oSIST prEN 1366-14:2026
(Main)Fire resistance tests for service installations - Part 14: Partial penetration seals
- Abstract
This part of the EN 1366 series specifies a method of test and criteria for the evaluation (including field of direct application rules) of the ability of a partial penetration seal to maintain the fire resistance of a separating element at the position at which it has been penetrated by a device or devices that passes through one face of the element only. Partial penetration seals are used to seal apertures for electrical sockets, downlighters, media devices, cables and any item which requires an opening to be made in one face of the element of construction but does not include a device which passes through both faces.
Supporting constructions are used in this part of the EN 1366 series to represent separating elements such as walls or floors. The supporting construction shall be a system that has been subject to a fire test in accordance with one of the following standards: EN 13381 1 for horizontal membranes, EN 13381 2 for vertical membranes, EN 1364 1 or EN 1365 1 for walls, EN 1366 3 for walls based on a standard supporting construction, or EN 1364 2 or EN 1365 2 for floors. This is referred to throughout this document as the applicable test standard for the supporting construction.
This part of the EN 1366 series is used in conjunction with EN 1363 1.
The purpose of a test described in this part of the EN 1366 series is to assess the integrity and insulation performance of the partial penetration seal, of the partially penetrating service(s) or device(s) and of the separating element in the surrounding area of the partial penetration seal. Where partial penetration seals are installed in loadbearing elements, it is possible that the loadbearing capacity is also considered.
It is not the intention of this test to provide quantitative information on the rate of leakage of smoke and/or hot gases or on the transmission or generation of fumes.
Tests in accordance with this part of the EN 1366 series are not intended to supply any information on the ability of the partial penetration seal to withstand stress caused by movements or displacements of the penetrating devices.
The risk of spread of fire downwards cannot be assessed with this test.
Tests in accordance with this part of the EN 1366 series do not address any risks associated with leakage of dangerous liquids or gases caused by failure of the device in case of fire.
- Status
- Not Published
- Public Enquiry End Date
- 23-Sep-2026
- Technical Committee
- POZ - Požarna varnost
- Current Stage
- 4020 - Public enquire (PE) (Adopted Project)
- Start Date
- 09-Jul-2026
- Due Date
- 26-Nov-2026
- Completion Date
- 28-Sep-2026
oSIST prEN 1366-14:2026 is the Slovenian version of draft European Standard prEN 1366-14:2026 from the European Committee for Standardization (CEN). It specifies a fire resistance test method and evaluation rules for partial penetration seals - seals used where a device or service passes through only one face of a wall, floor, ceiling or similar separating element.
The document is for laboratories, manufacturers, specifiers and approval bodies that need to judge whether a one-sided opening closure keeps the surrounding construction performing in fire. In practice, it is used for items such as electrical sockets, downlighters, media devices and cables.
What does oSIST prEN 1366-14:2026 specify?
oSIST prEN 1366-14:2026 specifies how to test partial penetration seals and how to assess the fire resistance of the seal, the penetrating device or service, and the surrounding separating element. It is used together with EN 1363-1, and the supporting construction must itself be a system tested to an appropriate fire test standard.
The scope is focused on openings made in one face only. It does not aim to quantify smoke leakage, hot gas leakage, fumes, movement resistance of the penetrating device, downward fire spread, or risks from dangerous liquids or gases released by device failure in fire.
The document is organized into main clauses for scope, references, terms, equipment, test conditions, specimen preparation, installation, conditioning, instrumentation, procedure, performance criteria, reporting and direct application. Annexes A to E give standard configurations and direct application rules for specific cases.
| Annex | What it covers |
|---|---|
| A | Partial penetration seals for electrical sockets in walls |
| B | Partial penetration seals for devices other than electrical sockets in walls |
| C | Partial penetration seals for services in walls |
| D | Partial penetration seals in ceilings with loadbearing test |
| E | Partial penetration seals in floors |
What are the key requirements of oSIST prEN 1366-14:2026?
Test conditions and specimen setup
oSIST prEN 1366-14:2026 requires the test to use a supporting construction that has already been fire tested to the appropriate standard for the wall, floor or membrane being represented. The supporting construction must be suitable for the fire resistance period being claimed, and if it is loadbearing, the applied load is determined from the applicable supporting-construction standard.
Clause 5 sets the heating, pressure and loading conditions. Heating follows EN 1363-1 or EN 1363-2 where applicable. Services are only included in the zone where positive pressure exceeds 10 Pa, and horizontal constructions use a nominal 20 Pa pressure in the plane below the construction. In practice, this fixes the furnace exposure so the seal is tested under a defined fire pressure regime.
Clause 6 sets the specimen geometry and spacing. The perimeter of the seal must be at least 200 mm from furnace boundaries or construction edges to limit edge effects. Where multiple seals are tested, the spacing must reflect either separate evaluation or intended interaction, and any close spacing must be recorded.
Clause 7 requires the test construction to be installed as it would be used in practice, including wiring or other associated components. Unintentional support of the device must be avoided, because that could make the result unrealistically favourable.
Instrumentation, procedure and performance criteria
Clause 9 defines the temperature and integrity measurements. Furnace control uses plate thermometers located 100 mm from the exposed face, with a minimum number based on heated area. On the unexposed face, thermocouples are placed at defined positions on the device, blank seal, wall or service, depending on the size and type of opening. A roving thermocouple is used to find local hot spots unless it could damage the specimen, and the laboratory may add fixed thermocouples where hot spots are expected.
Clause 10 says the test procedure follows EN 1363-1, with the annex chosen to match the specimen type. The test report then records the actual installation, observations and measurements so the result can be checked and used correctly.
Clause 11 gives the acceptance criteria. Insulation failure occurs if any unexposed-face thermocouple rises more than 180 K above its initial temperature, or if the mean of five thermocouples rises more than 140 K. Integrity is assessed according to EN 1363-1, and loadbearing capacity, where relevant, follows the applicable supporting-construction standard. Results are stated as elapsed time to the nearest completed minute until criteria are no longer met.
Direct application of results
Clause 13 limits how test results may be extended. Results apply only to the same orientation used in the test, meaning wall or floor as tested. The seal size may be reduced for smaller apertures and devices, but not increased. Device depth may be reduced but not increased, and the separation or offset between seals may be increased but not reduced.
The annexes add case-specific rules. For example, Annex A covers sockets in walls with back-to-back and offset arrangements, Annex B covers other devices in walls, Annex C covers services in walls, Annex D covers ceilings with loadbearing testing, and Annex E covers floors. These annexes matter because they define the standard test build and the direct field of application for each product type.
What terms does oSIST prEN 1366-14:2026 define?
- Back to back - devices installed on both faces of a vertical construction with 200 mm or less separation in the plane of the wall.
- Device - electrical or mechanical equipment that penetrates one face of the separating element, often at the end of a service.
- Partial penetration - an aperture in one face of the separating element that does not pass completely through it.
- Partial penetration seal - the system used to maintain fire resistance where one or more services or devices pass through one face only.
- Supporting construction - the wall or floor construction that carries the seal during the fire test.
- Separation - the distance between the closest edges of two partial penetration seals on the same face.
- Offset - the distance between the centres of two partial penetration seals on opposite faces.
- Blank seal - a seal tested without a device, used to establish field of application.
Who uses oSIST prEN 1366-14:2026?
oSIST prEN 1366-14:2026 is used by fire test laboratories, product manufacturers, notified or approval bodies, designers and quality managers working with building services and fire stopping. It is relevant to electrical and mechanical devices that create one-sided openings in walls, ceilings or floors, especially in building services, electrical installation and construction product supply.
Manufacturers use it to plan test specimens and define the device sizes, cable types and separations they want covered. Laboratories use it to set up the furnace, instrument the specimen and report the result in the format needed for evaluation and direct application.
Which standards are used with oSIST prEN 1366-14:2026?
- EN 1363-1 - provides the general fire resistance test requirements, including heating, conditioning, measurement and integrity assessment.
- EN 1363-2 - supplies alternative and additional test procedures when they are used.
- EN ISO 13943 - gives fire safety vocabulary used alongside the definitions in this document.
- EN 13381-1 and EN 13381-2 - are used for supporting horizontal and vertical membranes.
- EN 1364-1 and EN 1364-2 - are used for wall and floor supporting constructions.
- EN 1365-1 and EN 1365-2 - are used for loadbearing wall and floor supporting constructions.
- EN 1366-3 - is used for walls based on a standard supporting construction.
- EN 60670-1 - is required for electrical sockets in Annex A.
- HD 603.3 and HD 604.5 - provide the cable designations listed in Annex A.
What does the oSIST prEN 1366-14:2026 document contain?
oSIST prEN 1366-14:2026 contains the test method, specimen preparation rules, instrumentation layout, procedure, performance criteria, reporting requirements and direct application rules for partial penetration seals. It also contains annexes with standard configurations for sockets, other devices, services, ceilings and floors.
The document includes specific thermocouple positions, pressure conditions, spacing rules, report items and the direct application limits that govern how far a test result can be extended. It also includes Table A.1 for cable designations and figures showing standard layouts and measurement positions, which are used to build comparable test specimens and interpret the fire test result consistently.
Get Certified
Connect with accredited certification bodies for this standard
DIN CERTCO
DIN Group product certification.
CIS Institut d.o.o.
Personal Protective Equipment (PPE) certification body. Notified Body NB-2890 for EU Regulation 2016/425 PPE.

Kiwa BDA Testing
Building and construction product certification.
Sponsored listings
Frequently Asked Questions
oSIST prEN 1366-14:2026 is a draft published by the Slovenian Institute for Standardization (SIST). Its full title is "Fire resistance tests for service installations - Part 14: Partial penetration seals". This standard covers: This part of the EN 1366 series specifies a method of test and criteria for the evaluation (including field of direct application rules) of the ability of a partial penetration seal to maintain the fire resistance of a separating element at the position at which it has been penetrated by a device or devices that passes through one face of the element only. Partial penetration seals are used to seal apertures for electrical sockets, downlighters, media devices, cables and any item which requires an opening to be made in one face of the element of construction but does not include a device which passes through both faces. Supporting constructions are used in this part of the EN 1366 series to represent separating elements such as walls or floors. The supporting construction shall be a system that has been subject to a fire test in accordance with one of the following standards: EN 13381 1 for horizontal membranes, EN 13381 2 for vertical membranes, EN 1364 1 or EN 1365 1 for walls, EN 1366 3 for walls based on a standard supporting construction, or EN 1364 2 or EN 1365 2 for floors. This is referred to throughout this document as the applicable test standard for the supporting construction. This part of the EN 1366 series is used in conjunction with EN 1363 1. The purpose of a test described in this part of the EN 1366 series is to assess the integrity and insulation performance of the partial penetration seal, of the partially penetrating service(s) or device(s) and of the separating element in the surrounding area of the partial penetration seal. Where partial penetration seals are installed in loadbearing elements, it is possible that the loadbearing capacity is also considered. It is not the intention of this test to provide quantitative information on the rate of leakage of smoke and/or hot gases or on the transmission or generation of fumes. Tests in accordance with this part of the EN 1366 series are not intended to supply any information on the ability of the partial penetration seal to withstand stress caused by movements or displacements of the penetrating devices. The risk of spread of fire downwards cannot be assessed with this test. Tests in accordance with this part of the EN 1366 series do not address any risks associated with leakage of dangerous liquids or gases caused by failure of the device in case of fire.
This part of the EN 1366 series specifies a method of test and criteria for the evaluation (including field of direct application rules) of the ability of a partial penetration seal to maintain the fire resistance of a separating element at the position at which it has been penetrated by a device or devices that passes through one face of the element only. Partial penetration seals are used to seal apertures for electrical sockets, downlighters, media devices, cables and any item which requires an opening to be made in one face of the element of construction but does not include a device which passes through both faces. Supporting constructions are used in this part of the EN 1366 series to represent separating elements such as walls or floors. The supporting construction shall be a system that has been subject to a fire test in accordance with one of the following standards: EN 13381 1 for horizontal membranes, EN 13381 2 for vertical membranes, EN 1364 1 or EN 1365 1 for walls, EN 1366 3 for walls based on a standard supporting construction, or EN 1364 2 or EN 1365 2 for floors. This is referred to throughout this document as the applicable test standard for the supporting construction. This part of the EN 1366 series is used in conjunction with EN 1363 1. The purpose of a test described in this part of the EN 1366 series is to assess the integrity and insulation performance of the partial penetration seal, of the partially penetrating service(s) or device(s) and of the separating element in the surrounding area of the partial penetration seal. Where partial penetration seals are installed in loadbearing elements, it is possible that the loadbearing capacity is also considered. It is not the intention of this test to provide quantitative information on the rate of leakage of smoke and/or hot gases or on the transmission or generation of fumes. Tests in accordance with this part of the EN 1366 series are not intended to supply any information on the ability of the partial penetration seal to withstand stress caused by movements or displacements of the penetrating devices. The risk of spread of fire downwards cannot be assessed with this test. Tests in accordance with this part of the EN 1366 series do not address any risks associated with leakage of dangerous liquids or gases caused by failure of the device in case of fire.
oSIST prEN 1366-14:2026 is classified under the following ICS (International Classification for Standards) categories: 13.220.50 - Fire-resistance of building materials and elements; 81.060.10 - Raw materials; 83.140.50 - Seals. The ICS classification helps identify the subject area and facilitates finding related standards.
oSIST prEN 1366-14:2026 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.
Standards Content (Sample)
Contents
- Introduction
- 1 Scope
- 2 Normative references
- 3 Terms and definitions
- 3.1 back to back
- 3.2 device
- 3.3 flexible construction
- 3.4 offset
- 3.5 partial penetration
- 3.5.1 small partial penetration
- 3.5.2 medium partial penetration
- 3.5.3 large partial penetration
- 3.6 partial penetration seal
- 3.7 separation
- 3.8 supporting construction
- 3.9 test specimen
- 3.10 wall segment
- 3.11 blank seal
- 4 Test equipment
- 5 Test conditions
- 5.1 Heating conditions
- 5.2 Pressure conditions
- 5.3 Loading conditions
- 6 Test specimen
- 6.1 Size and distances
- 6.2 Number of test specimens
- 7 Installation of test specimen
- 7.1 General
- 7.2 Supporting construction
- 8 Conditioning
- 9 Application of instrumentation
- 9.1 General
- 9.2 Thermocouples
- 9.3 Integrity measurement
- 10 Test procedure
- 10.1 General
- 10.2 Installation of test construction
- 10.3 Measurements and observations
- 11 Performance criteria
- 11.1 Insulation
- 11.2 Integrity
- 11.3 Loadbearing capacity
- 11.4 Expression of results
- 12 Test report
- 13 Field of direct application of test results
- 13.1 Orientation
- 13.2 Supporting construction
- 13.3 Seal size
- 13.4 Device depth
- 13.5 Distances
- Annex A
- Annex B
- Annex C
- Annex D
- Annex E
- Bibliography
Introduction
This part of the EN 1366 series specifies a method of test and criteria for the evaluation (including field of direct application rules) of the ability of a partial penetration seal to maintain the fire resistance of a separating element at the position at which it has been penetrated by a device or devices that passes through one face of the element only. Partial penetration seals are used to seal apertures for electrical sockets, downlighters, media devices, cables and any item which requires an opening to be made in one face of the element of construction but does not include a device which passes through both faces.
oSIST prEN 1366-14:2026 prEN 1366-14:2026 (E)
1 Scope
This part of the EN 1366 series specifies a method of test and criteria for the evaluation (including field of direct application rules) of the ability of a partial penetration seal to maintain the fire resistance of a separating element at the position at which it has been penetrated by a device or devices that passes through one face of the element only. Partial penetration seals are used to seal apertures for electrical sockets, downlighters, media devices, cables and any item which requires an opening to be made in one face of the element of construction but does not include a device which passes through both faces. Supporting constructions are used in this part of the EN 1366 series to represent separating elements such as walls or floors. The supporting construction shall be a system that has been subject to a fire test in accordance with one of the following standards: EN 13381-1 for horizontal membranes, EN 13381-2 for vertical membranes, EN 1364-1 or EN 1365-1 for walls, EN 1366-3 for walls based on a standard supporting construction, or EN 1364-2 or EN 1365-2 for floors. This is referred to throughout this document as the applicable test standard for the supporting construction. This part of the EN 1366 series is used in conjunction with EN 1363-1. The purpose of a test described in this part of the EN 1366 series is to assess the integrity and insulation performance of the partial penetration seal, of the partially penetrating service(s) or device(s) and of the separating element in the surrounding area of the partial penetration seal. Where partial penetration seals are installed in loadbearing elements, it is possible that the loadbearing capacity is also considered.
It is not the intention of this test to provide quantitative information on the rate of leakage of smoke and/or hot gases or on the transmission or generation of fumes. Tests in accordance with this part of the EN 1366 series are not intended to supply any information on the ability of the partial penetration seal to withstand stress caused by movements or displacements of the penetrating devices.
The risk of spread of fire downwards cannot be assessed with this test. Tests in accordance with this part of the EN 1366 series do not address any risks associated with leakage of dangerous liquids or gases caused by failure of the device in case of fire.
2 Normative references
The following documents are referred to in the text in such a way that some or all of their content constitutes requirements of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. EN 1363-1, Fire resistance tests — Part 1: General requirements EN 1363-2, Fire resistance tests — Part 2: Alternative and additional procedures EN ISO 13943, Fire safety — Vocabulary
3 Terms and definitions
For the purposes of this document, the terms and definitions given in EN 1363-1 and EN ISO 13943 and the following apply.
3.1 back to back
devices installed on both faces of a vertical construction with a separation distance of 200 mm or less in any direction (in the plane of the wall)
oSIST prEN 1366-14:2026 prEN 1366-14:2026 (E)
3.2 device
electrical or mechanical equipment which penetrates one face of the separating element, often at the termination of a service EXAMPLE Electrical socket or recessed media equipment.
3.3 flexible construction
horizontal or vertical supporting construction consisting of studs or joists, including linings and optional insulation
3.4 offset
distance between the centres of two partial penetration seals in opposite faces of the element of construction
3.5 partial penetration
aperture in one face of the separating element, including any service(s) or device(s) and associated seal, that does not pass completely through the element
3.5.1 small partial penetration
partial penetration with an area of up to 0,025 m
3.5.2 medium partial penetration
2 2 partial penetration with an area greater than 0,025 m up to 0,12 m
3.5.3 large partial penetration
partial penetration with an area greater than 0,12 m
3.6 partial penetration seal
system used to maintain the fire resistance of a separating element at the position where one or more services or devices pass through one face of a separating element Note 1 to entry: These are sometimes referred to as “membrane penetrations”, “one-sided opening closures” or “seals for one-sided outlets and installed components”.
3.7 separation
distance between the closest extremities of two partial penetration seals in the same face of the element of construction
3.8 supporting construction
wall or floor construction used to support the partial penetration seal being evaluated
oSIST prEN 1366-14:2026 prEN 1366-14:2026 (E)
3.9 test specimen
assembly for the fire test consisting of the partial penetrating service(s) or device(s) and the partial penetration seal materials or partial penetration seal devices
3.10 wall segment
section of a stud wall between adjacent studs
3.11 blank seal
seal is tested without the inclusion of a device for the purpose of generating field of application EXAMPLE A hollow wall box including cable and blind cover, but without a switch or socket.
4 Test equipment
See EN 1363-1, and if applicable EN 1363-2.
5 Test conditions
5.1 Heating conditions
The heating and furnace atmosphere shall conform to those given in EN 1363-1 or, if applicable, EN 1363-2.
5.2 Pressure conditions
Pressure conditions including tolerances shall be as given in the applicable test standard for the supporting construction, subject to the following additional requirements:
Services shall only be included in the zone where the positive pressure exceeds 10 Pa (a minimum pressure of 10 Pa shall be maintained at the lowest point of the lowest service, see Figure 7). NOTE A pressure of 10 Pa is expected to be maintained ca. 1 200 mm below the plane where a pressure of 20 Pa is maintained in accordance with the pressure gradient given in EN 1363-1. For horizontal supporting constructions a nominal pressure of 20 Pa shall be maintained in the horizontal plane (100 ± 10) mm below the underside of the supporting construction.
5.3 Loading conditions
If the supporting construction is loadbearing, the test specimen shall be subjected to loads determined in accordance with the applicable test standard for the supporting construction, which will refer back to EN 1363-1. The determination of the load shall be clearly indicated in the test report.
6 Test specimen
6.1 Size and distances
The dimensions of the test specimen shall be in accordance with the applicable test standard for the supporting construction.
In order to avoid boundary effects, the distance between the perimeter of the partial penetration seal and the internal surfaces of the furnace or edges of the supporting construction shall be not less than 200 mm at any point.
oSIST prEN 1366-14:2026 prEN 1366-14:2026 (E) Separation of partial penetration seals installed within the same face of a wall construction shall comply with the following:
a) Partial penetration seals that are intended to be evaluated separately shall be separated by a minimum 200 mm in any direction in the plane of the wall, unless the separation distance used in practice is less, in which case the actual separation distance shall be used. b) Partial penetration seals that are intended to be evaluated with interaction (evaluated for the effect that other partial penetration seals may have on the performance of any given seal), shall be tested with a separation of less than 200 mm (in any direction in the plane of the wall), unless the separation distance used in practice is less. In each case the actual separation distance used shall be the desired minimum separation.
c) The distances between partial penetration seals shall be recorded in the test report wherever this is less than 200 mm (horizontally or vertically in the plane of the wall). Separation of partial penetration seals installed within the opposite faces of a wall construction shall comply with the following:
a) Partial penetration seals that are intended to be evaluated separately shall be separated by a minimum 200 mm in any direction in the plane of the wall, unless the separation distance used in practice is less, in which case the actual separation distance shall be used. b) Partial penetration seals that are intended to be evaluated with interaction, shall be tested with a separation of less than 200 mm (in any direction in the plane of the wall), unless the separation distance used in practice is less. In each case the actual separation distance used shall be the desired minimum separation.
c) The distances (both vertical and horizontal in the plane of the wall) between the centre points of partial penetration seals shall be recorded in the test report wherever this is less than 200 mm (horizontally or vertically in the plane of the wall).
6.2 Number of test specimens
The minimum number of test specimens shall be accordance with the applicable test standard for the supporting construction.
Electrical sockets, other devices and services intended for use in walls shall comply with the provisions of Annex A, B, or C.
7 Installation of test specimen
7.1 General
The supporting construction shall be installed in accordance with the applicable test standard for the supporting construction.
...