Electrical installations of buildings -- Part 7-740: Requirements for special installations or locations - Temporary electrical installations for structures, amusement devices and booths at fairgrounds, amusement parks and circuses

Specifies the minimum electrical installation requirements to facilitate the safe design, installation and operation of mobile, temporarily or permanently installed electrical machines and structure which incorporate electrical equipment. The machines and structures are intended to be installed repeatedly, without loss of safety, temporarily or permanently, at fairgrounds, amusement parks, cirsuses or any other places.

Elektrische Anlagen von Gebäuden -- Teil 7-740: Anforderungen für Betriebsstätten, Räume und Anlagen besonderer Art -- Vorübergehend errichtete elektrische Anlagen für Aufbauten, Vergnügungseinrichtungen und Buden auf Kirmesplätzen, Vergnügungsparks und für Zirkusse

Installations électriques des bâtiments -- Partie 7-740: Règles pour les installations ou emplacements spéciaux - Installations électriques temporaires de structures, jeux et baraques dans des champs de foire, des parcs de loisirs et des cirques

Donne les prescriptions minimales assurant une conception, une mise en oeuvre et un fonctionnement sûrs des machines électriques et des structures incorporant des matériels électriques, mobiles et d'installation temporaire ou permanente. Les machines et les structures sont destinées à être mises en oeuvre de manière répétée sans perte de sécurité, de façon temporaire ou permanente, dans des champs de foire, des parcs de loisirs, des cirques ou dans tout autre emplacement. Définit les prescriptions pour les installations électriques relatives aux structures et aux machines, lesquelles font soit partie des dispositifs de loisirs ou en constituent l'ensemble. N'est pas applicable aux équipements électriques des machines (voir EN 60204-1).

Električne inštalacije zgradb - 7-740. del: Zahteve za posebne inštalacije ali lokacije - Začasne električne inštalacije za objekte, zabaviščne naprave in stojnice na sejmiščih, v zabaviščnih parkih in cirkusih (IEC 60364-7-740:2000, spremenjen)

Navaja minimalne električno inštalacijske zahteve, ki omogočajo varno sestavo, inštalacijo in delovanje prenosnih, začasnih ali stalno inštaliranih električnih strojev in konstrukcij, vključenih v električno opremo. Stroji in konstrukcije so namenjene, za ponavljajoče inštaliranje, brez zmanjšanja varnosti, začasne ali stalne, na sejmiščih, zabaviščnih parkih, cirkusih in ostalih mestih.

General Information

Status
Published
Publication Date
31-Dec-2006
Current Stage
6060 - National Implementation/Publication (Adopted Project)
Start Date
01-Jan-2007
Due Date
01-Jan-2007
Completion Date
01-Jan-2007

Relations

Buy Standard

Standardization document
HD 60364-7-740:2007
English language
16 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

6/29(16., 6,67+'

67$1'$5'
MDQXDU
(OHNWULþQHLQãWDODFLMH]JUDGEGHO=DKWHYH]DSRVHEQHLQãWDODFLMHDOL
ORNDFLMH=DþDVQHHOHNWULþQHLQãWDODFLMH]DREMHNWH]DEDYLãþQHQDSUDYHLQ
VWRMQLFHQDVHMPLãþLKY]DEDYLãþQLKSDUNLKLQFLUNXVLK ,(&
VSUHPHQMHQ
LVWRYHWHQ+'
(OHFWULFDOLQVWDOODWLRQVRIEXLOGLQJV3DUW5HTXLUHPHQWVIRUVSHFLDO
LQVWDOODWLRQVRUORFDWLRQV7HPSRUDU\HOHFWULFDOLQVWDOODWLRQVIRUVWUXFWXUHV
DPXVHPHQWGHYLFHVDQGERRWKVDWIDLUJURXQGVDPXVHPHQWSDUNVDQGFLUFXVHV
,(&PRGLILHG
,&6 5HIHUHQþQDãWHYLOND

6,67+' HQ
!"#$%&’( )&!*+,%- .

---------------------- Page: 1 ----------------------

HARMONIZATION DOCUMENT
HD 60364-7-740

DOCUMENT D'HARMONISATION
August 2006
HARMONISIERUNGSDOKUMENT

ICS 20.020; 91.140.50


English version


Electrical installations of buildings
Part 7-740: Requirements for special installations or locations –
Temporary electrical installations for structures, amusement devices
and booths at fairgrounds, amusement parks and circuses
(IEC 60364-7-740:2000, modified)


Installations électriques des bâtiments Elektrische Anlagen von Gebäuden
Partie 7-740: Règles pour les installations Teil 7-740: Anforderungen für
ou emplacements spéciaux – Betriebsstätten, Räume und Anlagen
Installations électriques temporaires besonderer Art –
de structures, jeux et baraques Vorübergehend errichtete elektrische
dans des champs de foire, des parcs Anlagen für Aufbauten,
de loisirs et des cirques Vergnügungseinrichtungen und Buden
(CEI 60364-7-740:2000, modifiée) auf Kirmesplätzen, Vergnügungsparks
und für Zirkusse
(IEC 60364-7-740:2000, modifiziert)



This Harmonization Document was approved by CENELEC on 2005-10-01. CENELEC members are bound to
comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for implementation of this
Harmonization Document at national level.

Up-to-date lists and bibliographical references concerning such national implementations may be obtained on
application to the Central Secretariat or to any CENELEC member.

This Harmonization Document exists in three official versions (English, French, German).

CENELEC members are the national electrotechnical committees of Austria, Belgium, Cyprus, the Czech
Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia,
Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain,
Sweden, Switzerland and the United Kingdom.

CENELEC
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung

Central Secretariat: rue de Stassart 35, B - 1050 Brussels


© 2006 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members.
Ref. No. HD 60364-7-740:2006 E

---------------------- Page: 2 ----------------------

HD 60364-7-740:2006 – 2 –
Foreword
The text of the International Standard IEC 60364-7-740:2000, prepared by IEC TC 64, Electrical
installations and protection against electric shock, together with the common modifications prepared
by SC 64B, Protection against thermal effects, of Technical Committee CENELEC TC 64, Electrical
installations and protection against electric shock, was submitted to the formal vote and was
approved by CENELEC as HD 60364-7-740 on 2005-10-01.
The following dates were fixed:
- latest date by which the existence of the HD (doa) 2006-04-01
has to be announced at national level
- latest date by which the HD has to be implemented (dop) 2007-03-01
at national level by publication of a harmonized
national standard or by endorsement
- latest date by which the national standards conflicting (dow) 2008-10-01
with the HD have to be withdrawn
Annexes ZA, ZB and ZC have been added by CENELEC.
Clauses, subclauses, notes, tables, figures and annexes which are additional to those of
IEC 60364-7-740 are prefixed "Z".
In this standard, the common modifications to the International Standard are indicated by a vertical
line in the left margin of the text.

---------------------- Page: 3 ----------------------

– 3 – HD 60364-7-740:2006
Introduction
The requirements of this part of HD 60364 modify or replace certain of the general requirements of
HD 60364.
The clause numbering of Part 7-740 follows the pattern and corresponding references of IEC 60364.
The numbers following the particular number of Part 7-740 are those of the corresponding parts or
clauses of IEC 60364.
The absence of reference to a part or a clause means that the general requirements of HD 60364
are applicable.
Numbering in parenthesis corresponds to the numbering of the “non restructured” IEC 60364 dated
before 2002.
740.1 (740.11) Scope, object and fundamental principles
740.1.1 (740.11) Scope
Add:
This part of HD 60364 specifies the minimum electrical installation requirements to facilitate the
safe design, installation and operation of temporarily installed mobile or transportable electrical
machines and structures which incorporate electrical equipment. The machines and structures are
intended to be installed repeatedly, without loss of safety, temporarily, at fairgrounds, amusement
parks, circuses or similar places.
NOTE Z1 The permanent electrical installation is excluded from the scope.

The object of this part of HD 60364 is to define the electrical installation requirements for such
structures and machines, being either integral parts or constituting the total amusement device.
This part does not apply to the electrical equipment of machines (see EN 60204-1).
NOTE Z2 See also Annex ZA.
740.1.2 (740.12) Normative references
Add:
The following referenced documents are indispensable for the application of this document. For
dated references, only the edition cited applies. For undated references, the latest edition of the
referenced document (including any amendments) applies.
NOTE Where an international publication has been modified by common modifications, indicated by (mod), the relevant
EN/HD applies.

---------------------- Page: 4 ----------------------

HD 60364-7-740:2006 – 4 –
Publication Year Title EN/HD Year
  Cables of rated voltages up to and including HD 22.8 S2
450/750 V and having cross-linked insulation
Part 8: Polychloroprene or equivalent synthetic
elastomer sheathed cable for decorative chains
  Cable trunking systems and cable ducting systems EN 50085 Series
for electrical installations
  Conduit systems for cable management EN 50086 Series
  Common test methods for cables under fire EN 50265 Series
conditions – Test for resistance to vertical flame
propagation for a single insulated conductor or
cable
IEC 60050-826 International Electrotechnical Vocabulary (IEV) - - -
Chapter 826: Electrical installations of buildings
IEC 60309-1 Plugs, socket-outlets and couplers for industrial EN 60309-1
purposes - Part 1: General requirements
IEC 60309-2 Plugs, socket-outlets and couplers for industrial EN 60309-2
purposes - Part 2: Dimensional interchangeability
requirements for pin and contact-tube accessories
IEC 60364-3 Electrical installations of buildings - Part 3: HD 384.3 S2
(mod.) Assessment of general characteristics
IEC 60364-4-41 Low-voltage electrical installations – Part 4-41: HD 60364-4-41
(mod.) Protection for safety - Protection against electric
shock
IEC 60364-5-54 Electrical installations of buildings -- Part 5-54: HD 60364-5-54
(mod.) Selection and erection of electrical equipment -
Earthing arrangements, protective conductors and
protective bonding conductors
IEC 60947-2 Low-voltage switchgear and controlgear - Part 2: EN 60947-2
Circuit-breakers
IEC 61008-1 Residual current operated circuit-breakers without EN 61008-1
(mod.) integral overcurrent protection for household and
similar uses (RCCBs) – Part 1: General rules
IEC 61009-1 Residual current operated circuit-breakers with EN 61009-1
(mod.) integral overcurrent protection for household and
similar uses (RCBOs) – Part 1: General rules
IEC 61347-2-2 Lamp controlgear - Part 2-2: Particular EN 61347-2-2
requirements for d.c. or a.c. supplied electronic
step-down convertors for filament lamps

---------------------- Page: 5 ----------------------

– 5 – HD 60364-7-740:2006
Publication Year Title EN/HD Year
IEC 61386-21 Conduit systems for cable management - Part 21: EN 61386-21
Particular requirements - Rigid conduit systems
IEC 61537 Cable tray systems and cable ladder systems for EN 61537
cable management
IEC 61558-2-4 Safety of power transformers, power supply units EN 61558-2-4
and similar - Part 2-4: Particular requirements for
isolating transformers for general use
IEC 61558-2-6 Safety of power transformers, power supply units EN 61558-2-6
and similar - Part 2-6: Particular requirements for
safety isolating transformers for general use
740.2 (740.B.1.0) Definitions
For the purpose of this part of HD 60364, the definitions given in IEC 60050-826 as well as the
following definitions apply:
740.2.1
fairground
area where one or more stands, amusement devices or booths are erected for leisure use
740.2.2
booth
non-stationary unit, intended to accommodate equipment generally for pleasure or demonstration
purposes
740.2.3
stand
area or temporary structure used for display, marketing, sales or entertainment
740.2.4
amusement device
ride, stand, textile or membrane building, side stall, side show, tent, booth or grandstand intended
for the entertainment of the public
740.2.Z1
temporary electrical installation
electrical installation erected and dismantled at the same time as the structure with which it is
associated
740.3 Assessment of general characteristics
740.31 Purposes, supplies and structure
740.313 Supplies
740.313.1.3 Voltage
The nominal supply voltage of a temporary electrical installation in a booth, stand or amusement
device shall not exceed 230 V / 400 V a.c or 440 V d.c.

---------------------- Page: 6 ----------------------

HD 60364-7-740:2006 – 6 –
740.313.3 Supply from the public network
Irrespective of the number of sources of supply, the phase and neutral conductors from different
sources shall not be interconnected downstream of the origin of the temporary electrical installation
(see Annex ZA). The instructions of the supply network operator shall be followed.
740.4 Protection for safety
740.41 Protection against electric shock
740.412 Protection against electric shock in normal service
        (Protection against direct contact, or basic protection)
740.412.5 Additional protection by residual current devices
Add:
Every final circuit for
- lighting
- socket-outlets rated up to 32 A and
- portable equipment connected by means of flexible cable or cord with a current-carrying
capacity up to 32 A
shall be additionally protected by an RCD with a rated residual operating current not exceeding
30 mA.
NOTE Z1 The requirements for additional protection relates to the increased risk of damage to cables.
The supply of battery operated emergency lighting circuit(s) shall be connected to the same RCD
protecting the lighting circuit(s).
These requirements do not apply to
- circuits protected by SELV or PELV, or
- circuits protected by electrical separation, or
- lighting circuits placed out of arm’s reach provided they are not supplied by socket-outlets for
household or similar purposes or socket-outlets according to EN 60309-1.
740.413 Protection against electric shock under fault condition
        (Protection against indirect contact, or fault protection)
740.413.1 Protection by automatic disconnection of supply
NOTE For supplies to a.c. motors, RCDs when used, should be of the time delayed type in accordance with EN 60947-2 or be of the
S-type in accordance with EN 61008-1 or EN 61009-1.
740.413.1.3 TN systems
Add:
Where the type of system earthing is TN, a PEN conductor shall not be used downstream of the
origin of the temporary electrical installation (see Annex ZA).

---------------------- Page: 7 ----------------------

– 7 – HD 60364-7-740:2006
740.413.1.5 IT systems
Add:
Where an alternative system is available, an IT system shall not be used. An IT system, however,
may be used for d.c. applications where continuity of service is needed.
NOTE Z1 In Norway IT system is commonly used for public distribution system.
740.413.1.6 Supplementary equipotential bonding
740.413.1.6.1
Add:
In a location intended for animals, local supplementary equipotential bonding shall connect all
exposed-conductive-parts and extraneous-conductive-parts which can be touched simultaneously.
740.462 (740.536) Isolation
740.462.1 (740.536.2.1.1)
Add:
Every separate temporary electrical installation for an amusement device and each distribution
circuit supplying an outdoor installation shall be provided with its own readily accessible and
properly identified means of isolation.
740.47 Application of protective measures for safety
740.471 Measures of protection against electric shock
740.471.1 (740.412.3) Protection against electric shock in normal service
Replace:
The protective measure against direct contact by means of obstacles (see Clause 412.3 of
HD 384.4.41) shall not be used.
Placing out of arm’s reach is acceptable for electric dodgems (see 740.55.09).
740.471.2 (740.413.3) Protection against electric shock in case of fault
Replace:
The protective measure against indirect contact by non-conducting location (see Clause 413.3 of
HD 384.4.41) and by earth-free equipotential bonding (see Clause 413.4 of HD 384.4.41) shall not
be used.

---------------------- Page: 8 ----------------------

HD 60364-7-740:2006 – 8 –
740.48 Choice of protective measures as a function of external influences
740.481 Selection of measures for protection against electric shock in relation to external
influences
784.481.1 General
740.481.1.4
Deleted
740.481.3 Choice of protective measures against indirect contact
740.481.3.1.3 (740.410.3.4.3)
Automatic disconnection of supply to the temporary electrical installation shall be provided at the
origin of the installation by an RCD with a rated residual operating current not exceeding 300 mA
w
...

Questions, Comments and Discussion