EN IEC 61936-1:2021
(Main)Power installations exceeding 1 kV AC and 1,5 kV DC - Part 1: AC
Power installations exceeding 1 kV AC and 1,5 kV DC - Part 1: AC
This part of IEC 61936 provides requirements for the design and the erection of electrical power installations in systems with nominal voltages exceeding 1 kV AC and nominal frequency up to and including 60 Hz, so as to provide safety and proper functioning for the use intended. For the purpose of interpreting this document, an electrical power installation is considered to be one of the following: a) substation, including substation for railway power supply; b) electrical power installations on mast, pole and tower, switchgear and/or transformers located outside a closed electrical operating area; c) one (or more) power station(s) located on a single site, the electrical power installation includes generators and transformers with all associated switchgear and all electrical auxiliary systems. Connections between generating stations located on different sites are excluded; d) the electrical system of a factory, industrial plant or other industrial, agricultural, commercial or public premises; e) electrical power installations on offshore facilities for the purpose of generation, transmission, distribution and/or storage of electricity; f) transition towers/poles (between overhead lines and underground lines). The electrical power installation includes, among others, the following equipment: - rotating electrical machines; - switchgear; - transformers and reactors; - converters; - cables; - wiring systems; - batteries; - capacitors; - earthing systems; - buildings and fences which are part of a closed electrical operating area; - associated protection, control and auxiliary systems; - large air core reactor. NOTE 1 In general, equipment standards take precedence over the requirements of this document. This document does not apply to the design and erection of any of the following: - overhead and underground lines between separate electrical power installations; - electrified railway tracks and rolling stock; - mining equipment and installations; - fluorescent lamp installations; - installations on ships according to IEC 60092 (all parts) and offshore units according to IEC 61892 (all parts), which are used in the offshore petroleum industry for drilling, processing and storage purposes; - electrostatic equipment (e.g. electrostatic precipitators, spray-painting units); - test sites; - medical equipment, e.g. medical X-ray equipment. This document does not apply to the design of prefabricated, type-tested switchgear and high voltage/low voltage prefabricated substation, for which separate IEC standards exist. NOTE 2 The scope of this document does not include the requirements for carrying out live working on electrical power installations. NOTE 3 The scope of this document considers safety requirements for HV installations and the influences of HV installations on LV installations. For electrical installations up to 1 kV, IEC 60364 (all parts) applies.
Starkstromanlagen mit Nennwechselspannungen über 1 kV AC und 1,5 kV DC - Teil 1: Wechselstrom
Installations électriques de puissance de tension supérieure à 1 kV en courant alternatif et 1,5 kV en courant continu - Partie 1: Courant alternatif
L’IEC 61936-1:2021 fournit des exigences relatives à la conception et au montage des installations électriques dans des systèmes dont les tensions nominales sont supérieures à 1 kV en courant alternatif et la fréquence nominale inférieure ou égale à 60 Hz, afin d'assurer la sécurité et le fonctionnement correct pour l'utilisation prévue. L'installation électrique comprend notamment les matériels suivants:
machines électriques tournantes;
appareillage;
transformateurs et réactances;
convertisseurs;
câbles;
canalisations électriques;
batteries;
condensateurs;
installations de mise à la terre;
bâtiments et clôtures qui font partie d'une installation électrique fermée;
systèmes associés de protection, de commande et auxiliaires;
réactance élevée à noyau d’air. Le présent document ne s'applique pas à la conception des appareillages préfabriqués soumis à un essai de type et des postes préfabriqués à haute tension/basse tension, pour lesquels des normes IEC spécifiques existent. Cette édition inclut les modifications techniques majeures suivantes par rapport à l'édition précédente:
l’introduction a été remaniée pour refléter la réalité au moment de la rédaction du présent document;
le domaine d’application a été amélioré pour clarifier l’application du présent document;
les termes et définitions manquants et obsolètes ont été mis à jour, et les termes existants ont été améliorés;
le Tableau 1 a été mis à jour pour tenir compte des situations qui nécessitent des accords entre le fournisseur et l’utilisateur;
les exigences en matière de compatibilité électromagnétique ont été clarifiées;
la formulation de l’Article 5) relatif à la coordination de l’isolement a été améliorée et la coordination de son contenu technique avec les dernières versions des normes de coordination de l’isolement a été mise à jour;
la formulation concernant les matériels électriques a été améliorée et clarifiée;
le paragraphe relatif aux fusibles a été amélioré et reformulé;
des exigences en matière d’étiquetage ont été introduites lorsque des sources multiples doivent être déconnectées;
les exigences manquantes pour les postes sous enveloppe métallique (PSEM) ont été réintroduites;
amélioration du paragraphe relatif à la ventilation
Elektroenergetski postroji za izmenične napetosti nad 1 kV in enosmerne napetosti nad 1,5 kV - 1. del: Izmenična napetost
General Information
Relations
Standards Content (Sample)
SLOVENSKI STANDARD
01-november-2021
Nadomešča:
SIST EN 61936-1:2011
SIST EN 61936-1:2011/A1:2014
SIST EN 61936-1:2011/AC:2012
SIST EN 61936-1:2011/AC:2013
Elektroenergetski postroji za izmenične napetosti nad 1 kV in enosmerne
napetosti nad 1,5 kV - 1. del: Izmenična napetost
Power installations exceeding 1 kV AC and 1,5 kV DC - Part 1: AC
Ta slovenski standard je istoveten z: EN IEC 61936-1:2021
ICS:
29.240.01 Omrežja za prenos in Power transmission and
distribucijo električne energije distribution networks in
na splošno general
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
EUROPEAN STANDARD EN IEC 61936-1
NORME EUROPÉENNE
EUROPÄISCHE NORM
August 2021
ICS 29.020; 29.080.01 Supersedes EN 61936-1:2010 and all of its amendments
and corrigenda (if any)
English Version
Power installations exceeding 1 kV AC and 1,5 kV DC - Part 1:
AC
(IEC 61936-1:2021)
Installations électriques de puissance de tension supérieure Starkstromanlagen mit Nennwechselspannungen über 1 kV
à 1 kV en courant alternatif et 1,5 kV en courant continu - AC und 1,5 kV DC - Teil 1: Wechselstrom
Partie 1: Courant alternatif (IEC 61936-1:2021)
(IEC 61936-1:2021)
This European Standard was approved by CENELEC on 2021-08-11. CENELEC members are bound to comply with the CEN/CENELEC
Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration.
Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN-CENELEC
Management Centre or to any CENELEC member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by translation
under the responsibility of a CENELEC member into its own language and notified to the CEN-CENELEC Management Centre has the
same status as the official versions.
CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus, the Czech Republic,
Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, the
Netherlands, Norway, Poland, Portugal, Republic of North Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland,
Turkey and the United Kingdom.
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung
CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Brussels
© 2021 CENELEC All rights of exploitation in any form and by any means reserved worldwide for CENELEC Members.
Ref. No. EN IEC 61936-1:2021 E
European foreword
The text of document 99/311/FDIS, future edition 3 of IEC 61936-1, prepared by IEC/TC 99 “Insulation
co-ordination and system engineering of high voltage electrical power installations above 1,0 kV AC
and 1,5 kV DC” was submitted to the IEC-CENELEC parallel vote and approved by CENELEC as
The following dates are fixed:
• latest date by which the document has to be implemented at national (dop) 2022–05–11
level by publication of an identical national standard or by endorsement
• latest date by which the national standards conflicting with the (dow) 2024–08–11
document have to be withdrawn
This document supersedes EN 61936-1:2010 and all of its amendments and corrigenda (if any).
Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. CENELEC shall not be held responsible for identifying any or all such patent rights.
Any feedback and questions on this document should be directed to the users’ national committee. A
complete listing of these bodies can be found on the CENELEC website.
Endorsement notice
The text of the International Standard IEC 61936-1:2021 was approved by CENELEC as a European
Standard without any modification.
In the official version, for Bibliography, the following notes have to be added for the standards
indicated:
IEC 60034-3 NOTE Harmonized as EN IEC 60034-3
IEC 60038 NOTE Harmonized as EN 60038
IEC 60068 (series) NOTE Harmonized as EN 60068 (series)
IEC 60076-13 NOTE Harmonized as EN 60076-13
IEC 60092 (series) NOTE Harmonized as EN 60092 (series)
IEC 60282-1 NOTE Harmonized as EN IEC 60282-1
IEC 60364-4-41 NOTE Harmonized as HD 60364-4-41
IEC 60364-7-729 NOTE Harmonized as HD 60364-7-729
IEC 60376 NOTE Harmonized as EN IEC 60376
IEC 60480 NOTE Harmonized as EN IEC 60480
IEC 60664-1 NOTE Harmonized as EN IEC 60664-1
IEC 60721 (series) NOTE Harmonized as EN 60721 (series)
IEC 60721-2-2 NOTE Harmonized as EN 60721-2-2
IEC 60721-2-3 NOTE Harmonized as EN 60721-2-3
IEC 60721-2-4 NOTE Harmonized as EN IEC 60721-2-4
IEC 60721-2-7 NOTE Harmonized as EN IEC 60721-2-7
IEC 60721-3-1 NOTE Harmonized as EN IEC 60721-3-1
IEC 60721-3-2 NOTE Harmonized as EN IEC 60721-3-2
IEC 60832 (series) NOTE Harmonized as EN 60832 (series)
IEC 60855-1 NOTE Harmonized as EN 60855-1
IEC 60865-1 NOTE Harmonized as EN 60865-1
IEC 60909 (series) NOTE Harmonized as EN 60909 (series)
IEC 61000 (series) NOTE Harmonized as EN IEC 61000 (series)
IEC 61039 NOTE Harmonized as EN 61039
IEC 61082-1 NOTE Harmonized as EN 61082-1
IEC 61243 (series) NOTE Harmonized as EN 61243 (series)
IEC 61355-1 NOTE Harmonized as EN 61355-1
IEC 61869 (series) NOTE Harmonized as EN IEC 61869 (series)
IEC 62271-4 NOTE Harmonized as EN 62271-4
IEC 62271-100 NOTE Harmonized as EN 62271-100
IEC 62271-102 NOTE Harmonized as EN IEC 62271-102
IEC 62271-103 NOTE Harmonized as EN 62271-103
IEC 62271-104 NOTE Harmonized as EN IEC 62271-104
IEC 62271-105 NOTE Harmonized as EN 62271-105
IEC 62271-206 NOTE Harmonized as EN 62271-206
IEC 62305 (series) NOTE Harmonized as EN 62305 (series)
IEC 81346 (series) NOTE Harmonized as EN IEC 81346 (series)
ISO 26800 NOTE Harmonized as EN ISO 26800
Annex ZA
(normative)
Normative references to international publications
with their corresponding European publications
The following documents are referred to in the text in such a way that some or all of their content
constitutes requirements of this document. For dated references, only the edition cited applies. For
undated references, the latest edition of the referenced document (including any amendments)
applies.
NOTE 1 Where an International Publication has been modified by common modifications, indicated by (mod), the
relevant EN/HD applies.
NOTE 2 Up-to-date information on the latest versions of the European Standards listed in this annex is available
here: www.cenelec.eu.
Publication Year Title EN/HD Year
IEC 60034-1 - Rotating electrical machines - Part 1: - -
Rating and performance
IEC 60060-1 - High-voltage test techniques - Part 1: EN 60060-1 -
General definitions and test requirements
IEC 60071-1 2019 Insulation co-ordination - Part 1: EN IEC 60071-1 2019
Definitions, principles and rules
IEC 60071-2 - Insulation co-ordination – Part 2: EN IEC 60071-2 -
Application guidelines
IEC 60076 series Power transformers EN 60076 series
IEC 60079-0 - Explosive atmospheres - Part 0: EN IEC 60079-0 -
Equipment - General requirements
IEC 60079-10-1 - Explosive atmospheres - Part 10–1: EN IEC 60079-10-1 -
Classification of areas - Explosive gas
atmospheres
IEC 60079-10-2 Explosive atmospheres - Part 10–2: EN 60079-10-2
Classification of areas - Explosive dust
atmospheres
IEC 60255 series Measuring relays and protection equipment EN 60255 series
IEC 60331-1 - Tests for electric cables under fire EN IEC 60331-1 -
conditions - Circuit integrity - Part 1: Test
method for fire with shock at a temperature
of at least 830 °C for cables of rated
voltage up to and including 0,6/1,0 kV and
with an overall diameter exceeding 20 mm
IEC 60331-21 - Tests for electric cables under fire - -
conditions - Circuit integrity - Part 21:
Procedures and requirements - Cables of
rated voltage up to and including
0,6/1,0 kV
IEC 60332 series Tests on electric cables under fire EN 60332 series
conditions
IEC 60364 series Low-voltage electrical installations HD 60364 series
IEC 60479-1 2018 Effects of current on human beings and - -
livestock - Part 1: General aspects
IEC 60529 - Degrees of protection provided by - -
enclosures (IP Code)
IEC 60754 series Test on gases evolved during combustion EN 60754 series
of materials from cables
IEC 61034-1 - Measurement of smoke density of cables EN 61034-1 -
burning under defined conditions - Part 1:
Test apparatus
IEC 61219 - Live working - Earthing or earthing and EN 61219 -
short-circuiting equipment using lances as
a short-circuiting device - Lance earthing
IEC 61230 - Live working - Portable equipment for EN 61230 -
earthing or earthing and short-circuiting
IEC 62271-1 2017 High-voltage switchgear and controlgear - EN 62271-1 2017
Part 1: Common specifications for
alternating current switchgear and
controlgear
IEC 62271-200 - High-voltage switchgear and controlgear - EN IEC 62271-200 -
Part 200: AC metal-enclosed switchgear
and controlgear for rated voltages above
1 kV and up to and including 52 kV
IEC 62271-201 - High-voltage switchgear and controlgear - EN 62271-201 -
Part 201: AC solid-insulation enclosed
switchgear and controlgear for rated
voltages above 1 kV and up to and
including 52 kV
IEC 62271-202 - High-voltage switchgear and controlgear - EN 62271-202 -
Part 202: High-voltage/ low-voltage
prefabricated substation
IEC 62271-203 - High-voltage switchgear and controlgear - EN 62271-203 -
Part 203: Gas-insulated metal-enclosed
switchgear for rated voltages above 52 kV
IEC 62271-207 - High-voltage switchgear and controlgear - EN 62271-207 -
Part 207: Seismic qualification for gas-
insulated switchgear assemblies for rated
voltages above 52 kV
IEC 62305 series Protection against lightning EN 62305 series
IEC/TR 61000-5-2 - Electromagnetic compatibility (EMC) - Part - -
5: Installation and mitigation guidelines -
Section 2: Earthing and cabling
IEC/TR 62271-300 - High-voltage switchgear and controlgear - - -
Part 300: Seismic qualification of
alternating current circuit-breakers
IEC/TS 60815-1 - Selection and dimensioning of high-voltage - -
insulators intended for use in polluted
conditions - Part 1: Definitions, information
and general principles
IEC/TS 60815-2 - Selection and dimensioning of high-voltage - -
insulators intended for use in polluted
conditions - Part 2: Ceramic and glass
insulators for a.c. systems
IEC/TS 60815-3 - Selection and dimensioning of high-voltage - -
insulators intended for use in polluted
conditions - Part 3: Polymer insulators for
a.c. systems
IEC/TS 61463 - Bushings - Seismic qualification - -
IEC/IEEE 82079-1 - Preparation of information for use EN -
(instructions for use) of products - Part 1: IEC/IEEE 82079-1
Principles and general requirements
IEC 61936-1 ®
Edition 3.0 2021-07
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE
colour
inside
Power installations exceeding 1 kV AC and 1,5 kV DC –
Part 1: AC
Installations électriques de puissance de tension supérieure à 1 kV en courant
alternatif et 1,5 kV en courant continu –
Partie 1: Courant alternatif
INTERNATIONAL
ELECTROTECHNICAL
COMMISSION
COMMISSION
ELECTROTECHNIQUE
INTERNATIONALE
ICS 29.020; 29.080.01 ISBN 978-2-8322-9887-9
– 2 – IEC 61936-1:2021 © IEC 2021
CONTENTS
FOREWORD . 8
INTRODUCTION . 11
1 Scope . 12
2 Normative references . 13
3 Terms and definitions . 15
3.1 General definitions . 15
3.2 Definitions concerning electrical power installations . 17
3.3 Definitions concerning types of electrical power installations. 18
3.4 Definitions concerning safety measures against electric shock . 18
3.5 Definitions concerning clearances . 19
3.6 Definitions concerning control and protection . 21
3.7 Definitions concerning earthing . 21
4 Fundamental requirements . 25
4.1 General . 25
4.1.1 General requirements . 25
4.1.2 Agreements between supplier and user . 26
4.2 Electrical requirements . 28
4.2.1 Methods of neutral earthing . 28
4.2.2 Voltage classification . 28
4.2.3 Current in normal operation . 28
4.2.4 Short-circuit current . 28
4.2.5 Rated frequency . 29
4.2.6 Corona . 29
4.2.7 Electric and magnetic fields . 29
4.2.8 Overvoltages . 30
4.2.9 Harmonics . 30
4.2.10 Electromagnetic compatibility . 30
4.3 Mechanical requirements . 30
4.3.1 General . 30
4.3.2 Tension load . 31
4.3.3 Erection load . 31
4.3.4 Ice load . 31
4.3.5 Wind load . 31
4.3.6 Switching forces . 31
4.3.7 Short-circuit forces . 31
4.3.8 Loss of conductor tension . 31
4.3.9 Seismic loads . 31
4.3.10 Dimensioning of structures . 32
4.4 Climatic and environmental conditions . 32
4.4.1 General . 32
4.4.2 Normal conditions . 32
4.4.3 Special conditions . 34
4.5 Particular requirements . 35
4.5.1 Effects of small animals and micro-organisms. 35
4.5.2 Noise level . 35
4.5.3 Transport . 35
IEC 61936-1:2021 © IEC 2021 – 3 –
5 Insulation . 35
5.1 General . 35
5.2 Selection of insulation level. 36
5.2.1 General . 36
5.2.2 Consideration of methods of neutral earthing . 36
5.2.3 Consideration of rated withstand voltages . 36
5.3 Verification of withstand values . 36
5.4 Minimum clearances of live parts . 37
5.4.1 General . 37
5.4.2 Minimum clearances in voltage range I . 37
5.4.3 Minimum clearances in voltage range II . 37
5.5 Minimum clearances between parts under special conditions . 40
5.6 Tested connection zones . 40
6 Electrical equipment . 40
6.1 General requirements . 40
6.1.1 Electrical equipment safety . 40
6.1.2 User safety . 40
6.2 Specific requirements . 41
6.2.1 Switching devices . 41
6.2.2 Power transformers and reactors . 41
6.2.3 Prefabricated type-tested switchgear . 42
6.2.4 Instrument transformers . 42
6.2.5 Surge arresters . 43
6.2.6 Capacitors . 43
6.2.7 Line traps . 44
6.2.8 Insulators . 44
6.2.9 Insulated cables . 44
6.2.10 Conductors and accessories . 47
6.2.11 Rotating electrical machines . 47
6.2.12 Generating units . 48
6.2.13 Generating unit main connections . 48
6.2.14 Static converters . 48
6.2.15 Fuses . 49
6.2.16 Electrical and mechanical interlocking . 49
7 Electrical power installations . 49
7.1 General . 49
7.1.1 Common requirements . 49
7.1.2 Circuit arrangement . 50
7.1.3 Documentation . 51
7.1.4 Transport routes . 51
7.1.5 Aisles and access areas . 52
7.1.6 Lighting . 53
7.1.7 Operational safety . 53
7.1.8 Labelling . 53
7.2 Outdoor electrical power installations of open design . 53
7.2.1 General . 53
7.2.2 Protective barrier clearances . 54
7.2.3 Protective obstacle clearances . 54
7.2.4 Boundary clearances . 55
– 4 – IEC 61936-1:2021 © IEC 2021
7.2.5 Minimum height over access area . 56
7.2.6 Clearances to buildings . 57
7.2.7 External fences or walls and access doors . 59
7.3 Indoor electrical power installations of open design . 59
7.4 Installation of prefabricated type-tested switchgear . 60
7.4.1 General . 60
7.4.2 Additional requirements for gas-insulated metal-enclosed switchgear . 60
7.5 Requirements for buildings . 62
7.5.1 General . 62
7.5.2 Structural provisions . 62
7.5.3 Rooms for switchgear . 63
7.5.4 Maintenance and operating areas . 63
7.5.5 Doors . 63
7.5.6 Draining of insulating liquids . 64
7.5.7 Heating, ventilation and air conditioning (HVAC) . 64
7.5.8 Buildings which require special consideration . 65
7.6 High voltage/low voltage prefabricated substations . 65
7.7 Electrical power installations on mast, pole and tower . 65
8 Safety measures . 65
8.1 General . 65
8.2 Protection against direct contact . 66
8.2.1 General . 66
8.2.2 Measures for protection against direct contact . 66
8.2.3 Protection requirements . 67
8.3 Means to protect persons in case of indirect contact . 68
8.4 Means to protect persons working on or near electrical power installations . 68
8.4.1 General . 68
8.4.2 Electrical equipment for isolating installations or apparatus . 68
8.4.3 Devices to prevent reclosing of isolating devices . 69
8.4.4 Devices for determining the de-energized state . 69
8.4.5 Devices for earthing and short-circuiting . 69
8.4.6 Equipment acting as protective barriers against adjacent live parts . 70
8.4.7 Storage of personal protection equipment . 71
8.5 Protection from danger resulting from arc fault . 71
8.6 Protection against direct lightning strokes . 71
8.7 Protection against fire . 72
8.7.1 General . 72
8.7.2 Transformers, reactors . 73
8.7.3 Cables . 79
8.7.4 Other equipment with flammable liquid . 79
8.8 Protection against leakage of insulating liquid and SF . 80
8.8.1 Insulating liquid leakage and subsoil water protection . 80
8.8.2 SF leakage . 82
8.8.3 Failure with loss of SF and its decomposition products . 83
8.9 Identification and marking . 83
8.9.1 General . 83
8.9.2 Information plates and warning plates . 84
8.9.3 Electrical hazard warning . 84
IEC 61936-1:2021 © IEC 2021 – 5 –
8.9.4 Electrical power installations with incorporated capacitors . 84
8.9.5 Emergency signs for emergency exits . 84
8.9.6 Cable identification marks . 84
9 Protection, automation and auxiliary systems . 84
9.1 Protection systems. 84
9.2 Automation systems . 85
9.3 Auxiliary systems . 86
9.3.1 AC and DC supply circuits . 86
9.3.2 Compressed air systems . 87
9.3.3 SF gas handling plants . 88
9.3.4 Hydrogen handling plants . 88
9.4 Basic rules for electromagnetic compatibility of control systems . 88
9.4.1 General . 88
9.4.2 Electrical noise sources in electrical power installations . 89
9.4.3 Measures to be taken to reduce the effects of high frequency
interference . 89
9.4.4 Measures to be taken to reduce the effects of low frequency
interference . 89
9.4.5 Measures related to the selection of electrical equipment . 90
9.4.6 Other possible measures to reduce the effects of interference . 91
10 Earthing systems . 91
10.1 General . 91
10.2 Fundamental requirements . 91
10.2.1 Safety criteria . 91
10.2.2 Functional requirements . 92
10.2.3 High and low voltage earthing systems . 92
10.3 Design of earthing systems . 93
10.3.1 General . 93
10.3.2 Power system faults. 94
10.3.3 Lightning and transient overvoltages. 94
10.4 Construction work on earthing systems . 95
10.5 Measurements . 95
10.6 Maintainability . 95
10.6.1 Inspections . 95
10.6.2 Measurements . 95
11 Inspection and testing . 96
11.1 General . 96
11.2 Verification of specified performances . 96
11.3 Tests during installation and commissioning . 97
11.4 Trial running . 97
12 Operation and maintenance manual . 97
Annex A (informative) Values of rated insulation levels and minimum clearances
based on current practice in some countries . 98
Annex B (normative) Method of calculating permissible touch voltages . 101
Annex C (normative) Permissible touch voltage according to IEEE 80 . 102
Annex D (normative) Earthing system design flow chart . 103
– 6 – IEC 61936-1:2021 © IEC 2021
Annex E (informative) Protection measures against direct lightning strokes . 104
E.1 General . 104
E.2 Shield wires . 104
E.3 Lightning rods . 104
Annex F (informative) Considerations of design for safe working . 107
Annex G (informative) List of notes concerning particular conditions in certain
countries . 109
Bibliography . 115
Figure 1 – Minimum approach distance for transport within closed electrical operating
areas . 52
Figure 2 – Protection against direct contact by protective barriers or protective
obstacles within closed electrical operating areas . 55
Figure 3 – Boundary distances and minimum height at the external fence/wall . 56
Figure 4 – Minimum heights within closed electrical operating areas . 57
Figure 5 – Approaches with buildings within closed electrical operating areas . 58
Figure 6 – Separating walls between transformers . 75
Figure 7 – Fire protection between transformer and building . 77
Figure 8 – Example for small transformers without gravel layer and catchment tank . 80
Figure 9 – Sump with integrated catchment tank . 81
Figure 10 – Sump with separate catchment tank . 82
Figure 11 – Sump with integrated common catchment tank . 82
Figure 12 – Permissible touch voltage U . 95
Tp
Figure C.1 – Permissible touch voltage U according to IEEE 80 . 102
Tp
Figure E.1 – Single shield wire . 105
Figure E.2 – Two shield wires . 105
Figure E.3 – Single lightning rod . 106
Figure E.4 – Two lightning rods . 106
Figure F.1 – Working clearances within closed electrical operating areas . 108
Table 1 – References to subclauses where agreement between supplier and user is
required . 27
Table 2 – Minimum clearances in air – Voltage range I (1 kV < U ≤ 245 kV) . 38
m
Table 3 – Minimum clearances in air – Voltage range II (U > 245 kV) . 39
m
Table 4 – Guide values for outdoor transformer clearances . 74
Table 5 – Minimum requirements for the installation of indoor transformers . 78
Table 6 – Minimum requirements for interconnection of low-voltage and high-voltage
earthing systems based on EPR limits . 93
Table A.1 – Values of rated insulation levels and minimum clearances in air for
1 kV < U ≤ 245 kV for highest voltage for installation U not standardized by the IEC
m m
based on current practice in some countries . 98
Table A.2 – Values of rated insulation levels and minimum clearances in air for
1 kV < U ≤ 245 kV for highest voltage for installation U not standardized by the IEC
m m
based on current practice in some countries . 99
IEC 61936-1:2021 © IEC 2021 – 7 –
Table A.3 – Values of rated insulation levels and minimum clearances in air for
U > 245 kV for highest voltages for installation U not standardized by the IEC
m m
based on current practice in some countries . 100
– 8 – IEC 61936-1:2021 © IEC 2021
INTERNATIONAL ELECTROTECHNICAL COMMISSION
____________
POWER INSTALLATIONS EXCEEDING
1 kV AC AND 1,5 kV DC –
Part 1: AC
FOREWORD
1) The International Electrotechnical Commission (IEC) is a worldwide organization for standardization comprising
all national electrotechnical committees (IEC National Committees). The object of IEC is to promote international
co-operation on all questions concerning standardization in the electrical and electronic fields. To this end and
in addition to other activities, IEC publishes International Standards, Technical Specifications, Technical Reports,
Publicly Available Specifications (PAS) and Guides (hereafter referred to as "IEC Publication(s)"). Their
preparation is entrusted to technical committees; any IEC National Committee interested in the subject dealt with
may participate in this preparatory work. International, governmental and non-governmental organizations liaising
with the IEC also participate in this preparation. IEC collaborates closely with the International Organization for
Standardization (ISO) in accordance with conditions determined by agreement between the two organizations.
2) The formal decisions or agreements of IEC on technical matters express, as nearly as possible, an international
consensus of opinion on the relevant subjects since each technical committee has representation from all
interested IEC National Committees.
3) IEC Publications have the form of recommendations for international use and are accepted by IEC National
Committees in that sense. While all reasonable efforts are made to ensure that the technical content of IEC
Publications is accurate, IEC cannot be held responsible for the way in which they are used or for any
misinterpretation by any end user.
4) In order to promote international uniformity, IEC National Committees undertake to apply IEC Publications
transparently to the maximum extent possible in their national and regional publications. Any divergence between
any IEC Publication and the corresponding national or regional publication shall be clearly indicated in the latter.
5) IEC itself does not provide any attestation of conformity. Independent certification bodies provide conformity
assessment services and, in some areas, access to IEC marks of conformity. IEC is not responsible for any
services carried out by independent certification bodies.
6) All users should ensure that they have the latest edition of this publication.
7) No liability shall attach to IEC or its directors, employees, servants or agents including individual experts and
members of its technical committees and IEC National Committees for any personal injury, property damage or
other damage of any nature whatsoever, whether direct or indirect, or for costs (including legal fees) and
expenses arising out of the publication, use of, or reliance upon, this IEC Publication or any other IEC
Publications.
8) Attention is drawn to the Normative references cited in this publication. Use of the referenced publications is
indispensable for the correct application of this publication.
9) Attention is drawn to the possibility that some of the elements of this IEC Publication may be the subject of patent
rights. IEC shall not be held responsible for identifying any or all such patent rights.
International Standard IEC 61936-1 has been prepared by IEC technical committee 99:
Insulation co-ordination and system engineering of high voltage electrical power installations
above 1,0 kV AC and 1,5 kV DC.
This third edition cancels and replaces the second edition published in 2010 and
Amendment 1:2014. This edition constitutes a technical revision.
This edition includes the following significant technical changes with respect to the previous
edition:
a) introduction has been rewritten to reflect the status when this document is produced;
b) the scope has been improved to clarify the application of this document;
c) missing and obsolete terms and definitions have been updated including improvement of
existing terms;
d) Table 1 has been updated where agreements between supplier and user are needed;
e) requirements of electromagnetic compatibility have been clarified;
IEC 61936-1:2021 © IEC 2021 – 9 –
f) insulation coordination clause (Clause 5) has improved wording for better clarity and the
technical content has an updated coordination to the latest versions of the insulatio
...
SLOVENSKI STANDARD
01-november-2021
Nadomešča:
SIST EN 61936-1:2011
SIST EN 61936-1:2011/A1:2014
SIST EN 61936-1:2011/AC:2012
SIST EN 61936-1:2011/AC:2013
Elektroenergetski postroji za izmenične napetosti nad 1 kV in enosmerne
napetosti nad 1,5 kV - 1. del: Izmenična napetost
Power installations exceeding 1 kV AC and 1,5 kV DC - Part 1: AC
Starkstromanlagen mit Nennwechselspannungen über 1 kV AC und 1,5 kV DC - Teil 1:
Wechselstrom
Installations électriques de puissance de tension supérieure à 1 kV en courant alternatif
et 1,5 kV en courant continu - Partie 1: Courant alternatif
Ta slovenski standard je istoveten z: EN IEC 61936-1:2021
ICS:
29.240.01 Omrežja za prenos in Power transmission and
distribucijo električne energije distribution networks in
na splošno general
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
EN IEC 61936-1
NORME EUROPÉENNE
EUROPÄISCHE NORM
EUROPEAN STANDARD
Août 2021
ICS 29.020; 29.080.01 Remplace l' EN 61936-1:2010 ainsi que l'ensemble de
ses amendements et corrigenda (le cas échéant)
Version française
Installations électriques de puissance de tension supérieure à 1
kV en courant alternatif et 1,5 kV en courant continu - Partie 1:
Courant alternatif
(IEC 61936-1:2021)
Starkstromanlagen mit Nennwechselspannungen über 1 kV Power installations exceeding 1 kV AC and 1,5 kV DC -
AC und 1,5 kV DC - Teil 1: Wechselstrom Part 1: AC
(IEC 61936-1:2021) (IEC 61936-1:2021)
La présente Norme Européenne a été adoptée par le CENELEC le 2021-08-11. Les membres du CENELEC sont tenus de se soumettre au
Règlement Intérieur du CEN/CENELEC, qui définit les conditions dans lesquelles doit être attribué, sans modification, le statut de norme
nationale à cette Norme Européenne.
Les listes mises à jour et les références bibliographiques relatives à ces normes nationales peuvent être obtenues auprès du CEN-
CENELEC Management Centre ou auprès des membres du CENELEC.
La présente Norme Européenne existe en trois versions officielles (allemand, anglais, français). Une version dans une autre langue faite par
traduction sous la responsabilité d'un membre du CENELEC dans sa langue nationale, et notifiée au CEN-CENELEC Management Centre,
a le même statut que les versions officielles.
Les membres du CENELEC sont les comités électrotechniques nationaux des pays suivants: Allemagne, Autriche, Belgique, Bulgarie,
Chypre, Croatie, Danemark, Espagne, Estonie, Finlande, France, Grèce, Hongrie, Irlande, Islande, Italie, Lettonie, Lituanie, Luxembourg,
Malte, Norvège, Pays-Bas, Pologne, Portugal, République de Macédoine du Nord, République de Serbie, République Tchèque, Roumanie,
Royaume-Uni, Slovaquie, Slovénie, Suède, Suisse et Turquie.
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung
European Committee for Electrotechnical Standardization
CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Bruxelles
© 2021 CENELEC Tous droits d'exploitation sous quelque forme et de quelque manière que ce soit réservés dans le monde entier aux
membres du CENELEC.
Réf. n° EN IEC 61936-1:2021 F
Avant-propos européen
Le texte du document 99/311/FDIS, future édition 3 de IEC 61936-1, préparé par le CE 99 de la CEI,
"Installations électriques de tension supérieure à 1,0 kV en courant alternatif et 1,5 kV en courant
continu : Coordination de l'isolement et conception", a été soumis au vote parallèle IEC-CENELEC et
approuvé par le CENELEC en tant que EN IEC 61936-1:2021.
Les dates suivantes sont fixées:
• date limite à laquelle ce document doit être mis en application au (dop) 2022-05-11
niveau national par publication d’une norme nationale identique ou par
entérinement
• date limite à laquelle les normes nationales conflictuelles doivent être (dow) 2024-08-11
annulées
Ce document remplace l’EN 61936-1:2010 ainsi que l’ensemble de ses amendements et corrigenda
(le cas échéant).
L’attention est appelée sur le fait que certains des éléments du présent document peuvent faire l’objet
de droits de propriété intellectuelle ou de droits analogues. Le CENELEC ne saurait être tenu pour
responsable de ne pas avoir identifié de tels droits de propriété et averti de leur existence.
Il convient que l’utilisateur adresse tout retour d’information et toute question concernant le présent
document à l’organisme national de normalisation de son pays. Une liste exhaustive desdits
organismes se trouve sur le site web du CENELEC.
Notice d’entérinement
Le texte de la Norme internationale IEC 61936-1:2021 a été approuvé par le CENELEC comme
Norme Européenne sans aucune modification.
Dans la version officielle, ajouter dans la Bibliographie les notes suivantes pour les normes indiquées:
IEC 60034-3 NOTE Harmonisée comme EN IEC 60034-3
IEC 60038 NOTE Harmonisée comme EN 60038
IEC 60068 (série) NOTE Harmonisée comme EN 60068 (série)
IEC 60076-13 NOTE Harmonisée comme EN 60076-13
IEC 60092 (série) NOTE Harmonisée comme EN 60092 (série)
IEC 60282-1 NOTE Harmonisée comme EN IEC 60282-1
IEC 60364-4-41 NOTE Harmonisée comme HD 60364-4-41
IEC 60364-7-729 NOTE Harmonisée comme HD 60364-7-729
IEC 60376 NOTE Harmonisée comme EN IEC 60376
IEC 60480 NOTE Harmonisée comme EN IEC 60480
IEC 60664-1 NOTE Harmonisée comme EN IEC 60664-1
IEC 60721 (série) NOTE Harmonisée comme EN 60721 (série)
IEC 60721-2-2 NOTE Harmonisée comme EN 60721-2-2
IEC 60721-2-3 NOTE Harmonisée comme EN 60721-2-3
IEC 60721-2-4 NOTE Harmonisée comme EN IEC 60721-2-4
IEC 60721-2-7 NOTE Harmonisée comme EN IEC 60721-2-7
IEC 60721-3-1 NOTE Harmonisée comme EN IEC 60721-3-1
IEC 60721-3-2 NOTE Harmonisée comme EN IEC 60721-3-2
IEC 60832 (série) NOTE Harmonisée comme EN 60832 (série)
IEC 60855-1 NOTE Harmonisée comme EN 60855-1
IEC 60865-1 NOTE Harmonisée comme EN 60865-1
IEC 60909 (série) NOTE Harmonisée comme EN 60909 (série)
IEC 61000 (série) NOTE Harmonisée comme EN IEC 61000 (série)
IEC 61039 NOTE Harmonisée comme EN 61039
IEC 61082-1 NOTE Harmonisée comme EN 61082-1
IEC 61243 (série) NOTE Harmonisée comme EN 61243 (série)
IEC 61355-1 NOTE Harmonisée comme EN 61355-1
IEC 61869 (série) NOTE Harmonisée comme EN IEC 61869 (série)
IEC 62271-4 NOTE Harmonisée comme EN 62271-4
IEC 62271-100 NOTE Harmonisée comme EN 62271-100
IEC 62271-102 NOTE Harmonisée comme EN IEC 62271-102
IEC 62271-103 NOTE Harmonisée comme EN 62271-103
IEC 62271-104 NOTE Harmonisée comme EN IEC 62271-104
IEC 62271-105 NOTE Harmonisée comme EN 62271-105
IEC 62271-206 NOTE Harmonisée comme EN 62271-206
IEC 62305 (série) NOTE Harmonisée comme EN 62305 (série)
IEC 81346 (série) NOTE Harmonisée comme EN IEC 81346 (série)
ISO 26800 NOTE Harmonisée comme EN ISO 26800
Annexe ZA
(normative)
Références normatives à d'autres publications internationales
avec les publications européennes correspondantes
Les documents suivants cités dans le texte constituent, pour tout ou partie de leur contenu, des
exigences du présent document. Pour les références datées, seule l'édition citée s'applique. Pour les
références non datées, la dernière édition du document de référence s'applique (y compris les
éventuels amendements).
NOTE 1 Dans le cas où une publication internationale est modifiée par des modifications communes, indiqué
par (mod), l'EN/le HD correspondant(e) s'applique.
NOTE 2 Les informations les plus récentes concernant les dernières versions des Normes Européennes
listées dans la présente annexe sont disponibles à l'adresse suivante: www.cenelec.eu.
Publication Année Titre EN/HD Année
IEC 60034-1 - Rotating electrical machines - Part 1: - -
Rating and performance
IEC 60060-1 - Technique des essais à haute tension - EN 60060-1 -
Partie 1: Définitions et exigences
générales
IEC 60071-1 2019 Coordination de l'isolement Partie 1: EN IEC 60071-1 2019
Définitions, principes et règles
IEC 60071-2 - Coordination de l'isolement - Partie 2 : EN IEC 60071-2 -
Lignes directrices en matière d’application
IEC 60076 série Transformateurs de puissance EN 60076 série
IEC 60079-0 - Atmosphères explosives - Partie 0: EN IEC 60079-0 -
Matériel - Exigences générales
IEC 60079-10-1 - Atmosphères explosives - Partie 10-1: EN IEC 60079-10-1 -
Classification des emplacements -
Atmosphères explosives gazeuses
IEC 60079-10-2 - Explosive atmospheres - Part 10-2 : EN 60079-10-2 -
Classification of areas - Explosive dust
atmospheres
IEC 60255 série Relais de mesure et dispositifs de EN 60255 série
protection
IEC 60331-1 - Essais de câbles électriques soumis au feu EN IEC 60331-1 -
- Intégrité des circuits - Partie 1 : Méthode
d'essai au feu avec chocs pour les câbles
de tension assignée au plus égale à
0,6/1,0 kV et de diamètre externe
supérieur à 20 mm, à une température
d'au moins 830 °C
IEC 60331-21 - Essais de câbles électriques soumis au feu - -
- Intégrité des circuits - Partie 21:
Procédures et prescriptions - Câbles de
tension assignée jusque et y compris
0,6/1,0 kV
IEC 60332 série Tests on electric cables under fire -EN 60332 série
conditions
IEC 60364 série Installations électriques à basse tension HD 60364 série
IEC 60479-1 2018 Effects of current on human beings and - -
livestock - Part 1: General aspects
IEC 60529 - Degrés de protection procurés par les - -
enveloppes (Code IP)
IEC 60754 série Test on gases evolved during combustion EN 60754 série
of materials from cables
IEC 61034-1 - Mesure de la densité de fumées dégagées EN 61034-1 -
par des câbles brûlant dans des conditions
définies - Partie 1: Appareillage d'essai
IEC 61219 - Travaux sous tension - Appareils de mise à EN 61219 -
la terre ou de mise à la terre et en court-
circuit utilisant des cannes comme
dispositif de mise en court-circuit - Mise à
la terre au moyen de cannes
IEC 61230 - Travaux sous tension - Equipements EN 61230 -
portables de mise à la terre ou de mise à la
terre et en court-circuit
IEC 62271-1 2017 Appareillage à haute tension - Partie 1: EN 62271-1 2017
Spécifications communes pour
appareillage à courant alternatif
IEC 62271-200 - Appareillage à haute tension - Partie 200: EN IEC 62271-200 -
Appareillage sous enveloppe métallique
pour courant alternatif de tensions
assignées supérieures à 1 kV et inférieures
ou égales à 52 kV
IEC 62271-201 - Appareillage à haute tension - Partie 201: EN 62271-201 -
Appareillage sous enveloppe isolante
solide pour courant alternatif de tensions
assignées supérieures à 1 kV et inférieures
ou égales à 52 kV
IEC 62271-202 - Appareillage à haute tension - Partie 202: EN 62271-202 -
Postes préfabriqués haute tension/basse
tension
IEC 62271-203 - Appareillage à haute tension - Partie 203: EN 62271-203 -
Appareillage sous enveloppe métallique à
isolation gazeuse de tensions assignées
supérieures à 52 kV
IEC 62271-207 - Appareillage à haute tension - Partie 207: EN 62271-207 -
Qualification sismique pour ensembles
d'appareillages à isolation gazeuse pour
des niveaux de tension assignée
supérieurs à 52 kV
IEC 62305 série Protection contre la foudre EN 62305 série
IEC/TR 61000-5-2 - Compatibilité électromagnétique (CEM) - - -
Partie 5: Guides d'installation et
d'atténuation - Section 2: Mise à la terre et
câblage
IEC/TR 62271-300 - Appareillage à haute tension - Partie 300: - -
Qualification sismique des disjoncteurs à
courant alternatif
IEC/TS 60815-1 - Selection and dimensioning of high-voltage - -
insulators intended for use in polluted
conditions - Part 1: Definitions, information
and general principles
IEC/TS 60815-2 - Selection and dimensioning of high-voltage - -
insulators intended for use in polluted
conditions - Part 2: Ceramic and glass
insulators for a.c. systems
IEC/TS 60815-3 - Selection and dimensioning of high-voltage - -
insulators intended for use in polluted
conditions - Part 3: Polymer insulators for
a.c. systems
IEC/TS 61463 - Traversées - Qualification sismique - -
IEC/IEEE 82079-1 - Élaboration des informations d'utilisation EN IEC/IEEE -
(Instructions d'utilisation) des produits - 82079-1
Partie 1: Principes et exigences générales
IEC 61936-1 ®
Edition 3.0 2021-07
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE
colour
inside
Power installations exceeding 1 kV AC and 1,5 kV DC –
Part 1: AC
Installations électriques de puissance de tension supérieure à 1 kV en courant
alternatif et 1,5 kV en courant continu –
Partie 1: Courant alternatif
IEC 61936-1:2021-07(en-fr)
– 120 – IEC 61936-1:2021 © IEC 2021
SOMMAIRE
AVANT-PROPOS . 126
INTRODUCTION . 129
1 Domaine d'application . 130
2 Références normatives . 131
3 Termes et définitions . 133
3.1 Définitions générales . 133
3.2 Définitions concernant les installations électriques. 136
3.3 Définitions concernant les types d’installations électriques . 136
3.4 Définitions concernant les mesures de protection contre les chocs
électriques . 137
3.5 Définitions concernant les distances d’isolement. 137
3.6 Définitions concernant la commande et la protection . 139
3.7 Définitions concernant la mise à la terre . 140
4 Exigences fondamentales . 144
4.1 Généralités . 144
4.1.1 Exigences générales . 144
4.1.2 Accords entre fournisseur et utilisateur . 144
4.2 Exigences électriques . 147
4.2.1 Méthodes de mise à la terre du neutre . 147
4.2.2 Classification des tensions . 147
4.2.3 Courant en exploitation normale . 147
4.2.4 Courant de court-circuit . 147
4.2.5 Fréquence assignée . 148
4.2.6 Effet couronne . 148
4.2.7 Champs électriques et magnétiques . 149
4.2.8 Surtensions . 149
4.2.9 Harmoniques . 149
4.2.10 Compatibilité électromagnétique (CEM) . 149
4.3 Exigences mécaniques . 149
4.3.1 Généralités . 149
4.3.2 Charge de tension mécanique . 150
4.3.3 Charge de montage . 150
4.3.4 Charge de glace . 150
4.3.5 Charge due au vent . 150
4.3.6 Efforts dus aux manœuvres . 151
4.3.7 Forces de court-circuit . 151
4.3.8 Perte de la tension mécanique d'un conducteur . 151
4.3.9 Charges sismiques . 151
4.3.10 Dimensionnement des structures . 151
4.4 Conditions climatiques et environnementales . 152
4.4.1 Généralités . 152
4.4.2 Conditions normales . 152
4.4.3 Conditions particulières . 153
4.5 Exigences particulières . 155
4.5.1 Effets dus à la présence de petits animaux et micro-organismes . 155
4.5.2 Niveau de bruit . 155
IEC 61936-1:2021 © IEC 2021 – 121 –
4.5.3 Transport . 155
5 Isolement. 155
5.1 Généralités . 155
5.2 Choix du niveau d'isolement . 155
5.2.1 Généralités . 155
5.2.2 Considération relative aux méthodes de mise à la terre du neutre . 155
5.2.3 Considération relative aux tensions assignées de tenue au choc . 156
5.3 Vérification des valeurs de tenue au choc . 156
5.4 Distances minimales d’isolement des parties actives . 156
5.4.1 Généralités . 156
5.4.2 Distances minimales d’isolement dans la plage de tensions I . 157
5.4.3 Distances minimales d’isolement dans la plage de tensions II . 157
5.5 Distances minimales d’isolement entre les parties dans des conditions
spéciales . 160
5.6 Zones de connexion soumises à l’essai . 160
6 Matériel électrique . 160
6.1 Exigences générales . 160
6.1.1 Sécurité du matériel électrique . 160
6.1.2 Sécurité de l’utilisateur . 161
6.2 Exigences spécifiques . 161
6.2.1 Dispositifs de coupure . 161
6.2.2 Transformateurs de puissance et réactances . 162
6.2.3 Appareillage préfabriqué soumis à un essai de type . 163
6.2.4 Transformateurs de mesure . 163
6.2.5 Parafoudres . 164
6.2.6 Condensateurs . 164
6.2.7 Circuits-bouchons . 164
6.2.8 Isolateurs . 164
6.2.9 Câbles isolés . 164
6.2.10 Conducteurs et accessoires . 167
6.2.11 Machines électriques tournantes. 168
6.2.12 Générateurs . 169
6.2.13 Connexions principales du générateur . 169
6.2.14 Convertisseurs statiques . 169
6.2.15 Fusibles . 170
6.2.16 Verrouillage électrique et mécanique . 170
7 Installations électriques . 171
7.1 Généralités . 171
7.1.1 Exigences communes . 171
7.1.2 Agencement des circuits . 171
7.1.3 Documentation . 172
7.1.4 Voies de circulation . 172
7.1.5 Allées et zones d'accès . 174
7.1.6 Éclairage . 175
7.1.7 Sécurité d’exploitation . 175
7.1.8 Étiquetage . 175
7.2 Installations électriques extérieures de conception libre . 175
7.2.1 Généralités . 175
7.2.2 Distances d’isolement des barrières de protection . 176
– 122 – IEC 61936-1:2021 © IEC 2021
7.2.3 Distances d’isolement des obstacles de protection . 176
7.2.4 Distances d’isolement des clôtures . 177
7.2.5 Hauteur minimale au-dessus de la zone d'accès . 178
7.2.6 Distances d’isolement des bâtiments . 179
7.2.7 Clôtures ou murs extérieurs et portes d'accès . 181
7.3 Installations électriques intérieures de conception libre . 181
7.4 Installation de l’appareillage préfabriqué soumis à l’essai de type . 182
7.4.1 Généralités . 182
7.4.2 Exigences supplémentaires relatives aux appareillages sous enveloppe
métallique à isolation gazeuse . 182
7.5 Exigences relatives aux bâtiments . 184
7.5.1 Généralités . 184
7.5.2 Dispositions structurelles . 184
7.5.3 Salles des appareillages . 185
7.5.4 Zones de maintenance et d’exploitation . 185
7.5.5 Portes . 186
7.5.6 Évacuation des liquides isolants . 186
7.5.7 Chauffage, ventilation et climatisation (CVC) . 186
7.5.8 Bâtiments qui exigent un examen particulier . 187
7.6 Postes préfabriqués à haute tension/basse tension . 187
7.7 Installations électriques sur mât, pylône et tour. 188
8 Mesures de sécurité . 188
8.1 Généralités . 188
8.2 Protection contre les contacts directs . 188
8.2.1 Généralités . 188
8.2.2 Mesures de protection contre les contacts directs . 189
8.2.3 Exigences de protection . 190
8.3 Dispositions de protection des personnes contre le contact indirect . 191
8.4 Dispositions de protection des personnes travaillant sur ou à proximité des
installations électriques . 191
8.4.1 Généralités . 191
8.4.2 Matériel électrique pour l'isolement des installations ou des appareils . 191
8.4.3 Dispositifs pour empêcher le réenclenchement des dispositifs de
sectionnement . 191
8.4.4 Dispositifs de vérification de l'absence de tension . 192
8.4.5 Dispositifs de mise à la terre et en court-circuit . 192
8.4.6 Matériels agissant comme barrières de protection contre les parties
actives voisines . 193
8.4.7 Stockage de l’équipement de protection individuelle . 194
8.5 Protection contre les dangers provenant d'un défaut d’arc . 194
8.6 Protection contre les coups de foudre directs . 194
8.7 Protection contre l'incendie . 195
8.7.1 Généralités . 195
8.7.2 Transformateurs, réactances . 196
8.7.3 Câbles . 203
8.7.4 Autres matériels contenant un liquide inflammable . 204
8.8 Protection contre les fuites de liquide isolant et de gaz SF . 204
8.8.1 Fuites de liquide isolant et protection de la nappe phréatique . 204
8.8.2 Fuite de gaz SF . 207
IEC 61936-1:2021 © IEC 2021 – 123 –
8.8.3 Défaillance avec perte de gaz SF et de ses produits de décomposition . 208
8.9 Identification et marquage . 208
8.9.1 Généralités . 208
8.9.2 Plaques d’identification et plaques de mise en garde . 208
8.9.3 Avertissement concernant les dangers dus à l'électricité . 208
8.9.4 Installations électriques avec des condensateurs incorporés . 209
8.9.5 Panneaux de sécurité pour sorties de secours . 209
8.9.6 Marquage d’identification des câbles . 209
9 Systèmes de protection, d’automatisation et auxiliaires . 209
9.1 Systèmes de protection . 209
9.2 Systèmes d’automatisation . 210
9.3 Systèmes auxiliaires . 211
9.3.1 Circuits d'alimentation en courant alternatif et courant continu . 211
9.3.2 Systèmes à air comprimé. 212
9.3.3 Installations de manipulation du gaz SF . 213
9.3.4 Centrales d’hydrogène . 213
9.4 Règles de base applicables à la compatibilité électromagnétique des
systèmes de commande . 214
9.4.1 Généralités . 214
9.4.2 Sources de bruit électrique dans les installations électriques . 214
9.4.3 Mesures à prendre pour réduire les effets des perturbations à haute
fréquence . 214
9.4.4 Mesures à prendre pour réduire les effets des perturbations à basse
fréquence . 215
9.4.5 Mesures liées au choix du matériel électrique . 215
9.4.6 Autres mesures possibles pour réduire les effets des perturbations . 216
10 Installations de mise à la terre . 216
10.1 Généralités . 216
10.2 Exigences fondamentales . 216
10.2.1 Critères de sécurité . 216
10.2.2 Exigences fonctionnelles . 217
10.2.3 Installations de mise à la terre à haute et à basse tension . 217
10.3 Conception des installations de mise à la terre . 219
10.3.1 Généralités . 219
10.3.2 Défauts du réseau électrique . 220
10.3.3 Foudre et surtensions transitoires . 220
10.4 Construction des installations de mise à la terre . 221
10.5 Mesurages . 221
10.6 Maintenabilité . 221
10.6.1 Contrôles . 221
10.6.2 Mesurages . 221
11 Contrôle et essais . 222
11.1 Généralités . 222
11.2 Vérification des performances spécifiées . 223
11.3 Essais lors de l’installation et de la mise en service . 223
11.4 Essai de mise en exploitation . 223
12 Manuel d’exploitation et de maintenance . 224
Annexe A (informative) Valeurs des niveaux d’isolement assignés et des distances
minimales d’isolement fondées sur les pratiques courantes dans certains pays . 225
– 124 – IEC 61936-1:2021 © IEC 2021
Annexe B (normative) Méthode de calcul des tensions de contact admissibles . 228
Annexe C (normative) Tension de contact admissible conformément à l’IEEE 80 . 229
Annexe D (normative) Diagramme de conception d’une installation de mise à la terre . 230
Annexe E (informative) Méthodes de protection contre les coups de foudre directs . 231
E.1 Généralités . 231
E.2 Câbles de garde . 231
E.3 Paratonnerres . 232
Annexe F (informative) Considérations relatives à la conception pour un travail en
toute sécurité . 234
Annexe G (informative) Liste des notes concernant les conditions particulières en
vigueur dans certains pays . 236
Bibliographie . 242
Figure 1 – Distance minimale d’approche pour le transport à l’intérieur d’installations
électriques fermées . 174
Figure 2 – Protection contre les contacts directs au moyen de barrières ou d’obstacles
de protection à l'intérieur d’installations électriques fermées . 177
Figure 3 – Distances d’isolement de séparation et hauteur minimale à la clôture/au
mur extérieur . 178
Figure 4 – Hauteurs minimales à l'intérieur d’installations électriques fermées . 179
Figure 5 – Approches avec bâtiments à l'intérieur d’installations électriques fermées . 180
Figure 6 – Cloisons de séparation entre les transformateurs . 199
Figure 7 – Protection contre l'incendie entre le transformateur et le bâtiment . 201
Figure 8 – Exemple de petits transformateurs sans couche de gravier ni réservoir de
recuperation . 204
Figure 9 – Fosse avec réservoir de récupération intégré . 206
Figure 10 – Fosse avec réservoir de récupération séparé . 206
Figure 11 – Fosse avec réservoir de récupération commun intégré . 207
Figure 12 – Tension de contact admissible U . 222
Tp
Figure C.1 – Tension de contact admissible U conformément à l’IEEE 80 . 229
Tp
Figure E.1 – Câble de garde unique . 232
Figure E.2 – Deux câbles de garde . 232
Figure E.3 – Paratonnerre unique . 233
Figure E.4 – Deux paratonnerres . 233
Figure F.1 – Distance de travail à l’intérieur d’installations électriques fermées . 235
Tableau 1 – Références aux paragraphes pour lesquels un accord entre fournisseur et
utilisateur est exigé . 146
Tableau 2 – Distances minimales d’isolement dans l'air – Plage de tensions I (1 kV U
m
≤ 245 kV) . 158
Tableau 3 – Distances minimales d’isolement dans l'air – Plage de tensions II
(U > 245 kV) . 159
m
Tableau 4 – Valeurs indicatives pour les distances d’isolement des transformateurs à
l’extérieur. 198
Tableau 5 – Exigences minimales applicables à l'installation de transformateurs à
l’intérieur . 202
IEC 61936-1:2021 © IEC 2021 – 125 –
Tableau 6 – Exigences minimales pour l’interconnexion d’installations de mise à la
terre à basse et à haute tension fondées sur les limites d’EPR . 219
Tableau A.1 – Valeurs des niveaux d’isolement assignés et distances minimales
d'isolement dans l’air pour 1 kV
m
l’installation U non normalisées par l’IEC, sur la base des pratiques courantes dans
m
certains pays . 225
Tableau A.2 – Valeurs des niveaux d’isolement assignés et distances minimales
d’isolement dans l’air pour 1 kV < U ≤ 245 kV pour la tension la plus élevée pour
m
l’installation U non normalisées par l’IEC, sur la base des pratiques courantes dans
m
certains pays . 226
Tableau A.3 – Valeurs des niveaux d’isolement assignés et distances minimales
d’isolement dans l’air pour U > 245 kV pour les tensions les plus élevées pour
m
l’installation U non normalisées par l’IEC, sur la base des pratiques courantes dans
m
certains pays . 227
– 126 – IEC 61936-1:2021 © IEC 2021
COMMISSION ÉLECTROTECHNIQUE INTERNATIONALE
____________
INSTALLATIONS ÉLECTRIQUES DE PUISSANCE
DE TENSION SUPÉRIEURE À 1 kV EN COURANT
ALTERNATIF ET 1,5 kV EN COURANT CONTINU –
Partie 1: Courant alternatif
AVANT-PROPOS
1) La Commission Électrotechnique Internationale (IEC) est une organisation mondiale de normalisation composée
de l'ensemble des comités électrotechniques nationaux (Comités nationaux de l’IEC). L’IEC a pour objet de
favoriser la coopération internationale pour toutes les questions de normalisation dans les domaines de
l'électricité et de l'électronique. À cet effet, l’IEC – entre autres activités – publie des Normes internationales,
des Spécifications techniques, des Rapports techniques, des Spécifications accessibles au public (PAS) et des
Guides (ci-après dénommés "Publication(s) de l’IEC"). Leur élaboration est confiée à des comités d'études, aux
travaux desquels tout Comité national intéressé par le sujet traité peut participer. Les organisations
internationales, gouvernementales et non gouvernementales, en liaison avec l’IEC, participent également aux
travaux. L’IEC collabore étroitement avec l'Organisation Internationale de Normalisation (ISO), selon des
conditions fixées par accord entre les deux organisations.
2) Les décisions ou accords officiels de l’IEC concernant les questions techniques représentent, dans la mesure du
possible, un accord international sur les sujets étudiés, étant donné que les Comités nationaux de l’IEC intéressés
sont représentés dans chaque comité d’études.
3) Les Publications de l’IEC se présentent sous la forme de recommandations internationales et sont agréées
comme telles par les Comités nationaux de l’IEC. Tous les efforts raisonnables sont entrepris afin que l’IEC
s'assure de l'exactitude du contenu technique de ses publications; l’IEC ne peut pas être tenue responsable de
l'éventuelle mauvaise utilisation ou interprétation qui en est faite par un quelconque utilisateur final.
4) Dans le but d'encourager l'uniformité internationale, les Comités nationaux de l’IEC s'engagent, dans toute la
mesure possible, à appliquer de façon transparente les Publications de l’IEC dans leurs publications nationales
et régionales. Toutes divergences entre toutes Publications de l’IEC et toutes publications nationales ou
régionales correspondantes doivent être indiquées en termes clairs dans ces dernières.
5) L’IEC elle-même ne fournit aucune attestation de conformité. Des organismes de certification indépendants
fournissent des services d'évaluation de conformité et, dans certains secteurs, accèdent aux marques de
conformité de l’IEC. L’IEC n'est responsable d'aucun des services effectués par les organismes de certification
indépendants.
6) Tous les u
...










Questions, Comments and Discussion
Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.
Loading comments...