Abstract

Specifies performance requirements for the subfamily. Forms part of a series dealing with measuring relays with more than one input energizing quantity and for which IEC 60255-6 gives the general requirements.

Status
Published
Publication Date
31-Jul-1995
Current Stage
6060 - National Implementation/Publication (Adopted Project)
Start Date
01-Aug-1995
Due Date
01-Aug-1995
Completion Date
01-Aug-1995

Buy Documents

Standard

SIST IEC 60255-13:1995

English language (14 pages)
Preview
Preview
e-Library read for
×1 day

SIST IEC 60255-13:1995 is the Slovenian standard identical to IEC 60255-13 for biased (percentage) differential relays. It specifies performance requirements and methods of presenting characteristics for electrically biased differential relays used mainly to detect faults in a.c. generators, motors and transformers. It is intended for manufacturers, test laboratories, and users who need to declare, compare, and verify relay behavior.

What does SIST IEC 60255-13:1995 specify?

SIST IEC 60255-13:1995 specifies the performance requirements, declared data, presentation methods, and type test methods for biased (percentage) differential relays. It is part of the IEC series for measuring relays with more than one input energizing quantity and uses IEC Publication 255-6 for the general requirements of that family.

The standard is organized into three sections:

  • Section One - Scope and Definitions
  • Section Two - Requirements
  • Section Three - Test Methods

It applies to relays in new condition, and all tests in this standard are type tests. The scope excludes relays for busbar protection and current differential relays such as pilot wire relays used for transmission line protection.

What are the key requirements of SIST IEC 60255-13:1995?

SIST IEC 60255-13:1995 focuses on what the manufacturer must declare, how the relay characteristic is described, and how compliance is checked. In practice, it tells the buyer or test engineer which relay data must be available and which companion IEC publications carry the general test requirements.

  • Clause 3, standard values - Input and auxiliary energizing quantities and frequency follow IEC Publication 255-6. The manufacturer also declares characteristic quantities, setting ranges, restraint percentage, and resetting and disengaging ratios, because there are no standard rated values for those items.
  • Clause 4, operation and accuracy - The manufacturer declares the operating characteristic, the effective range of restraint current, the maximum through current, and any harmonic restraint behavior. The maximum through current declaration matters because the relay shall withstand sudden application and removal of that current for at least 100 ms.
  • Clause 5, presentation of characteristics - The standard gives recommended ways to present operating characteristics, operating time, and harmonic restraint, including graphical forms in Figures 1 to 3. This helps users compare relays and check setting ranges without reading each design differently.
  • Clauses 6 to 9 and 12 to 14 - Thermal, mechanical, auxiliary energizing, shock and vibration, contact performance, insulation, markings and data, and high-frequency disturbance follow companion IEC publications. If the differential circuit has lower thermal capability than the restraint circuit, that capability must be declared, which matters for burden and overload decisions.
  • Clause 11, rated burden - The manufacturer declares burden between appropriate input terminals both with no differential current and with differential current equal to input current. This gives a realistic view of loading in service and during test.
  • Clauses 15 to 18, test methods - Tests are based on reference values for influencing quantities and rated auxiliary energizing quantities unless otherwise stated. For operating time tests, the relay is checked at three and ten times the operating value at minimum and maximum settings, and through-current tests and mechanical tests use the declared conditions.

What terms does SIST IEC 60255-13:1995 define?

SIST IEC 60255-13:1995 defines the core relay terms needed to read the requirements correctly.

  • Differential relay - A relay designed to respond to differential current.
  • Biased (or percentage) differential relay - A differential relay whose response is modified by a restraint current.
  • Differential current - The phasor difference between specified incoming and outgoing currents.
  • Restraint current - The combination of incoming and outgoing currents that restrains relay operation.
  • Restraint percentage - The percentage relationship between differential current and restraint current(s) up to which the relay does not operate.
  • Through current - The part of the total incoming current that is also present in the outgoing current.

Who uses SIST IEC 60255-13:1995?

SIST IEC 60255-13:1995 is used by relay manufacturers, protection engineers, test laboratories, and utility or industrial buyers. Manufacturers use it to declare relay settings and performance data, while test labs use it to run type tests for operating characteristic, operating time, thermal behavior, mechanical behavior, and through-current performance.

It is especially relevant for equipment used on a.c. generators, motors, and transformers. Quality managers and buyers use it to check whether a relay declaration, test report, or tender specification covers the required data and companion IEC references.

Which standards are used with SIST IEC 60255-13:1995?

SIST IEC 60255-13:1995 relies on these IEC publications:

  • IEC Publication 255-6 - Provides general requirements for measuring relays with more than one input energizing quantity, including standard values and assigned errors.
  • IEC Publication 255-6A - Provides the thermal, mechanical, auxiliary energizing, shock and vibration requirements and related test provisions.
  • IEC Publication 255-0-20 - Provides contact performance requirements for electrical relays.
  • IEC Publication 255-5 - Provides insulation tests for electrical relays.
  • IEC International Electrotechnical Vocabulary (I.E.V.) - Provides general relay terminology when a term is not defined in this standard.

What does the SIST IEC 60255-13:1995 document contain?

SIST IEC 60255-13:1995 contains Table I and Table II for reference conditions and nominal range limits, plus Figures 1 to 4 for relay characteristics and test circuits. The figures show how to present the operate and non-operate zones, operating time, and harmonic restraint behavior.

The test section describes how to measure operating characteristic, operating time, harmonic restraint, thermal performance, through-current performance, and mechanical requirements. It also states the conditions for applying input and auxiliary quantities during tests, which makes the standard useful for design verification, type testing, and product comparison.

Buy Documents

Standard

SIST IEC 60255-13:1995

English language (14 pages)
Preview
Preview
e-Library read for
×1 day

Get Certified

Connect with accredited certification bodies for this standard

IMQ S.p.A. (Certification)

Italian electrical product certification.

ACCREDIA Italy Verified

SLG Prüf- und Zertifizierungs GmbH

German testing and certification body.

DAKKS Germany Verified

UL Solutions

Global safety science company with testing, inspection and certification.

ANAB United States Verified

Sponsored listings

Frequently Asked Questions

SIST IEC 60255-13:1995 is a standard published by the Slovenian Institute for Standardization (SIST). Its full title is "Electrical relays - Part 13: Biased (percentage) differential relays". This standard covers: Specifies performance requirements for the subfamily. Forms part of a series dealing with measuring relays with more than one input energizing quantity and for which IEC 60255-6 gives the general requirements.

Specifies performance requirements for the subfamily. Forms part of a series dealing with measuring relays with more than one input energizing quantity and for which IEC 60255-6 gives the general requirements.

SIST IEC 60255-13:1995 is classified under the following ICS (International Classification for Standards) categories: 29.120.40 - Switches; 29.120.70 - Relays. The ICS classification helps identify the subject area and facilitates finding related standards.

SIST IEC 60255-13:1995 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.

Standards Content (Sample)

Contents

  • 1. Scope
  • 2. Definitions
  • 2.1 Differential relay
  • 2.2 Biased (or percentage) differential relay
  • 2.3 Differential current
  • 2.4 Restraint current
  • 2.5 Restraint percentage
  • 2.6 Through current
  • 3. Standard values
  • 3.3 Characteristic quantity(ies) and setting range(s)
  • 3.4 Restraint percentage
  • 3.5 Resetting and disengaging ratios
  • 4. Operation and accuracy
  • 4.1 Operation
  • 4.2 Accuracy
  • 5. Methods of presenting relay characteristics and
  • 5.1 Operating characteristics
  • 5.2 Operating time
  • 5.3 Harmonic restraint
  • 6. Thermal requirements
  • 7. Mechanical
  • 8. Values of the limits of the operative range of the auxiliary energizing quantities
  • 9. Shock and vibration
  • 10. Contact performance
  • 11. Rated burden
  • 12. Insulation
  • 13. Markings and data
  • 14. High-frequency disturbance test
  • 15. Tests related to accuracy and operating characteristics
  • 15.1 General requirements
  • 15.2 Test circuits and methods for measuring the relay characteristics
  • 16. Tests for thermal requirements
  • 18. Tests for mechanical requirements

1. Scope

This standard specifies the performance requirements of electrically biased (percentage) differential relays. These relays constitute a particular sub-family of measuring relays with more than one input energizing quantity as defined in IEC Publication 255-6, Electrical Relays, Part 6: Measuring Relays with More than One Input Energizing Quantity, and the parameters whose values are to be declared by the manufacturer of such relays. It also specifies methods of presentation of the characteristics and performance of these relays. This standard applies to relays designed for the detection of faults particularly in a.c. generators, motors and transformers. It does not apply to relays designed for busbar protection, nor does it apply to current differential (e.g. pilot wire) relays used for the protection of transrhission lines. This standard covers the majority of biased (percentage) differential relays and also, for example, those where the restraint percentage increases as the through-current increases. For particular cases, supplementary requirements may be stated in national standards.

All tests in this standard are type tests.

This standard applies only to relays in a new condition.

2. Definitions

For definitions of general terms not defined in this standard, reference should be made to the IEC International Electrotechnical Vocabulary (I.E.V.), to IEC Publication 255-6, and to IEC Publication 255-6A: First supplement to IEC Publication 255-6 (1978). For the purpose of this standard, the following definitions shall apply:

2.1 Differential relay

A relay which, by its design, is intended to respond to differential current.

2.2 Biased (or percentage) differential relay

A differential relay in which the designed response is modified by a restraint current.

2.3 Differential current

In a differential relay, a current which is the phasor difference between specified incoming and outgoing currents.

2.4 Restraint current

In a differential relay, the combination of incoming and outgoing currents, which restrains operation of the relay.

SIST IEC 60255-13:1995

2.5 Restraint percentage

The ratio, expressed as a percentage, between the differential current and the restraint current(s) up to which the relay does not operate.

Note. — The definition of restraint percentage ignores an error, which may not be negligible, due to the finite operating current required under zero restraint conditions. This may be taken into account when necessary.

2.6 Through current

In a differential relay, that portion of the total incoming current that is also present in the outgoing current.

SECTION TWO — REQUIREMENTS

3. Standard values

Input and auxiliary energizing quantities and frequency 3.1 The standard values of input and auxiliary energizing quantities, and of frequency, are specified in IEC Publication 255-6.

3.2 Standard reference values of influencing quantities and factors and standard values of their nominal and extreme ranges

3.2.1 Influencing quantities and factors

The standard reference conditions are specified in Table I of IEC Publication 255-6. In addition, the standard conditions given in Table I in this standard apply to biased (percentage) differential relays.

TABLE I Standard reference conditions and test tolerances of influencing quantities and factors Influencing quantity or factor Reference conditions Test tolerances the manufacturer or as specified in national Input energizing currents As declared by - Restraint current standards unless specified in clauses below or in lower-level - Differential current documents C. a) Phase angle between input Zp o° ± energizing quantities u a U ,- CO ^ 2N Zero 62-0 Transient 5% of peak a.c. value (See note) g d.c. component in a.c.

.2 U As declared by the manufacturer or as specified in national Setting value(s), where setting adjustments are possible standards unless specified in clauses below or in lower-level documents Auxiliary Transient Zero ° energizing d.c. component /o of peak a.c. value

quantities in a.c. (See note) Note. — In the special case of relays in which polyphase measurements are made on a single relay, the manufacturer or national standards shall define which of the input currents shall be under reference conditions.

SIST IEC 60255-13:1995 Limits of the nominal ranges of influencing quantities and factors 3.2.2 The standard values are specified in Table II of I E C Publication 255-6. In addition, the standard values given in Table II in this standard apply to biased (percentage) differential relays.

TABLE II Standard values of the limits of the nominal ranges of influencing quantities and factors Nominal range Influencing quantity or factor Reference input energizing quantity Non-reference input energizing quantity .2 Phase angle between input energizing quantities a" G ca z 7.:

As declared by the manufacturer or as

specified in national standards Frequency

.N N t Waveform m G U Steady-state d.c. component in a.c.

Transient d.c. component in a.c.

Voltage or current As declared by the manufacturer or as specified in national standards unless _ " Frequency specified in clauses below cr Waveform CL .E 0 to 12% of the rated d.c. value') a.c. component in d.c. (ripple) ':1 o o T Steady state d.c. component in a.c.

As declared by the manufacturer or as specified in national standards unless specified in clauses below Transient d.c. component in a.c.

This value of the tolerance is based on the definition given in the International Electrotechnical Vocabulary (I.E.V. 131-03-14) Peak ripple factor.

3.3 Characteristic quantity(ies) and setting range(s)

There are no standard rated values of either characteristic quantity(ies) or setting range(s). The values and the limits of setting range(s) shall be declared by the manufacturer.

3.4 Restraint percentage

There are no standard values of restraint percentage. The setting values shall be declared by the manufacturer.

SIST IEC 60255-13:1995

3.5 Resetting and disengaging ratios

There are no standard values of the resetting and disengaging ratios. The values shall be declared by the manufacturer.

4. Operation and accuracy

4.1 Operation

4.1.1 Operating characteristic

The manufacturer shall declare the operating characteristics of the relay under reference conditions, these including the reference setting of the differential circuit, and at the maximum and minimum settings of the restraint circuits, when applicable.

...