SIST EN 61800-3:2005/A1:2012
(Amendment)Adjustable speed electrical power drive systems - Part 3: EMC requirements and specific test methods
Adjustable speed electrical power drive systems - Part 3: EMC requirements and specific test methods
Specifies electromagnetic compatibility (EMC) requirements for power drive systems (PDSs). A PDS is defined in 3.1. These are adjustable speed a.c. or d.c. motor drives. Requirements are stated for PDSs with converter input and/or output voltages (line-to-line voltage), up to 35 kV a.c. r.m.s. The three main changes are: a) the classes of distribution of the PDS have been replaced by categories of PDS (C1 to C4) with definitions related to the product itself and its intended use, b) better coverage of emission limits, c) an EMC plan is generalized for categeory C4.
Drehzahlveränderbare elektrische Antriebe - Teil 3: EMV-Anforderungen einschließlich spezieller Prüfverfahren
Entraînements électriques de puissance à vitesse variable - Partie 3: Exigences de CEM et méthodes d'essais spécifiques
Električni pogonski sistemi z nastavljivo hitrostjo - 3. del: Zahteve za elektromagnetno združljivost in posebne preskusne metode
Standard določa zahteve za elektromagnetno združljivost za pogonske sisteme. Pogonski sistem je opredeljen v točki 3.1. Pogonski sistemi so motorni pogoni z enosmerno ali izmenično napetostjo z nastavljivo hitrostjo. Zahteve so določene za pogonske sisteme s pretvornimi vhodnimi in/ali izhodnimi napetostmi (medlinijska napetost), do 35 kV izmenične napetosti efektivne vrednosti. Tri glavne spremembe so: a) distribucijske razrede pogonskih sistemov so nadomestile kategorije pogonskih sistemov (C1 do C4), pri čemer so opredelitve povezane s samim proizvodom in njegovo nameravano uporabo, b) boljša pokritost mejnih vrednosti emisij, c) za kategorijo C4 je posplošen načrt v zvezi z elektromagnetno združljivostjo.
General Information
Relations
Standards Content (Sample)
SLOVENSKI STANDARD
SIST EN 61800-3:2005/A1:2012
01-junij-2012
(OHNWULþQLSRJRQVNLVLVWHPL]QDVWDYOMLYRKLWURVWMRGHO=DKWHYH]D
HOHNWURPDJQHWQR]GUXåOMLYRVWLQSRVHEQHSUHVNXVQHPHWRGH
Adjustable speed electrical power drive systems - Part 3: EMC requirements and specific
test methods
Drehzahlveränderbare elektrische Antriebe - Teil 3: EMV-Anforderungen einschließlich
spezieller Prüfverfahren
Entraînements électriques de puissance à vitesse variable - Partie 3: Exigences de CEM
et méthodes d'essais spécifiques
Ta slovenski standard je istoveten z: EN 61800-3:2004/A1:2012
ICS:
29.200 8VPHUQLNL3UHWYRUQLNL Rectifiers. Convertors.
6WDELOL]LUDQRHOHNWULþQR Stabilized power supply
QDSDMDQMH
33.100.01 Elektromagnetna združljivost Electromagnetic compatibility
na splošno in general
SIST EN 61800-3:2005/A1:2012 en
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
---------------------- Page: 1 ----------------------
SIST EN 61800-3:2005/A1:2012
---------------------- Page: 2 ----------------------
SIST EN 61800-3:2005/A1:2012
EUROPEAN STANDARD
EN 61800-3/A1
NORME EUROPÉENNE
March 2012
EUROPÄISCHE NORM
ICS 29.200; 33.100
English version
Adjustable speed electrical power drive systems -
Part 3: EMC requirements and specific test methods
(IEC 61800-3:2004/A1:2011)
Entraînements électriques de puissance à Drehzahlveränderbare elektrische
vitesse variable - Antriebe -
Partie 3: Exigences de CEM et méthodes Teil 3: EMV-Anforderungen einschließlich
d'essais spécifiques spezieller Prüfverfahren
(CEI 61800-3:2004/A1:2011) (IEC 61800-3:2004/A1:2011)
This amendment A1 modifies the European Standard EN 61800-3:2004; it was approved by CENELEC on 2011-
12-19. CENELEC members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate
the conditions for giving this amendment the status of a national standard without any alteration.
Up-to-date lists and bibliographical references concerning such national standards may be obtained on
application to the CEN-CENELEC Management Centre or to any CENELEC member.
This amendment exists in three official versions (English, French, German). A version in any other language
made by translation under the responsibility of a CENELEC member into its own language and notified to the
CEN-CENELEC Management Centre has the same status as the official versions.
CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus,
the Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy,
Latvia, Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia,
Spain, Sweden, Switzerland, Turkey and the United Kingdom.
CENELEC
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung
Management Centre: Avenue Marnix 17, B - 1000 Brussels
© 2012 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members.
Ref. No. EN 61800-3:2004/A1:2012 E
---------------------- Page: 3 ----------------------
SIST EN 61800-3:2005/A1:2012
EN 61800-3:2004/A1:2012 - 2 -
Foreword
The text of document 22G/227/FDIS, future edition 2 of IEC 61800-3:2004/A1, prepared by SC 22G,
"Adjustable speed electric drive systems incorporating semiconductor power converters", of IEC/TC 22,
"Power electronic systems and equipment" was submitted to the IEC-CENELEC parallel vote and
approved by CENELEC as EN 61800-3:2004/A1:2012.
The following dates are fixed:
(dop) 2012-09-19
• latest date by which the document has
to be implemented at national level by
publication of an identical national
standard or by endorsement
• latest date by which the national (dow) 2014-12-19
standards conflicting with the
document have to be withdrawn
Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. CENELEC [and/or CEN] shall not be held responsible for identifying any or all such patent
rights.
Endorsement notice
The text of the International Standard IEC 61800-3:2004/A1:2011 was approved by CENELEC as a
European Standard without any modification.
In the official version, for Bibliography, the following note has to be added for the standard indicated:
IEC 61400-21:2008 NOTE Harmonized as EN 61400-21:2008 (not modified).
---------------------- Page: 4 ----------------------
SIST EN 61800-3:2005/A1:2012
- 3 - EN 61800-3:2004/A1:2012
Annex ZA
(normative)
Normative references to international publications
with their corresponding European publications
The following documents, in whole or in part, are normatively referenced in this document and are
indispensable for its application. For dated references, only the edition cited applies. For undated
references, the latest edition of the referenced document (including any amendments) applies.
NOTE When an international publication has been modified by common modifications, indicated by (mod), the relevant EN/HD
applies.
Publication Year Title EN/HD Year
Replace:
IEC 61000-2-4 2002 Electromagnetic compatibility (EMC) - EN 61000-2-4 2002
Part 2-4: Environment - Compatibility levels in
industrial plants for low-frequency conducted
disturbances
Add:
IEC 61000-4-11 2004 Electromagnetic compatibility (EMC) - EN 61000-4-11 2004
Part 4-11: Testing and measurement
techniques - Voltage dips, short interruptions
and voltage variations immunity tests
IEC 61000-4-13 2002 Electromagnetic compatibility (EMC) - EN 61000-4-13 2002
Part 4-13: Testing and measurement
techniques - Harmonics and interharmonics
including mains signalling at a.c. power port,
low frequency immunity tests
IEC 61000-4-34 2005 Electromagnetic compatibility (EMC) - EN 61000-4-34 2007
Part 4-34: Testing and measurement
techniques - Voltage dips, short interruptions
and voltage variations immunity tests for
equipment with input current more than 16 A
per phase
---------------------- Page: 5 ----------------------
SIST EN 61800-3:2005/A1:2012
---------------------- Page: 6 ----------------------
SIST EN 61800-3:2005/A1:2012
IEC 61800-3
®
Edition 2.0 2011-11
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE
colour
inside
AMENDMENT 1
AMENDEMENT 1
Adjustable speed electrical power drive systems –
Part 3: EMC requirements and specific test methods
Entraînements électriques de puissance à vitesse variable –
Partie 3: Exigences de CEM et méthodes d'essais spécifiques
INTERNATIONAL
ELECTROTECHNICAL
COMMISSION
COMMISSION
ELECTROTECHNIQUE
INTERNATIONALE PRICE CODE
R
CODE PRIX
ICS 29.200; 33.100 ISBN 978-2-88912-713-9
® Registered trademark of the International Electrotechnical Commission
Marque déposée de la Commission Electrotechnique Internationale
---------------------- Page: 7 ----------------------
SIST EN 61800-3:2005/A1:2012
– 2 – 61800-3 Amend. 1 © IEC:2011
FOREWORD
This Amendment has been prepared by IEC sub-committee 22G: Adjustable speed electric
drive systems incorporating semiconductor power converters, of IEC technical committee 22:
Power electronic systems and equipment.
The text of this amendment is based on the following documents:
FDIS Report on voting
22G/227/FDIS 22G/229/RVD
Full information on the voting for the approval of this amendment can be found in the report
on voting indicated in the above table.
The committee has decided that the contents of this amendment and the base publication will
remain unchanged until the stability date indicated on the IEC web site under
"http://webstore.iec.ch" in the data related to the specific publication. At this date, the
publication will be
• reconfirmed,
• withdrawn,
• replaced by a revised edition, or
• amended.
IMPORTANT – The 'colour inside' logo on the cover page of this publication indicates
that it contains colours which are considered to be useful for the correct
understanding of its contents. Users should therefore print this document using a
colour printer.
_____________
---------------------- Page: 8 ----------------------
SIST EN 61800-3:2005/A1:2012
61800-3 Amend. 1 © IEC:2011 – 3 –
2 Normative references
Replace, in the existing list, the existing reference to IEC 61000-2-4 by the following new
reference:
IEC 61000-2-4:2002, Electromagnetic compatibility (EMC) – Part 2-4: Environment –
Compatibility levels in industrial plants for low-frequency conducted disturbances
Add, to the existing list, the following new references:
IEC 61000-4-11:2004, Electromagnetic compatibility (EMC) – Part 4-11: Testing and
measurement techniques – Voltage dips, short interruptions and voltage variations immunity
tests
IEC 61000-4-13:2002, Electromagnetic compatibility (EMC) – Part 4-13: Testing and
measurement techniques – Harmonics and interharmonics including mains signalling at a.c.
power port, low frequency immunity tests
IEC 61000-4-34:2005, Electromagnetic compatibility (EMC) – Part 4-34: Testing and
measurement techniques – Voltage dips, short interruptions and voltage variations immunity
tests for equipment with input current more than 16 A per phase
3 Terms and definitions
3.1 Overview
Replace the existing title of this subclause by the following new title:
3.1 Definition of the installation and its content
Delete the existing three paragraphs of this subclause.
Add, before the existing Figure 1, the following new sentence:
Figure 1 shows the major parts of the PDS as defined below and the rest of the installation.
Add, after the existing Figure 1, the following new terms and definitions 3.1.1, 3.1.2, 3.1.3 and
3.1.4:
3.1.1
basic drive module
BDM
electronic power converter and related control, connected between an electric supply and a
motor. The BDM is capable of transmitting power from the electric supply to the motor and
may be capable of transmitting power from the motor to the electric supply. The BDM controls
some or all of the following aspects of power transmitted to the motor and motor output:
• current;
• frequency;
• voltage;
• speed;
• torque;
• force;
• position
---------------------- Page: 9 ----------------------
SIST EN 61800-3:2005/A1:2012
– 4 – 61800-3 Amend. 1 © IEC:2011
3.1.2
complete drive module
CDM
drive module consisting of, but not limited to, the BDM and extensions such as protection
devices, transformers and auxiliaries. However the motor and the sensors which are
mechanically coupled to the motor shaft are not included
3.1.3
power drive system
PDS
system consisting of one or more complete drive module(s) (CDM) and a motor or motors.
Any sensors which are mechanically coupled to the motor shaft are also part of the PDS;
however the driven equipment is not included
3.1.4
installation
equipment or equipments which include at least both the PDS and the driven equipment
3.3 Location, ports and interfaces
3.3.5
port for process measurement and control
Delete, in the existing definition, the existing words "as defined in Clause 3 (see Figure 2)".
3.3.9
mechanical link
Delete, in the existing definition, the existing words "as defined in Clause 3".
3.4 Components of PDS
3.4.2
(electric) motor
Add, after the existing definition and source, the following new note:
NOTE For the purposes of this standard, the motor includes all sensors which are mounted on it and which are
relevant for supporting the operating mode and interacting with a CDM.
Delete the existing definition 3.4.3 and renumber the existing definition 3.4.4 as 3.4.3.
Add, after definition 3.4.3, the following new subclause 3.5 and the following new terms and
definitions 3.5.1 to 3.5.4 as follows:
3.5 Phenomena-related definitions
3.5.1
voltage deviation
difference, generally expressed as a percentage, between the voltage at a given instant at a
point in the system, and a reference voltage such as: nominal voltage, a mean value of the
operating voltage, declared supply voltage
[IEV 604-01-17]
---------------------- Page: 10 ----------------------
SIST EN 61800-3:2005/A1:2012
61800-3 Amend. 1 © IEC:2011 – 5 –
3.5.2
voltage change
variation of the r.m.s. or peak value of a voltage between two consecutive levels sustained for
definite but unspecified durations
NOTE Whether the r.m.s. or peak value is chosen depends upon the application, and which is used should be
specified.
[IEV 161-08-01]
3.5.3
voltage fluctuation
series of voltage changes or a continuous variation of the r.m.s. or peak value of the voltage
NOTE Whether the r.m.s. or peak value is chosen depends upon the application, and which is used should be
specified.
[IEV 161-08-05]
3.5.4
voltage dip
sudden reduction of the voltage at a point in an electrical system followed by voltage recovery
after a short period of time from a few cycles to a few seconds
[IEV 604-01-25, IEV 161-08-10]
4.2.1 Conditions
Renumber the existing note of this subclause as Note 1.
Replace the existing third paragraph of this subclause by the following new paragraph and
new Note 2:
For the tests, the CDM shall be connected to a motor recommended by the manufacturer with
a cable and earthing rules defined by the manufacturer. Alternatively, a passive test load
(resistive, or resistive and inductive) may be applied (for example, for evaluation of the low-
frequency emissions), if permitted by the manufacturer.
NOTE 2 For high frequency emissions, because it is necessary to simulate differential and common mode
capacitances and couplings, a passive test load may not be suitable for this application.
4.3 Documentation for the user
Replace the existing second paragraph of this subclause by the following new paragraph and
new Notes 1 and 2:
The manufacturer shall supply the documentation necessary for the correct installation of a
BDM, CDM or PDS into a typical system or process in the intended environment. This
information includes any emission warnings required by 6.1 and Table 13. It also includes the
warnings required by 5.3.2 in the case where the immunity of a BDM, CDM or PDS is not
suitable for the second environment.
NOTE 1 From the emission point of view, a PDS (or BDM or CDM) with a lower emission category, such as C1,
can always be used instead of one with a higher emission category, such as C3.
NOTE 2 Emission categories are independent of immunity. For example, a statement that a PDS has emission
category C1 does not imply that the immunity is only suitable for the first environment.
---------------------- Page: 11 ----------------------
SIST EN 61800-3:2005/A1:2012
– 6 – 61800-3 Amend. 1 © IEC:2011
5.1 General conditions
5.1.1 Acceptance criteria (performance criteria)
Add, after the last existing paragraph, the following new paragraph:
Subclauses 5.2 and 5.3 state the acceptance criterion required for each phenomenon.
5.2 Basic immunity requirements – low-frequency disturbances
5.2.1 Common principle
Delete the existing Note 3.
5.2.2.1 Low voltage PDSs – (voltage distortion)
Replace the existing paragraph, note and Table 2 of this subclause, by the following new
paragraph, new note and new Tables 23, 24 and 25:
The BDM, CDM or PDS shall sustain the immunity levels while meeting the performance
criteria given in Tables 23, 24 and 25. It shall be verified that these levels will not cause the
ratings for the input circuits (filters, etc.) to be exceeded. Analysis of commutation notches
shall be in the time domain. The manufacturer may verify immunity by calculation, simulation,
or test, according to 5.2.1. If the chosen verification method is by test, it shall be performed
using the PDS with the motor connected. For equipment rated below 16 A per phase, the test
method of IEC 61000-4-13 can be applied.
NOTE Frequency domain analysis of the contribution from notches to the total harmonic distortion will not fully
account for harmful effects, see B.1.
Table 23 – Minimum immunity requirements for total harmonic distortion
on power ports of low voltage PDSs
Phenomenon First environment Second environment Performance
(acceptance)
Reference Level Reference Level criterion
document document
Harmonics – IEC 61000-2-2 8 % IEC 61000-2-4 12 % A
class 3
THD
---------------------- Page: 12 ----------------------
SIST EN 61800-3:2005/A1:2012
61800-3 Amend. 1 © IEC:2011 – 7 –
Table 24 – Minimum immunity requirements for individual harmonic orders
on power ports of low voltage PDSs
Phenomenon First environment Second environment Performance
(acceptance)
Harmonic Reference Level Reference Level criterion
order document document
2 IEC 61000-4-13 3 % IEC 61000-4-13 5 % A
class 2 class 3
3 8 % 9 %
4 1,5 % 2 %
5 9 % 12 %
Even orders No requirement 1,5 %
6 ≤ h ≤ 50
7 7,5 % 10 %
9 2,5 % 4 %
11 5 % 7 %
13 4,5 % 7 %
15 No requirement 3 %
17 3 % 6 %
19 2 % 6 %
21 No requirement 2 %
23 2 % 6 %
25 2 % 6 %
27 No requirement 2 %
29 1,5 % 5 %
31 1,5 % 3 %
33 No requirement 2 %
35 1,5 % 3 %
37 1,5 % 3 %
39 No requirement 2 %
NOTE 1 For individual harmonic orders, levels are from Class 2 in IEC 61000-4-13 (these are approximately
1,5 times the compatibility levels of IEC 61000-2-4).
NOTE 2 For individual harmonic orders, levels are from Class 3 in IEC 61000-4-13 (these are approximately
1,5 times the compatibility levels of IEC 61000-2-4).
Table 25 – Minimum immunity requirements for commutation notches
on power ports of low voltage PDSs
Phenomenon First environment Second environment Performance
(acceptance)
Reference Level Reference Level criterion
document document
Commutation (None) No requirement IEC 60146-1-1 Depth = 40 %, A
notches Class B total area = 250
in % degrees
---------------------- Page: 13 ----------------------
SIST EN 61800-3:2005/A1:2012
– 8 – 61800-3 Amend. 1 © IEC:2011
Table 3 – Minimum immunity requirements for harmonics and commutation
notches/voltage distortion on main power ports of PDSs of rated voltage above 1 000 V
a b c a
Delete, the existing table footnotes " " and " ", and renumber existing footnote " " as " ".
Delete the entire two rows starting with "Interhamonics steady state", and "Interharmonics
short term (< 15 s)".
5.2.2.2.2 Auxiliary power port
Replace the existing first sentence of the subclause by the following new sentence:
The auxiliary power ports of PDSs shall sustain the immunity levels for the second
environment given in Tables 23, 24 and 25 while meeting the performance criteria in those
tables.
Delete the existing Table 4 of this subclause.
5.2.3 Voltage deviations (variations, changes, fluctuations), dips and short interruptions
Delete, in the existing title of this subclause, the words "(variations, changes, fluctuations)".
---------------------- Page: 14 ----------------------
SIST EN 61800-3:2005/A1:2012
61800-3 Amend. 1 © IEC:2011 – 9 –
Table 5 – Minimum immunity requirements for voltage deviations, dips and short
interruptions on power ports of low voltage PDSs
Replace the existing Table 5 by the following new Table 5:
Table 5 – Minimum immunity requirements for voltage deviations, dips
and short interruptions on power ports of low voltage PDSs
Phenomenon First environment Second environment Performance
(acceptance)
Reference Level Reference Level
criterion
document document
b
a a
Voltage IEC 61000-2-2 IEC 61000-2-4 A
± 10 % ± 1
...
Questions, Comments and Discussion