High-voltage switchgear and controlgear - Part 102: Alternating current disconnectors and earthing switches

The contents of the corrigendum of January 2012 have been included in this copy.

Hochspannungs-Schaltgeräte und -Schaltanlagen - Teil 102: Wechselstrom-Trennschalter und -Erdungsschalter

Appareillage à haute tension - Partie 102: Sectionneurs et sectionneurs de terre à courant alternatif

Le contenu du corrigendum de janvier 2012 a été pris en considération dans cet exemplaire.

Visokonapetostne stikalne in krmilne naprave - 102. del: Ločilna stikala za izmenični tok in ozemljitvena stikala (IEC 62271-102:2001/A1:2011)

Uporablja se za ločilna stikala za izmenični tok in ozemljitvena stikala za notranje in zunanje zaprte in odprte inštalacije priključkov za napetosti nad 1000 V in storitvene frekvence do in vključno s 60 Hz. Prav tako se uporablja za krmilne naprave teh ločilnih in ozemljitvenih stikal ter njihovo dodatno opremo.

General Information

Status
Withdrawn
Publication Date
06-Oct-2011
Current Stage
6060 - Document made available
Completion Date
07-Oct-2011

RELATIONS

Buy Standard

Amendment
EN 62271-102:2002/A1:2011
English language
15 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (sample)

SLOVENSKI STANDARD
SIST EN 62271-102:2002/A1:2011
01-november-2011
9LVRNRQDSHWRVWQHVWLNDOQHLQNUPLOQHQDSUDYHGHO/RþLOQDVWLNDOD]D
L]PHQLþQLWRNLQR]HPOMLWYHQDVWLNDOD ,(&$

High-voltage switchgear and controlgear - Part 102: Alternating current disconnectors

and earthing switches (IEC 62271-102:2001/A1:2011)
Hochspannungs-Schaltgeräte und -Schaltanlagen - Teil 102: Wechselstrom-
Trennschalter und -Erdungsschalter (IEC 62271-102:2001/A1:2011)

Appareillage à haute tension - Partie 102: Sectionneurs et sectionneurs de terre à

courant alternatif (CEI 62271-102:2001/A1:2011)
Ta slovenski standard je istoveten z: EN 62271-102:2002/A1:2011
ICS:
29.130.10 Visokonapetostne stikalne in High voltage switchgear and
krmilne naprave controlgear
SIST EN 62271-102:2002/A1:2011 en

2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

---------------------- Page: 1 ----------------------
SIST EN 62271-102:2002/A1:2011
---------------------- Page: 2 ----------------------
SIST EN 62271-102:2002/A1:2011
EUROPEAN STANDARD
EN 62271-102/A1
NORME EUROPÉENNE
October 2011
EUROPÄISCHE NORM
ICS 29.130.10; 29.130.99
English version
High-voltage switchgear and controlgear -
Part 102: Alternating current disconnectors and earthing switches
(IEC 62271-102:2001/A1:2011)
Appareillage à haute tension - Hochspannungs-Schaltgeräte und -
Partie 102: Sectionneurs et sectionneurs Schaltanlagen -
de terre à courant alternatif Teil 102: Wechselstrom-Trennschalter und
(CEI 62271-102:2001/A1:2011) -Erdungsschalter
(IEC 62271-102:2001/A1:2011)

This amendment A1 modifies the European Standard EN 62271-102:2002; it was approved by CENELEC on

2011-09-23. CENELEC members are bound to comply with the CEN/CENELEC Internal Regulations which

stipulate the conditions for giving this amendment the status of a national standard without any alteration.

Up-to-date lists and bibliographical references concerning such national standards may be obtained on

application to the CEN-CENELEC Management Centre or to any CENELEC member.

This amendment exists in three official versions (English, French, German). A version in any other language

made by translation under the responsibility of a CENELEC member into its own language and notified to the

CEN-CENELEC Management Centre has the same status as the official versions.

CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus,

the Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy,

Latvia, Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia,

Spain, Sweden, Switzerland and the United Kingdom.
CENELEC
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung
Management Centre: Avenue Marnix 17, B - 1000 Brussels

© 2011 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members.

Ref. No. EN 62271-102:2002/A1:2011 E
---------------------- Page: 3 ----------------------
SIST EN 62271-102:2002/A1:2011
EN 62271-102:2002/A1:2011 - 2 -
Foreword

The text of document 17A/972/FDIS, future edition 1 of IEC 62271-102:2001/A1, prepared by SC 17A,

"High-voltage switchgear and controlgear", of IEC TC 17, "Switchgear and controlgear" was submitted to

the IEC-CENELEC parallel vote and approved by CENELEC as EN 62271-102:2002/A1:2011.

The following dates are fixed:
(dop) 2012-06-23
• latest date by which the document has
to be implemented at national level by
publication of an identical national
standard or by endorsement
(dow) 2014-09-23
• latest date by which the national
standards conflicting with the
document have to be withdrawn

This standard is to be read in conjunction with EN 62271-1:2008, to which it refers and which is

applicable unless otherwise specified in this standard. In order to simplify the indication of corresponding

requirements, the same numbering of clauses and subclauses is used as in EN 62271-1. Amendments to

these clauses and subclauses are given under the same references whilst additional subclauses are

numbered from 101.

Attention is drawn to the possibility that some of the elements of this document may be the subject of

patent rights. CENELEC [and/or CEN] shall not be held responsible for identifying any or all such patent

rights.
Endorsement notice

The text of the International Standard IEC 62271-102:2001/A1:2011 was approved by CENELEC as a

European Standard without any modification.

In the official version, for Bibliography, the following note has to be added for the standard indicated:

IEC 62271-101:2006 NOTE Harmonized as EN 62271-101:2006 (not modified).
---------------------- Page: 4 ----------------------
SIST EN 62271-102:2002/A1:2011
- 3 - EN 62271-102:2002/A1:2011
Annex ZA
(normative)
Normative references to international publications
with their corresponding European publications

The following referenced documents are indispensable for the application of this document. For dated

references, only the edition cited applies. For undated references, the latest edition of the referenced

document (including any amendments) applies.

NOTE When an international publication has been modified by common modifications, indicated by (mod), the relevant EN/HD

applies.
Addition to Annex ZA of EN 62271-102:2002
Publication Year Title EN/HD Year
IEC 62271-1 2007 High-voltage switchgear and controlgear - EN 62271-1 2008
Part 1: Common specifications
IEC 62271-100 2008 High-voltage switchgear and controlgear - EN 62271-100 2009
Part 100: Alternating current circuit-breakers
---------------------- Page: 5 ----------------------
SIST EN 62271-102:2002/A1:2011
---------------------- Page: 6 ----------------------
SIST EN 62271-102:2002/A1:2011
IEC 62271-102
Edition 1.0 2011-08
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE
AMENDMENT 1
AMENDEMENT 1
High-voltage switchgear and controlgear –
Part 102: Alternating current disconnectors and earthing switches
Appareillage à haute tension –
Partie 102: Sectionneurs et sectionneurs de terre à courant alternatif
INTERNATIONAL
ELECTROTECHNICAL
COMMISSION
COMMISSION
ELECTROTECHNIQUE
INTERNATIONALE PRICE CODE
CODE PRIX
ICS 29.130.10; 29.130.99 ISBN 978-2-88912-635-4
® Registered trademark of the International Electrotechnical Commission
Marque déposée de la Commission Electrotechnique Internationale
---------------------- Page: 7 ----------------------
SIST EN 62271-102:2002/A1:2011
– 2 – 62271-102 Amend.1 © IEC:2011
FOREWORD

This amendment has been prepared by subcommittee 17A: High-voltage switchgear and

controlgear, of IEC technical committee 17: Switchgear and controlgear.
The text of this amendment is based on the following documents:
FDIS Report on voting
17A/972/FDIS 17A/978/RVD

Full information on the voting for the approval of this amendment can be found in the report

on voting indicated in the above table.

The committee has decided that the contents of this publication will remain unchanged until

the stability date indicated on the IEC web site under "http://webstore.iec.ch" in the data

related to the specific publication. At this date, the publication will be
• reconfirmed,
• withdrawn,
• replaced by a revised edition, or
• amended.
_____________
1.2 Normative references
Add the following new references to the existing list:

IEC 62271-1:2007, High-voltage switchgear and controlgear – Part 1: Common specifications

IEC 62271-100:2008, High-voltage switchgear and controlgear – Part 100: Alternating-current

circuit-breakers
3.4.101
disconnector
Replace the content of Notes 1 and 2 as follows:

NOTE 1 "Negligible current" implies currents such as the capacitive currents of bushings, busbars, connections,

very short lengths of cable, currents of permanently connected grading impedances of circuit-breakers and currents

of voltage transformers and dividers (see also IEC 62271-305). For rated voltages of 420 kV and below, a current

not exceeding 0,5 A is a negligible current for the purpose of this definition; for rated voltage above 420 kV and

currents exceeding 0,5 A, the manufacturer should be consulted. "No significant change in voltage" refers to such

applications as the by-passing of induction voltage regulators or circuit-breakers and bus transfer.

NOTE 2 For a disconnector having a rated voltage of 52 kV and above, a rated ability of bus transfer current

switching may be assigned.
3.4.105
earthing switch
Replace the existing text by the following:
IEV 441-14-11 is applicable with the following additional notes

NOTE 101 An earthing switch having a rated voltage of 52 kV and above may have a rating for switching and

carrying induced currents.
---------------------- Page: 8 ----------------------
SIST EN 62271-102:2002/A1:2011
62271-102 Amend.1 © IEC:2011 – 3 –

NOTE 102 These devices may sometimes be operated against short-circuit. The different classes of earthing

switches are related to the number of short-circuit making operations.

NOTE 103 For special applications such as fault initiating earthing switches the test procedures and the number

of tests may be agreed upon between the manufacturer and the user.
3.4.105.1
earthing switch class E0
Replace the existing definition by the following new definition:

earthing switch suitable for applications in distribution and transmission systems fulfilling the

general requirements of this standard, without a short-circuit making capability
3.4.105.2
earthing switch class E1
Replace the existing definition by the following new definition:

earthing switch suitable for applications in distribution and transmission systems fulfilling the

general requirements of this standard, with the capability to withstand two short-circuit making

operations
3.4.105.3
earthing switch class E2 (for earthing switches up to and including 52 kV)

Replace the existing definition and note by the following new definition and note:

earthing switch suitable for applications in distribution and transmission systems fulfilling the

general requirements of this standard, with the capability to withstand five short-circuit making

operations

NOTE The increased number of making operations in Class E2 is restricted to voltages up to and including 52 kV

only depending on the operating conditions and the protection systems typical to such networks

Add, after definition 3.4.105.3, the following new definitions 3.4.105.4, 3.4.105.5 and

3.4.105.6:
3.4.105.4
earthing switch class M0 (for earthing switches)

earthing switch suitable for applications in distribution and transmission systems fulfilling the

general requirements of this standard, with the capability to withstand 1 000 operating cycles

3.4.105.5
combined function earthing switch

earthing switch having a common contact system for earthing and at least one of the following

functions:
• disconnecting;
• making and/or breaking of load currents;
• making and/or breaking of currents up to the rated short-circuit current
3.4.105.6
toggle point

point beyond which any further movement of the charging mechanism causes the stored

energy to be released
3.6.106
dependent manual operation (of a mechanical switching device)
Add the following note:
---------------------- Page: 9 ----------------------
SIST EN 62271-102:2002/A1:2011
– 4 – 62271-102 Amend.1 © IEC:2011

NOTE 101 Earthing switches with dependent manual operations should not be rated for short circuit making

capability.
4.5 Rated short-time withstand current (I )
Replace the existing text of this subclause by the following new text:
Subclause 4.5 of IEC 62271-1 is applicable with the following addition.

The rated short-time withstand current of an earthing switch forming an integral part of a

combined function earthing switch shall be equal to the rated short-time withstand current of

the combined function earthing switch, unless otherwise specified.
4.6 Rated peak withstand current (I )
Replace the existing text of this subclause by the following new text:
Subclause 4.6 of IEC 62271-1 is applicable with the following addition.

The rated peak withstand current of an earthing switch forming an integral part of a combined

function earthing switch shall be equal to the rated peak withstand current of the combined

function earthing switch, unless otherwise specified.
4.101 Rated short-circuit making current
Add the following new text after the existing text of this subclause:

The rated short-circuit making current of an earthing switch forming an integral part of a

combined function earthing switch shall be equal to the rated peak making current of the

combined function earthing switch, unless otherwise specified.
4.107 Rated values of electrical endurance for earthing switches
Replace the existing text by the following new text and Table 7:
Table 3b provides a classification of earthing switch for electrical endurance.
Table 7 – Classification of earthing switch for electrical endurance
Class Type of earthing switch
E0 Earthing switches with no making capability

E1 Earthing switches with capability to withstand two short-circuit making operations

E2 Earthing switches with capability to withstand five short-circuit making operations

6.101 Test to prove the short-circuit making performance of earthing switches

Replace the existing Subclauses 6.101.1, 6.101.2 and 6.101.3 by the following new

Subclauses 6.101.1, 6.101.2, 6.101.3, 6.101.4, 6.101.5, 6.101.6, 6.101.7, 6.101.8, 6.101.9,

6.101.10 and 6.101.11:
6.101.1 General test conditions

Earthing switches of class E1 or E2 according to definition 3.4.105, having a short-circuit

making current capability, shall be subjected to two (class E1) or five (class E2) making

operations respectively, in a making test series in accordance with the procedures of 6.101.7.

---------------------- Page: 10 ----------------------
SIST EN 62271-102:2002/A1:2011
62271-102 Amend.1 © IEC:2011 – 5 –

In case of combined function earthing switches, the short-circuit making tests shall first be

performed in the contact positions for other functions, in accordance with the relevant

standards, followed by the short-circuit making tests of the earthing function, without

intermediate maintenance.

Alternatively, the short-circuit making tests of the combined function earthing switch according

to the specified class can be performed on a new combined function earthing switch preceded

by at least one short-circuit making test of the other function followed by the short-circuit

making tests of the earthing function without intermediate maintenance.
6.101.2 Arrangement of the earthing switch for tests

The earthing switch shall be tested under the representative conditions of installation and

use, concerning the connections, support, enclosure and dimensions.

Its operating device shall be operated in the manner prescribed and in particular, if it is

electrically, hydraulically or pneumatically operated, it shall be operated at the minimum

supply voltage or pressure.

For gas-filled earthing switches, the tests shall be performed at the minimum functional

pressure of the gas for insulation and making operation.

NOTE 1 For convenience of testing the supply voltage to the coil for the closing operation may be increased to

obtain a consistent closing time, provided it does not increase the closing speed of the contacts.

NOTE 2 For convenience of testing in order to obtain accurate closing times an electrically or pneumatically

released latch may be introduced at the toggle point.

NOTE 3 Earthing switches with independent manual operation may be operated by an arrangement provided for

the purpose of making remote control possible.

NOTE 4 For testing purposes, it may be necessary to measure the travel characteristics, for example by using a

travel recorder.
6.101.3 Test frequency

Earthing switches shall be tested at rated frequency, with a tolerance of ± 10 %.

However, tests with a peak factor of 2,6 or above, at a supply frequency of 50 Hz or 60 Hz

cover the requirements of both frequencies.
6.101.4 Test voltage
The test voltage shall be as follows:

a) For three-phase tests, the average value of the applied voltage phase-to-phase shall not

be less than the rated voltage U and shall no
...

Questions, Comments and Discussion