water-to-water and brine-to-water units in heating mode, depending on the temperature
applications;
 Table 11 for water-to-water, brine-to-water, water-to-brine and brine-to-brine units in cooling mode;
 Tables 12 to 15 for air-to-water in heating mode, depending on the temperature applications;
 Table 16 for air-to-water and air-to-brine units in cooling mode;
 Table 17 for liquid chilling packages with remote condenser;
 Table 18 for liquid chilling packages for heat recovery condenser;
 Table 19 for basic, multiple circuit and modular air-cooled multisplit systems in the heating mode;
 Table 20 for basic, multiple circuit and modular air-cooled multisplit systems in the cooling mode;
 Table 21 for modular heat recovery air-cooled multisplit systems;
 Table 22 for basic, multiple circuit and modular water-cooled multisplit systems in the heating mode;
 Table 23 for basic, multiple circuit and modular water-cooled multisplit systems in the cooling mode.
For units with brine, the test shall be carried out with the brine specified by the manufacturer, see 7.2.1 of
prEN 14511-4:2009.
Table 3 — Air-to-air units - Heating mode
Outdoor heat exchanger Indoor heat exchanger

Inlet dry bulb Inlet wet bulb Inlet dry bulb Inlet wet bulb
temperature temperature temperature temperature
°C °C °C °C
Outside air / recycled air 7 6 20 15 max
(e.g. window, double duct,
split units)
Standard rating
Exhaust air / recycled air 20 12 20 12
Conditions
(e.g. single duct heat
pump)
Exhaust air / outdoor air 20 12 7 6
Outside air / recycled air
(e.g. window, double duct, 2 1 20 15 max.
split units)
Outside air / recycled air
(e.g. window, double duct, - 7 - 8 20 15 max.
split units)
Application rating
conditions
Outside air / recycled air
(e.g. window, double duct, - 15 - 20 15 max.
split units)
Exhaust air / outdoor air 20 12 2 1
Exhaust air / outdoor air 20 12 - 7 - 8
6

---------------------- Page: 8 ----------------------
oSIST prEN 14511-2:2009
prEN 14511-2:2009 (E)
Table 4 — Air-to-air units - Cooling mode
Outdoor heat exchanger Indoor heat exchanger
Inlet dry bulb Inlet wet bulb Inlet dry bulb Inlet wet bulb
temperature temperature temperature temperature
°C °C °C °C
a
Comfort (outside air / 35 24 27 19
recycled air) (e.g. window,
double duct, split units)
Comfort (exhaust air / 27 19 27 19
recycled air)
Standard rating
Comfort (exhaust air / 27 19 35 24
Conditions
outdoor air)

b, c
35 24 35 24
Single duct
Control cabinet 35 24 35 24
Close control 35 24 24 17
Comfort (outside air /

a
recycled air) (e.g. window, 27 19 21 15
double duct, split units)
b, c
Single duct 27 19 27 19
Application rating
Comfort (outside air /
conditions
a
recycled air) (e.g. window, 46 24 29 19
double duct, split units)
Control cabinet 50 30 35 24
Close control 27 19 21 15

a
The wet bulb temperature condition is not required when testing units which do not evaporate condensate.
b
When using the calorimeter room method, pressure equilibrium between indoor and outdoor compartments shall be

obtained by introducing into indoor compartment, air at the same rating temperature conditions.

c
The pressure difference between the two compartments of the calorimeter room shall not be greater than 1,25 Pa.
This pressure equilibrium can be achieved by using an equalising device or by creating an open space area in the
separation partition wall, which dimensions shall be calculated for the maximum airflow of the unit to be tested. If an
open space is created in the partition wall, an air sampling device or several temperature sensors shall be used to

measure the temperature of the air from the outdoor compartment to the indoor compartment
Table 5 — Water-to-air and brine-to-air units - Heating mode
Outdoor heat exchanger Inlet heat exchanger
Inlet Outlet Inlet dry bulb Inlet wet bulb
temperature temperature temperature temperature
°C °C °C °C

a
Water 10 20 15 max.
7/
Standard rating
a
Brine 0 -3/ 20 15 max.
conditions
a
Water loop 20 20 15 max.
17/
b
Water 15 20 15 max.
Application rating
conditions
b
Brine 5 20 15 max.


a
For units designed for heating and cooling mode, the flow rate obtained during the test at standard rating conditions in

cooling mode (see Table 6) is used.

b
The test is performed at the flow rate obtained during the test at the corresponding standard rating conditions.
7

---------------------- Page: 9 ----------------------
oSIST prEN 14511-2:2009
prEN 14511-2:2009 (E)
Table 6 — Water-to-air and brine-to-air units - Cooling mode
Outdoor heat exchanger Indoor heat exchanger
Inlet Outlet Inlet dry bulb Inlet wet bulb
temperature temperature temperature temperature
°C °C °C °C
Cooling tower 30 35 27 19
Ground coupled (water or 10 15 27 19
Standard rating
brine)
conditions
Control cabinet 15 20 35 24
Close control 30 35 24 17
a
Cooling tower 40 27 19

Ground coupled (water or
a
15 27 19

Application rating
brine)
conditions
a
Close control 15 21 15

a
Close control 40 24 17


a
The test is performed at the water flow rate obtained during the test at the corresponding standard rating conditions.
Table 7 — Water-to-water and brine-to-water units - Heating mode

Outdoor heat exchanger Indoor heat exchanger
low temperature applications
Inlet Outlet Inlet Outlet
temperature temperature temperature temperature
°C °C °C °C
a
Water 10 7 30 35
Standard rating
conditions
Brine 0 -3 30 35

b b
Water 15 35
Application rating

condit
...