Amendment 2 - Plugs and socket-outlets for household and similar purposes - Part 1: General requirements

Amendement 2 - Prises de courant pour usages domestiques et analogues - Partie 1: Règles générales

General Information

Status
Published
Publication Date
13-Feb-2013
Current Stage
PPUB - Publication issued
Start Date
14-Feb-2013
Completion Date
14-Feb-2013
Ref Project

Buy Standard

Standard
IEC 60884-1:2002/AMD2:2013 - Amendment 2 - Plugs and socket-outlets for household and similar purposes - Part 1: General requirements
English and French language
118 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (sample)

IEC 60884-1
Edition 3.0 2013-02
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE
AMENDMENT 2
AMENDEMENT 2
Plugs and socket-outlets for household and similar purposes –
Part 1: General requirements
Prises de courant pour usages domestiques et analogues –
Partie 1: Règles générales
IEC 60884-1:2002/A2:2013
---------------------- Page: 1 ----------------------
THIS PUBLICATION IS COPYRIGHT PROTECTED
Copyright © 2013 IEC, Geneva, Switzerland

All rights reserved. Unless otherwise specified, no part of this publication may be reproduced or utilized in any form

or by any means, electronic or mechanical, including photocopying and microfilm, without permission in writing from

either IEC or IEC's member National Committee in the country of the requester.

If you have any questions about IEC copyright or have an enquiry about obtaining additional rights to this publication,

please contact the address below or your local IEC member National Committee for further information.

Droits de reproduction réservés. Sauf indication contraire, aucune partie de cette publication ne peut être reproduite ni

utilisée sous quelque forme que ce soit et par aucun procédé, électronique ou mécanique, y compris la photocopie et les

microfilms, sans l'accord écrit de la CEI ou du Comité national de la CEI du pays du demandeur.

Si vous avez des questions sur le copyright de la CEI ou si vous désirez obtenir des droits supplémentaires sur cette

publication, utilisez les coordonnées ci-après ou contactez le Comité national de la CEI de votre pays de résidence.

IEC Central Office Tel.: +41 22 919 02 11
3, rue de Varembé Fax: +41 22 919 03 00
CH-1211 Geneva 20 info@iec.ch
Switzerland www.iec.ch
About the IEC

The International Electrotechnical Commission (IEC) is the leading global organization that prepares and publishes

International Standards for all electrical, electronic and related technologies.
About IEC publications

The technical content of IEC publications is kept under constant review by the IEC. Please make sure that you have the

latest edition, a corrigenda or an amendment might have been published.
Useful links:

IEC publications search - www.iec.ch/searchpub Electropedia - www.electropedia.org

The advanced search enables you to find IEC publications The world's leading online dictionary of electronic and

by a variety of criteria (reference number, text, technical electrical terms containing more than 30 000 terms and

committee,…). definitions in English and French, with equivalent terms in

It also gives information on projects, replaced and additional languages. Also known as the International

withdrawn publications. Electrotechnical Vocabulary (IEV) on-line.

IEC Just Published - webstore.iec.ch/justpublished Customer Service Centre - webstore.iec.ch/csc

Stay up to date on all new IEC publications. Just Published If you wish to give us your feedback on this publication

details all new publications released. Available on-line and or need further assistance, please contact the

also once a month by email. Customer Service Centre: csc@iec.ch.
A propos de la CEI

La Commission Electrotechnique Internationale (CEI) est la première organisation mondiale qui élabore et publie des

Normes internationales pour tout ce qui a trait à l'électricité, à l'électronique et aux technologies apparentées.

A propos des publications CEI

Le contenu technique des publications de la CEI est constamment revu. Veuillez vous assurer que vous possédez

l’édition la plus récente, un corrigendum ou amendement peut avoir été publié.
Liens utiles:

Recherche de publications CEI - www.iec.ch/searchpub Electropedia - www.electropedia.org

La recherche avancée vous permet de trouver des Le premier dictionnaire en ligne au monde de termes

publications CEI en utilisant différents critères (numéro de électroniques et électriques. Il contient plus de 30 000

référence, texte, comité d’études,…). termes et définitions en anglais et en français, ainsi que

Elle donne aussi des informations sur les projets et les les termes équivalents dans les langues additionnelles.

publications remplacées ou retirées. Egalement appelé Vocabulaire Electrotechnique

International (VEI) en ligne.
Just Published CEI - webstore.iec.ch/justpublished
Service Clients - webstore.iec.ch/csc
Restez informé sur les nouvelles publications de la CEI.

Just Published détaille les nouvelles publications parues. Si vous désirez nous donner des commentaires sur

Disponible en ligne et aussi une fois par mois par email. cette publication ou si vous avez des questions

contactez-nous: csc@iec.ch.
---------------------- Page: 2 ----------------------
IEC 60884-1
Edition 3.0 2013-02
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE
AMENDMENT 2
AMENDEMENT 2
Plugs and socket-outlets for household and similar purposes –
Part 1: General requirements
Prises de courant pour usages domestiques et analogues –
Partie 1: Règles générales
INTERNATIONAL
ELECTROTECHNICAL
COMMISSION
COMMISSION
ELECTROTECHNIQUE
PRICE CODE
INTERNATIONALE
CODE PRIX XA
ICS 29.120.30 ISBN 978-2-83220-577-8

Warning! Make sure that you obtained this publication from an authorized distributor.

Attention! Veuillez vous assurer que vous avez obtenu cette publication via un distributeur agréé.

® Registered trademark of the International Electrotechnical Commission
Marque déposée de la Commission Electrotechnique Internationale
---------------------- Page: 3 ----------------------
– 2 – 60884-1 Amend.2 © IEC:2013
FOREWORD
This amendment has been prepared by subcommittee 23B: Plugs, socket-outlets and
switches, of IEC technical committee 23: Electrical accessories.
The text of this amendment is based on the following documents:
FDIS Report on voting
23B/1088/FDIS 23B/1096/RVD

Full information on the voting for the approval of this amendment can be found in the report

on voting indicated in the above table.

The committee has decided that the contents of this amendment and the base publication will

remain unchanged until the stability date indicated on the IEC web site under

"http://webstore.iec.ch" in the data related to the specific publication. At this date, the

publication will be
• reconfirmed,
• withdrawn,
• replaced by a revised edition, or
• amended.
The contents of the corrigendum of March 2014 have been included in this copy.
_____________
INTRODUCTION to Amendment 2
The changes listed in this Amendment 2 apply to IEC 60884-1:2002 as amended by
Amendment 1:2006.
---------------------- Page: 4 ----------------------
60884-1 Amend.2 © IEC:2013 – 3 –
1 Scope
Replace the fourth paragraph by the following new paragraph:

This standard also applies to plugs which are a part of cord sets, to plugs and portable

socket-outlets which are a part of cord extension sets and to plugs and socket-outlets which

are a component of an appliance, unless otherwise stated in the standard for the relevant

appliance.

Replace the penultimate paragraph and Note 4 by the following new paragraph and Note 4

and add new Note 5 as follows:

Plugs and socket-outlets complying with this standard should be suitable for use at ambient

temperatures not normally exceeding +40 °C, but their average over a period of 24 h does not

exceed +35 °C, with a lower limit of the ambient air temperature of –5 °C.

NOTE 4 Socket-outlets complying with this standard are only suitable for incorporation or mounting in equipment

in such a way and in such a place that it is unlikely that the surrounding temperature exceeds 35 °C.

NOTE 5 In the following country it is required that plugs and socket-outlets complying with this standard are

suitable for use at ambient temperatures not normally exceeding 35 °C, but occasionally reaching 40 °C: CN.

2 Normative references

Replace "IEC 60068-2-30:1980" by "IEC 60068-2-30, Environmental testing – Part 2-30:

Tests – Test Db: Damp heat, cyclic (12 + 12 h cycle)".

Replace "IEC 60068-2-32:1975" by "IEC 60068-2-31, Environmental testing – Part 2-31:

Tests – Test Ec: Rough handling shocks, primarily for equipment-type specimens".

Replace "IEC 60417-2:1998" by "IEC 60417, Graphical symbols for use on equipment"

Add the following new normative references:
IEC 60068-2-75, Environmental testing – Part 2-75: Tests – Test Eh: Hammer tests

IEC 60669 (all parts), Switches for household and similar fixed-electrical installations

IEC 61058 (all parts), Switches for appliances
IEC 61058-1, Switches for appliances – Part 1: General requirements
ISO/IEC Guide 51, Safety aspects – Guidelines for their inclusion in standards
3 Definitions

Replace the existing definitions 3.1, 3.2, 3.4, 3.16, 3.27 and 3.33 by the following new

definitions:
3.1
plug

accessory intended for frequent use by ordinary persons, having pins designed to engage

with the contacts of a socket-outlet, also incorporating means for the electrical connection and

mechanical retention of one flexible cable
---------------------- Page: 5 ----------------------
– 4 – 60884-1 Amend.2 © IEC:2013

NOTE For special purposes such as lighting chains (see also IEC 60598-2-20), two or three single-core cables

can be connected within the plug.
3.2
socket-outlet

accessory intended for frequent use by ordinary persons, having socket contacts designed to

engage with the pins of a plug and having terminals or terminations for the connection of

cable
3.4
portable socket-outlet

socket-outlet intended to be connected to or integral with one flexible cable and which can

easily be moved from one place to another while connected to the supply
3.16
screw-type terminal
terminal for the connection and subsequent disconnection of one conductor or the

interconnection and subsequent disconnection of two or more conductors, the connection

being made, directly or indirectly, by means of screws or nuts of any kind
3.27
shutter

movable part incorporated into a socket-outlet arranged to shield at least the live

socket contacts automatically when the plug is withdrawn
3.33
main part

assembly consisting of the base and other parts. This assembly is not intended to be

dismantled at any time after manufacture
Add, after the existing definition 3.33, the following new definitions:
3.34
grommet
component used to support and protect the cable or conduit at the point of entry
NOTE 1 It may also prevent the ingress of moisture or contaminants.
NOTE 2 Examples of membranes and grommets are shown in Figure 45.
3.35
entry membrane

component or integral part of the accessory used to protect the cable which may be used to

support the cable or conduit at the point of entry

NOTE 1 An entry membrane may also prevent the ingress of moisture or contaminants and may be part of a

grommet.
NOTE 2 Examples of membranes and grommets are shown in Figure 45.
3.36
protecting membrane

component or integral part of the accessory that is not intended to be penetrated in normal

use and is intended to provide protection against ingress of water or solid objects and/or to

allow the operation of an accessory
NOTE Examples of membranes and grommets are shown in Figure 45.
---------------------- Page: 6 ----------------------
60884-1 Amend.2 © IEC:2013 – 5 –
4 General requirements
Replace the first paragraph by the following new paragraph:

Accessories and boxes of surface mounting accessories shall be so designed and constructed

that, in normal use, their performance is reliable and safety is achieved by reducing risk to a

tolerable level, as defined in ISO/IEC Guide 51.
5 General remarks on tests
5.2
Add, at the end of the subclause, the following paragraph:

The fixing screws of terminals, covers and cover plates shall be tightened with a torque equal

to two-thirds of the values specified in Table 6 unless otherwise specified.
5.4
Add, at the end of the first paragraph, the following sentence:
For the test of 10.6, three additional specimens are required.
6 Ratings
Table 1 – Preferred combinations of types and ratings
Replace the existing Table 1 by the following new Table 1:
Type Rated voltage Rated current
V A
2P (non-rewirable plugs only) 130 or 250 2,5
2P (plugs only) 130 or 250 6
130 or 250
2P +
2P +
440
3P +
3P + N +

NOTE Standardized values and configurations of existing systems are reported in IEC 60083.

Replace the note below the table as follows:

NOTE In the following countries fixed 2P socket-outlets are not allowed: AT, BR CH, DE, FR, IT.

6.3
Delete this subclause.
---------------------- Page: 7 ----------------------
– 6 – 60884-1 Amend.2 © IEC:2013
7 Classification
7.1.1
Replace the existing subclause as follows:

7.1.1 Accessories are classified according to the degree of protection against access to

hazardous parts and against harmful effects due to the ingress of solid foreign object as

described in IEC 60529.
7.1.2
Replace the existing subclause as follows:

7.1.2 Accessories are classified according to the degree of protection against harmful

effects due to the ingress of water as described in IEC 60529.
7.1.5
Add, at the end of this subclause, the following new Note:

NOTE In the following country accessories with screwless terminals for rigid conductors only are not allowed: IT.

7.2.4
Replace the existing Note by the following new Note:

NOTE If a fixed socket-outlet has a base which cannot be separated from the cover or cover-plate, and requires a

supplementary plate to meet the standard which can be removed for redecorating the wall without displacement of

the conductors, it is considered to be of design A, provided the supplementary plate meets the requirements

specified for covers and cover-plates.
7.3 Plugs classification
Replace the existing text of this subclause by the following new text:

Plugs are classified according to the class of equipment to which they are intended to be

connected:
– plugs for equipment of class I;
– plugs for equipment of class II.
For the description of the classes of equipment, see IEC 61140.
NOTE This standard does not apply to plugs for equipment of class 0.
8 Marking
8.1
Add, after the fifth dashed item, the following new Note 1:
NOTE 1 The type reference may be the series reference only.
Replace the existing sixth and seventh dashed items by the following:

– first characteristic numeral for the degree of protection against access to hazardous parts

and against harmful effects due to ingress of solid foreign objects, if declared to be higher

---------------------- Page: 8 ----------------------
60884-1 Amend.2 © IEC:2013 – 7 –

than 2, and for fixed socket-outlets higher than 4 in which case the second characteristic

numeral shall also be marked;

– second characteristic numeral for the degree of protection against harmful effects due to

ingress of water, if declared to be higher than 0, and for fixed socket-outlets higher than 2

in which case the first characteristic numeral shall also be marked.
Renumber the existing Note 1 as Note 2 and delete the existing Note 2.
8.2
Add, after the symbol of protective earth, the following reference:
(IEC 60417-5019 (2006-08))
Replace, in Note 1, “IEC 60417-2” by “IEC 60417”.
8.3
Delete, in the third dashed item, the words "if any".
Add, after the third dashed item, the following new dashed item:

– an indication of the suitability to accept rigid conductors only for screwless terminals for

those socket-outlets having this restriction;
8.6
Replace the existing subclause by the following new subclause:

8.6 For surface-type mounting boxes forming an integral part of socket-outlets having an IP

code higher than IP4X, or higher than IPX2, the IP code shall be marked on the outside of its

associated enclosure so as to be easily discernible when the socket-outlet is mounted and

wired as in normal use.
8.8
Replace the first paragraph of this subclause by the following:

The marking shall be durable and clearly legible with normal or corrected vision, without

additional magnification.
9 Checking of dimensions
9.2
Replace the third dashed item by the following new dashed item:

– a socket-outlet with earthing contact, if the existing plug of the present national system is

a plug for class 0 equipment.
Replace the second paragraph by the following new paragraph:

It shall not be possible to engage existing plugs on the present national system for equipment

of class 0 or of class I with a socket-outlet exclusively designed to accept plugs for class II

equipment.
---------------------- Page: 9 ----------------------
– 8 – 60884-1 Amend.2 © IEC:2013
10 Protection against electric shock
10.1
Replace the first paragraph by the following new paragraph:

Fixed socket-outlets, plugs when engaged and portable socket-outlets shall be so designed

and constructed that when they are mounted and/or wired as for normal use, live parts are not

accessible, even after removal of parts which can be removed without the use of a tool.

10.2
Replace the word "bases" by the words "main parts".
Delete the words "plugs and".
10.2.1

Replace, in the first paragraph, the words “Metal covers or cover-plates” by “Accessible metal

parts”, twice.
10.2.2

Replace, in the first paragraph, the words “Metal covers or cover-plates are automatically

connected” by “Accessible metal parts are reliably connected”.
10.4
Replace, in the first paragraph "10.2" by "10.2.1 or 10.2.2".
Replace the last paragraph by the following new paragraph:
Compliance is checked by inspection and by the tests of 10.2.1 or 10.2.2.
10.5
Add, after the third paragraph, the following new paragraph:

Shutters shall be so designed that a plug is inserted with the same movement in a socket-

outlet with shutters as in a socket-outlet without shutters.
10.7

Replace the first two paragraphs by the following new paragraphs and add a new note after

the first paragraph, as follows:

Socket-outlets with or without lid, classified according to 7.2.1 b), shall be so constructed that,

when mounted and wired as in normal use, live parts shall not be accessible with a test wire

of 1 mm in diameter (see Figure 10).

NOTE In the following countries the increased protection is considered fulfilled when the lid (spring loaded) is

closed: CH, DE.

Compliance is checked by applying with a test wire of 1,0 mm in diameter (see Figure 10) a

force of 1 N on all accessible surfaces in the most unfavourable conditions without a plug

inserted with the lid, if any, open.
---------------------- Page: 10 ----------------------
60884-1 Amend.2 © IEC:2013 – 9 –
11 Provision for earthing
11.2
Delete the fourth paragraph.
11.3
Replace Note 1 by the following new Note 1:

NOTE 1 This requirement does not apply to the accessible metal parts mentioned in 10.2.1.

Replace in Note 2 the word "bases" by the words "main parts".
12 Terminals and terminations

Table 3 – Relationship between rated current and connectable nominal cross-sectional

areas of copper conductors
Replace the entire existing Table 3 by the following new Table 3:
Rigid (solid or stranded)
Flexible copper conductors
copper conductors
Current and type
Nominal cross- Diameter Nominal cross- Diameter of the
of accessory
sectional area of the largest sectional area largest conductor
conductor
2 2
mm mm mm mm
From 0,75 up to
6 A – – 1,73
1,5 inclusive
10 A
From 1 up to 2,5 From 1 up to 2,5
2,13 2,21
3P+N+
inclusive inclusive
(fixed accessory)
10 A
From 0,75 up to
– – 1,73
3P+N+
2,5 inclusive
(portable accessory)
10 A and 13 A
2P and From 1 up to 2,5 From 1 up to 2,5
2,13 2,21
ab ab
inclusive inclusive
2P+
(fixed accessory)
10 A and 13 A
2P and From 0,75 up to
– – 1,73
1,5 inclusive
2P+
(portable accessory)
13 A
2P and
From 1,5 up to
From 1,5 up to
2P+
3 × 2,5
3 × 2,5
2,72 2,72
From 1,5 up to
From 1,5 up to 2 × 4
(fixed accessory)
2 × 4
(Socket-outlets for
fused plugs)
---------------------- Page: 11 ----------------------
– 10 – 60884-1 Amend.2 © IEC:2013
Rigid (solid or stranded)
Flexible copper conductors
copper conductors
Current and type
Nominal cross- Diameter Nominal cross- Diameter of the
of accessory
sectional area of the largest sectional area largest conductor
conductor
2 2
mm mm mm mm
13 A
2P and
2P+
– – From 0,5 up to 1,5 1,73
(portable accessory)
(fused plugs)
16 A
2P and From 1,5 up to
2,13 – –
2 × 2,5 inclusive
2P +
(fixed accessory)
16 A
2P and
From 0,75 up to
– – 1,73
1,5 inclusive
2P +
(portable accessory)
16 A other than 2P and
From 1,5 up to 4
2P + 2,72 – –
inclusive
(fixed accessory)
16 A other than 2P and
From 1 up to 2,5
2P + 2,21
inclusive
(portable accessory)
25A
From 2,5 up to 6
3,47
2P +
inclusive
(fixed accessory)
25A
From 2,5 up to 6
3,05
2P +
inclusive
(portable accessory)
32 A
From 2,5 up to 10
4,32 – –
inclusive
(fixed accessory)
32 A
From 2,5 up to 6
3,87
inclusive
(portable accessory)
a 2

The terminal shall allow the connection of two 1,5 mm conductors which have a diameter of 1,45 mm.

b 2 2

Some countries require the looping-in of three conductors of 2,5 mm , or two conductors of 4 mm .

The use of flexible conductors is permitted.
12.3.7
Replace the first and the second dashed items by the following new dashed items:

– the clamping of one of the conductors is independent of the clamping of the other

conductor(s);

– during the connection or disconnection the conductors can be connected or disconnected

either at the same time or separately.
---------------------- Page: 12 ----------------------
60884-1 Amend.2 © IEC:2013 – 11 –
12.3.8
Delete the Note.
Replace the last paragraph by the following new paragraph:
Compliance is checked by inspection.
12.3.11
Replace the existing Table 10 by the following new Table 10:
Rated current Test current Nominal cross-sectional area
of the conductor
A A mm
10 and 13 17,5 1,5
16 22 2,5

NOTE For socket-outlets having rated currents lower than 10 A, the test current is proportionally determined and

the cross-sectional area of the conductors is 1,5 mm .
Replace the fifth paragraph of b) by the following new paragraph:

The voltage drop in each screwless terminal is determined as prescribed for the test of a) and

is done at the following moments:
– after the first 24 temperature cycles and after the 192 temperature cycle;

– additional measurements shall be carried out after any 3 of the following temperature

th nd th th th th
cycles: after the 48 , 72 , 96 , 120 , 14 or 168 temperature cycles.
Table 12 – Deflection test forces
Replace the title of Table 12 by the following new title:
Table 12 – Deflection test forces for screwless terminals
13 Construction of fixed socket-outlets
13.1
Add, after the first paragraph, the following new paragraph:

Parts of socket contact assemblies, which will be in contact with the portion of the pin

intended to make electrical contact when the plug is fully inserted in the socket-outlet shall

ensure metallic opposing contacts at least on two sides of each pin.
13.2
Replace the second paragraph by the following new paragraphs and new note:

Socket contacts and pin(s) of socket-outlets, which are made of copper or copper alloy, as

specified in 26.5, are considered as complying with this requirement.
Compliance is checked by inspection or by chemical analysis, if necessary.
---------------------- Page: 13 ----------------------
– 12 – 60884-1 Amend.2 © IEC:2013

The pin(s) of socket-outlets shall be constructed in such a way that the mechanical strength of

the pin(s) does not depend on the plastic material.

NOTE In certain designs the pin(s) of the accessories are hollow and filled with plastic.

Compliance is checked by inspection and in case of doubt by the tests of 14.2 and Clause 21

on a new set of specimens without plastic.
13.4
Replace the entire subclause by the following new subclause:
13.4 Socket-outlets shall be so constructed as to permit

– easy introduction into the terminal and reliable connection of the conductors in the

terminals, except for lead wires of pilot lights;

NOTE 1 Screw terminals as shown in Figures 2 to 5 are considered suitable for reliable connection of the

conductors.
– easy fixing of the main part to a wall or in a mounting box;
– correct positioning of the conductors;

– adequate space between the underside of the main part and the surface on which the

main part is mounted or between the sides of the main part and the enclosure (cover or

box) so that, after installation of the socket-outlet, the insulation of the conductors is not

necessarily pressed against live parts of different polarity.

NOTE 2 This requirement does not imply that the metal parts of the terminal are necessarily protected by

insulating barriers or insulating shoulders, to avoid contact due to incorrect installation of the terminal metal parts,

with the insulation of the conductor.

For surface type socket-outlets to be mounted on a mounting plate, a wiring channel may be

needed to comply with this requirement.

Compliance is checked by inspection and by an installation test with conductors of the largest

nominal cross-sectional area specified in Table 3.

In addition, for socket-outlets having screwless terminals, the socket-outlets shall be so

constructed that the connecting and/or disconnecting means of the screwless terminals

cannot be activated by the conductors during and after installation of the socket-outlet in a

box or on a wall.

NOTE 3 This requirement does not imply that the connecting and/or disconnecting means cannot be touched by

the conductors.

NOTE 4 This requirement may be met by the placement of the connecting and/or disconnecting means and/or the

use of protective barriers or shoulders placed around the connecting and/or disconnecting means.

Compliance is checked by inspection and in case of doubt by the following test.

The test is carried out with a solid copper conductor having the smallest cross-sectional area,

as specified in 12.3.2.

The conductor is pushed as far as possible into the terminal under test or is inserted so that

adequate connection is obvious.

A test probe according to IEC 61032 test probe 1 is pushed against the connecting or

disconnecting means with a force of 120 N in the direction opposite to the mounting direction

as described in Figure 46a.
---------------------- Page: 14 ----------------------
60884-1 Amend.2 © IEC:2013 – 13 –

During the application of the force, the conductor, except for lead wires of pilot lights, is

subjected to a pull of 30 N; the pull is applied in one smooth and continuous motion, for 1 min,

in the direction of the longitudinal axis of the conductor space.

During the application of the pull, the conductor shall not come out of the screwless terminal.

The force of 120 N has to be applied before the force of 30 N is applied. The force of 30 N is

maintained on the conductor during the complete test.

Care shall be taken that the test probe does not touch the conductor during the application of

the forces.

Where the axis between the application force and the axis through the force necessary to

operate the connecting/disconnecting means deviates by more than 20°, it is allowed to exert

the calculated resulting force directly onto the connecting/disconnecting means using the test

probe; an example is shown in Figure 46b.

If the angle is greater than 60° no test is necessary and the product is deemed to comply with

the requirements without further tests.

If it is not possible to exert a force onto the connecting/disconnecting device, the product is

deemed to comply with the requirements without further tests.

In addition, socket-outlets classified as design A shall permit easy positioning and removal of

the cover or cover-plate, without displacing the conductors or activating the connecting and/or

disconnecting means of screwless terminals.

NOTE 5 This requirement does not imply that the connecting and/or disconnecting means cannot be touched by

the cover or cover plate.

Compliance is checked by inspection and by an installation test with conductors of the largest

nominal cross-sectional area specified in Table 3.
13.7
Replace in the third paragraph the word "base" by the words "main part".
13.9
Replace the second paragraph by the following new paragraph:

Drain holes, small gaps between enclosures or boxes and conduits, cables, or earthing

contacts, if any, or between enclosures or boxes and grommets or membranes and knockouts

are neglected provided they do not compromise the declared IP rating.
13.16
Replace the second paragraph by the following new paragraph:

Surface-type socket-outlets having a degree of protection from IPX4 to IPX6 shall have

provision for opening a drain hole.
13.18
Replace the existing subclause by the following new subclause:

13.18 Earthing contacts, phase contacts and neutral contacts shall be locked against

rotation.
---------------------- Page: 15 ----------------------
– 14 – 60884-1 Amend.2 © IEC:2013

When the product is ready for the wiring it shall not be possible to remove the earthing

contacts, phase contacts and neutral contact without the use of a tool.
Compliance is checked by inspection and by manual test.
Table 14 – External cable dimension limits for surface-type socket-outlets
Replace the existing Table 14 by the following new Table 14:
Limits of external dimensions of cables
Nominal cross-sectional
Rated current Number of
areas of conductors
A conductors
Minimum Maximum
2 13,5
10 1
...