EN 15502-2-1:2022
(Main)Gas-fired central heating boilers - Part 2-1: Specific standard for type C appliances and type B2, B3 and B5 appliances of a nominal heat input not exceeding 1 000 kW
Gas-fired central heating boilers - Part 2-1: Specific standard for type C appliances and type B2, B3 and B5 appliances of a nominal heat input not exceeding 1 000 kW
This document specifies the requirements and test methods, as well as the classification and marking of gas-fired central heating boilers that are fitted with atmospheric burners, fan assisted atmospheric burners or fully premixed burners, and are hereafter referred to as "boilers".
This document is intended to be used in conjunction with EN 15502-1:2021.
This document covers gas-fired central heating boilers from the types C1 up to C(11) and the types B2, B3 and B5:
NOTE 1 For further background information on appliance types see EN 1749:2020.
a) that have a nominal heat input (on the basis of net calorific value) not exceeding 1 000 kW;
b) that use one or more combustible gases of the three gas families at the pressures stated in EN 437:2021;
c) where the temperature of the heat transfer fluid does not exceed 105 °C during normal operation;
d) where the maximum operating pressure in the water circuit does not exceed 6 bar;
e) which can give rise to condensation under certain circumstances;
f) which are declared in the instructions for installation to be either a "condensing" boiler or a "low temperature boiler" or a "standard boiler"; if no declaration is given the boiler is to be considered a "standard boiler";
g) which are intended to be installed inside a building or in a partially protected place;
h) which are intended to produce also hot water either by the instantaneous or storage principle as a single unit;
i) which are designed for either sealed water systems or for open water systems;
j) which are either modular boilers, or non-modular boilers.
k) which are from the types C(10) that are equipped with a gas-air ratio control and that have a ∆pmax, saf(min) of 25 Pa, and C(11) that have condensing boiler modules that are equipped with a gas-air ratio control and that have a ∆pmax, saf(min) of 25 Pa.
NOTE 2 This document provides requirements for boilers with known constructions. For boilers with any alternative constructions, which might not fully be covered by this standard, the risk associated with this alternative construction needs to be assessed.
An example of an assessment methodology, based upon risk assessment, is given in Clause 11.
This document does not cover all the requirements for:
aa) appliances above 1 000 kW;
ab) appliances that are intended to be connected to gas grids where the quality of the distributed gas is likely to vary to a large extent over the lifetime of the appliance (see Annex AB of EN 15502-1:2021);
ac) appliances using flue dampers;
ad) appliances of the types B21, B31, B51, C21, C41, C51, C61, C71, C81, C(12) and C(13);
ae) C7 appliances that have a nominal heat input (on the basis of net calorific value) exceeding 70 kW;
af) appliances incorporating flexible plastic flue liners;
ag) C(10) boilers:
1) without a gas-air ratio control, or
2) which are non-condensing appliances, or
3) which have a maximum safety pressure difference at minimum heat input not equal to 25 Pa (∆pmax, saf(min));
ah) C(11) boilers that have boiler modules:
1) without a gas-air ratio control, or
2) which are non-condensing appliances, or
3) which have a maximum safety pressure difference at minimum heat input not equal to 25 Pa (∆pmax, saf(min));
ai) appliances intended to be connected to a flue having mechanical extraction;
aj) surface temperatures of external parts particular to children and elderly people;
ak) appliances that are intended to burn natural gases of the second family where hydrogen is added to the natural gas;
al) appliances equipped with an adaptive combustion control function (ACCF);
am) boilers intended to be installed in areas accessible to elderly people and children.
Heizkessel für gasförmige Brennstoffe - Teil 2-1: Heizkessel der Bauart C und Heizkessel der Bauarten B2, B3 und B5 mit einer Nennwärmebelastung nicht größer als 1 000 kW
Dieses Dokument legt Anforderungen und Prüfmethoden sowie die Klassifizierung und Kennzeichnung von gasbefeuerten Heizkesseln fest, die mit atmosphärischen Brennern mit oder ohne Gebläse oder mit Vormischbrenner ausgerüstet sind und nachfolgend kurz "Kessel" genannt werden.
Dieses Dokument ist in Verbindung mit EN 15502-1:2021 zu verwenden.
Dieses Dokument schließt gasbefeuerte Zentralheizungskessel der Bauarten C1 bis C11 und die Bauarten B2, B3 und B5 ein:
ANMERKUNG 1 Zu weiteren Hintergrundinformationen zu Gerätearten siehe EN 1749:2020.
a) die eine Nennwärmebelastung (bezogen auf den Heizwert) von nicht mehr als 1 000 kW haben;
b) die mit einem oder mehreren brennbaren Gasen der drei Gasfamilien mit den in EN 437:2021 genannten Drücken betrieben werden;
c) bei denen die Temperatur der Wärme leitenden Flüssigkeit unter normalen Betriebsbedingungen 105 °C nicht überschreitet;
d) deren maximaler wasserseitiger Betriebsdruck 6 bar nicht überschreitet;
e) bei denen sich unter bestimmten Bedingungen Kondenswasser bilden kann;
f) die in der Installationsanleitung entweder als „Brennwertgeräte“, als „Niedertemperaturkessel“ oder als „Standardkessel“ bezeichnet werden. Wenn keine Angabe gemacht wird, wird der Kessel als „Standardkessel“ betrachtet;
g) die dafür vorgesehen sind, im Gebäude oder an einer teilweise geschützten Stelle aufgestellt zu werden;
h) die dafür vorgesehen sind, nach dem Durchlaufprinzip oder nach dem Speicherprinzip auch Warmwasser als eine Einheit herzustellen;
i) die entweder für geschlossene oder offene Wassersysteme ausgelegt sind;
j) die entweder modulare oder nicht modulare Kessel sind.
k) die von der Art C(10) sind, die mit einem Regel- und Steuergerät für das Gas-Luft-Druckverhältnis ausgestattet sind und ein ∆pmax, saf(min) von 25 Pa haben, sowie C(11) mit Brennwertkesselmodulen, ausgestattet mit einem Regel- und Steuergerät für das Gas-Luft-Druckverhältnis und mit einem ∆pmax, saf(min) von 25 Pa.
ANMERKUNG 2 Dieses Dokument gibt Anforderungen an Kessel mit bekannter Bauweise an. Für Kessel mit alternativer Bauweise, die eventuell nicht vollständig durch diese Norm abgedeckt werden, muss das Risiko, das mit dieser alternativen Bauweise verbunden ist, bewertet werden.
Ein Beispiel für ein Bewertungsverfahren, das auf einer Risikoanalyse beruht, wird in Abschnitt 11 beschrieben.
Dieses Dokument behandelt nicht alle Anforderungen an:
aa) Geräte über 1 000 kW;
ab) Geräte, die dafür ausgelegt sind, an ein Gasnetz angeschlossen zu werden, in dem die Qualität des verteilten Gases über die Lebensdauer des Gerätes wahrscheinlich stark schwankt (siehe Anhang AB von EN 15502-1:2021);
ac) Geräte, die Abgasklappen nutzen;
ad) Geräte der Arten B21, B31, B51, C21, C41, C51, C61, C71, C81, C(12) und C(13);
ae) C7-Geräte, die eine Nennwärmebelastung (auf Basis des Heizwertes) von 70 kW überschreiten;
af) Geräte, die flexible Kunststoffabzüge beinhalten;
ag) C(10)-Kessel:...
Chaudières de chauffage central utilisant les combustibles gazeux - Partie 2-1 : Norme spécifique pour les appareils de type C et les appareils de types B2, B3 et B5 dont le débit calorifique nominal est inférieur ou égal à 1 000 kW
Le présent document spécifie les exigences et les méthodes d'essai, ainsi que la classification et le marquage des chaudières de chauffage central utilisant les combustibles gazeux et étant équipées de brûleurs atmosphériques, de brûleurs atmosphériques avec ventilateur ou de brûleurs à pré-mélange total, ci-après dénommées « chaudières ».
Le présent document est à utiliser conjointement avec l'EN 15502-1:2021.
Le présent document s'applique à certaines chaudières de types C1 à C(11), et des types B2, B3 et B5 :
NOTE 1 Pour plus d'informations sur les types d'appareils, voir l'EN 1749:2020.
a) de débit calorifique nominal (sur la base du pouvoir calorifique inférieur) inférieur à 1 000 kW ;
b) utilisant un ou plusieurs combustibles gazeux appartenant aux trois familles de gaz et aux pressions indiquées dans l'EN 437:2021 ;
c) dont la température du fluide caloporteur ne dépasse pas 105 °C en fonctionnement normal ;
d) dont la pression maximale de fonctionnement dans le circuit d'eau ne dépasse pas 6 bar ;
e) pouvant condenser dans certaines circonstances ;
f) déclarées dans la notice d'installation comme étant « chaudière à condensation » ou « chaudière à basse température » ou « chaudière standard » par le fabricant ; en l'absence d'information la chaudière est considérée comme « chaudière standard » ;
g) destinées à être installées dans un bâtiment ou à un emplacement partiellement protégé ;
h) destinées à produire aussi instantanément de l'eau chaude ou capables de la stocker, sous forme de monobloc ;
i) conçues pour un système avec circuit d'eau fermé ou ouvert ;
j) modulaires ou non ;
k) de type C(10) équipées d'un dispositif de contrôle du rapport air/gaz de ∆pmax, saf(min) de 25 Pa, et de type C(11) constituées de modules de chaudière à condensation équipées d'un dispositif de contrôle du ratio air/gaz de ∆pmax, saf(min) de 25 Pa.
NOTE 2 Le présent document fournit les exigences relatives aux chaudières dont la construction est connue. Pour les chaudières de construction différentes, susceptibles de ne pas être couvertes par la présente norme, le risque associé à cette construction différente doit être évalué.
L'Article 11 donne un exemple de méthodologie d'évaluation basée sur l'évaluation des risques.
Le présent document ne couvre pas toutes les exigences relatives :
aa) aux appareils d'une puissance supérieure à 1 000 kW ;
ab) aux appareils destinés à être raccordés au réseau de gaz lorsque la qualité du gaz distribué peut varier de façon importante pendant la durée de vie de l'appareil (voir l'Annexe AB de l'EN 15502 1:2021) ;
ac) aux appareils munis de registres ;
ad) aux appareils des types B21, B31, B51, C21, C41, C51, C61, C71, C81, C(12) et C(13) ;
ae) aux appareils de type C7 de débit calorifique nominal (basé sur le pouvoir calorifique inférieur) supérieur à 70 kW ;
af) aux appareils utilisant un conduit flexible en plastique pour l'évacuation des produits de combustion ;
ag) aux chaudières de type C(10) :
1) non équipées de dispositif de régulation du rapport air/gaz ; ou
2) qui ne sont pas des chaudières à condensation ; ou
3) qui ont une différence de pression maximale de sécurité au débit calorifique minimal inférieure à 25 Pa (∆pmax, saf(min)) ;
ah) aux chaudières de type C(11), avec des modules de chaudière :
1) non équipées de dispositif de régulation du rapport air/gaz ; ou
2) qui ne sont pas des chaudières à condensation ; ou
3) qui ont une différence de pression maximale de sécurité au débit calorifique minimal inférieure à 25 Pa (∆pmax, saf(min)) ;
ai) aux appareils destinés à être raccordés à un conduit d'évacuation des produits de combustion muni d'un dispositif d'extraction ;
aj) aux températures de surface des surfaces extérieures, en particulier pour les enfants et les personnes âgées ;
...
Plinski kotli za centralno ogrevanje - 2-1. del: Poseben standard za tip kotlov C in tipe kotlov B2, B3 in B5 z nazivno močjo do vključno 1000 kW
General Information
Relations
Standards Content (Sample)
SLOVENSKI STANDARD
01-december-2022
Nadomešča:
SIST EN 15502-2-1:2013+A1:2017
Plinski kotli za centralno ogrevanje - 2-1. del: Poseben standard za tip kotlov C in
tipe kotlov B2, B3 in B5 z nazivno močjo do vključno 1000 kW
Gas-fired central heating boilers - Part 2-1: Specific standard for type C appliances and
type B2, B3 and B5 appliances of a nominal heat input not exceeding 1 000 kW
Heizkessel für gasförmige Brennstoffe - Teil 2-1: Heizkessel der Bauart C und Heizkessel
der Bauarten B2, B3 und B5 mit einer Nennwärmebelastung nicht größer als 1 000 kW
Chaudières de chauffage central utilisant les combustibles gazeux - Partie 2-1 : Norme
spécifique pour les appareils de type C et les appareils de types B2, B3 et B5 dont le
débit calorifique nominal est inférieur ou égal à 1 000 kW
Ta slovenski standard je istoveten z: EN 15502-2-1:2022
ICS:
27.060.30 Grelniki vode in prenosniki Boilers and heat exchangers
toplote
91.140.10 Sistemi centralnega Central heating systems
ogrevanja
97.100.20 Plinski grelniki Gas heaters
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
EN 15502-2-1
EUROPEAN STANDARD
NORME EUROPÉENNE
September 2022
EUROPÄISCHE NORM
ICS 27.060.30; 91.140.10 Supersedes EN 15502-2-1:2012+A1:2016
English Version
Gas-fired central heating boilers - Part 2-1: Specific
standard for type C appliances and type B2, B3 and B5
appliances of a nominal heat input not exceeding 1 000 kW
Chaudières de chauffage central utilisant les Heizkessel für gasförmige Brennstoffe - Teil 2-1:
combustibles gazeux - Partie 2-1 : Norme spécifique Heizkessel der Bauart C und Heizkessel der Bauarten
pour les appareils de type C et les appareils de types B2, B3 und B5 mit einer Nennwärmebelastung nicht
B2, B3 et B5 dont le débit calorifique nominal est größer als 1 000 kW
inférieur ou égal à 1 000 kW
This European Standard was approved by CEN on 24 July 2022.
CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this
European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references
concerning such national standards may be obtained on application to the CEN-CENELEC Management Centre or to any CEN
member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by
translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC Management
Centre has the same status as the official versions.
CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,
Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway,
Poland, Portugal, Republic of North Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland, Türkiye and
United Kingdom.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION
EUROPÄISCHES KOMITEE FÜR NORMUNG
CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Brussels
© 2022 CEN All rights of exploitation in any form and by any means reserved Ref. No. EN 15502-2-1:2022 E
worldwide for CEN national Members.
Contents Page
European foreword . 6
Introduction .10
1 Scope .11
2 Normative references .12
3 Terms, definitions and symbols .14
3.1 Terms and definitions .14
3.2 Symbols .15
4 Classification .15
5 Construction .15
5.1 General .15
5.2 Conversion to different gases .15
5.3 Materials .15
5.4 Method of construction .15
5.4.1 Design .15
5.4.2 Checking the state of operation .15
5.4.3 Use and servicing .15
5.4.4 Connections to the gas and water pipes .15
5.4.5 Soundness .15
5.4.6 Supply of combustion air and evacuation of the combustion products .15
5.4.7 Dampers .16
5.4.8 Air proving .16
5.4.9 Gas/air ratio controls .16
5.4.10 Fan .17
5.4.11 Drainage .17
5.4.12 Operational safety in the event of failure of the auxiliary energy .17
5.4.13 Special provision for low temperature boilers and condensing boilers .17
5.5 Burners .17
5.6 Pressure test points.17
5.7 Requirements for the application of control and safety devices .17
5.8 Additional requirements for modular boilers .17
5.8.101 Additional requirements for non-return valves in type C boilers and C
(10) (11)
boiler modules .17
6 Electrical safety .17
7 Controls .17
8 Operational requirements .17
8.1 General .17
8.1.1 Characteristics of the reference and limit gases .18
8.1.2 General test conditions .18
8.2 Soundness .21
8.2.1 Soundness of the gas circuit .21
8.2.2 Soundness of the combustion circuit .21
8.2.3 Soundness of the water circuit .25
8.2.4 Soundness of the domestic water circuit .25
8.3 Hydraulic resistance . 25
8.4 Heat inputs and heat outputs . 25
8.4.101 Additional operational requirements for type C and C boiler modules . 26
(10) (11)
8.5 Limiting temperatures . 26
8.5.1 General . 26
8.5.2 Limiting temperatures of the adjusting, control and safety devices . 26
8.5.3 Limiting temperatures of the side walls, the front and the top . 27
8.5.4 Limiting temperature of the test panels and the floor . 27
8.5.101 External temperature of the ducts where the ducts are in contact with and or
passing through a wall . 27
8.6 Ignition, cross lighting, flame stability . 27
8.6.1 General . 27
8.6.2 Limit conditions . 27
8.6.3 Special flue conditions . 28
8.6.4 Reduction of the gas rate of the ignition burner . 30
8.6.101 Resistance to draught for type B boilers . 31
8.7 Reduction of the gas pressure . 31
8.8 Defective closure of the gas valve immediately upstream of the main burner . 31
8.9 Pre-purge . 31
8.9.101 General . 31
8.9.102 Tests and test conditions for pre-purging . 33
8.9.103 Requirements for verification of the protected nature of a combustion chamber
8.9.104 Test conditions for verification of the protected nature of a combustion
chamber . 33
8.9.105 Requirements for verification of normal ignition in a combustible air/gas
mixture for type C boilers incorporating a fan . 33
8.9.106 Test conditions for verification of normal ignition in a combustible air/gas
mixture for type C boilers incorporating a fan . 34
8.10 Functioning of a permanent ignition burner when the fan stops during the standby
time . 34
8.11 Adjustment, control and safety devices . 34
8.11.1 General . 34
8.11.2 Boilers intended to be installed in a partially protected place . 34
8.11.3 Combination boilers . 34
8.11.4 Control devices . 34
8.11.5 Ignition devices . 34
8.11.6 Flame supervision device . 34
8.11.7 Gas pressure regulator . 35
8.11.8 Thermostats and water temperature limiting devices . 35
8.11.101 Air proving . 35
8.12 Carbon monoxide . 38
8.12.1 General . 38
8.12.2 Limit conditions . 38
8.12.3 Special conditions . 39
8.12.4 Sooting . 42
8.12.5 Supplementary test for low temperature boilers and condensing boilers . 42
8.13 NO . 42
x
8.14 Special provisions for boilers intended to be installed in a partially protected place
................................................................................................................................................................... 42
8.15 Formation of condensate . 42
8.16 Temperature of combustion products . 42
8.16.101 General . 42
8.16.102 Designation and measurement of reference temperatures of flue systems .43
8.17 Sound power level .43
8.101 Mechanical resistance and stability of ducts, terminal and fitting pieces .43
8.101.1 General requirement .43
8.101.2 Compressive strength .43
8.101.3 Lateral strength .44
8.101.4 Flexible metallic liners .45
8.102 Requirements for plastic in the combustion product evacuation ducts, terminals and
fitting pieces of boilers .45
8.102.1 Thermal resistance .45
8.102.2 Materials .45
8.103 Requirements for elastomeric seals and elastomeric sealants in the combustion
product evacuation ducts, terminals and fitting pieces .51
8.103.1 Characterization .51
8.103.2 Long-term resistance to thermal load .52
8.103.3 Long-term resistance to condensate exposure .53
8.103.4 Cyclic condensate resistance test .54
8.103.5 Relaxation behaviour .54
8.103.6 Compression set .55
8.103.7 Low temperature resistance .55
8.103.8 Joints in elastomeric seals .55
8.104 Additional requirements for non-return valve for type C boilers and C boiler
(10) (11)
modules .55
8.104.1 General .55
8.104.2 Nominal working temperature at the position of the non-return valve .56
8.104.3 Leak tightness of the non-return valve .56
8.104.4 Functional durability of the non-return valve .56
8.104.5 Safety of boilers in case of a failing non-return valve .57
8.105 Additional requirements for the evaluation of the maximum heat input of the
common duct system of type C boilers.58
(11)
8.105.1 Requirements of common duct system without wind conditions .58
8.105.2 Additional requirements of common duct system due to wind influence .59
9 Useful efficiencies .60
10 Electric auxiliary energy .60
11 Risk assessment .60
12 Marking and instructions .60
12.1 Boiler marking .60
12.2 Instructions .60
12.2.1 Instructions for installation .60
12.2.2 Instructions for use and servicing .66
12.3 Presentation .66
Figures .66
Listing of tables and numbers .79
Annexes .79
Annexes A-V, AA, AB, AC and ZA .79
Annex XA (normative) Test apparatus for type C boilers .80
Annex XB (normative) Test methods to determine the effects of long-term thermal load,
long-term condensate exposure, condensing/non-condensing cycling and resistance
to UV radiation . 81
Annex XC (informative) This annex is empty on purpose . 82
Annex XD (informative) Example on calculation of common duct system for type C
(11)
boilers . 83
Annex ZA (informative) Left empty on purpose . 85
Annex ZB (informative) Clauses of this European Standard addressing the methods for the
verification of the efficiency of the EU Directive 92/42/EEC, relating to the efficiency
of new hot boilers with an output of (4 – 400) kW . 86
Annex ZC (informative) Relationship between this European Standard and the ecodesign
requirements of Commission Regulation (EU) No 813/2013 L 239/136 aimed to be
covered . 87
Annex ZD (informative) Relationship between this European Standard and the energy
labelling requirements of Commission Delegated Regulation (EU) No
811/2013 L 239/1 aimed to be covered . 90
Annex ZE (informative) Relationship between this European Standard and the essential
requirements of Regulation (EU) 2016/426 of the European Parliament and of the
Council of 9 March 2016 on appliances burning gaseous fuels and repealing
Directive 2009/142/EC aimed to be covered . 93
Bibliography . 107
European foreword
This document (EN 15502-2-1:2022) has been prepared by Technical Committee CEN/TC 109 “Central
heating boilers using gaseous fuels”, the secretariat of which is held by NEN.
This European Standard shall be given the status of a national standard, either by publication of an
identical text or by endorsement, at the latest by March 2023, and conflicting national standards shall be
withdrawn at the latest by September 2025.
Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. CEN shall not be held responsible for identifying any or all such patent rights.
This document supersedes EN 15502-2-1:2012+A1:2016.
The main technical changes compared to EN 15502-2-1:2012+A1:2016 are the following:
I) Resulting from the revision of EN 15502-1:2012+A1:2015 into EN 15502-1:2021
a) Technical changes related to eco-design and energy labelling for appliances ≤ 400 kW:
1) deletion of the requirements that can be found in the legislation itself;
2) modification of Annexes ZC and ZD.
b) New or generally reworded requirements:
1) separation between requirements and test methods into different clauses;
2) moving of additional common parts from EN 15502-2-1:2012+A1:2016 and/or
EN 15502-2-2:2014 to EN 15502-1:2021 (for example, all definitions used in the parts 2 are
moved to part 1; therefore, most of the definitions in this part are now by reference to part 1);
3) definitions added for instructions for installation, instructions for use and servicing, and
technical documentation and consequently applied throughout the document;
4) improved wording of definitions related to the air supply and combustion products circuit;
5) improved references to the Annexes Z. The Annex Z referring to the GAD has been removed and
an Annex Z referring to the GAR has been inserted;
6) only “instructions for installation” and “instructions for use and servicing” are defined; therefore,
these are the only instructions to be used in this document;
7) improved definitions “ducts / circuits”;
8) definition weighted value of the NOx concentration added. With regard to Ecodesign, it is
clarified that the emissions declared are the emissions when using the references gases.
c) Limitation of the scope compared to the standards superseded by the EN 15502 series (that were
cited in the OJEU under the GAD):
1) Types B and B appliances, as covered in EN 297:1994/A4:2004 are not covered by this
14 4
standard as there seems to be a limited market for these appliances due to the introduction of
the Ecodesign Directive that only has an exemption for B appliances.
NOTE B and B are non-condensing appliances.
14 4
2) This document does not cover all the requirements for appliances designed and constructed to
burn gas containing toxic components. In the past it was always considered that the gases were
not toxic, however this was never clearly indicated in the scope. In fact, this is not a change of
scope, but a clarification of the scope.
3) This document is not intended to cover appliances intended for connection to gas grids where
the quality of the distributed gas is likely to vary to a large extent over the lifetime of the
appliance (see Annex AB). In the past no big variation in gas quality occurred. Due to the EASEE-
gas CBP wide variations of gas quality are considered. As these were never covered in this
document, the scope is modified to make clear that these variations are not covered. In fact, this
is not a change of scope, but a clarification of the scope.
4) This document does not cover all the requirements for appliances above 1 000 kW. In fact, this
is not a change of scope, but a clarification of the scope.
5) This document does not cover all the requirements for appliances having a supplementary
heater. In fact, this is not a change of scope, but a clarification of the scope as these appliances
were never included in the past, however due to the Ecodesign Regulation it has become
necessary to mention this more explicitly.
II) Additional changes, not resulting from the revision of EN 15502-1:2012+A1:2015 into
EN 15502-1:2021
a) Technical changes related to eco-design and energy labelling for appliances ≤ 400 kW:
1) no changes.
b) New or generally reworded requirements:
1) separation between requirements and test methods in to different clauses;
2) changes resulting from moving additional common parts from EN 15502-2-1:2012+A1:2016
and/or EN 15502-2-2:2014 to EN 15502-1:2021 (for example all definitions used in the parts 2
are moved to part 1; therefore, most of the definitions in this part are now by reference to part 1);
3) the definitions for Instructions for installation, Instructions for use and servicing, and Technical
documentation are now consequently applied throughout the document;
4) an Annex Z referring to the GAR has been inserted;
5) only “instructions for installation” and “instructions for use and servicing” are defined; therefore,
these are the only instructions to be used in this document.
c) Limitation of the scope compared to the standards superseded by the EN 15502 series (that were
cited in the OJEU under the GAD):
This revision only covers the update from the EN 15502-1 and an addition of an Annex Z referring to
the GAR. This revision aimed not to introduce any new technical content. As some specific
requirements are not covered in the EN 15502-2-1:2012+A1:2016. The scope has been modified to
clarify this, stating that this standard does not include:
1) specific requirements on surface temperatures of external parts particular to children and
elderly people;
2) specific requirements on appliances that are intended to burn natural gases of the second family
where hydrogen is added to the natural gas;
3) specific requirements for appliances equipped with an adaptive combustion control function.
In fact, these changes are not a change of scope, but a clarification of the scope.
EN 15502 consists of the following parts under the general title “Gas-fired heating boilers”:
— Part 1: General requirements and tests;
— Part 2-1: Specific standard for type C appliances and type B2, B3 and B5 appliances of a nominal heat
input not exceeding 1 000 kW (this document);
—
Part 2-2: Specific standard for type B1 appliances.
Relationship between this document and EN 15502-1, Gas-fired heating boilers — Part 1: General
requirements and tests:
This document is to be used in conjunction with EN 15502-1:2021 and follows the numbering structure
of EN 15502-1:2021.
Where this European Standard states:
— shall be according to EN 15502-1:2021, (clause number) with the following modification;
— shall be according to EN 15502-1:2021, (clause number) with the following addition;
— EN 15502-1:2021, (clause number) is replaced by the following;
— EN 15502-1:2021, (clause number) is not applicable;
the relevant text of EN 15502-1:2021 is to be adapted accordingly.
This document adds clauses or subclauses to the structure of EN 15502-1:2021 which are particular to
this Part 2 standard. It should be noted that these clauses and subclauses are not indicated as an addition.
Clauses, subclauses and annexes which are additional to those in EN 15502-1:2021 are numbered
starting from 101, or designated as Annex XA, XB, XC, etc.
This document has been prepared under mandates M89/6 and M066, given to CEN by the European
Commission and the European Free Trade Association, and supports essential requirements as meant in
article 3 of EU Directive 2009/142/EC, relating to appliances burning gaseous fuels and the verification
methods valid for production and measurements, as meant in article 5.2 of EU Directive 92/42/EEC,
relating to the efficiency requirements for new hot water boilers fired with liquid or gaseous fuels, with
an output of 4 – 400 kW.
This document has been prepared under the mandates M/534 and M/535, given to CEN by the European
Commission and the European Free Trade Association to provide a means of conforming to:
— requirements of Commission Regulation (EC) No 813/2013 of 2 August 2013 implementing Directive
2009/125/EC of the European Parliament and of the Council with regard to ecodesign requirements
for space heaters and combination heaters;
— requirements of Commission Delegated Regulation (EC) No 811/2013 of 18 February 2013
supplementing Directive 2010/30/EC of the European Parliament and of the Council with regard to
energy labelling of space heaters, combination heaters, packages of space heater, temperature
control and solar device and packages of combination heater, temperature control and solar device.
For relationship with EU Directive(s) / Regulation(s), see informative Annexes ZB, ZC, ZD and ZE which
are integral parts of this document.
Any feedback and questions on this document should be directed to the users’ national standards body.
A complete listing of these bodies can be found on the CEN website.
According to the CEN-CENELEC Internal Regulations, the national standards organisations of the
following countries are bound to implement this European Standard: Austria, Belgium, Bulgaria, Croatia,
Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland,
Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Republic of North
Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland, Türkiye and the United
Kingdom.
Introduction
The basic function of gas-fired heating boiler is to generate heat by direct heat transfer in a heat
exchanger, from the combustion gasses to the water.
The boiler can include in one design more than one function. It can include for example:
— a sanitary hot water function;
— a function to supply the combustion air from the outside/open air;
— a function to dispose the combustion products to the outside/open air.
The boiler can be supplied to the market in more than one part. If the boiler is supplied to the market in
multiple parts, the boiler is the assembly of various parts according to the instructions for installation.
Boilers can be designed to be connected to specific parts of a building. Connection to a chimney and the
means of combustion air supply is particularly relevant.
Matters related to quality assurance systems, tests during production, and certificates of conformity of
auxiliary devices are not dealt with in this series of European Standards.
1 Scope
This document specifies the requirements and test methods, as well as the classification and marking of
gas-fired central heating boilers that are fitted with atmospheric burners, fan assisted atmospheric
burners or fully premixed burners, and are hereafter referred to as “boilers”.
This document is intended to be used in conjunction with EN 15502-1:2021.
This document covers gas-fired central heating boilers from the types C up to C and the types B , B
1 (11) 2 3
and B :
NOTE 1 For further background information on appliance types see EN 1749:2020.
a) that have a nominal heat input (on the basis of net calorific value) not exceeding 1 000 kW;
b) that use one or more combustible gases of the three gas families at the pressures stated in
EN 437:2021;
c) where the temperature of the heat transfer fluid does not exceed 105 °C during normal operation;
d) where the maximum operating pressure in the water circuit does not exceed 6 bar;
e) which can give rise to condensation under certain circumstances;
f) which are declared in the instructions for installation to be either a “condensing” boiler or a “low
temperature boiler” or a “standard boiler”; if no declaration is given the boiler is to be considered a
“standard boiler”;
g) which are intended to be installed inside a building or in a partially protected place;
h) which are intended to produce also hot water either by the instantaneous or storage principle as a
single unit;
i) which are designed for either sealed water systems or for open water systems;
j) which are either modular boilers, or non-modular boilers.
k) which are from the types C that are equipped with a gas-air ratio control and that have a ∆p
(10) max,
of 25 Pa, and C that have condensing boiler modules that are equipped with a gas-air ratio
saf(min) (11)
control and that have a ∆p of 25 Pa.
max, saf(min)
NOTE 2 This document provides requirements for boilers with known constructions. For boilers with any
alternative constructions, which might not fully be covered by this standard, the risk associated with this alternative
construction needs to be assessed.
An example of an assessment methodology, based upon risk assessment, is given in Clause 11.
This document does not cover all the requirements for:
aa) appliances above 1 000 kW;
ab) appliances that are intended to be connected to gas grids where the quality of the distributed gas is
likely to vary to a large extent over the lifetime of the appliance (see Annex AB of EN 15502-1:2021);
ac) appliances using flue dampers;
ad) appliances of the types B , B , B , C , C , C , C , C , C , C and C ;
21 31 51 21 41 51 61 71 81 (12) (13)
ae) C appliances that have a nominal heat input (on the basis of net calorific value) exceeding 70 kW;
af) appliances incorporating flexible plastic flue liners;
ag) C boilers:
(10)
1) without a gas-air ratio control, or
2) which are non-condensing appliances, or
3) which have a maximum safety pressure difference at minimum heat input not equal to 25 Pa
(∆p );
max, saf(min)
ah) C boilers that have boiler modules:
(11)
1) without a gas-air ratio control, or
2) which are non-condensing appliances, or
3) which have a maximum safety pressure difference at minimum heat input not equal to 25 Pa
(∆p );
max, saf(min)
ai) appliances intended to be connected to a flue having mechanical extraction;
aj) surface temperatures of external parts particular to children and elderly people;
ak) appliances that are intended to burn natural gases of the second family where hydrogen is added to
the natural gas;
al) appliances equipped with an adaptive combustion control function (ACCF);
am) boilers intended to be installed in areas accessible to elderly people and children.
2 Normative references
The following documents are referred to in the text in such a way that some or all of their content
constitutes requirements of this document. For dated references, only the edition cited applies. For
undated references, the latest edition of the referenced document (including any amendments) applies.
In this standard the normative references of Part 1 are valid. Furthermore, the following normative
references are valid:
EN 513:2018, Plastics — Poly(vinyl chloride) (PVC) based profiles — Determination of the resistance to
artificial weathering
EN 1856-2:2009, Chimneys — Requirements for metal chimneys — Part 2: Metal flue liners and connecting
flue pipes
EN 1749:2020, Classification of gas appliances according to the method of supplying combustion air and of
evacuation of the combustion products (types)
EN 13216-1:2019, Chimneys — Test methods for system chimneys — Part 1: General test methods
EN 13501-1:2018, Fire classification of construction products and building elements — Part 1:
Classification using data from reaction to fire tests
EN 14241-1:2013, Chimneys — Elastomeric seals and elastomeric sealants — Material requirements and
test methods — Part 1: Seals in flue liners
EN 14471:2013+A1:2015, Chimneys — System chimneys with plastic flue liners — Requirements and test
methods
EN 14989-1:2007, Chimneys — Requirements and test methods for metal chimneys and material
independent air supply ducts for roomsealed heating applications — Part 1: Vertical air/flue terminals for
C6-type appliances
EN 15502-1:2021, Gas-fired heating boilers — Part 1: General requirements and tests
CEN/TS 16134:2011, Chimney terminals — General requirements and material independent test methods
EN ISO 178:2019, Plastics — Determination of flexural properties (ISO 178:2019)
EN ISO 179-1:2010, Plastics — Determination of Charpy impact properties — Part 1: Non-instrumented
impact test (ISO 179-1:2010)
EN ISO 527-1:2019, Plastics — Determination of tensile properties — Part 1: General principles (ISO 527-
1:2019)
EN ISO 527-2:2012, Plastics — Determination of tensile properties — Part 2: Test conditions for moulding
and extrusion plastics (ISO 527-2:2012)
EN ISO 1183-1:2019, Plastics — Methods for determining the density of non-cellular plastics — Part 1:
Immersion method, liquid pycnometer method and titration method (ISO 1183-1:2019, Corrected version
2019-05)
EN ISO 1183-2:2019, Plastics — Methods for determining the density of non-cellular plastics — Part 2:
Density gradient column method (ISO 1183-2:2019)
EN ISO 1183-3:1999, Plastics — Methods for determining the density of non-cellular plastics — Part 3: Gas
pyknometer method (ISO 1183-3:1999)
EN ISO 9969:2016, Thermoplastics pipes — Determination of ring stiffness (ISO 9969:2016)
ISO 37:2017, Rubber, vulcanized or thermoplastic — Determination of tensile stress-strain properties
ISO 188:2011, Rubber, vulcanized or thermoplastic — Accelerated ageing and heat resistance tests
ISO 815-1:2019, Rubber, vulcanized or thermoplastic — Determination of compression set — Part 1: At
ambient or elevated temperatures
ISO 815-2:2019, Rubber, vulcanized or thermoplastic — Determination of compression set — Part 2: At low
temperatures
ISO 1817:2015, Rubber, vulcanized or thermoplastic — Determination of the effect of liquids
ISO 2781:2018, Rubber, vulcanized or thermoplastic — Determination of density
ISO 6914:2014, Rubber, vulcanized or thermoplastic — Determination of ageing characteristics by
measurement of stress relaxation in tension
ISO 48-4:2018, Rubber, vulcanized or thermoplastic — Determination of hardness — Part 4: Indentation
hardness by durometer method (Shore ha
...
Frequently Asked Questions
EN 15502-2-1:2022 is a standard published by the European Committee for Standardization (CEN). Its full title is "Gas-fired central heating boilers - Part 2-1: Specific standard for type C appliances and type B2, B3 and B5 appliances of a nominal heat input not exceeding 1 000 kW". This standard covers: This document specifies the requirements and test methods, as well as the classification and marking of gas-fired central heating boilers that are fitted with atmospheric burners, fan assisted atmospheric burners or fully premixed burners, and are hereafter referred to as "boilers". This document is intended to be used in conjunction with EN 15502-1:2021. This document covers gas-fired central heating boilers from the types C1 up to C(11) and the types B2, B3 and B5: NOTE 1 For further background information on appliance types see EN 1749:2020. a) that have a nominal heat input (on the basis of net calorific value) not exceeding 1 000 kW; b) that use one or more combustible gases of the three gas families at the pressures stated in EN 437:2021; c) where the temperature of the heat transfer fluid does not exceed 105 °C during normal operation; d) where the maximum operating pressure in the water circuit does not exceed 6 bar; e) which can give rise to condensation under certain circumstances; f) which are declared in the instructions for installation to be either a "condensing" boiler or a "low temperature boiler" or a "standard boiler"; if no declaration is given the boiler is to be considered a "standard boiler"; g) which are intended to be installed inside a building or in a partially protected place; h) which are intended to produce also hot water either by the instantaneous or storage principle as a single unit; i) which are designed for either sealed water systems or for open water systems; j) which are either modular boilers, or non-modular boilers. k) which are from the types C(10) that are equipped with a gas-air ratio control and that have a ∆pmax, saf(min) of 25 Pa, and C(11) that have condensing boiler modules that are equipped with a gas-air ratio control and that have a ∆pmax, saf(min) of 25 Pa. NOTE 2 This document provides requirements for boilers with known constructions. For boilers with any alternative constructions, which might not fully be covered by this standard, the risk associated with this alternative construction needs to be assessed. An example of an assessment methodology, based upon risk assessment, is given in Clause 11. This document does not cover all the requirements for: aa) appliances above 1 000 kW; ab) appliances that are intended to be connected to gas grids where the quality of the distributed gas is likely to vary to a large extent over the lifetime of the appliance (see Annex AB of EN 15502-1:2021); ac) appliances using flue dampers; ad) appliances of the types B21, B31, B51, C21, C41, C51, C61, C71, C81, C(12) and C(13); ae) C7 appliances that have a nominal heat input (on the basis of net calorific value) exceeding 70 kW; af) appliances incorporating flexible plastic flue liners; ag) C(10) boilers: 1) without a gas-air ratio control, or 2) which are non-condensing appliances, or 3) which have a maximum safety pressure difference at minimum heat input not equal to 25 Pa (∆pmax, saf(min)); ah) C(11) boilers that have boiler modules: 1) without a gas-air ratio control, or 2) which are non-condensing appliances, or 3) which have a maximum safety pressure difference at minimum heat input not equal to 25 Pa (∆pmax, saf(min)); ai) appliances intended to be connected to a flue having mechanical extraction; aj) surface temperatures of external parts particular to children and elderly people; ak) appliances that are intended to burn natural gases of the second family where hydrogen is added to the natural gas; al) appliances equipped with an adaptive combustion control function (ACCF); am) boilers intended to be installed in areas accessible to elderly people and children.
This document specifies the requirements and test methods, as well as the classification and marking of gas-fired central heating boilers that are fitted with atmospheric burners, fan assisted atmospheric burners or fully premixed burners, and are hereafter referred to as "boilers". This document is intended to be used in conjunction with EN 15502-1:2021. This document covers gas-fired central heating boilers from the types C1 up to C(11) and the types B2, B3 and B5: NOTE 1 For further background information on appliance types see EN 1749:2020. a) that have a nominal heat input (on the basis of net calorific value) not exceeding 1 000 kW; b) that use one or more combustible gases of the three gas families at the pressures stated in EN 437:2021; c) where the temperature of the heat transfer fluid does not exceed 105 °C during normal operation; d) where the maximum operating pressure in the water circuit does not exceed 6 bar; e) which can give rise to condensation under certain circumstances; f) which are declared in the instructions for installation to be either a "condensing" boiler or a "low temperature boiler" or a "standard boiler"; if no declaration is given the boiler is to be considered a "standard boiler"; g) which are intended to be installed inside a building or in a partially protected place; h) which are intended to produce also hot water either by the instantaneous or storage principle as a single unit; i) which are designed for either sealed water systems or for open water systems; j) which are either modular boilers, or non-modular boilers. k) which are from the types C(10) that are equipped with a gas-air ratio control and that have a ∆pmax, saf(min) of 25 Pa, and C(11) that have condensing boiler modules that are equipped with a gas-air ratio control and that have a ∆pmax, saf(min) of 25 Pa. NOTE 2 This document provides requirements for boilers with known constructions. For boilers with any alternative constructions, which might not fully be covered by this standard, the risk associated with this alternative construction needs to be assessed. An example of an assessment methodology, based upon risk assessment, is given in Clause 11. This document does not cover all the requirements for: aa) appliances above 1 000 kW; ab) appliances that are intended to be connected to gas grids where the quality of the distributed gas is likely to vary to a large extent over the lifetime of the appliance (see Annex AB of EN 15502-1:2021); ac) appliances using flue dampers; ad) appliances of the types B21, B31, B51, C21, C41, C51, C61, C71, C81, C(12) and C(13); ae) C7 appliances that have a nominal heat input (on the basis of net calorific value) exceeding 70 kW; af) appliances incorporating flexible plastic flue liners; ag) C(10) boilers: 1) without a gas-air ratio control, or 2) which are non-condensing appliances, or 3) which have a maximum safety pressure difference at minimum heat input not equal to 25 Pa (∆pmax, saf(min)); ah) C(11) boilers that have boiler modules: 1) without a gas-air ratio control, or 2) which are non-condensing appliances, or 3) which have a maximum safety pressure difference at minimum heat input not equal to 25 Pa (∆pmax, saf(min)); ai) appliances intended to be connected to a flue having mechanical extraction; aj) surface temperatures of external parts particular to children and elderly people; ak) appliances that are intended to burn natural gases of the second family where hydrogen is added to the natural gas; al) appliances equipped with an adaptive combustion control function (ACCF); am) boilers intended to be installed in areas accessible to elderly people and children.
EN 15502-2-1:2022 is classified under the following ICS (International Classification for Standards) categories: 27.060.30 - Boilers and heat exchangers; 91.140.10 - Central heating systems. The ICS classification helps identify the subject area and facilitates finding related standards.
EN 15502-2-1:2022 has the following relationships with other standards: It is inter standard links to EN 15502-2-1:2012+A1:2016, EN 15502-2-1:2022+A1:2023. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.
EN 15502-2-1:2022 is associated with the following European legislation: EU Directives/Regulations: 2016/426, 811/2013, 813/2013, 92/42/EEC; Standardization Mandates: M/066, M/535, M/BC/CEN/89/6. When a standard is cited in the Official Journal of the European Union, products manufactured in conformity with it benefit from a presumption of conformity with the essential requirements of the corresponding EU directive or regulation.
You can purchase EN 15502-2-1:2022 directly from iTeh Standards. The document is available in PDF format and is delivered instantly after payment. Add the standard to your cart and complete the secure checkout process. iTeh Standards is an authorized distributor of CEN standards.
記事のタイトル:EN 15502-2-1:2022 - ガス中央暖房ボイラー - Part 2-1:C型およびB2、B3、B5型ボイラーの1,000 kW以下の定格熱出力に対する特定の標準 記事の内容:本文書は、大気バーナー、ファン補助大気バーナー、または完全プレミックスバーナーを搭載したガス中央暖房ボイラー(以下、「ボイラー」とする)の要件と試験方法、分類と表示を規定しています。 本文書は、EN 15502-1:2021と併用することを意図しています。 本文書は、C1からC(11)およびB2、B3、B5型のガス中央暖房ボイラーを対象としています。 注1:機器タイプの詳細な背景情報については、EN 1749:2020を参照してください。 a)正味熱価を基準にした定格熱出力が1,000 kW以下の製品。 b)EN 437:2021で規定された圧力で、3つのガスファミリーのいずれかの可燃性ガスを使用する製品。 c)通常運転時の熱媒体の温度が105°C以下の製品。 d)水回路の最大作動圧力が6 bar以下の製品。 e)特定の条件下で凝縮が発生する可能性のある製品。 f)取り付けの説明書に「コンデンシング」ボイラーまたは「低温」ボイラーまたは「標準」ボイラーのいずれかとして宣言されている製品。宣言がない場合、ボイラーは「標準」ボイラーと見なされます。 g)建物内または部分的に保護された場所に設置することを目的とした製品。 h)単一ユニットとして瞬間または貯蔵原理で温水を供給することもできる製品。 i)密閉水系または開放水系のいずれかに設計された製品。 j)モジュール式ボイラーまたは非モジュール式ボイラーのいずれかの製品。 k)ガス-空気比制御装置が搭載され、∆pmax、saf(min)が25 PaのC(10)型製品およびガス-空気比制御装置が搭載され、∆pmax、saf(min)が25 Paのコンデンシングボイラーモジュールを備えたC(11)型製品。 注2:本文書は既知の構造のボイラーに関する要件を提供します。本標準で完全にカバーされない代替構造を持つボイラーのリスクは評価する必要があります。 代替構造に関連するリスク評価に基づく評価方法の例は、第11節に記載されています。 本文書は、次の要件を網羅していません。 aa)1,000 kW以上の製品。 ab)ガスの品質が製品の寿命にわたって大幅に変動する可能性のあるガスグリッドに接続される製品(EN 15502-1:2021の付録ABを参照)。 ac)フルーダンパーを使用する製品。 ad)B21、B31、B51、C21、C41、C51、C61、C71、C81、C(12)、C(13)型の製品。 ae)正味熱価を基準にした定格熱出力が70 kWを超えるC7型製品。 af)柔軟なプラスチック排気ライナーを組み込んだ製品。 ag)ガス-空気比制御装置がないC(10)型ボイラーや凝縮が発生しない製品、または∆pmax、saf(min)が25 Paでない最大安全圧力差を持つ製品は含まれていません。 ah)ガス-空気比制御装置がないC(11)型ボイラーや凝縮が発生しない製品、または∆pmax、saf(min)が25 Paでない最大安全圧力差を持つボイラーモジュールを持つ製品は含まれていません。 ai)機械的排気を持つ排気に接続する予定の製品。 aj)子供や高齢者に特に関連する外部部品の表面温度。 ak)水素が天然ガスに追加され
기사 제목: EN 15502-2-1:2022 - 가스 중앙 난방 보일러 - 파트 2-1: 1,000 kW 이하의 명목 효율 열 출력을 가진 C 유형 기기 및 B2, B3 및 B5 기기에 대한 특정 표준 기사 내용: 본 문서는 대기 연소기, 팬 보조 대기 연소기 또는 완전 사전혼합 연소기가 장착된 가스 중앙 난방 보일러의 요구 사항 및 시험 방법, 분류 및 표시를 명시합니다. 본 문서는 "보일러"라고도 지칭됩니다. 본 문서는 EN 15502-1:2021과 함께 사용하기 위한 것입니다. 본 문서는 C1부터 C(11) 및 B2, B3, B5 유형의 가스 중앙 난방 보일러를 다룹니다. 주의 1. 가스기의 배경 정보에 대한 자세한 내용은 EN 1749:2020을 참조하십시오. a) 순 칼로리 가치를 기준으로 한 명목 효율 열 출력이 1,000 kW 이하인 제품, b) EN 437:2021에 기재된 압력의 세 가지 가스 가족 중 하나 이상의 연소 가스 사용, c) 정상 작동 중 열 전달 유체의 온도가 105°C 이하인 제품, d) 수 회로의 최대 작동 압력이 6 bar를 초과하지 않는 제품, e) 특정 상황에서 응결 작용을 유발할 수 있는 제품, f) 설치 지침에 "응축" 보일러 또는 "저온" 보일러 또는 "표준" 보일러 중 하나로 명시되어 있는 제품. 명시가 없는 경우 "표준" 보일러로 간주, g) 건물 내부 또는 일부 보호된 곳에 설치할 수 있는 제품, h) 단일 기기로 순간적 또는 저장 원리에 따라 뜨거운 물도 생산할 수 있는 제품, i) 밀폐 수도계통 또는 개방 수도계통에 사용할 수 있는 제품, j) 모듈식 보일러 또는 비모듈식 보일러, k) ∆pmax, saf(min)이 25 Pa인 가스-공기 비율 제어 장치가 장착된 C(10) 유형의 제품 및 ∆pmax, saf(min)이 25 Pa인 가스-공기 비율 제어 장치가 장착된 응축 보일러 모듈이 있는 C(11) 유형의 제품입니다. 주의 2. 이 문서는 알려진 구성의 보일러에 대한 요구 사항을 제공합니다. 이 표준으로 완전히 다루지 못하는 대체 구성을 갖는 보일러의 위험은 평가되어야 합니다. 위험 평가에 기반한 평가 방법론의 예시는 11절에 제공됩니다. 본 문서는 다음에 대한 모든 요구 사항을 다루지 않습니다. aa) 1,000 kW 이상의 제품, ab) 기기 수명 동안 분포되는 가스의 품질이 크게 변동할 수 있는 가스 그리드에 연결될 예정인 제품 (EN 15502-1:2021의 부록 AB 참조), ac) 배기 담치를 사용하는 기기, ad) B21, B31, B51, C21, C41, C51, C61, C71, C81, C(12) 및 C(13) 유형의 기기, ae) 순 칼로리 가치를 기준으로 한 명목 효율 열 출력이 70 kW를 초과하는 C7 기기, af) 유연한 플라스틱 배기 라이너를 포함한 기기, ag) 가스-공기 비율 제어 장치가 없는 C(10) 보일러, 응축이 발생하지 않는 기기 또는 ∆pmax, saf(min)이 25 Pa가 아닌 최대 안전 압력 차이를 가지는 기기, ah) 가스-공기 비율 제어 장치가 없는 C(11) 보일러 또는 응축이 발생하지 않는 기기 또는 ∆pmax, saf(min)이 25 Pa가 아닌 최대 안전 압력 차이를 가지는 보일러 모듈이 있는 기기, ai) 기계적 배기를 가진 플루에 연결될 예정인 기기, aj) 아동 및 노약자에게 특히 노출되는 외부 부품의 표면 온도, ak) 수소가 첨가된 제2 가스 가족 천연가스를 연소하기 위한 기기, al) 적응형 연소 제어 기능 (ACCF)이 장착된 기기, am) 노인 및 어린이가 접근 가능한 지역에 설치할 예정인 보일러.
The article discusses the requirements and test methods for gas-fired central heating boilers. These boilers include types C1 to C(11) and types B2, B3, and B5, with a nominal heat input not exceeding 1,000 kW. They use combustible gases of the three gas families, with a maximum operating pressure of 6 bar. The boilers can produce hot water and can be installed inside a building or in a partially protected place. They may also give rise to condensation under certain conditions. The article specifies different types of boilers and their limitations. It also provides an example of a risk assessment methodology for boilers with alternative constructions. The article lists the requirements that are not covered, such as appliances above 1,000 kW, appliances connected to gas grids with varying gas quality, and appliances using flue dampers. It also excludes specific types of boilers and addresses other factors like flue extraction, surface temperatures, and adaptive combustion control.








Questions, Comments and Discussion
Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.
Loading comments...