Oil-immersed cable connection assemblies for transformers and reactors having highest voltage for equipment Um from 72,5 kV to 550 kV - Part 2: Dry-type cable terminations

This European Standard covers the oil-immersed single-phase connection assemblies of cables for
transformers and reactors designed in accordance with EN 60076 series.
NOTE The term "transformer" is used as common definition for transformer and reactor.
If no separate cable connection box is used and dry-type cable terminations are directly installed into the
transformer tank the requirements of this standard should be followed.
The purpose of EN 50299-2 is to establish for the cable connection assemblies:
• electrical and mechanical requirements including interchangeability;
• limits of supply;
• tests to be carried out.
It complements and amends, if necessary, the relevant standards and applies to dry-type cable terminations
for power cables with extruded insulation which may be used with similar interfaces for the cable entrance in
switchgear applications according to EN 62271-209.
This standard applies to oil-filled cable connection boxes of transformers with highest voltage for equipment
from Um = 72,5 kV to 550 kV, including the conductor current terminal with removable link between the
transformer and the dry-type cable termination.

Ölgefüllte Kabelanschlusseinheiten mit Kompaktkabelanschlüssen für Transformatoren und Drosselspulen mit einer höchsten Spannung für Betriebsmittel Um von 72,5 kV bis 550 kV - Teil 2: Kompaktkabelan-schlüsse

Boîte de raccordement de câble pour transformateurs immergés et bobine d'inductance de tensions comprises entre 72,5 kV et 550 kV - Partie 2: Extrémité de câble sèche

Povezovalni sestavi oljnih kablov za transformatorje in dušilke, pri katerih je najvišja napetost opreme Um od 72,5 kV do 550 kV - 2. del: Suhi kabelski priključki

Ta evropski standard obravnava povezovalne sestave oljnih enofaznih kablov za
transformatorje in dušilke, zasnovane v skladu s skupino standardov EN 60076.
OPOMBA Izraz »transformator« je uporabljen kot splošni izraz za transformator in dušilko.
Če se ne uporablja ločena priključna vtičnica in so suhi kabelski priključki nameščeni neposredno v transformatorski kotel, je treba uporabljati zahteve tega standarda.
Namen standarda EN 50299-2 je za povezovalne sestave kablov določiti:
• električne in mehanske zahteve, vključno z medsebojno zamenljivostjo;
• omejitve dobave;
• preskuse, ki jih je treba izvesti.
Standard po potrebi dopolnjuje in popravlja ustrezne standarde, uporablja pa se za suhe kabelske priključke za napajalne kable z ekstrudirano izolacijo, ki se lahko uporabljajo s podobnimi vmesniki za kabelske vhode pri stikalnih napravah v skladu s standardom EN 62271-209.
Ta standard se uporablja za oljne kabelske priključne vtičnice na transformatorjih, pri katerih je najvišja napetost opreme Um od 72,5 kV do 550 kV, vključno s priključkom električnega prevodnika z odstranljivo povezavo med transformatorjem in suhim kabelskim priključkom.

General Information

Status
Published
Publication Date
08-Apr-2015
Technical Committee
Current Stage
6060 - National Implementation/Publication (Adopted Project)
Start Date
08-Dec-2014
Due Date
12-Feb-2015
Completion Date
09-Apr-2015

Relations

Buy Standard

Standard
EN 50299-2:2015
English language
14 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

SLOVENSKI STANDARD
SIST EN 50299-2:2015
01-maj-2015
1DGRPHãþD
SIST EN 50299:2004
3RYH]RYDOQLVHVWDYLROMQLKNDEORY]DWUDQVIRUPDWRUMHLQGXãLONHSULNDWHULKMH
QDMYLãMDQDSHWRVWRSUHPH8PRGN9GRN9GHO6XKLNDEHOVNLSULNOMXþNL
Oil-immersed cable connection assemblies for transformers and reactors having highest
voltage for equipment Um from 72,5 kV to 550 kV - Part 2: Dry-type cable terminations
Ölgefüllte Kabelanschlusseinheiten mit Kompaktkabelanschlüssen für Transformatoren
und Drosselspulen mit einer höchsten Spannung für Betriebsmittel Um von 72,5 kV bis
550 kV - Teil 2: Kompaktkabelan-schlüsse
Boîte de raccordement de câble pour transformateurs immergés et bobine d'inductance
de tensions comprises entre 72,5 kV et 550 kV - Partie 2: Extrémité de câble sèche
Ta slovenski standard je istoveten z: EN 50299-2:2014
ICS:
29.060.20 Kabli Cables
29.180 Transformatorji. Dušilke Transformers. Reactors
SIST EN 50299-2:2015 en
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

---------------------- Page: 1 ----------------------

SIST EN 50299-2:2015

---------------------- Page: 2 ----------------------

SIST EN 50299-2:2015


EUROPEAN STANDARD EN 50299-2

NORME EUROPÉENNE

EUROPÄISCHE NORM
November 2014
ICS 29.180 Supersedes EN 50299:2002 (PART)
English Version
Oil-immersed cable connection assemblies for transformers and
reactors having highest voltage for equipment Um from 72,5 kV
to 550 kV - Part 2: Dry-type cable terminations
Boîte de raccordement de câble pour transformateurs Ölgefüllte Kabelanschlusseinheiten mit
immergés et bobine d'inductance de tensions comprises Kompaktkabelanschlüssen für Transformatoren und
entre 72,5 kV et 550 kV - Partie 2: Extrémité de câble sèche Drosselspulen mit einer höchsten Spannung für
Betriebsmittel Um von 72,5 kV bis 550 kV - Teil 2:
Kompaktkabelanschlüsse
This European Standard was approved by CENELEC on 2014-10-13. CENELEC members are bound to comply with the CEN/CENELEC
Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration.
Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN-CENELEC
Management Centre or to any CENELEC member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by translation
under the responsibility of a CENELEC member into its own language and notified to the CEN-CENELEC Management Centre has the
same status as the official versions.
CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus, the Czech Republic,
Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia,
Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland,
Turkey and the United Kingdom.


European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung
CEN-CENELEC Management Centre: Avenue Marnix 17, B-1000 Brussels
© 2014 CENELEC All rights of exploitation in any form and by any means reserved worldwide for CENELEC Members.
 Ref. No. EN 50299-2:2014 E

---------------------- Page: 3 ----------------------

SIST EN 50299-2:2015
EN 50299-2:2014 - 2 -
Contents
Foreword .3
1 Scope .4
2 Normative references .4
3 Terms and definitions .5
4 Limits of supply .5
5 Rated values .5
6 Preferred values .6
6.1 Highest voltage for equipment (U ) .6
m
6.2 Rated currents (I ) .6
r
6.3 Transformer test voltages .6
6.4 Transformer test currents .6
6.5 Cable installation test voltage .6
7 Requirements .6
7.1 Isolation of transformer during cable installation tests .6
7.2 Connection interface .6
7.3 Mechanical requirements .6
7.4 Shielding electrode .7
7.5 Insulating liquids .7
7.6 Dimensions .7
7.7 Protection against corrosion .7
7.8 Measuring tap .7
7.9 Earthing .7
7.10 Sealing cap .7
7.11 Dummy plug.7
7.12 Material compatibility .8
8 Tests .8
8.1 General .8
8.2 Tests on sockets .8
8.3 Factory tests on the transformer.8
8.4 Tests after installation of the cable system .9
Annex A (informative) . 13
Dielectric tests on sockets . 13
A.1 General . 13
A.2 Type approval tests . 13
A.3 Routine tests . 13
Bibliography . 14
Figures
Figure 1 – Limits of supply between transformer and dry-type cable termination . 10
Figure 2 – Typical arrangement of cable connection assemblies . 11

---------------------- Page: 4 ----------------------

SIST EN 50299-2:2015
 - 3 - EN 50299-2:2014
Foreword
This document (EN 50299-2:2014) has been prepared by CLC/TC 14 "Power transformers".

The following dates are fixed:

(dop) 2015-10-13
• latest date by which this document has
to be implemented at national level by
publication of an identical national
standard or by endorsement
• latest date by which the national (dow) 2017-10-13
standards conflicting with this
document have to be withdrawn

This document partially supersedes EN 50299:2002, together with EN 50299-1:2014.

The new standard EN 50299-2 is issued which describes requirements for dry-type cable terminations only.

Dimensions mentioned in EN 50299-1 are valid for fluid-filled cable terminations. Dry-type cable terminations
may also fit to these requirements.

_______________

---------------------- Page: 5 ----------------------

SIST EN 50299-2:2015
EN 50299-2:2014 - 4 -
1 Scope
This European Standard covers the oil-immersed single-phase connection assemblies of cables for
transformers and reactors designed in accordance with EN 60076 series.
NOTE The term "transformer" is used as common definition for transformer and reactor.
If no separate cable connection box is used and dry-type cable terminations are directly installed into the
transformer tank the requirements of this standard should be followed.
The purpose of EN 50299-2 is to establish for the cable connection assemblies:
• electrical and mechanical requirements including interchangeability;
• limits of supply;
• tests to be carried out.
It complements and amends, if necessary, the relevant standards and applies to dry-type cable terminations
for power cables with extruded insulation which may be used with similar interfaces for the cable entrance in
switchgear applications according to EN 62271-209.
This standard applies to oil-filled cable connection boxes of transformers with highest voltage for equipment
from U = 72,5 kV to 550 kV, including the conductor current terminal with removable link between the
m
transformer and the dry-type cable termination.
2 Normative references
The following documents, in whole or in part, are normatively referenced in this document and are
indispensable for its application. For dated references, only the edition cited applies. For undated references,
the latest edition of the referenced document (including any amendments) applies.
EN 60076 Series Power transformers (IEC 60076 Series)
EN 60076-3:2013 Power transformers —Part 3: Insulation levels, dielectric tests and external clearances in
air (IEC 60076-3:2013)
EN 60296 Fluids for electrotechnical applications — Unused mineral insulating oils for transformers
and switchgear (IEC 60296)
EN 60422 Mineral insulating oils in electrical equipment — Supervision and maintenance guidance
(IEC 60422)
EN 60529 Degrees of protection provided by enclosures (IP code) (IEC 60529)
EN 61099 Insulating liquids — Specifications for unused synthetic organic esters for electrical
purposes (IEC 61099)
EN ISO 1302 Geometrical product specifications (GPS) — Indication of surface texture in technical
product documentation (ISO 1302)
IEC 60076-7 Power transformers — Part 7: Loading guide for oil-immersed power transformers
IEC 60840 Power cables with extruded insulation and their accessories for rated voltages above
30 kV (U = 36 kV) up to 150 kV (U = 170 kV) — Test methods and requirements
m m
IEC 62067 Power cables with extruded insulation and their accessories for rated voltages above
150 kV (U = 170 kV) up to 500 kV (U = 550 kV) — Test methods and requirements
m m
HD 632 S2 Power cables with extruded insulation and their accessories for rated voltages above
36 kV (U = 42 kV) up to 150 kV (U = 170 kV)
m m

---------------------- Page: 6 ----------------------

SIST EN 50299-2:2015
 - 5 - EN 50299-2:2014

3 Terms and definitions
For the purposes of this document, the following terms and definitions apply.
3.1
cable connection assembly
combination of a dry-type cable termination and a cable connection box which mechanically and electrically
connects the cable to the transformer
3.1.1
dry-type cable termination
cable termination which comprises an elastomeric electrical stress control component in intimate contact with
a separating insulation barrier (insulator or socket) between the extruded cable insulation and the liquid
insulation of the transformer cable connection box. The cable termination does not require any insulating fluid
3.1.1.1
socket
part to be installed in the cable connection box to plug the cable connector. Insulating barrier (socket)
between cable connector and the insulating fluid of the cable connection box enabling the mechanical and
electrical connection to the transformer
3.1.1.2
plug-in cable connector
equipment fitted to the end of a cable to ensure in combination with the socket an electrical connection to the
transformer
3.1.1.3
dummy plug
insulating device for voltage proof sealing of the socket
3.1.1.4
sealing cap
for protection of the socket against environmental conditions
3.1.2
cable connection box
part of the transformer which houses the dry-type cable termination and the conductor current terminal with
removable link
3.1.2.1
conductor current terminal with removable link
interface to the transformer with removable connection between transformer and socket which allows the
transformer to be electrically separated from the cable
4 Limits of supply
The limits of supply between the transformer and the dry-type cable termination are defined in Figure 1. The
manufacturer of the dry-type cable termination supplies the parts inside of the dotted line. The manufacturer
of the transformer supplies the other components. Typically, the socket will be installed in the cable
connection box by the transformer manufacturer. For details refer to table of Figure 1.
5 Rated values
When dimensioning the cable connection assembly the following rated values shall apply:
a) highest voltage for equipment (U );
m
b) rated currents (I );
r
c) rated short-time and peak withstand currents;
d) rated durat
...