SIST HD 384.7.702 S2:2003
(Main)Electrical installations of buildings -- Part 7: Requirements for special installations or locations -- Section 702: Swimming pools and other basins
Electrical installations of buildings -- Part 7: Requirements for special installations or locations -- Section 702: Swimming pools and other basins
Applies to the basins of swimming pools and paddling pools and their surrounding zones where the risk of electric shock is increased by a reduction in body resistance and contact of the body with earth potential.
Elektrische Anlagen von Gebäuden -- Teil 7: Anforderungen für Betriebsstätten, Räume und Anlagen besonderer Art -- Hauptabschnitt 702: Schwimmbäder und andere Becken
Installations électriques des bâtiments -- Partie 7: Règles pour les installations et emplacements spéciaux -- Section 702: Piscines et autres bassins
S'applique aux bassins des piscines, y compris les pédiluves, et aux volumes les entourant dans lesquels le risque de choc électrique est augmenté en raison de la résistance électrique du corps humain et de son contact avec le potentiel de la terre.
Električne inštalacije zgradb – 7. del: Zahteve za posebne inštalacije ali lokacije – 702. oddelek: Plavalni in drugi bazeni (IEC 60364-7-702:1997, spremenjen)
General Information
Relations
Standards Content (Sample)
SLOVENSKI STANDARD
SIST HD 384.7.702 S2:2003
01-junij-2003
1DGRPHãþD
SIST HD 384.7.702 S1:2000
(OHNWULþQHLQãWDODFLMH]JUDGE±GHO=DKWHYH]DSRVHEQHLQãWDODFLMHDOLORNDFLMH±
RGGHOHN3ODYDOQLLQGUXJLED]HQL,(&VSUHPHQMHQ
Electrical installations of buildings -- Part 7: Requirements for special installations or
locations -- Section 702: Swimming pools and other basins
Elektrische Anlagen von Gebäuden -- Teil 7: Anforderungen für Betriebsstätten, Räume
und Anlagen besonderer Art -- Hauptabschnitt 702: Schwimmbäder und andere Becken
Installations électriques des bâtiments -- Partie 7: Règles pour les installations et
emplacements spéciaux -- Section 702: Piscines et autres bassins
Ta slovenski standard je istoveten z: HD 384.7.702 S2:2002
ICS:
91.140.50 Sistemi za oskrbo z elektriko Electricity supply systems
97.220.10 Športni objekti Sports facilities
SIST HD 384.7.702 S2:2003 en
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
---------------------- Page: 1 ----------------------
SIST HD 384.7.702 S2:2003
---------------------- Page: 2 ----------------------
SIST HD 384.7.702 S2:2003
HARMONIZATION DOCUMENT HD 384.7.702 S2
DOCUMENT D'HARMONISATION
HARMONISIERUNGSDOKUMENT December 2002
ICS 29.020; 91.140.50 Supersedes HD 384.7.702 S1:1991
English version
Electrical installations of buildings
Part 7: Requirements for special installations or locations
Section 702: Swimming pools and other basins
(IEC 60364-7-702:1997, modified)
Installations électriques des bâtiments Elektrische Anlagen von Gebäuden
Partie 7: Règles pour les installations et Teil 7: Anforderungen für Betriebsstätten,
emplacements spéciaux Räume und Anlagen besonderer Art
Section 702: Piscines et autres bassins Hauptabschnitt 702: Schwimmbäder und
(CEI 60364-7-702:1997, modifiée) andere Becken
(IEC 60364-7-702:1997, modifiziert)
This Harmonization Document was approved by CENELEC on 2002-06-01. CENELEC members are
bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for
implementation of this Harmonization Document on a national level.
Up-to-date lists and bibliographical references concerning such national implementation may be obtained on
application to the Central Secretariat or to any CENELEC member.
This Harmonization Document exists in three official versions (English, French, German).
CENELEC members are the national electrotechnical committees of Austria, Belgium, Czech Republic,
Denmark, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Luxembourg, Malta,
Netherlands, Norway, Portugal, Slovakia, Spain, Sweden, Switzerland and United Kingdom.
CENELEC
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung
Central Secretariat: rue de Stassart 35, B - 1050 Brussels
© 2002 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members.
Ref. No. HD 384.7.702 S2:2002 E
---------------------- Page: 3 ----------------------
SIST HD 384.7.702 S2:2003
HD 384.7.702 S2:2002 - 2 -
Foreword
The text of the International Standard IEC 60364-7-702:1997, prepared by IEC TC 64, Electrical
installations and protection against electric shock, together with the common modifications
prepared by SC 64A, Protection against electric shock, of Technical Committee CENELEC TC 64,
Electrical installations of buildings, was submitted to the formal vote and was approved by
CENELEC as HD 384.7.702 S2 on 2002-06-01.
This Harmonization Document supersedes HD 384.7.702 S1:1991.
The following dates were fixed:
- latest date by which the existence of the HD
has to be announced at national level (doa) 2002-12-01
- latest date by which the HD has to be implemented
at national level by publication of a harmonized
national standard or by endorsement (dop) 2003-06-01
- latest date by which the national standards conflicting
with the HD have to be withdrawn (dow) 2005-06-01
Annexes designated "normative" are part of the body of the standard.
Annexes designated "informative" are given for information only.
In this standard, annex ZA is normative and annex A is informative.
Annex ZA has been added by CENELEC.
In this Harmonization Document the common modifications to the International Standard are indicated
by a vertical line in the left margin of the text.
__________
---------------------- Page: 4 ----------------------
SIST HD 384.7.702 S2:2003
- 3 - HD 384.7.702 S2:2002
702 Swimming pools and other basins
702.1 Scope, object and fundamental principles
702.11 Scope
The particular requirements of this section apply to the basins of swimming pools, the basins of
fountains and the basins of paddling pools. They also apply to the surrounding zones of all these
basins. In these areas, in normal use, the effect of an electric shock is increased by a reduction in
body resistance and contact of the body with earth potential. Swimming pools within the scope of
an equipment standard are outside the scope of this standard. For swimming pools for medical
purposes special precautions may be necessary.
Except for areas especially designed as swimming pools, this section does not apply to natural
waters, lakes in gravel pits, coastal areas and similar areas.
702.12 Normative references
See annex ZA.
702.2 Definitions
702.2.21 Guide to general terms
For the purpose of this section, the following definitions apply. For other general definitions, see
HD 384.2.
702.2.21.1
basin of fountain
basin not intended to be occupied by persons and which cannot be accessed (reached by persons)
without the use of ladders and similar means. For basins of fountains which may be occupied by
persons, the specifications and requirements for swimming pools apply
702.2.21.2
small swimming pool
a pool where there is no zone 2
702.3 Assessment of general characteristics
702.32 Classification of external influences
These requirements are based on the dimensions of three zones (examples are given in
Figures 702A, 702B, 702C and 702D).
Zones 1 and 2 may be limited by fixed partitions having a minimum height of 2,5 m.
a) Zone 0
This zone is the interior of the basins including any recesses in their walls or floors, basins
for foot cleaning and waterjets or waterfalls and the space below them.
b) Zone 1
This zone is limited by
- zone 0,
- a vertical plane 2 m from the rim of the basin,
- the floor, or the surface expected to be occupied by persons,
- the horizontal plane 2,5 m above the floor or the surface expected to be occupied by
persons.
---------------------- Page: 5 ----------------------
SIST HD 384.7.702 S2:2003
HD 384.7.702 S2:2002 - 4 -
When the swimming pool contains diving boards, spring boards, starting blocks, chutes or other
components expected to be occupied by persons, zone 1 comprises the zone limited by
- a vertical plane situated 1,5 m around the diving boards, spring boards, starting blocks, chutes
and other components such as accessible sculptures and decorative basins,
- the horizontal plane 2,5 m above the highest surface expected to be occupied by persons.
c) Zone 2
This zone is limited by
- the vertical plane external to zone 1 and a parallel plane 1,5 m from the former,
- the floor or surface expected to be occupied by persons,
- the horizontal plane 2,5 m above the floor or the surface expected to be occupied by
persons.
There is no zone 2 for fountains.
702.4 Protection for safety
702.41 Protection against electric shock
NOTE 1 For protection of socket-outlets, see also clause 702.53.
NOTE 2 For protection of other equipment, see also clause 702.55.
702.411 Protection against both direct and indirect contact
702.411.1 Protection by extra-low-voltage: SELV and PELV
702.411.1.4 Requirements for unearthed circuits (SELV)
702.411.1.4.3 Where SELV is used, whatever the nominal voltage, protection against direct
contact shall be provided by
- barriers or enclosures affording at least the degree of protection IPXXB according to EN 60529,
or
- insulation capable of withstanding a test voltage of 500 V a.c. for 1 minute.
702.412 Protection against electric shock in normal service
(Protection against direct contact or basic protection)
702.412.3 Protection by obstacles
Protection by obstacles is not permitted.
702.412.4 Protection by placing out of reach
Protection by placing out of reach is not permitted.
702.413 Protection against indirect contact
702.413.1.6 Supplementary protective equipotential bonding
All extraneous-conductive-parts in zones 0, 1 and 2 shall be connected by protective equipotential
bonding conductors and connected to the protective conductor of the exposed-conductive-parts of
equipment situated in these zones.
NOTE 1 The connection with the protective conductor may be provided in the proximity of the location, e.g. in an
accessory or in a distribution board.
NOTE 2 See also 702.55.1.
702.413.3 Protection by non-conducting locations
Protection by non-conducting locations is not permitted.
702.413.4 Protection by earth free local equipotential bonding
Protection by earth free local equipotential bonding is not permitted.
---------------------- Page: 6 ----------------------
SIST HD 384.7.702 S2:2003
- 5 - HD 384.7.702 S2:2002
702.47 Application of protective measures for safety
702.471 Measures of protection against electric shock
702.471.4 Particular requirements for each zone
702.471.4.1 Zones 0 and 1
Except for fountains as stated in 702.471.4.2 and the exceptions specified in clause 702.53, in
zones 0 and 1, only protection by SELV at a nominal voltage not exceeding 12 V a.c. or 30 V d.c.
is permitted, the source for SELV being installed external to zones 0, 1 and 2.
Equipment for use in the interior of basins which are only intended to be in operation when people
are not inside zone 0 shall be supplied by circuits protected either by
- SELV (see clause 411.1 of HD 384.4.41), the source for SELV being installed outside zones 0,
1 and 2. The source for SELV may be installed in zone 2 if its supplying circuit is protected by a
residual current protective device with a rated residual operating current I not exceeding
Δn
30 mA, or
- automatic disconnection of the supply (see clause 413.1 of HD 384.4.41), using a residual
current protective device with a rated residual operating current I not exceeding 30 mA, or
Δn
- electrical separation (see clause 413.5 of HD 384.4.41), the source for electrical separation
supplying only one item of current-using equipment and being installed external to zones 0, 1
and 2. The source for electrical separation may be installed in zone 2 if its supplying circuit is
protected by a residual current protective device with a rated residual operating current I not
Δn
exceeding 30 mA.
The socket-outlets of circuits supplying such equipment and the control device of such equipment
shall have a notice, in order to warn the user that this equipment shall be used only when the
swimming pool is not occupied by persons.
702.471.4.2 Zones 0 and 1 of fountains
In zones 0 and 1, one or more of the following protective measures shall be employed:
- SELV (see clause 411.1 of HD 384.4.41), the source for SELV being installed outside zones 0
and 1; or
- automatic disconnection of supply (see clause 413.1 of HD 384.4.41) using a residual current
protective device with a rated residual operating current I not exceeding 30 mA; or
Δn
- electrical separation (see clause 413.5 of HD 384.4.41), the source for electrical separation
supplying only one item of current-using equipment and being installed external to zones 0
and 1.
702.471.4.3 Zone 2
NOTE There is no zone 2 for fountains.
One or more of the following protective measures shall be employed:
- SELV (see clause 411.1 of HD 384.4.41), the source for SELV being installed outside zones 0,
1 and 2. The source for SELV may be installed in zone 2 if its supplying circuit is protected by a
residual current protective device with a rated residual operating current I not exceeding
Δn
30 mA; or
- automatic disconnection of supply (see clause 413.1 of HD 384.4.41), using a residual current
protective device with a rated residual operating current I not exceeding 30 mA; or
Δn
- electrical separation (see clause 413.5 of HD 384.4.41), the source for electrical separation
supplying only one item of current-using equipment and being installed external to zones 0, 1
and 2. The source for electrical separation may be installed in zone 2 if its supplying circuit is
protected by a residual current protective device with a rated residual operating current I not
Δn
exceeding 30 mA.
---------------------- Page: 7 ----------------------
SIST HD 384.7.702 S2:2003
HD 384.7.702 S2:2002 - 6 -
702.5 Selection and erection of electrical equipment
702.51 Common rules
702.512 Operational conditions and external Influences
702.512.2 External influences
Electrical equipment shall have at least the following degrees of protection according to EN 60529:
- zone 0: IPX8;
- zone 1: IPX4,
IPX5 where water jets are likely to occur for cleaning purposes;
- zone 2: IPX2 for indoor locations,
IPX4 for outdoor locations,
IPX5 where water jets are likely to occur for cleaning purposes.
702.52 Wiring systems
702.520 General
The following rules apply to surface wiring systems and to wiring systems embedded either in the
walls, ceilings or in floors at a depth not exceeding 5 cm.
702.522 Selection and erection in relation to external influences
702.522.21 Erection according to the zones
In zones 0, 1 and 2, any metallic sheath or metallic covering of wiring systems shall be connected
to the supplementary protective equipotential bonding.
NOTE Cables should preferably be installed in conduits made of insulating material.
702.522.22 Limitation of wiring systems according to the zones
In zones 0 and 1, wiring systems shall be limited to those necessary to supply equipment situated
in these zones.
702.522.23 Additional requirements for the wiring of fountains
For fountains, the following additional requirements shall be met:
a) cables for electrical equipment in zone 0 shall be installed as far outside the basin rim as
reasonably practical and run to the electrical equipment inside zon
...