Leak detection systems - Part 7: Requirements and test/assessment methods for interstitial spaces, leak detection linings and leak detection jackets

This standard gives requirements and the corresponding test/assessment methods applicable to leak detection lining kits and leak detection jacket kits. Leak detection lining kits and leak detection jackets kits intended to be used as post-installed to create an interstitial space or leakage containment in single skin underground or above ground, non-pressurized, tanks designed for water polluting liquids. The kit has to be used only in conjunction with leak detection kits covered by prEN 13160-2 to prEN 13160-4.

Leckanzeigesysteme - Teil 7: Anforderungen und Prüf-/Bewertungsverfahren für Überwachungsräume, Leckschutzauskleidungen und Leckschutzummantelungen

Diese Norm legt Anforderungen an Leckschutzauskleidungen und Leckschutzummantelungen und die ent-sprechenden Prüf-/Bewertungsverfahren fest. Leckschutzauskleidungen und Leckschutzummantelungen sind für den Einsatz nach Installation zur Schaffung eines Überwachungsraums oder eines Leckageraumes in einwandigen, unterirdischen oder oberirdischen, nicht druckbeaufschlagten Tanks vorgesehen, die für wassergefährdende Flüssigkeiten ausgelegt sind. Das System ist ausschließlich in Verbindung mit den von prEN 13160 2 bis prEN 13160 4 abgedeckten Leckanzeigern zu verwenden.

Systèmes de détection de fuites - Partie 7: Exigences et méthodes d'essai/d'évaluation pour les espaces interstitiels, les détecteurs de fuite des revêtements et les détecteurs de fuite d'enveloppes

La présente Norme spécifie les exigences et les méthodes d'essai/d'évaluation correspondantes applicables aux kits de revêtements intérieurs et aux kits de revêtements extérieurs protecteurs de fuites. Les kits de revêtements intérieurs et les kits de revêtements extérieurs protecteurs de fuites, destinés à être utilisés après installation pour créer un espace interstitiel ou un espace de confinement des fuites dans des réservoirs à simple paroi, aériens ou souterrains, sans pression, conçus pour des liquides polluant l'eau. Le kit est destiné à être utilisé conjointement aux kits de détection de fuites couverts par les prEN 13160-2 à prEN 13160-4.

Sistemi za kontrolo tesnosti - 7. del: Zahteve in metode za preskušanje in ocenjevanje vmesnih prostorov, zunanjih oblog in plaščev za zaznavanje netesnosti

Ta standard določa zahteve ter ustrezne metode za preskušanje in ocenjevanje, ki se uporabljajo za komplete zunanjih oblog in komplete plaščev za zaznavanje netesnosti. Kompleti zunanjih oblog in kompleti plaščev za zaznavanje netesnosti so namenjeni za naknadno vgradnjo za ustvarjanje vmesnih prostorov ali zadrževalnikov pri dvoplaščnih, podzemnih ali nadzemnih rezervoarjih, ki so ali niso pod tlakom, in so zasnovani za tekočine, ki onesnažujejo vodo. Komplet se lahko uporablja samo skupaj s kompleti za kontrolo tesnosti, ki jih zajemajo standardi od prEN 13160-2 do prEN 13160-4.

General Information

Status
Published
Public Enquiry End Date
04-Dec-2014
Publication Date
11-Oct-2016
Technical Committee
Current Stage
6060 - National Implementation/Publication (Adopted Project)
Start Date
07-Oct-2016
Due Date
12-Dec-2016
Completion Date
12-Oct-2016

Relations

Buy Standard

Standard
EN 13160-7:2016
English language
51 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.YDQMHQHWHVQRVWLLeckanzeigesysteme - Teil 7: Anforderungen und Prüf-/Bewertungsverfahren für Überwachungsräume, Leckschutzauskleidungen und LeckschutzummantelungenSystèmes de détection de fuites - Partie 7: Exigences et méthodes d'essai/d'évaluation pour les espaces interstitiels, les détecteurs de fuite des revêtements et les détecteurs de fuite d'enveloppesLeak detection systems - Part 7: Requirements and test/assessment methods for interstitial spaces, leak detection linings and leak detection jackets23.020.01Fluid storage devices in generalICS:Ta slovenski standard je istoveten z:EN 13160-7:2016SIST EN 13160-7:2016en,fr,de01-november-2016SIST EN 13160-7:2016SLOVENSKI
STANDARDSIST EN 13160-7:20031DGRPHãþD



SIST EN 13160-7:2016



EUROPEAN STANDARD NORME EUROPÉENNE EUROPÄISCHE NORM
EN 13160-7
July
t r s x ICS
t uä r t rä r sâ
t uä r v rä { {â
t {ä t x rä t r Supersedes EN
s u s x ræ yã t r r uEnglish Version
Leak detection systems æ Part
yã Requirements and detection linings and leak detection jackets Systèmes de détection de fuites æ Partie
yã Exigences et interstitielsá les détecteurs de fuite des revêtements et les détecteurs de fuite d 5enveloppes
Leckanzeigesysteme æ Teil
yã Anforderungen und PrüfæLeckschutzauskleidungen und Leckschutzummantelungen This European Standard was approved by CEN on
z April
t r s xä
egulations which stipulate the conditions for giving this European Standard the status of a national standard without any alterationä Upætoædate lists and bibliographical references concerning such national standards may be obtained on application to the CENæCENELEC Management Centre or to any CEN memberä
translation under the responsibility of a CEN member into its own language and notified to the CENæCENELEC Management Centre has the same status as the official versionsä
CEN members are the national standards bodies of Austriaá Belgiumá Bulgariaá Croatiaá Cyprusá Czech Republicá Denmarká Estoniaá Finlandá Former Yugoslav Republic of Macedoniaá Franceá Germanyá Greeceá Hungaryá Icelandá Irelandá Italyá Latviaá Lithuaniaá Luxembourgá Maltaá Netherlandsá Norwayá Polandá Portugalá Romaniaá Slovakiaá Sloveniaá Spainá Swedená Switzerlandá Turkey andUnited Kingdomä
EUROPEAN COMMITTEE FOR STANDARDIZATION COMITÉ EUROPÉEN DE NORMALISATION EUROPÄISCHES KOMITEE FÜR NORMUNG
CEN-CENELEC Management Centre:
Avenue Marnix 17,
B-1000 Brussels
9
t r s x CEN All rights of exploitation in any form and by any means reserved worldwide for CEN national Membersä Refä Noä EN
s u s x ræ yã t r s x ESIST EN 13160-7:2016



EN 13160-7:2016 (E) 2
Contents Page European foreword . 4 1 Scope . 6 2 Normative references . 6 3 Terms and definitions . 7 4 Requirements . 7 4.1 Effectiveness of leak detection lining kits and leak detection jacket kits . 7 4.1.1 Tightness against liquid and vapour. 7 4.1.2 Permeability of leak detection linings and leak detection jackets . 7 4.1.3 Free passage of liquid in the interstitial space . 8 4.1.4 Free passage of air . 8 4.1.5 Flow resistance after impact of stored media . 8 4.1.6 Mechanical resistance against the imposed load by the stored medium . 8 4.1.7 Chemical resistance . 15 4.2 Durability of effectiveness . 15 4.2.1 Durability against temperature . 15 4.2.2 Durability against chemical attack . 15 4.2.3 Durability against mechanical load . 15 5 Testing, assessment and sampling methods . 15 5.1 Effectiveness of leak detection lining kits and leak detection jacket kits . 15 5.1.1 Tightness against liquid and gas . 15 5.1.2 Permeability . 17 5.1.3 Free passage of liquid in the interstitial space . 18 5.1.4 Free passage of air . 19 5.1.5 Flow resistance after impact of stored media . 22 5.1.6 Mechanical resistance against the imposed load by the stored medium . 25 5.1.7 Chemical resistance . 25 5.2 Durability of effectiveness . 25 5.2.1 Durability against temperature . 25 5.2.2 Durability against chemical attack . 25 5.2.3 Durability against mechanical load . 25 6 Assessment and verification of constancy of performance – AVCP . 27 6.1 General. 27 6.2 Type testing . 28 6.2.1 General. 28 6.2.2 Test samples, testing and compliance criteria . 29 6.2.3 Test reports . 29 6.2.4 Shared other party results . 29 6.2.5 Cascading determination of the product type results . 30 6.3 Factory production control (FPC) . 31 6.3.1 General. 31 6.3.2 Requirements . 32 6.3.3 Product specific requirements. 34 6.3.4 Procedure for modifications . 35 SIST EN 13160-7:2016



EN 13160-7:2016 (E) 3
6.3.5 One-off products, pre-production products (e.g. prototypes) and products produced in very low quantity . 35 7 Marking, labelling and packaging . 36 8 Environmental aspects . 37 Annex A (normative)
Determination of the interstitial space volume for class I-systems . 38 A.1 Test equipment. 38 A.2 Preparation . 38 A.3 Procedure . 39 A.4 Evaluation. 41 Annex B (informative)
Environmental aspects . 42 Annex ZA (informative)
Clauses of this European Standard addressing the provisions of the EU Construction Products Regulation 305/2011/EU . 44 ZA.1 Scope and relevant characteristics . 44 ZA.2 Procedure for AVCP of leak detection linings and leak detection jackets . 45 ZA.2.1 System(s) of AVCP. 45 ZA.2.2 Declaration of performance (DoP) . 46 ZA.2.2.1 General . 46 ZA.2.2.2 Content . 47 ZA.2.2.3 Example of DoP . 47 ZA.3 CE marking and labelling . 49
SIST EN 13160-7:2016



EN 13160-7:2016 (E) 4
European foreword This document (EN 13160-7:2016) has been prepared by Technical Committee CEN/TC 393 “Equipment for storage tanks and for filling stations”, the secretariat of which is held by DIN. This European Standard shall be given the status of a national standard, either by publication of an identical text or by endorsement, at the latest by December 2016, and conflicting national standards shall be withdrawn at the latest by March 2018. Attention is drawn to the possibility that some of the elements of this document may be the subject of patent rights. CEN [and/or CENELEC] shall not be held responsible for identifying any or all such patent rights. This document supersedes EN 13160-7:2003. This document has been prepared under a mandate given to CEN by the European Commission and the European Free Trade Association, and supports essential requirements of EU Directive(s). For relationship with EU Directive(s), see informative Annex ZA, which is an integral part of this document. According to edition 2003 the following fundamental changes are given: — requirements and tests for permeation added; — material properties revised; —
requirements from EN 13160-1:2003 included, which are no longer contained in EN 13160-1:2016. This European Standard Leak detection systems consists of 7 parts: — Part 1: General principles — Part 2: Requirements and test/assessment methods for pressure and vacuum systems — Part 3: Requirements and test/assessment methods for liquid systems for tanks — Part 4: Requirements and test/assessment methods for sensor based leak detection systems — Part 5: Requirements and test/assessment methods for in-tank gauge systems and pressurized pipework systems — Part 6: Sensors in monitoring wells — Part 7: Requirements and test/assessment methods for interstitial spaces, leak detection linings and leak detection jackets According to the CEN/CENELEC Internal Regulations, the national standards organizations of the following countries are bound to implement this European Standard: Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, SIST EN 13160-7:2016



EN 13160-7:2016 (E) 5
Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and the United Kingdom. SIST EN 13160-7:2016



EN 13160-7:2016 (E) 6
1 Scope This European Standard gives requirements and the corresponding test/assessment methods applicable to leak detection lining kits and leak detection jacket kits. Leak detection lining kits and leak detection jackets kits intended to be used to create an interstitial space or leakage containment in single skin underground or above ground, non-pressurized, tanks designed for water polluting liquids. The kit has to be used only in conjunction with leak detection kits covered by EN 13160-2 to EN 13160-4. 2 Normative references The following documents, in whole or in part, are normatively referenced in this document and are indispensable for its application. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. EN 228, Automotive fuels — Unleaded petrol — Requirements and test methods EN 495–5, Flexible sheets for waterproofing — Determination of foldability at low temperature — Part 5: Plastic and rubber sheets for roof waterproofing EN 1107-2, Flexible sheets for waterproofing — Determination of dimensional stability — Part 2: Plastic and rubber sheets for roof waterproofing EN 1849-2, Flexible sheets for waterproofing — Determination of thickness and mass per unit area — Part 2: Plastic and rubber sheets EN 10300:2005, Steel tubes and fittings for onshore and offshore pipelines — Bituminous hot applied materials for external coating EN 13121-1, GRP tanks and vessels for use above ground — Part 1: Raw materials — Specification conditions and acceptance conditions EN 13121-2:2003, GRP tanks and vessels for use above ground — Part 2: Composite materials — Chemical resistance EN 13160-1:2016, Leak detection systems — Part 1: General principles EN 13160-2:2016, Leak detection systems — Part 2: Requirements and test/assessment methods for pressure and vacuum systems EN 13160-3:2016, Leak detection systems — Part 3: Requirements and test/assessment methods for liquid systems for tanks EN 13160-4:2016, Leak detection systems — Part 4: Requirements and test/assessment methods for sensor based leak detection systems EN 14879-4:2007, Organic coating systems and linings for protection of industrial apparatus and plants against corrosion caused by aggressive media — Part 4: Linings on metallic components EN ISO 62, Plastics — Determination of water absorption (ISO 62) EN ISO 75-1, Plastics — Determination of temperature of deflection under load — Part 1: General test method (ISO 75-1) SIST EN 13160-7:2016



EN 13160-7:2016 (E) 7
EN ISO 75-2, Plastics — Determination of temperature of deflection under load — Part 2: Plastics and ebonite (ISO 75-2) EN ISO 75-3, Plastics — Determination of temperature of deflection under load — Part 3: High-strength thermosetting laminates and long-fibre-reinforced plastics (ISO 75-3) EN ISO 175, Plastics — Methods of test for the determination of the effects of immersion in liquid chemicals (ISO 175) EN ISO 178, Plastics — Determination of flexural properties (ISO 178) EN ISO 179-1, Plastics — Determination of Charpy impact properties — Part 1: Non-instrumented impact test (ISO 179-1) EN ISO 179-2, Plastics — Determination of Charpy impact properties — Part 2: Instrumented impact test (ISO 179-2) EN ISO 527-1, Plastics — Determination of tensile properties — Part 1: General principles (ISO 527-1) EN ISO 527-3, Plastics — Determination of tensile properties — Part 3: Test conditions for films and sheets (ISO 527-3) EN ISO 604, Plastics — Determination of compressive properties (ISO 604) EN ISO 1183-1, Plastics — Methods for determining the density of non-cellular plastics — Part 1: Immersion method, liquid pyknometer method and titration method (ISO 1183-1) EN ISO 24345, Resilient floor coverings — Determination of peel resistance (ISO 24345) ISO 2528, Sheet materials — Determination of water vapour transmission rate — Gravimetric (dish) method ISO 6133, Rubber and plastics — Analysis of multi-peak traces obtained in determinations of tear strength and adhesion strength 3 Terms and definitions For the purposes of this document, the terms and definitions given in EN 13160-1:2016 apply. 4 Requirements 4.1 Effectiveness of leak detection lining kits and leak detection jacket kits 4.1.1 Tightness against liquid and vapour The integrity of the leak detection linings and leak detection jackets shall be maintained under all operating pressures. 4.1.2 Permeability of leak detection linings and leak detection jackets The permeation shall be according to Table 1 and Table 2. No condensation of vapour of the stored product in the interstitial space should occur. SIST EN 13160-7:2016



EN 13160-7:2016 (E) 8
Table 1 — Permeation of leak detection linings Property Required value Passage of stored products at installation of the leak protecting lining in metal tanks with a passage of stored product of 0 g/m2 „ d max 100 g/m2 „ day Passage of stored products at installation of the leak protecting lining in tanks with a passage of stored product > 0 g/m2 „ d max 0,1 g/m2 „ day
Passage of deionized water max 4 g/m2 „ day NOTE By permeation rates > 0 g/m2 „ d the exhaust line of the leak detector should be connected to the vapour space of the stored tank. Table 2 — Permeation of leak detection jackets Property Required value Passage of stored product max 2 g/m2 „ day Passage of deionized water max 4 g/m2 „ day 4.1.3 Free passage of liquid in the interstitial space The quantity of liquid, calculated according to EN 13160–2:2016, Formula (4) and the specific volume Vsp according to Annex A shall enter the interstitial space by a vacuum change from (60 ± 5) kPa (pPA) to (30 ± 5) kPa (pPE). Additional for leak detection systems class II according to EN 13160-3 the flow rate at the test nozzles shall be > 0,5 l/min. 4.1.4 Free passage of air 4.1.4.1 Free passage of air through intermediate layer The back pressure of the intermediate layer shall not be higher than 1 kPa at a volume flow of (85 ± 5) l/h of air. 4.1.4.2 Free passage of air through double skin tanks and pipes An opening of the interstitial space shall result in a pressure change in the interstitial space. 4.1.5 Flow resistance after impact of stored media The flow resistance shall not exceed the value of 1 kPa at an air volume flow of (85 ± 5) l/h. 4.1.6 Mechanical resistance against the imposed load by the stored medium 4.1.6.1 Influence of the mechanical resistance to the free passage in the interstitial space The flow resistance of the intermediate layer shall not be higher than 1 kPa at a volume flow of (85 ± 5) l/h of air under load. 4.1.6.2 Mechanical properties Mechanical properties for polyvinylchloride (PVC) shall be according to Table 3. SIST EN 13160-7:2016



EN 13160-7:2016 (E) 9
Table 3 — Mechanical properties for polyvinylchloride (PVC) No. Property Test method Dimension Required value 1 Tensile strength, Lengthwise and across EN ISO 527-1 and EN ISO 527-3; Test speed: 200 mm/min ± 10 % Specimen: Type 2 N/mm
· 15 2 Tensile elongation, Lengthwise and across EN ISO 527-1 and EN ISO 527-3; Test speed: 200 mm/min ± 10 % Specimen: Type 2 % > 200 3 Reaction of joint to shear test EN ISO 527-1 and EN ISO 527-3; Test speed: 200 mm/min ± 10 % Specimen: Type 2 — Off-joint fracture, joint factor
· 0,65 4 Adhesion of multilayered sheet material In conformity with EN ISO 24345, ISO 6133, EN ISO 527-1 and EN ISO 527-3; Test speed: 100 mm/min ± 10 % Specimen: Type 2 N/mm
· 2,0 5 Variation in dimension in either direction after storage at 80 °C EN 1107–2; in a hot cabinet 2 h in air of (80 ± 2) °C and then 30 min at normal climate on a cover, which shall not affect the dimensions %
¶ 2,0 6 Reaction in either direction to folding at a temperature of
« t r °C EN 495–5 — No fissures may occur on either top or bottom surface 7 Thickness EN 1849–2 %
Middle deviation ± 10 Deviation of single value
¶ 12 8 Density EN ISO 1183-1 % Middle deviation ± 2 Effects of test media for polyvinylchloride (PVC) shall be according to Table 4. SIST EN 13160-7:2016



EN 13160-7:2016 (E) 10
Table 4 — Effects of test media for polyvinylchloride (PVC) Property Test method Dimension Required value Change of mass after storage in deionized water and stored product or test liquids according to Annex C of EN 14879–4:2007 In conformity with EN ISO 62 at normal climate, change shall be determined after the following storage periods: 3, 14 and 56 d %
¶ 15 Change of tensile strength and elongation, in either direction after storage in deionized water and stored product (56 d at 23 °C) or test liquids according to Annex C of EN 14879–4:2007 EN ISO 527-1 and EN ISO 527-3 Test speed: 200 mm/min ± 10 % Specimen: Type 2 %
¶ 25 for tensile elongation the measured value as per Table 3 Change of tensile strength and elongation, in either direction after storage in of folded materials in deionized water and stored product
(56 d at 23 °C) or test liquids according to Annex C of EN 14879–4:2007 EN ISO 527-1 and EN ISO 527-3 Test speed: 200 mm/min ± 10 % Specimen: Type 2 %
¶ 25 Change of reaction of the joint to shear test after storage in deionized water and stored product (56 d at 23 °C) or test liquids according to Annex C of EN 14879–4:2007 EN ISO 527-1 and EN ISO 527-3 Test speed: 200 mm/min ± 10 % Specimen: Type 2 — Off-joint fracture Mechanical properties for thermoplastic and thermoplastic elastomers except polyvinylchloride (PVC) shall be according to Table 5. SIST EN 13160-7:2016



EN 13160-7:2016 (E) 11
Table 5 — Mechanical properties for thermoplastic and thermoplastic elastomers except polyvinylchloride (PVC) No. Property Test method Dimension Required value 1 Tensile strength, Lengthwise and across EN ISO 527-1 and EN ISO 527-3; Test speed: 200 mm/min ± 10 % Specimen: Type 2 N/mm
· 15 2 Tensile elongation, Lengthwise and across EN ISO 527-1 and EN ISO 527-3; Test speed: 200 mm/min ± 10 % Specimen: Type 2 % > 200 3 Reaction of joint to shear test EN ISO 527-1 and EN ISO 527-3; Test speed: 200 mm/min ± 10 % Specimen: Type 2 — Off-joint
fracture, joint factor
· 0,5 4 Adhesion of multilayered sheet material In conformity with EN ISO 24345, ISO 6133, EN ISO 527-1 and EN ISO 527-3; Test speed: 100 mm/min ± 10 % Specimen: Type 2 N/mm
· 1,0 5 Variation in dimension in either direction after storage at 80 °C EN 1107–2; in a hot cabinet 2 h in air of (80 ± 2) °C and then 30 min at normal climate on a cover, which shall not affect the dimensions %
¶ 10 6 Reaction in either direction to folding at a temperature of
« t r °C EN 495–5 — No fissures may occur on either top or bottom surface 7 thickness EN 1849–2 %
Middle deviation ± 10 8 density EN ISO 1183-1 % Middle deviation ± 10 % Effects of test media for thermoplastic and thermoplastic elastomers except polyvinylchloride (PVC) shall be according to Table 6. SIST EN 13160-7:2016



EN 13160-7:2016 (E) 12
Table 6 — Effects of test media for thermoplastic and thermoplastic elastomers except polyvinylchloride (PVC) Property Test method Dimension Required value Change of mass after storage in deionized water and stored product or test liquids according to Annex C of EN 14879–4:2007 In conformity with EN ISO 62 at normal climate, change shall be determined after the following storage periods: 3 d, 14 d and 56 d %
¶ 20 Change of tensile strength and elongation, in either direction after storage in deionized water and stored product (56 d at 23 °C) or test liquids according to Annex C of EN 14879–4:2007 EN ISO 527-1 and EN ISO 527-3 Test speed: 200 mm/min ± 10 % Specimen: Type 2 %
¶ 50 Change of tensile strength and elongation, in either direction after storage in of folded materials in deionized water and stored product
(56 d at 23 °C) or test liquids according to Annex C of EN 14879–4:2007 EN ISO 527-1 and EN ISO 527-3 Test speed: 200 mm/min ± 10 % Specimen: Type 2 %
¶ 60 for tensile elongation the measured value as per Table 5 Change of reaction of the joint to shear test after storage in deionized water and stored product (56 d at 23 °C) or test liquids according to Annex C of EN 14879–4:2007 EN ISO 527-1 and EN ISO 527-3 Test speed: 200 mm/min ± 10 % Specimen: Type 2 — Off-joint fracture Requirements for inner layer of leak detection linings and outer layer of leak detection jackets with epoxide resin (EP) or unsaturated polyester resin (UP) moulding materials shall be according to Table 7. The inner layer by leak detection linings/outer layer by leak detection jacket of original height without spacer shall be used for testing. SIST EN 13160-7:2016



EN 13160-7:2016 (E) 13
Table 7 — Requirements for inner layer of leak detection linings and outer layer of leak detection jackets with epoxide resin (EP) or unsaturated polyester resin (UP) moulding materials Property Dimension Test method Sample Mean value of property dimension mm number Flexural strength MPa EN ISO 178 EN ISO 178 5
· 80 Impact strength kJ/m2 EN ISO 179-1 and EN ISO 179-2 EN ISO 179-1 5
· 5 Dimensional stability under heat °C EN ISO 75-1 EN ISO 75-2 EN ISO 75-3 EN ISO 75-2 EN ISO 75-3 3
· 50 Change in weight after 28 days storage — distilled water at (20 ± 5) °C — stored product at (20 ± 5) °C or test liquids according to Annex C of EN 14879–4:2007 %
EN ISO 175 The sample shall be wiped dry and weighed immediately after the storage.
EN ISO 175 Cut surfaces shall be sealed.
3 3
+4
« t
Change of flexural strength after 28 days storage — distilled water at (20 ± 5) °C — stored product at (20 ± 5) °C or test liquids according to Annex C of EN 14879–4:2007 %
EN ISO 178
EN ISO 178 Cut surfaces shall be sealed.
5 5

« u r The mean values of the flexural strength and of the impact strength shall fulfil the requirements of Table 7. The single value of the flexural strength may be up to 15 % and the single value of the impact strength may be up to 30 % under the values of Table 7. The single value of the other properties shall fulfil the requirements of Table 7. Requirements for intermediate layer of resin and spacer of leak detection linings and of leak detection jackets according to Figure 1 shall be according to Table 8. SIST EN 13160-7:2016



EN 13160-7:2016 (E) 14
Table 8 — Requirements for intermediate layer of resin and spacer of leak detection linings and of leak detection jackets Property Dimension Test method sample Values of property dimension
mm number Compression strength at condition at time of supply N/mm2 EN ISO 604 length and width according to EN ISO 604 height: sampling height 5
· 1,0 (no break) for tanks with a height or diameter of
¶ 3 m
· 3,0 (no break) for tanks with a height or diameter of > 3 m
Change of compression strength after 112 days storage at ambient temperature in water and stored product or test liquids according to Annex C of EN 14879–4:2007 % EN ISO 604 length and width according to EN ISO 604 height: sampling height Cut surfaces shall be sealed. 5
· 0,6 (no break) for tanks with a height or diameter of
¶ 3 m
· 1,8 (no break) for tanks with a height or diameter of > 3 m The construction of leak detection linings and leak detection jackets can be according to Figure 1.
a)
b)
c) NOTE Before installation of the leak detection lining/leak detection jacket the tank wall may be coated according to EN 14879-4. Key 1 inner layer by leak detection linings/outer layer by leak detection jackets 2 intermediate layer 3 tank w
...

Questions, Comments and Discussion